PRALLATANTOPER INSTTION IS IMPOR. IFT A CONTRACTYOU NEED ASSISTANCE, CONSULOR, ELECTRICIAN
OR TELEVISION ANTENNA INSTALLER (CHECK WITH YOUR LOCAL BUILDING SUPPLY, OR HARDWARE STORE
FOR REFERRALS). TO PROMOTE CONFIDENCE, PERFORM A TRIAL WIRING BEFORE INSTALLATION.
1
Connect the AC adapter to Mystic and plug into outlet. The display will
briefly light up all the indicator lights (self test).xt the display will showNe
the unit of measurement codes and then will show the barometer function
light and the center display will show a pressure reading. This is the
altitude adjustment mode. Leave it in this mode for now.
Mount the temperature sensor assembly with the two
large wood screws. Select a location that is protected
from direct sunlight and sheltered from rain and physical
damage. (A north exposure, six feet above the ground
will give the best results.)
Form a drip loop with the wire at least eight inches
below the exit from the sensor and at least eight inches
below the point of entruilding. Anchor anyy into the b
exposed wire with insulated cable clips. Run the wire
through the building to the location where the indicator
will be located. Caulk any holes when done.
4
No.w calibrour altitudeate the barometer for yObtain the current barometric
pressure for your area by calling a near-by airport or an individual who has a
properw drly set barometert a small scre. Inseriver into the recessed slotted
screw at the back of Mystic. Turn the screw while observing the pressure read
out on the front of Mystic. Due to the sensitivity of this adjustment, the numbers
on the display may fluctuate during this procedure. It may take a minute to
achievvOnce the unit is set, moe the exact setting.e the toggle switch to the
right (auto) one time to lock in the setting.
2
3
CAULK
8"
MIN
CABLE
CLIP
DRIP
LOOP
5
Unplug the AC adaptor and disconnect the wires Mystic is now ready for the final installation..
The adjustment that you have made will always remain intact.
Connect the AC adapter wires with
the hex nuts. The polarity does not
matter. Connect the two wires from
the air-temperature sensor to
terminals 4 and 5. Again, the polarity
does not matter.
MYSTIC
Feed the cables from the AC adapter and the temperature
sensor through the wall to Mystic. We recommend using one
of our pre-drilled panels for mounting Mystic. Take precautions
to avoid crimping the wires under the lip of the brass readout.
8
7
CABLE FROM
AC ADAPTER
3
CABLE FROM
TEMPERATURE
SENSOR
3
JUMPER WIRE
CONNECTING
MERLIN AND MYSTIC
NOTE: After any full reset, Mystic will display the pressure adjustment mode. It is never necessary to
perform the pressure adjustment again. Simply exit this mode by moving the switch to Auto and
releasing it.
3
Plug the AC adaptor into a 110VAC outlet. Mystic will power
up and self test briefly then the center display will show the
9
pressure adjustment mode. You must exit the adjustment
mode by moving the switch to Auto and releasing it.
If you own a Merlin, connect the jumper wire (supplied)
to terminals #1 and #2 on Merlin. There will now be two
wires connected to terminals #1 and #2. Connect the
other end of the jumper wires to terminals #1 and #2 of
Mystic. Note that terminal #1 of Merlin connects to
terminal #1 of Mystic and #2 connects to #2.
Move the toggle switch at the bottom of the case to the right (auto) and allow it
to return. This manually moves the Mystic through the individual functions. The
illuminated function LED's indicate which function and setting is being displayed.
Moving the toggle sight (auto) and holding it for at least threewitch to the r
seconds will put Mystic into its Auto sequencing mode Y.ou will see each
function light stay on and that particular information displayed for approximately
four seconds and then mo e to the next function automaticallyv.
If Mystic is Auto sequencing and yn that function off - movou wish to ture the
toggle sou can nowitch to the rYight (auto) and release it.w manually step
through the functions as previously mentioned.
Any Individual function's memory can be independently reset.
Movwitch to the right (auto) until that pare the toggle sticular function is
displayed. Then move the toggle switch to the left (reset) and hold it for
six secondskly b.y will quicThe displalank, indicating that the memory
for that function has been reset.
A "FULL" reset may also be done to clear all memories simultaneously
or if an adjustment to the barometer setting is needed. Toggle through Mystics settings until the "Present"
fuction is displayed.vThen mo e the toggle switch to the left (reset) and hold it for six secondsy. The displa
will self-test and enter into the barometer adjustment mode.y the barometer may be reset at thisIf necessar
time bExit the barometer adjustment mode by adjusting the set scre.w on the backplatey moving the toggle
switch to the right (auto) and releasing it.
NOature and/or wind chill data will be displaTE:y "FULL" reset, temperAfter anyed and
stored after ten secondso min.ed and stored after twPressure data will be displayutes.
However, Rate of Change/Pressure will show "HOLD" for 72 minutes following a
"FULL" reset.
When the toggle switch is in the center position Mystic will display the
infory the function light. All the other functionsmation that is indicated b
data are being recorded and stored.
Mystic can be set to displaature in Fahrenheit or Celsius.y the temper
The barometric pressure can be set to inches of mercury, millimeters
of mercury, millibars or kilopascals. To change the units of
measurement follow these steps:
1. Press the small push button switch on the back of the indicator.
The display will show "F" or "C"
2.ailabPress the push bvutton again to advance through the ale units.
3. When you have the code showing for the units of measurement you
want. Press the toggle switch on the side of the case to the right
(auto position). The display will now show "UN" and a number.
The number indicates the units of measurement for pressure.
UN0 = inches of mercury
UN1 = millimeters of mercury
UN2 = millibars
UN3 = kilopascals
4.ailabPress the push bvutton again to advance through the ale units.
5. When you have the code showing for the units of measurement you want, press the toggle switch
on the side of the case to the right (auto position). Mystic will then perfn toorm a self-test and retur
normal operation.
IN GND OUT
3
IMPORTFACTS ABOUTANTYOUR MYSTIC
Latch Up- Power Line disturbances, improper powering up or an error in wiring can cause a blank or
improper display reading. If MYSTIC is "latched up" in this way proceed as follows:
1.C adapter from the 110 VAC outlet.Unplug the A
2. Wait 15 seconds.
3.C poPlug the AAC adapter in to the 110 Vwer outlet.
Durlank out and the instring long poy will bwer outages MYSTIC's displaument will not continue to
accumulate data. It will preserve the previously accumulated data for up to 10 years.
Moving the switch to "Auto" does not erase stored information.
You do not need to time the 6 second reset time.y to indicate that theMystic will blank out the displa
memory has been erased.
Set barometer by obtaining an accruate reading from a source as close to your location as possible.
The closest airport, weather bureau or an individual with an accurate barometer would be a few
examples.
Rate-of-Change indicates the measure of the red oise or fvall of the barometric pressure observer a
one hour pery 12 miniod.erIt is updated evutes.
The Mystic will display the lowest “Wind Chill” reading since the last time that the memory was reset
when both the “Low” and “Wind Chill” function LED’s are illuminated simultaneously. For this
function to be active you must have a Merlin wind speed and direction instrument and the jumper
wire referenced in step 8 of the Mystic installation instructions must be installed.
If at any time the temperature reading seems to be giving you difficulty,
prodeed as follows:
1
Removument from the wall.e the instr
3
At the back of the indicator, disconnect the sensor wires from
terThe current temperature reading shouldminals #4 and #5.
drop to -40 F (-40 C) or below. This is the normal open circuit reading.
3
Use a jumper to connect between terminals #3 and #4. The calibration
test point has been hand-written on the bacvek of the Indicator just abo
terminals #3 and #4.
If the indicator is in proper working order, it will read within2Fofthis number. We
recommend you mount the instrument back on the wall in this mode for several
hours and observe it periodically. This will help detect most intermittent problems.
If the indicator registers within2Fofthetest point, the problem is in your sensor or wire.
Use a jumper wire (a paper clip will do) to connect across the sensor
3
terminals #4 and #5. The indicator should read 122 F (50 C). If so,
disconnect this jumper and proceed to the next step.
Warning: Changes or modifications to this unit not expressly approved by the party
responsible for compliance could void the user's authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the
following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Shielded cables must be used with the wind sensors to ensure compliance with the
Class B FCC limits.
Electrical Damage – Common Causes & Recommended Prevention
Electrical damage can be caused by many different factors. Below are
some suggested methods of minimizing potential problems.
Common Causes:
Storm Activit
way is due to a direct or nearby strike. In addition, lightening storms, dust storms, dry snowstorms and
strong dry winds can all cause static electricity to build up on and around your external sensors. Rega rdless
of the cause, this built up electricity can discharge itself through the cable connecting the external sensors to
the instrument.
Po
Yourself – Are you con
wer Surges – A surge may come from the electric company’s switching generators or power grids, from
local in
Even the on-and-off switching of large electrical appliances, such as refrigerators or clothes dryers can
create damaging fluctuations. This is especially true with sensitive weather recording devices.
person? If so, you have a great deal of static electricity in your environment. Depending on where you live,
static electricity may be a year round problem or only a seasonal problem. In either case, it is possible for a
person to carry enough of a charge to damage an instrument.
dustries or after power interruption when accumulated power suddenly surges back through AC lines.
y – lightening in your area can do damage to your instruments in different ways. The obvious
s
tantly giving and/or receiving a shock every time you touch a doorknob or another
Recommended Prevention:
Use Surge Protec
recommended. This rating will be clearly listed on the packaging of all good qualit y surge protector.
Discharge Y
make sure that you discharge yourself before touching the instrument(s). The shock that you get from
touching a doorknob or another person can often be sufficient to damage an instrument.
tors – For the AC adapter, a UL 1449 rated surge protector with EMI/RFI filtering is
ourself – If the instruments are located in an environment where static electricity is a problem,