MAX-Ability Pressalit Care 2000 Adjustable Height Changing Table INSTALLATION GUIDE

Page 1
Installation Drawing
Pub. May 2020 Page 1/7
Pressalit 2000 Hi Lo Changing Table R8592 (Coated Canvas Mattress) R8478 (Removable Mesh Mattress)
Subject to change without further notice.
Find more product information on our website: R8592 / R8478
Page 2
Mounting Instruction
Installation Drawing
Pub. May 2020 Page 2/7
Please read and carefully follow these instructions. Find the product number on the product label and ensure that these assembly instructions match your product.
WARNING: Failure to comply with these instructions may result in accidents involving serious personal injury or the product being damaged. WARNING: If you suspect that any individual parts may be damaged, contact your Pressalit dealer or service provider. Do not remove, attempt to repair or install parts yourself, unless directed to do so by Pressalit or its agents. WARNING: No modification of this equipment is allowed without express authorization from Pressalit. WARNING: These instructions must be followed, and the product must be installed professionally by a qualified person; e.g. a licensed plumber, in order to avoid personal injury or property damage while using the product. WARNING: Pressalit cannot be held liable for injury to persons or damage to property caused by faulty mounting.
Installation location
This product is designed for indoor use in a wet environment, such as a bathroom or washroom. It may only be used in an environment corresponding to the system’s IP rating. Ensure that the installation location environment also complies with the following operating parameters of the product:
Environmental factor Operating range
Temperature 5°C to 40°C
Relative humidity 20% to 90% @ 30°C (condensation free)
Atmospheric pressure 700 to 1060 hPa
WARNING: Medical electrical equipment needs special precautions regarding electromagnetic compatibility (EMC) and needs to be installed and put into service in accordance with the EMC information (provided in your product’s operating instructions). It is unlikely that the user will encounter problems with the product because of inadequate electromagnetic compatibility. However, electromagnetic immunity is always relative and standards anticipate environments of usage. Portable and mobile RF communications equipment can affect medical electrical equipment. When the product is connected to the local mains power supply, we recommend the use of electromagnetic shielding and similar preventative measures to avoid conducted emissions.
When choosing an installation location, ensure that there will be adequate space for movement of—and access to—the product.
Assembly and installation
Mount the product against a wall in accordance with the illustrations in this assembly instruction. Connect the product components—hand control unit, motor, control box and power cable—to each other as shown. Ensure that the connectors are pressed in as far as possible into their corresponding sockets.
Connection to the mains supply
There is a range of potential configurations to connect the product to the mains power supply. See pages with . The product is supplied with a plug attached, but this may need to be replaced with an IP-rated plug and socket combination appropriate to the location of the socket relative to moisture, or alternatively the product may be hardwired to a mains supply.
WARNING: Ensure that the circuit on the mains supply side is isolated from power while connecting the product to the mains supply.
WARNING: The product must be connected to the mains supply and a protective earth connection by a qualified electrician in accordance with IEC 60601-1 and IEC 60364-7, as well as any locally applicable standards. WARNING: Ensure that the voltage of the local mains supply to be connected is compliant with that stated on the label on the product. WARNING: To ensure protection by electrical separation, the product must be supplied by a mains supply circuit that does not supply power to any other equipment, unless it incorporates a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA. The circuit must be grounded using a protective earth connection and able to be isolated from mains supply by means of a switch installed in a wall or cabinet. WARNING: The integrity of the external protective earthing system must be verified. WARNING: The installer must verify that the protective earth terminal of the control box is connected to the external protective earthing system. WARNING: Ensure that location of the mains isolation switch or coupling is easy to access and use. WARNING: External cables need to be fixed in such a way that users cannot stumble and injure themselves.
Troubleshooting
If the product does not function, check that that all cables are securely connected, and that the electrical circuit is powered. A more detailed troubleshooting guide can be found in the product’s operation and maintenance manual. Contact your Pressalit agent, if assistance is needed when installing the product.
Page 3
!
Concrete >B25
Drywall water-resistant
Solid Brick >= Mz12
Solid Sand Lime Brick >= Hlz12
Aerated Concrete P4
Drywall water-resistant, re-enforced with wood
Drywall water-resistant, re-enforced with plywood
Drywall water-resistant, re-enforced with steel plates
(2 x 12,5 mm)
22 mm
(2 x 12,5 mm)
2 mm
(2 x 12,5 mm)
Installation Drawing
Concrete anchors included at no additional charge.
Pub. May 2020 Page 3/7
V8608
Ø10 x 70 fischer SX 12
V8608
Ø10 x 70 fischer SX 12
V8608
Ø10 x 70 fischer SX 12
V8658
Ø10 x 70 fischer GB 14
V8608
Ø10 x 70 fischer SX 12
(2 x 12,5 mm)
fischer KD 8 snaptight wingit
fischer KD 8 snaptight wingit
Page 4
3500 mm
CLICK
3500 mm
max 175 kg
Control box with transformer 230V, 50/60HZ
Fig. 1
Installation Drawing
R8592 / R8478: 120V
Pub. May 2020 Page 4/7
International protection rating: IPX6 Water projected in powerful jets -- from a nozzle up to 12.5 mm in size -- against the product from any direction shall have no harmful effects.
(386 lbs)
Page 5
Fig. 3b
Fig. 3c
4
2
3
1
90 (3⁄)
1050
(41⁄)
NB!
1
NB!
1
540 (21⁄) 340 (13⁄)
20 (⁄)
Fig. 3a Fig. 3b
Fig. 3c
Fig. 2
115
(4⁄)
130 (5⁄)
192
(7⁄)
80-100
(3⁄-3⁄)
Mounting Dimensions/ Wiring Options
Wall socket/Hard wire within install room
Hard wire/wall socket to an adjacent room through wall or ceiling
3
Pub. May 2020 Page 5/7
Page 6
2
1
1170
(46⁄)
750 (29⁄)
123
(4⁄)
2
3
1
2
3
3
4
200
(7⁄)
700 (27⁄)
Ø 40
(1⁄)
4
Installation Drawing
Pub. May 2020 Page 6/7
Page 7
max
1735
(68⁄)
123
(4⁄)
240 (9⁄)
min
1035
(40⁄)
max
1005
(39⁄)
min
305
(12)
895 (35⁄)
max
1135
(44⁄)
min 435
(17⁄)
300 (11⁄)
750
1800
870
820
115
1600
130
29⁄
70⁄
34⁄
32⁄
4⁄
63
5⁄
Pressalit 2000 Hi Lo Changing Table Dimensions
Pub. May 2020 Page 7/7
Page 8
2019-06-07 · 1/7
Wall Reinforcement Guide
US
Load bearing installation recommendations
Pressalit can only be held responsible for installations carried out by Pressalit’s own installers.
Pressalit can not be held responsible for reinforcements made in a faulty manner.
The below recommendations are based on experience and internal test results.
The below recommendations are to be considered as guidelines only.
Subject to alteration without further notice.
Page 9
2019-06-07 · 2/7
Wall Reinforcement Guide
Please refer to installation drawings and specification pages (go to max-ability.com) for further information about which types of bolts/anchors are recommended on specific wall types. MAX-Ability provides concrete anchors at no additional charge. Other fixing kits should be ordered separately.
This advisory document shows the maximum load capacity for individual bolts and other types of anchors that can be used for fixing Pressalit’s products to the wall. The maximum load capacities shown below are per bolt/anchor and must be considered in re­lation to the information provided for the product that is being fitted. The information specific to the product will show how great the load is on each fixing point when the product is used at its recommended safe working load. Only if the load on each fixing point of a given product is less than the maximum load capacity of the type of bolt/anchor under consideration, should the bolt/anchor in question be used.
E.g. One might wish to fit an adult changing table 3000 to an aerated concrete wall:
Maximum load Maximum load: 440 lbs. When the bench is loaded with 440 lbs, each mounting bolt supports 57 lbs.
Each fixing point is here carrying a load of 57 lbs, and the bolts typically recommended for aerated concrete (Ø10, M8, M10) all have a maximum load capacity that is higher than 57 lbs, so they can all be used.
Aerated Concrete P4 Plug Anchor / Bolt Maximum load
fischer GB 14 Ø10 x 80-105 198 Ibs
fischer FTP M 8 M8 x 35 143 Ibs
fischer FTP M 8 M8 X 35 143 Ibs
fischer FTP K 6 M5 x 50 88 Ibs
Page 10
Choose the appropriate anchor for your wall
Wall Types
Concrete > B25 Plug Anchor Maximum load
fischer SX 12 Ø10 x 70/80 375 Ibs.
fischer SX 10 Ø8 x 70/80 265 Ibs
fischer SX 6 Ø5 x 50 143 Ibs
Solid brick >= Mz12 Plug Anchor Maximum load
fischer SX 12 Ø10 x 70/80 154 Ibs
fischer SX 10 Ø8 x 70/80 132 Ibs
fischer SX 6 Ø5 x 50 66 Ibs
2019-06-07 · 3/7
Solid sand lime brick >= Hlz12 Plug Anchor Maximum load
fischer SX 12 Ø10 x 70/80 375 Ibs
fischer SX 10 Ø8 x 70/80 265 Ibs
fischer SX 6 Ø5 x 50 110 Ibs
Aerated Concrete P4 Plug Anchor / Bolt Maximum load
fischer GB 14 Ø10 x 80-105 198 Ibs
fischer FTP M 8 M8 x 35 143 Ibs
fischer FTP M 8 M8 X 35 143 Ibs
fischer FTP K 6 M5 x 50 88 Ibs
Page 11
Drywall
Wall Types
(2 X 0.5”) water-resistant, re-enforced with wood
2019-06-07 · 4/7
Anchor Maximum load
Ø10 x 70/80 265 Ibs
Ø8 x 70/80 220 Ibs
Ø5 x 50 88 Ibs
Drywall (2 X 0.5”) water-resistant, re-enforced with 1” plywood
Drywall (2 X 0.5”) water-resistant, re-enforced with steel plates (0.1”)
Anchor Maximum load
fischer KD8 toggle 293 Ibs
Wingit 293 Ibs
Snaptight 293 Ibs
Anchor Maximum load
fischer KD8 toggle 207 Ibs
Wingit 207 Ibs
Snaptight 207 Ibs
Drywall (2 X 0.5”) water-resistant
Anchor Maximum load
fischer KD8 toggle 187 Ibs
Wingit 187 Ibs
Snaptight 187 Ibs
Page 12
Reinforcement of wall with 1.5-2” wood
Reinforcement Diagram
Reinforcements of walls should always comply with national standards.
Metal or wood studs
Drywall (2 X 0.5” water-resistant)
Wood (1.5-2”)
2019-06-07 · 5/7
Drywall (2 X 0.5”)
Washer
Anchor to fit wall type
Please refer to mounting instructions for indication of the placement in height of wood plate.
Wall cross-section
Drywall (other side)
Hollow between walls
Wood (1.5-2”)
Page 13
Reinforcement of wall with plywood
Reinforcement Diagram
Reinforcements of walls should always comply with national standards.
Metal or wood studs
Drywall (2 X 0.5” water-resistant)
Plywood (1 X 0.5”)
2019-06-07 · 6/7
Drywall (2 X 0.5”)
Washer
Screw to fit wall type
Please refer to mounting instructions for indication of the placement in height of plywood plate.
Wall cross-section
Drywall (other side)
Hollow between walls
Plywood (1 X 0.5”)
Page 14
Reinforcement of wall with steel
Reinforcement Diagram
Reinforcements of walls should always comply with national standards.
Metal studs
Drywall (2 X 0.5” water-resistant)
Steel plate (1 X 0.1”)
Please refer to mounting instructions for indication of the placement in height of steel plate.
2019-06-07 · 7/7
Drywall (2 X 0.5”)
Washer
Screw to fit wall type
GO
Wall cross-section
Drywall (other side)
Hollow between walls
NO GO
Steel plate (1 X 0.1”)
Loading...