MAXA BDS28A, BDS35A Technical Manual

TECHNICAL MANUAL 2013
SPLIT MONO DC INVERTER
MODELS
BDS28A
BDS35A
This manual has been created for informative purpose. The company declines every responsibility for the results of projecting or installation based on the explanations and the technical specifications given
Serie / Series / Serie / Serie
TECHNICAL MANUAL
MONO DC INVERTER
Emissione / Issue Ausgabe / Emission
04 - 2013
Catalogo / Catalogue / Katalog / Catalogue
Sostituise / Supersade Ersetzt / Remplace
-
MTE01028D2505-00
2
Index
1. SPECIFICATIONS ......................................................................................................................................4
2. CHARACTERISTICS DATA........................................................................................................................ 6
2.1 Operation characteristic curve .................................................................................................................. 6
2.2 Capacity variation ratio according to temperature .................................................................................... 6
2.3 Noise criteria curve ................................................................................................................................... 6
2.4 Operation data .......................................................................................................................................... 6
3. DIMENSIONS ...........................................................................................................................................7
3.1 Indoor units ............................................................................................................................................... 7
3.2 Outdoor units ............................................................................................................................................7
4. REFRIGERANT DIAGRAM ......................................................................................................................8
5. ELECTRICAL CIRCUIT DIAGRAM ........................................................................................................... 9
5.1 Indoor units ............................................................................................................................................... 9
5.2 Outdoor units ............................................................................................................................................9
6. PRINTED CIRCUIT BOARD.....................................................................................................................10
6.1 Indoor units ............................................................................................................................................. 10
6.2 Outdoor units ..........................................................................................................................................10
7. CONTROL FUNCTIONS .........................................................................................................................11
7.1. Temperature parameters ....................................................................................................................... 11
7.2. Basic functions.......................................................................................................................................11
8. TROUBLESHOOTING ............................................................................................................................15
8.1 Malfunction diagnosis should be performed as below procedure...........................................................15
8.2 Confirmation ...........................................................................................................................................15
8.3 Flashing LED of Indoor/Outdoor unit and primary judgement ................................................................16
8.4. How to check simply the main parts ...................................................................................................... 21
Appendix 1: form for indoor/outdoor unit’s ambient sensor numerical value of resistance ......................... 32
Appendix 2: form for indoor/outdoor unit’s tube temperature sensor numerical value of resistance ..........33
Appendix 3: form for indoor/outdoor unit’s air exhaust temperature sensor numerical value of resistance..34
3
1. SPECIFICATIONS
Models of indoor units BDS28A BDS35A
Rated voltage 220-240V ~50Hz
Total capacity
Cooling
Heating
Air flow volume (SH/H/MH/M/ML/L/SL) m³/h 730/670/610/530/460/410/380 770/670/610/530/460/410/380
Dehumidifying volume l/h 0,8 1,4
Fan motor cooling speed (Max - Min) r/min 1300/1050/1000/900/800/700/500 1350/1070/1000/900/800/700/500
Fan motor heating speed (Max - Min) r/min 1300/1150/1080/1030/980/900/850 1350/1150/1080/1030/980/900/850
Output of fan motor W 15 15
Fan motor capacitor μF / /
Fan motor RLA A 0,07 0,07
Fan type - piece Cross flow - 1 Cross flow - 1
Diameter x length mm Φ98 x 662 Φ98 x 662
Indoor unit
Evaporator
Swing motor model MP24HA/MP24HB/MP24HC MP24HA/MP24HB/MP24HC
Output of swing motor W 2,4 2,4
Fuse A 3,15 3,15
Sound pressure level dBA 36/32/21 36/32/21
Sound power level dBA 46/42/31 46/42/31
Dimension (W/H/D) mm 866 x 292 x 209 866 x 292 x 209
Dimension of package (W/H/D) mm 945 x 377 x 297 945 x 377 x 297
Net weight/gross weight kg 11/14 11/14
Models of outdoor units BDS28A BDS35A
Compressor manufacturer/trademark SANYO
Compressor model C-6RZ110H1A C-6RZ110H1A
Compressor oil FV50S FVC 68D / RB 68EP
Compressor type ROTARY ROTARY
L.R.A. A 33,00 33,00
Compressor RLA A 4,59 4,59
Compressor power input W 800 800
Overload protector 1NT11L-3979 1NT11L-3979
Throttling method Electronic expansion valve
Starting method 16°C ~ 30°C
Working temperature range (°C) -20°C ~ 48°C
Outdoor unit
Condenser
Fan motor speed rpm 850/750/600 850/750/600
Output fan motor W 40 40
Fan motor RLA A 0,23 0,23
Power input W 520 900
Rated current A 2,3 4,0
S.E.E.R. W/W 7,5-A++ 7-A++
Total capacity
Power input W 565 895
Rated current A 2,37 7,5
S.C.O.P.
Evaporator type Aluminium Fin-copper Tube
Pipe diameter mm Φ7 Φ7
Row-fin gap mm 2-1.5 2-1,5
Coil length x height x width (l x H x L) mm 662 x 25,4 x 305 662 x 25,4 x 305
Condensor type Aluminium Fin-copper Tube
Pipe diameter mm Φ7,94 Φ7,94
Rows-fin gap mm 2,5-1,5 2,5-1,5
Coil length (l) x height (H) x width (L) mm 763 x 57 x 550 730 x 38.1 x 508
kW 2,5(0,7 ~ 4,4) 3,5(0,7 ~ 4,5)
Btu/h 8,53(2,3 ~ 15,00) 11,9(2,3 ~ 15,3)
kW 2,7(0,7 ~ 4,8) 3,5(0,7 ~ 5,5)
Btu/h 9,3(2,4 ~ 16,3) 12,4(2,4 ~ 18,7)
W/W
4,6 – A++ 4,6 – A++
4
g
[
]
Fan motor capacitor μF / /
Air flow volume of outdoor unit m³/h 2000 2000
Fan type-piece Axial-flow
Fan diameter mm Φ445 Φ445
Defrosting method Automatic Defrosting
Climate type T1 T1
Isolation I I
Moisture protection IP24 IP24 Permissible excessive operating pressure
for the dischar Permissible excessive operating pressure for the suction side
Sound pressure level dB(A) 49/-/- 50/-/-
Sound power level dB(A) 59/-/- 60/-/-
Dimensions (WXHXD) mm 906 x 596 x 378 906 x 596 x 378
Dimension of package (L/W/H) mm 948 x 420 x 645 348 x 420 x 645
Net weight/gross weight kg 43/47 43/47
Refrigerant charge (R410A) kg 1,3 1,3
Length m 5 5
Gas additional charge g/m 20 20
Outer diameter
Max distance
Connecting pipe
e side
Liquid pipe mm Φ6 Φ6
Gas pipe mm Φ9,52 Φ9,52
Height m 10 10
Length m 15 20
Mpa 3,8 3,8
Mpa 1,2 1,5
The above data of specifications are subject to change without prior notice. Please refer to the actual data specified on the nameplate of
the unit.
Note: Test conditions:
Standard condition
Rated cooling 27 19 35 24
Rated heating 20 15 7 6
3) Microphone at a distance of 1m from the unit.
Approximate calculation from Sound Pressure Level to Sound Power Level:
- Average Sound Pressure Level
L
: Sound pressure level of front test point.
1P
L
: Sound pressure level of side test point for indoor unit
2P
- Approximate Sound Power Lever
Dry bulb temp. °C Wet bulb temp. °C Dry bulb temp. °C Wet bulb temp. °C
Indoor side state Outdoor side state
*1.0*1.0
LL
21
L
L
=10*lg
p
=
W
+
L
+10.
L
p
PP
1010(*2/1
1P
.
L
,
.
2P
5
0
2. CHARACTERISTICS DATA
2.1 Operation characteristic curve
Cooling
10
Condition Indoor:DB27 Outdoor:DB35 WB24
8
Indoor air flow: Super High Pipe length: 5m
6
4
Current (A)
2
0
WB19
BDS35A
BDS28A
Compressor speed (rps)
2.2 Capacity variation ratio according to temperature
200
180
160
140
120
100
80
60
Capacity ratio(%)
40
20
0
33 35 37 39 41 43 45
BDS28A
BDS35A
Condition Indoor:DB27 Indoor air flow: Super High Pipe length: 5m
WB19
Outdoor temp.( )
2.3 Noise criteria curve
50
45
40
35
30
25
Noise/dB(A)
20
15
10
Super High
BDS35A
BDS28A
High Middle Low Quiet
Indoor fan motor rotating speed (rps)
2.4 Operation data
Heating
10
Condition Indoor:DB20 Outdoor:DB7
8
Indoor air flow:Super High Pipe length: 5m
6
4
Current (A)
2
0
505151 0 20 30 40 60 70 80 90020304060708090
BDS35A
BDS28A
Compressor speed (rps)
gnitaeHgnilooC
200
180
160
140
120
100
80
60
Capacity ratio(%)
40 20
0
-18 -14 -10 -6 -2 2 6 1
BDS28A
BDS35A
Condition Indoor:DB20 Indoor air flow:Super High Pipe length: 5m
Outdoor temp.( )
tinUroodtuOtinUroodnI
55
50
45
Noise/dB(A)
40
35
30
0 8 20 30 40 50 60 70 80 90
Compressor speed (rps)
BDS35A
BDS28A
Cooling:
Temperature
conditions (°C)
Indoor Outdoor
27/19 35/24
Model
name
BDS28A
BDS35A
Standard
pressure
Heat exchanger pipe
temp.
P(MPa) T1 (°C) T2 (°C)
0,9~1,2
In: 12~14
Out: 10~12
In: 41~43
Out: 43~45
Indoor fan speed
Outdoor fan
speed
Super high Super High
Compressor
revolution (rps)
34
55
6
Heating:
Temperature
conditions (°C)
Indoor Outdoor
20/15 7/6
Model
name
BDS28A
BDS35A
Standard
pressure
P(MPa) T1 (°C) T2 (°C)
2,0~2,6
Heat exchanger pipe
temp.
In: 33~35
Out: 42~44
In: 3~5
Out: 3~5
Indoor fan speed
Super high Super high
Outdoor fan
speed
Notes:
(1) Connecting piping condition: 5m.
(2) T1: Outlet and inlet pipe temperature of evaporator.
T2: Outlet and inlet pipe temperature of condenser.
P: Pressure of air pipe used for connecting outdoor and indoor units.
Notes:
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor thermometer)
(2) Connecting piping condition: 5m.
3. DIMENSIONS
3.1 Indoor units
866
209
Compressor
revolution (rps)
41
55
3.2 Outdoor units
541162 163
7
4. REFRIGERANT DIAGRAM
TINUROODTUOTINUROODNI
GAS SIDE
HEAT EXCHANGE
(EVAPORATOR)
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
Discharge
Suction
COMPRESSOR
4-Way valve
Accumlator
Electron expansion valve
HE AT EXCHANGE
(CONDENSER)
reniartSreniartS
COOLING
HEATING
8
5. ELECTRICAL CIRCUIT DIAGRAM
5.1 Indoor units: BDS28A, BDS35A
FAN
MOTOR
M1
DC-MOTOR
CAP
JUMP
SWING-LR
M2
SWING
ROOM
TEMP.SENSOR
0
TUBE
TEMP.SENSOR
0
RT2RT1
ROOM TUBE
AP2
PRINTEDCIRCUITBOAR D
SWING-UD1
M3
SWING
MOTOR(U.D1)MOTOR(L.R)
RECEIVER AND
DISPLAYBOARD
AP1
SWING-UD2
M4
SWING
MOTOR(U.D2)
MAGNETIC
RING
N
DISP2DISP1
AC-L
COM-OUT
L-OUT
K7
HEALTH-L HEALTH-N
RD BU
COOL PLASMA
GENERATOR
L
L
BN(BK) BU(WH)
POWER
L
N
YEGN(GN)
BU BK BN
XT1 N(1)
2 3
CONN WIRE
BU BK BN
YEGN
TERMINAL
BOARD
OUTDOOR UNIT
PE
YEGN
EVAPORATOR
YEGN
PE
5.2 Outdoor units: BDS28A, BDS35A
SAT
W3YEGN
PE
W10RD
YEGN
PE
XT2
BU
INDOOR UNIT
N(1)
BK BN
L1
2
L1
3
W2BU
W4BK
W1BN
E
OVC-COMP CN2
N1
COMU AC-L1
OFAN1
M
FAN
CN1
EKV
PE
TUBE
TEM.SENSOR
RT1
0
4V AC-L2
RT2
4YV
OUTROOM
TEM.SENSOR
0
L3
EXHAUST
TEM.SENSOR
RT3
0
LX-2
W11
L2 L2 L2
W5BU
COMP-U
AP1
LX-1
L3
L
COMP
R
COMP
S
W7RD
W6YE
COMP-V COMP-W
W12
W13WH
WHOG
P
HP
E
C
HPP
W8YEGN
HEAT-N2 HEAT-L
(CHASSIS)
PE
N2 N3
EH2
HEATER
W9BU
HEAT-N1
RD RD
EH1
HEATER
(COMP)
9
6
7
6. PRINTED CIRCUIT BOARD
6.1 Indoor unit: BDS28A, BDS35A
12345
15
14
13
6.2 Outdoor units: BDS28A, BDS35A
No Part name
1 DC fan
2 Microswitch
3 Electrostatic precipitation
4 Small up & down swing interface
5 Left and right
Big up & down swing interface
6
7 Display interface
8 Ambient temperature sensor
9 Tube temperature sensor
Outdoor unit live wire
10
Input interface of live wire for
11
indoor unit
Health
12
Fuse
13
Interface of neutral wire for
14
indoor and outdoor units
Communication interface of
8911 1012
15
indoor and outdoor units
No Part name
1 Input of neutral wire of power
2 Input of live wire of power
Communication interface
3
Interface 1 of electric reactor
4
Interface 2 of electric reactor
5
6 Interface of fan
Neutral wire of electric heater of
7
chassis
Neutral electric wire of
8
compressor
9 Neutral wire of 4-way valve
Live wire of 4-way valve
10
Live wire of electric heater
11
Input of overload
12
Temperature sensor
13
U, V, W three phases of
14
compressor
15 Input of ground wire of power
10
7. Control functions
7.1. Temperature Parameters
Indoor preset temperature (Tpreset)
Indoor ambient temperature (T
amb)
7.2. Basic functions
Once energized, the compressor should in no way be restarted unless after at least 3-minute time interval. In case of having
memory function, for the first energization, the compressor will be started without 3-minute lag, if being under the condition
of power-off, and the compressor will have 3-minutes delay to be started under the condition of power-on. Once started, the
compressor will not be stopped within 6 minutes with the changes of room temperature.
7.2.1 Cooling Mode
Cooling Condition and Process
When T
and the indoor fan will run at preset speed.
When T
at preset speed.
When T
Under this mode, the switchover (reversal) valve will be de-energized and the temperature can be set from 16°C to 30°C.
If the compressor is shut down for some reason, the indoor fan and the swing device will operate at the original state.
amb. Tpreset , the unit will run under cooling mode, in which case the compressor and outdoor fan will be started,
amb. Tpreset -3°C, the compressor will stop, the outdoor fan will stop with time lag of 30s, and the indoor fan will run
preset -3°C <Tamb. < Tpreset , the unit will maintain its original operating status.
Tpreset
Tpreset –2 ˚C
Tamb.
6 min. 3 min. 6 min.
Start cooling
Original operating status
Stop cooling
Compressor
Outdoor fan
Indoor fan
Run
Setting fan speed
Stop
Protection function
Overcurrent protection
If total current is high, the compressor will run in limited frequency. If total current is too high, the compressor will stop, the
outdoor fan will delay 30 seconds to stop, indoor unit will display E5 and outdoor yellow light will blink 5 times.
Antifreeze protection
When the antifreeze protection is detected, the compressor will stop, the outdoor fan will stop after 30 seconds, and the
indoor fan and swing motor will keep running in the original mode. When antifreeze protection is eliminated and the compressor has stopped for 3 minutes, the compressor will resume running in the original mode.
The period ofantifreezing protection
Compressor
3 min
Outdoor fan
Indoor fan
Low fan speed
Run
Stop
11
7.2.2 Dehumidifying mode
7.2.2.1 The condition and process of dehumidifying
If T
amb. > Tpreset, DRY mode will act, the indoor fan, outdoor fan and compressor will run, and indoor fan will run at low
speed.
set - 2°C ≤ Tambient Tpreset, the unit will keep running in the original mode.
If T
am. Tset - 2°C, the compressor will stop running, the outdoor fan will delay 30 seconds to stop and the indoor fan will
If T
run at low speed.
7.2.2.2 Protection function
Protection is the same as that under COOL mode.
7.2.3 HEAT mode
7.2.3.1 The condition and process of heating
If T
amb Tprset + 2°C, HEAT mode will act, the compressor, outdoor fan and reversal valve will run, the indoor fan will delay
3min to stop at the latest.
prset +2°C < Tamb < Tprset + 5°C, the unit will keep running in the original mode.
If T
amb > Tprset + 5°C, the compressor will stop, the outdoor fan will delay 30 sec to stop and Indoor unit fan blow with low
If T
speed for 60s,during this period, fan speed is not changeable.
In this mode, the temperature setting range is 16°C ~ 30°C.
The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient
temperature.
When the unit is turned off in HEAT mode, or switched to other mode from HEAT mode, the four –way valve will be
powered off after the compressor stops.
Stop heating
Original running state
Compressor
Outdoor Unit
Indoor Unit
Reversal valve
T
amb
6min 3min 6min
30s 30s
Set fan speed
3min
Run
60s
3min
Stop
Start heating
60s
7.2.3.2 The condition and process of defrosting
When frost is detected in the condenser, the system will enter into defrosting state. When defrosting starts, the compressor
and indoor fan will stop, and the outdoor fan and four-way valve will delay 30 seconds to stop. The compressor will start
after 15 seconds and then defrosting will be started. When the compressor has run for 7 minutes or defrosting is finished,
the compressor will stop. After 30 seconds the four – way valve opens and after an other 60 seconds, the compressor and
outdoor fan resume running. The indoor fan will delay 3 minutes to run at the la test and temperature on the display panel
shows H1.
The period of defrosting
Four-way valve
7min
Compressor
Outdoor Unit
Indoor Unit
Run Stop
12
3min
Set fan speed
7.2.3.3 Protection function
Anti-cold – wind protection
In HEAT mode, in order to prevent the indoor unit from blowing out cold wind, each time the compressor starts, the indoor
fan will delay 3 minutes after the compressor to run at the latest and it can adjust fan speed automatically when
temperature is low.
Overcurrent protection
Overcurrent protection is the same with that in COOL mode.
Protection
Cold air prevention
The unit is started under heating mode (the compressor is ON):
In the case of T
speed with a time lag of 2 minutes. Within 2 minutes, if T
indoor amb. < 24°C: if Ttube 40°C and the indoor fan is at stop state, the indoor fan will begin to run at low
tube > 40°C, the indoor fan also will run at low speed; and after
1-minute operation at low speed, the indoor fan will be converted to operation at preset speed. Within 1-minute low speed
operation or 2-minute non-operation, if T
In the case of T
indoor amb. 24°C: if Ttube > 42°C, the indoor fan will run at low speed, and after one minute, the indoor fan
will be converted to preset speed. Within one-minute low speed operation, if T
tube > 42°C, the fan will run at present speed.
tube > 42°C, the indoor fan will be converted to
preset speed.
Note: T
indoor amb. indicated in and refers to, under initially heating mode, the indoor ambient temperature before the
command to start the compressor is performed according to the program, or after the unit is withdrawn from defrost, the
indoor ambient temperature before the defrost symbol is cleared.
Total current up and frequency down protection
If the total current I
compressor will run at reduced frequency; and if I
total W, frequency rise will be allowed; if Itotal X, frequency rise will not be allowed; if Itotal ≥ Y, the
total Z, the compressor will stop and the outdoor fan will stop with a time
lag of 30s.
7.2.4 Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the
electric heater will stop.
7.2.5 AUTO Mode
Working conditions and process of AUTO mode
Under AUTO mode, standard cooling temperature T
a) Once energized, if T
amb. 22°C, the unit will be started under heating mode; if 23°C< Tamb.< 25°C, the unit will run under
fan mode and the run indicator will be bright; and if T
b) Under AUTO mode, if T
temperature is 25°C; if T
the indoor fan will run at set speed; and if T
c) Under AUTO mode, if T
preset temperature is 20°C; if T
amb. ≥ Tset is detected, the unit will select to run under cooling mode, in which case implicit set
amb. Tpreset - 2°C, the compressor will stop, the outdoor fan will stop with a time lag of 1 minute, and
set - 2°C< Tamb.< Tset, the unit will remain at its original state.
amb. Tset+2°C is detected, the unit will select to run under heating mode, in which case implicit
amb. Tset + 5°C, the compressor will stop, the outdoor fan will stop with a time lag of 1
set is 25°C and standard heating temperature Tset is 20°C.
amb. 25°C, the unit will be started under cooling mode.
minute, and the indoor fan will run under the mode of residue heat blowing; and if T
remain at its original state.
d) Under AUTO mode, if 23°C < T
amb.< 25°C, the unit will remain at its original state.
set +2°C< Tamb.< Tset + 5°C, the unit will
13
Protection
a) In cooling operation, protection is the same as that under the cooling mode;
b) In heating operation, protection is the same as that under the heating mode;
c) When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will
remain unchanged for at least 6 minutes.
7.2.6 Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
Overload protection
tube: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat
T
exchanger under heating mode.
1) Cooling overload
tube 52°C, the unit will return to its original operation state.
a) If T
b) If T
tube 55°C, frequency rise is not allowed.
tube 58°C, the compressor will run at reduced frequency.
c) If T
tube 62 °C, the compressor will stop and the indoor fan will run at preset speed.
d) If T
2) Heating overload
a) If T
tube 50°C, the unit will return to its original operation state.
b) If T
tube 53°C, frequency rise is not allowed.
tube 56°C, the compressor will run at reduced frequency.
c) If T
tube 60°C, the compressor will stop and the indoor fan will blow residue heat and then stop.
d) If T
Exhaust temperature protection of compressor
If exhaust temperature 98°C, frequency is not allowed to rise.
If exhaust temperature 103°C, the compressor will run at reduced frequency.
If exhaust temperature 110°C, the compressor will stop.
If exhaust temperature 90°C and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its
operation.
Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system
will stop and the display will show the error code E6.
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the
compressor will resume its operation. If module protection occurs six times in succession, the compressor will not be started
again.
Overload protection
If temperature sensed by the overload sensor is over 115°C, the compressor will stop and the outdoor fan will stop with a
time lag of 30 seconds. If temperature is below 95°C, the overload protection will be relieved.
If voltage on the DC bus is below 150V or over 420V
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of
30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3
minutes, the compressor will resume its operation.
14
Faults of temperature sensors
Designation of sensors Faults
Indoor ambient temperature The sensor is detected to be open-circuited or short-circuited for successive 30 seconds. Indoor tube temperature The sensor is detected to be open-circuited or short-circuited for successive 30 seconds. Outdoor ambient temperature The sensor is detected to be open-circuited or short-circuited for successive 30 seconds.
Outdoor tube temperature
Exhaust
Overload
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds, and no detection is performed within 10 minutes after defrost begins. After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or short-circuited for successive 30 seconds. After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or short-circuited for successive 30 seconds.
8 Power-failure memory protection
Memory content: mode, up-down purging, lighting, set temperature, and set fan speed. After having power failure, it can
automatically start operating according to the memory content after being powered on again. If no timing function is set in the
final remote control order, the system will memorize the latest remote control order and then operate based on the manner
set during the latest time. There is common timing function included in the latest remote control order. If the system has
power failure when the timed time is still not reached, the system will memorize the timing function in the latest remote
control order after being powered on again, and the timing time will be calculated from the power-on time again. If there is
timing function in the latest remote control order, when the timed time is reached and there is power-failure after the system
conduct the action of the set timed start or timed stop, then after powered on again, the system will memorize the operating
condition before power failure and will not implement the timing action, and also the moment timing will not be memorized.
8. TROUBLESHOOTING
8.1 Malfunction diagnosis should be performed as below procedure
Step Malfunction diagnosis procedure
1 Conform malfunction
2 Read out the error code for indoor/outdoor unit and then find out the corresponding malfunction name
3 Troubleshooting and maintenance (refer to the content as below for details)
Note: There’s high capacity electrolytic capacitor on outdoor unit’s main board. Therefore, there’s still high voltage (DC
280V-380V, which is depending on the input voltage) in the capacitor even if the power is disconnected.
That voltage can only be decreased to the safety valve after more than 20mins. There will be electric shock if you touch the
electrolytic capacitor within 20mins. Therefore, if it needs to maintain it after disconnecting the power, you must discharge
the electrolytic capacitor according to below method.
8.2 Confirmation
(1) Confirmation of Power Supply
Confirm that the power breaker operates (ON) normally;
(2) Confirmation of Power Voltage
Confirm that power voltage is AC 220–230–240 ±10%. If power voltage is not in this range, the unit may not operate
normally.
15
.
r
8.3 Flashing LED of Indoor/Outdoor unit and primary judgement
No Malfunction
High pressure
1
protection of system
Antifreezing
2
protection
Refrigerant
3
leakage protection
High discharge Temperature
4
protection of compressor
Overcurrent
5
protection
Communication
6
Malfunction
High temp.
7
resistant protection
EEPROM
8
malfunction
Limit/decrease frequency due
9
to high temp of module
Display Method of Indoor Unit
Indicator Display (during
blinking, ON 0.5s and OFF
LED
88
Operation Indicator
Blinks
E1
once
Blinks
E2
twice
F0
Blinks 4
E4
times
Blinks 5
E5
times
Blinks 6
E6
times
Blinks 8
E8
times
EE
EU
0.5s)
COOL
Indicator
Blinks 6 times
Heating
Indicator
Blinks 15 times
Blinks 6 times
Display Method of Outdoor Unit Indicator has 3 kinds of display
status and they will be displayed
circularly every 5s.
Yellow
Indicator
Red
Indicator
Blinks 3 times
Blinks 7 times
Blinks 5
times
Always
ON
Blinks 6 times
Blinks 11 times
Blinks 9 times
Green
Indicator
A/C status Possible causes
- During cooling and drying operation, except indoor fan operates, all loads stop operation.
- During heating operation, the complete unit stops.
During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates.
The Dual-8 Code Display will show F0 and the complete unit stops.
- During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates.
- During heating operation, all loads stop.
- During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates.
- During heating operation, all loads stop.
- During cooling operation, compressor stops while indoor fan motor operates.
- During heating operation, the complete unit stops.
- During cooling operation: compressor will stop while indoor fan will operate.
- During heating operation, the complete unit stops.
- During cooling and drying operation, compressor will stop while indoor fan will operate.
- During heating operation, the complete unit will stop
All loads operate normally, while operation frequency fo compressor is decreased
1. Refrigerant was superabundant.
2. Poor heat exchange (including filth blockage of heat exchanger and bad radiating environment);
3. Ambient temperature is too high.
1. Poor air-return in indoor unit.
2. Fan speed is abnormal.
3. Evaporator is dirty.
1. Refrigerant leakage;
2. Indoor evaporator temperature sensor works abnormally;
3. The unit has been plugged up somewhere
Please refer to the malfunction analysis (discharge protection, overload).
1. Supply voltage is unstable.
2. Supply voltage is too low and load is too high.
3. Current is too high.
Refer to the corresponding malfunction analysis.
Refer to the malfunction analysis (overload, high temperature resistant).
Replace outdoor control panel AP1.
Discharging after the complete unit is de-energized for 20min, check whether the thermal grease on IPM Module of outdoor control panel AP1 is sufficient and whether the radiator is inserted tightly. If it’s no use, please replace control panel AP1.
16
Malfunction protection of
10
jumper cap
Gathering
11
refrigerant
Indoor ambient temperature
12
sensor is open/short circuited
Indoor evaporator temperature
13
sensor is open/short circuited
Outdoor ambient temperature
14
sensor is open/short circuited
Outdoor condenser temperature
15
sensor is open/short circuited
Outdoor discharge temperature
16
sensor is open/short circuited
Limit/decrease frequency due
17
to overload
Decrease frequency due
18
to overcurrent
C5
F0
F1
F2
F3
F4
F5
F6
F8
Blinks 15 times
Blinks 1 time
Blinks 1 time
Blinks once
Blinks twice
Blinks 3 times
Blinks 4 times
Blinks 5 times
Blinks 6 times
Blinks 8 times
Blinks 17
time
Blinks 6 times
Blinks 5 times
Blinks 7 times
Blinks 3
times
Blinks
once
Wireless remote receiver and button are effective, but can not dispose the related command
When the outdoor unit receive signal of Gathering refrigerant, the system will be forced to run under cooling mode for gathering refrigerant
- During cooling and drying operation, indoor unit operates while other loads will stop.
- During heating operation, the complete unit will stop operation.
- During cooling and drying operation, indoor unit will operate while other loads will stop;
- During heating operation, the complete unit will stop operation.
- During cooling and drying operating, compressor stops while indoor fan operates;
- During heating operation, the complete unit will stop operation
- During cooling and drying operation, compressor stops while indoor fan will operate;
- During heating operation, the complete unit will stop operation.
- During cooling and drying operation, compressor will sop after operating for about 3 minutes, while indoor fan will operate;
- During heating operation, the complete unit will stop after operating for about 3 minutes. All loads operate normally, while operation frequency for compressor is decreased All loads operate normally, while operation frequency for compressor is decreased
1. No jumper cap insert on mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of mainboard.
Nominal cooling mode
1. Indoor ambient temperature sensor hasn’t been connected well with indoor unit’s control panel AP1 (refer to the wiring diagram for indoor unit).
2. Room temperature sensor is damaged (refer to the resistance table of temp. sensor appendix 1) 3 Mainboard damaged
1. Evaporator temp. sensor hasn’t been connected well with indoor unit’s control panel AP1 (refer to the wiring diagram for indoor unit).
2. Evaporator temp. sensor is damaged (please refer to the resistance table of temp. sensor).
1. Outdoor ambient temp. sensor hasn’t been connected well or is damaged.
2. Please check it by referring to the resistance table for temperature sensor appendix 1).
1. Condenser temp. sensor hasn’t been connected well or is damaged.
2. Please check it by referring to the resistance table for temperature sensor appendix 2)
1. Outdoor discharge temp. sensor hasn’t been connected well or is damaged. Please check it by referring to the resistance table for temp. sensor appendix 3).
2. The head of temp. sensor hasn’t been inserted into the copper tube. Refer to the malfunction analysis (overload, high temperature resistant).
The input supply voltage is too low; System pressure is too high and overload.
17
e
e
e
Decrease frequency due
19
to high air discharge
Limit/decrease frequency due
20
to antifreezing
DC generatrix
21
voltage is too high
Voltage of DC
22
bus-bar is too low
Compressor Min frequence
23
in test state Compressor rated frequence
24
in test state Compressor
Max frequence
25
in test state Compressor
intermediate
26
frequence in test state
Overcurrent protection of
27
phase current for compressor
Charging malfunction of
28
capacitor
Malfunction of module temp.
29
sensor circuit
1. Overload or
All loads operate normally, while operation frequency for compressor is decreased
All loads operate normally, while operation frequency for compressor is decreased
During cooling, dehumidifying, compressor stop running fan motor works. During heating: all will stop
- During cooling and drying operation, compressor will stop while indoor fan will operate.
- During heating operation, the complete unit will stop.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complet unit will stop operation.
- During cooling and drying operation, compressor will stop while indoor fan will operate.
- During heating operation, the complet unit will stop.
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the complet unit will stop
Blinks
twice
Blinks 4
times
F9
FH
PH
PL
P0
P1
P2
P3
P5
PU
P7
Blinks 9 times
Blinks 2 times
Blinks 11 times
Blinks
0.25Hz
Blinks
0.25Hz
Blinks
0.25Hz
Blinks
0.25Hz
Blinks
0.25Hz
Blinks 2 times
Blinks 21 times
Blinks
0.25Hz
Blinks
0.25Hz
Blinks
0.25Hz
Blinks
0.25Hz
Blinks
0.25Hz
Blinks 17 times
Blinks 18 times
Blinks 13 times
Blinks 12
times
temperature is too high.
2. Refrigerant is insufficient;
3. Malfunction of electric expansion valve (EXV.
Poor air-return in indoor unit or fan speed is too low
1. Testing the voltage of position L and N on terminal XT, if higher than 265VAC, please cut off the power supply and restart until back to normal.
2. If input voltage is normal, testing the voltage of electrolytic capacitor C on AP1 after turn on the unit. There may be some problem and replace the AP1 if the electrolytic capacitor voltage range at 200-280V.
1. Measure the voltage of position L and N on wiring board (XT), if the voltage is higher than 150VAC, turn on the unit after the supply voltage is increased to the normal range.
2. If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if it’s normal, there’s malfunction for the circuit, please replace
the control panel (AP1) Showing during min. cooling or min. heating test Showing during nominal cooling or nominal heating test Showing during max. cooling or max. heating test
Showing during
middle cooling or
middle heating test
Refer to the
malfunction analysis
(IPM protection, loss
of synchronism
protection and
overcurrent protection
of phase current for
compressor.
Refer to the part
three—charging
malfunction analysis
of capacitor.
Replace outdoor
control panel AP1
18
Module high
e
temperature
30
protection
Decrease frequency due to high temp.
31
resistant during heating operation Static dedusting
32
protection
Overload
33
protection for compressor
System is
34
abnormal
35 IPM protection H5
Module temp.
36
is too high
Internal motor (fan motor) do
37
not operate
Desynchronizing
38
of compressor
39 PFC protection HC
Outdoor DC fan motor
40
malfunction
Power
41
protection
P8
H0
H2
H3
H4
H5
Blinks 11
H6
times
H7
Blinks 23
L3
times
Blinks 20
L9
times
Blinks 19 times
Blinks 10 times
Blinks twice
Blinks 3 times
Blinks 4 times
Blinks 5 times
Blinks 5 times
Blinks 7 times
Blinks 6 times
Blinks 8 times
Blinks 6 times
Blinks 4 times
Blinks 10 times
Blinks 14 times
Blinks 9 times
Blinks 14 times
After the complete
During cooling operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop
All loads operate normally, while operation frequency for compressor is decreased
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the complete unit will stop operation.
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the complete unit will stop operation.
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the complete unit will stop operation
Internal fan motor, external fan motor, compressor and electric heater stop operation, guide louver stops at present location.
During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complet unit will stop operation.
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the unit will stop operation Outdoor DC fan
motor malfunction lead to compressor stop operation, compressor stop operation and outdoor fan motor will stop 30s latter, 3 minutes latter fan motor and compressor will restart
unit is deenergized for
20mins, check
whether the thermal
grease on IPM
Module of outdoor
control panel AP1 is
sufficient and whether
the radiator is inserted
tightly. If it’s no use,
please replace control
panel AP1.
Refer to the
malfunction analysis
(overload, high
temperature resistant)
1. Wiring terminal
OVC-COMP is
loosened. In normal
state, the resistance
for this terminal should
be less than 1ohm.
2. Refer to the
malfunction analysis
(discharge protection,
overload)
Refer to the
malfunction analysis
(overload, high
temperature resistant)
Refer to the
malfunction analysis
(IPM protection, loss
of synchronism
protection and
overcurrent protection
of phase current for
compressor.
1. Bad contact of DC
motor feedback
terminal.
2. Bad contact of DC
motor control end.
3. Fan motor is
stalling.
4. Motor malfunction.
5. Malfunction of
mainboard rev
detecting circuit.
Refer to the
malfunction analysis
(IPM protection, loss
of synchronism
protection and
overcurrent protection
of phase current for
compressor.
Refer to the
malfunction analysis.
DC fan motor
malfunction or system
blocked or the
connector loosed
To protect the
electronical
components when
detect high power
19
e
e
e
Indoor unit and outdoor unit
42
does not match
Failure
43
start-up
Malfunction of phase current detection
44
circuit for compressor
Malfunction of voltage
45
dropping for DC bus-bar
Malfunction of
46
complete unit’s current detection
The four-way valve is
47
abnormal
Zerocrossing malfunction of
48
outdoor unit
Blinks 19
LP
times
LC
U1
U3
U5
U7
U9
Blinks 11 times
Blinks 13 times
Blinks 20 times
Blinks 13 times
Blinks 20 times
Blinks 18 times
Blinks 16
times
compressor and outdoor fan motor can’t work
- During cooling and drying operation, compressor will stop while indoor fan will operate.
- During heating operation, the complete unit will stop operation.
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the complet unit will stop
- During cooling and drying operation, compressor will stop while indoor fan will operate;
- During heating operation, the complet unit will stop.
- During cooling and drying operation, the compressor will stop while indoor fan will operate;
- During heating operating, the complete unit will stop operation.
If this malfunction occurs during heating operation, the complet unit will stop operation.
During cooling operation, compressor will stop while indoor fan will operate; during heating, the complete unit will stop operation.
Indoor unit and
outdoor unit doesn't
match
Refer to the
malfunction analysis.
Replace outdoor
control panel.
Supply voltage is
unstable.
There’s circuit
malfunction on
outdoor unit’s control
panel AP1, please
replace the outdoor
unit’s control panel
AP1.
1. Supply voltage is
lower than AC175V;
2. Wiring terminal 4V
is loosened or broken;
3.4V is damaged,
please replace 4V.
Replace outdoor
control panel AP1
Frequency
49
limiting(power)
Compressor
50
running
The temp. for turning on the
51
unit is reached
Frequency limiting(module
52
temperature)
Normal
53
comunication
54 Defrosting
Blinks once (during blinking, ON 10s and OFF
0.5s)
Blinks
once
Blinks
twice
Blinks 13 times
Blinks 8 times
Blinks 11 times
Blinks
once
- Defrosting will occur in heating mode. Compressor will operate while indoor fan will stop operation.
It’s the normal state.
20
8.4. How to check simply the main part
8.4.1 Indoor Unit:
8.4.1.1 Temperature sensor malfunction (F1/F2)
F1 and F2 malfunction
Is the wiring terminal between temp. sensor and the controller loosened or poorly contacted?
Yes
No
No
Is there short circuit due to trip over of the parts?
No
No
Is the temperature sensor normal according to the resistance table?
Insert the temperature sensor tightly
Malfunction is eliminated
Yes
Make the parts upright
Yes
Malfunction is eliminated
No
Replace it with a temp. sensor with the same model
Replace the main board with the same model
Yes
No
Malfunction is eliminated
Yes
Yes
End
21
8.4.1.2 Indoor fan does not operate (H6 Malfunction) Possible causes:
1. Fan motor is locked;
2. The feedback terminal of PG motor is not connected tightly;
3. The control terminal of PG motor is not connected tightly;
4. Motor is damaged;
5. Malfunction of the rotation speed detection circuit of the mainboard.
See the flow chart below:
H6” is displayed on the unit.
Stir the fan blade with a hand when the unit is DE-ENERGIZED.
Does the blade rotate smoothly?
No
Reinstall the motor and the blade to make it rotate smoothly.
Yes
No
Is the malfunction eliminated?
Is the wiring terminal of PG motor loose?
Yes
Insert the wiring terminal of indoor fan
No
Is the malfunction eliminated?
Energize and retart up the unit, test if the voltage between motor terminal 1 and 2 is 280 ~ 310VDC
No
Yes
It’s the malfunction of the main
No
board. Replace the main board with the same model
No
Is the malfunction eliminated?
Test if the voltage between motor terminal 2 and 3 is 15VDC
No
It’s the malfunction of the main board. Replace the main board with the same model
Yes
No
Is the malfunction eliminated?
It’s the malfunction of the motor. Replace the motor
Yes
Yes
Yes
Yes
End
22
8.4.1.3. Jumper cap malfunction (C5) Possible causes:
1. There is no jumper cap on the controller;
2. Jumper cap is not inserted properly and tightly;
3. Jumper cap is damaged;
4. Controller is damaged. See the flow chart below:
C5 is displayed on the unit.
Is there jumper cap on the mainbaord? Install a matching jumper cap.
Yes
Is the jumper cap inserted incorrectly or improperly?
No
Replace the jumper cap
Is the malfunction eliminated?
The mainboard is defined abnormal; replace it
No
End
No
No
No
Is the malfunction eliminated?
Yes
Re-insert the jumper cap.
Is the malfunction eliminated?
Yes
Yes
Yes
23
f
f
8.4.1.4 Communication Malfunction (E6)
1. Check if connection wire between indoor and outdoor units and wire inside the unit are connected well.
2. Check if mainboard of indoor or outdoor unit is damaged.
Communication malfunction of indoor unit
Power off the unit and check if the connecting wire of indoor and outdoor unit and wiring o electric box are correct.
Is wire connected correctly?
Connect wires according to the wiring diagram
Power off the unit. Change the communication cable o indoor units. Energize the unit and wait for 3 min
Yes
Does the broken-down indoor unit resume normal?
No
Yes
Replace mainboard of outdoor unit
Replace the broken-down mainboard of the indoor unit
Yes
Is malfunction removed
24
End
8.4.2 Outdoor Unit:
8.4.2.1 Key detection points
Test5
Test3
Test2
Test4
Test1
Test6
Test point SN Test point Related specification Test value in normal condition
Test 1 Between AC-L1 and N1 Neutral and live wire 165V ~ 253V
Test 2 Left side of R201, radiator U404 DC bus bar 230V ~ 380V
Test 3 Top of D304, Bottom of D304 IPM drive voltage + 15V 13,5V ~ 15,5V
Test 4 Top of C116, bottom of C116 Relay drive voltage +12V 11V ~ 13V
Test 5 Right side of R228, left side of D228 PFC drive voltage +15V 13,5V ~ 15,5V
Test 6 Left and top ends of U4, bottom of U4 Chip +3,3V 3,1V ~ 3,3V
Test 7 Right and top end of U4, bottom of U4 +5V 4,8V ~ 5,1V
Test 8 Bottom of R506, bottom of U4 Outdoor unit receiving signal Fluctuate between 0 and 3,3V
Test 9 Bottom of R523, bottom of U4 Outdoor unit sending signal Fluctuate between 0 and 3,3V
Test7
Test8 Test9
25
8.4.2.2. Capacitor charging malfunction (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main detection point:
Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC ~ 240VAC.
If the reactor (L) is correctly connected? If the connection is loose or fallen? If the reactor (L) is damaged?
Fault diagnosis proess:
Switch on the unit and wait 1 minute.
Use DC voltmeter to measure the voltage on the two ends of electrolytic capacitor.
Voltage higher than 200V Faulty with the voltage testing
No
Yes
circuit on control panel AP1
Replace the control panel AP1
Measure the AC voltage between terminal L and N on wiring board XT(power supply)
Voltage within 210 ~ 250VAC.
Yes
Switch off the power and wait 20 minutes; or use DC voltmeter to measure the voltage on the two ends of capacitor (test3), until the voltage is lower than 20V.
Check the connection of reactor (L in the Electrical Wiring Diagram)
If the wiring of reactor L is normal?
Replace the control panel AP1
Yes
Switch off the power and repair
No
the supply power to restore the voltage to 210VAC ~ 250 VAC
No
Connect the reactor L according to Electrical Wiring Diagram
Re-energize and switch on the unit
No
Re-energize and switch on the unit
No
If the fault is elmininated?
If the fault is eliminated
Yes
Yes
8.4.2.3 IPM Protection, desynchronizing malfunction, Compressor Phase Overcurrent (AP1 below refers to the
outdoor control panel)
Main detection point:
If the connection between control panel AP1 and compressor COMP is secure? If loose? If the connections are correct?
If the voltage input of the machine is within normal range? (use AC voltmeter to measure the voltage between terminal L
and N on the wiring board XT)
If the compressor coil resistance is normal? If the insulation of compressor coil’s against the copper tube is in good
condition?
26
If the working loads of the machine are too hight? If the radiation is good?
If the charge volume of refrigerant is correct?
Fault diagnosis process:
Energize and switch on
IPM Protection occurs after the machine has run for a periode of time?
Yes
Use AC voltmeter to measure the voltage between terminal L and N on the wiring board XT
If the voltage between terminal L and N on wiring board XT is within 210VAC 250VAC?
Yes
Please confirm:
1. In the indoor and outdoor heat exchangers are obstructed by other objects which affect the heat exchange of indoor and outdoor unit.
2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high and exceeds the permissible range?
4. If the charge volume of refrigerant is too much, resulting in that the system the system pressure is too high?
5. Other conditions resulting in that the system pressure is becomes too high.
Voltage between the two ends of electrolytic capacitor (tes3) is higher than 250V.
Stop the unit and disconnect the power supply. Then, check the connection of capacitor C2 according to wiring diagram.
Remove the wires on the two ends of capacitor C2, then use capacitance meter to measure the capacitor C2. Verify as per the parameters sheet (spec).
Refer to the electrical wiring diagram and check if the connection between AP1 and COMP is loose and if the connection order is correct.
If the connection between AP1 and COMP is unsecure or the connection order is wrong?
Use ohmmeter to measure the resistance between the three terminals on compressor COMP, and compare the measurments with the compressor resistance on servuice manual
Use ohmmeter to measure the resistance between the two terminals of compressor COMP and copper tube.
No
If capacitor C2 is failled?
Connect the control panel AP1 and compressor COMP correctly according to the electrical wiring diagram. Then, energize and start the unit.
If the resistance is normal?
Resistance higher than 500MΩ?
Start and run the unit. Before protection occurs, use DC voltmeter to measure the voltage between the two ends of electrolytic capacitor on control panel AP1.
The connection of capacitor C2 is loose
Stop the unit and disconnect the power supply. Wait 20 minutes or use DC voltmeter to measure the voltage between the two ends of capacitor C2, until the voltage is lower than 20V
Replace the capacitor C2. Then, energize and start the unit
No
No
Replace the control panel AP1
The corrective actions according to Technical Service Manual, and then energize and start the unit.
Replace the control panel AP1.
No
Replace the compressor COMP
Replace the control panel AP1
End
Reconnect the capacitor C2 according to electrical wiring diagram, then energize and start the unit.
If the unit can work normally.
No
Check the supply voltage and restore it to 210VAC 250VAC
If the unit can work normall?
If the unit can work normally?
If the unit can work normally
If the unit can work normally
Yes
Yes
Yes
27
?
8.4.2.4. High temperature and overload protection diagnosis (AP1 herinafter refers to control board of the outdoor unit)
Main detection point:
Is outdoor ambient temperature in normal range?
Are the outdoor and indoor fans operating normally?
Is the heat dissipation environment inside and ouside the unit is good?
Overheat and high temperature protection
Is outdoor ambient temperature higher than 53°C?
Normal protection, please operate it after the outdoor ambient temp. is normalized.
20 minutes after the complete unit is powerd off
Is heat dissipation of the indoor unit and outdoor unit abnormal?
Does the outdoor fan work normally
Replace the control panel AP1
End
8.4.2.5. Start up failure (following AP1 for outdoor unit control board)
Main detection point:
Whether the compressor wiring is connected correct?
Is time for compressor stopping enough?
Is compressor broken?
Is the refrigerant charging is too much?
Improve the heat dissipation environment of the unit
1. Check if the fan terminal OFAN is connected correctly.
2. Resistance between any ohm gauge and should be less than 1kΩ.
Replace the fan capacitor C1
Replace the outdoor fan
Power on the unit
Is stop time of the compressor longer than 3 minutes
Restart it up after 3 minutes?
Does the start up fail?
Are the wires for the compressor connected correctly? Is connection sequence right?
Connect the wires as per the connection diagram.
Replace the control panel AP1
If the fault is eliminated?
Replace the compressor
End
28
8.4.2.6 Diagnosis for compressor Out of step (synchronism)(AP1 hereinafter refers to control board of the outdoor unit)
p
p
p
Main detection point:
Whether the unit voltage is too high?
Whether the work voltage is too low?
Out of step occurs once the unit is powerd on
Out of step (synchronism) occurred during operation
Is stop time of the compressor longer than 3 minutes
Are the compressor wires COMP(UVW) connected correctly? Is connection sequence right? Is the connection made in clockwise direction?
Connect the wires correctly
Replace the control panel AP1
If the fault is eliminated?
Is the outdoor fan working normally
Is the outdoor unit blocked by forein objects
If the input voltage of unit is normal?
If the refrigerant is too much?
Replace the control panel AP1
Check if the fan terminal OFAN is connected correctly
Remove foreign objects (clean heat exchanger and increase
Start to run until the unit resume normal voltage
Charge the refrigerant with technical manual
Replace the capacitor C1
Replace the outdoor fan
Replace the compressor
End
If the fault is eliminated?
Replace the compressor
Ye s
End
8.4.2.7 Overload and discharge malfunction detect (following AP1 for outdoor unit control board)
Main detection point:
Wether the electronic expansion valve is connected well or not? Is electronic expansion valve damaged?
Is the refrigerant leaked?
20 minutes after the complete unit is powered off
If the overload protector SAT is well connected?
Under amb. Temp., test the resistance of overload
rotector with ohmeic meter, resistance value is 1000
Is the terminal FA for the electronic ex
ansion valve connected correctly?
Connect the wires correctly?
Resistances between the first 4 pins close to the terminal hole and the fifth
in are almost the same, less than 100Ω.
Replace overload protector SAT
Refrigerant leakage, refilling the refrigerant, refer to specification
Replace the electronic expansion valve
Yes
If the fault is eliminated?
If the fault is eliminated?
Replace the control panel AP1
End
29
8.4.2.8 Power factor correction (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the
outdoor unit)
Main detection point:
Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken?
The failure diagnosis is as follows:
Start
Check wiring of the reactor (L) of the outdoor unit and the PFC capacitor
Whether there is any damage or short-circuit?
Ye s
Replace it as per the wiring diagram and reconnect the wires.
If the fault is eliminated?
Ye s
Remove the PFC capacitor and measure resistance between the two terminals.
No
Is the resistance around zero?
Disconnect the terminals for the reactor and measure the resistance between the two terminals of the reactor.
Whether there is any damage or short-circuit?
Replace the control panel AP1
End
Ye s
The capacitor is short circuited and the capacitor should be replaced.
Ye s
Replace the reactor
Restart the unit
Restart the unit
No
If the fault is eliminated?
If the fault is eliminated?
Ye s
30
8.4.2.9 Communication malfunction (following AP1 for outdoor unit control board)
Main detection point:
Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is
there any damage?
Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
The flow chart for the malfunction detect:
The AP1 voltage detection circuit is at fault
If the fault is eliminated?
Start
Did the unit operate normally before the failure occurs.
Ye s
Are wires broken?
Check the communication circuit of the outdoor unit
The communication circuit is abnormal.
Ye s
Ye s
Replace the main board (AP1) of the outdoor unit
Check the wiring of the indoor and outdoor units with reference to the wiring diagrams
Is the connection right?
Correctly connect the corresponding wires for the indoor and outdoor units with reference to the wiring diagram.
If the fault is eliminated?
Ye s
Replace the main board of the indoor unit.
If the fault is eliminated?
Ye s
Ye s
End
31
Appendix 1: Resistance table for indoor/outdoor ambient temperature sensors (numerical value of resistance) (15K)
Tem p . (° C ) Resistance (kΩ) Temp . (° C ) Resistance (kΩ) Tem p. ( °C) Resistance (kΩ) Temp . (° C ) Resistance (kΩ)
-19 138.100 20 18.750 59 3.848 98 1.071
-18 128.600 21 17.930 60 3.711 99 1.039
-17 121.600 22 17.140 61 3.579 100 1.009
-16 115.000 23 16.390 62 3.454 101 0.980
-15 108.700 24 15.680 63 3.333 102 0.952
-14 102.900 25 15.000 64 3.217 103 0.925
-13 97.400 26 14.360 65 3.105 104 0.898
-12 92.220 27 13.740 66 2.998 105 0.873
-11 87.350 28 13.160 67 2.896 106 0.848
-10 82.750 29 12.600 68 2.797 107 0.825
-9 78.430 30 12.070 69 2.702 108 0.802
-8 74.350 31 11.570 70 2.611 109 0.779
-7 70.500 32 11.090 71 2.523 110 0.758
-6 66.880 33 10.630 72 2.439 111 0.737
-5 63.460 34 10.200 73 2.358 112 0.717
-4 60.230 35 9.779 74 2.280 113 0.697
-3 57.180 36 9.382 75 2.206 114 0.678
-2 54.310 37 9.003 76 2.133 115 0.660
-1 51.590 38 8.642 77 2.064 116 0.642
0 49.020 39 8.297 78 1.997 117 0.625
1 46.600 40 7.967 79 1.933 118 0.608
2 44.310 41 7.653 80 1.871 119 0.592
3 42.140 42 7.352 81 1.811 120 0.577
4 40.090 43 7.065 82 1.754 121 0.561
5 38.150 44 6.791 83 1.699 122 0.547
6 36.320 45 6.529 84 1.645 123 0.532
7 34.580 46 6.278 85 1.594 124 0.519
8 32.940 47 6.038 86 1.544 125 0.505
9 31.380 48 5.809 87 1.497 126 0.492
10 29.900 49 5.589 88 1.451 127 0.480
11 28.510 50 5.379 89 1.408 128 0.467
12 27.180 51 5.197 90 1.363 129 0.456
13 25.920 52 4.986 91 1.363 130 0.444
14 24.730 53 4.802 92 1.282 131 0.433
32
15 23.600 54 4.625 93 1.244 132 0.422
16 22.530 55 4.456 94 1.207 133 0.412
17 21.510 56 4.294 95 1.171 134 0.401
18 20.540 57 4.139 96 1.136 135 0.391
19 19.630 58 3.990 97 1.103 136 0.382
Appendix 2: Resistance table for indoor/outdoor tube temperature sensor (20K)
Tem p . (° C ) Resistance (kΩ) Temp . (°C ) Resistance (kΩ) Temp . (°C ) Resistance (kΩ) Tem p . (° C ) Resistance (kΩ)
-19 181.400 20 25.010 59 5.130 98 1.427
-18 171.400 21 23.900 60 4.948 99 1.386
-17 162.100 22 22.850 61 4.773 100 1.346
-16 153.300 23 21.850 62 4.605 101 1.307
-15 145.000 24 20.900 63 4.443 102 1.269
-14 137.200 25 20.000 64 4.289 103 1.233
-13 129.900 26 19.140 65 4.140 104 1.198
-12 123.000 27 18.130 66 3.993 105 1.164
-11 116.500 28 17.550 67 3.861 106 1.131
-10 110.300 29 16.800 68 3.729 107 1.099
-9 104.600 30 16.100 69 3.603 108 1.069
-8 99.130 31 15.430 70 3.481 109 1.039
-7 94.000 32 14.790 71 3.364 110 1.010
-6 89.170 33 14.180 72 3.252 111 0.983
-5 84.610 34 13.590 73 3.144 112 0.956
-4 80.310 35 13.040 74 3.040 113 0.930
-3 76.240 36 12.510 75 2.940 114 0.904
-2 72.410 37 12.000 76 2.844 115 0.880
-1 68.790 38 11.520 77 2.752 116 0.856
0 65.370 39 11.060 78 2.663 117 0.833
1 62.130 40 10.620 79 2.577 118 0.811
2 59.080 41 10.200 80 2.495 119 0.770
3 56.190 42 9.803 81 2.415 120 0.769
4 53.460 43 9.420 82 2.339 121 0.746
5 50.870 44 9.054 83 2.265 122 0.729
6 48.420 45 8.705 84 2.194 123 0.710
7 46.110 46 8.370 85 2.125 124 0.962
8 43.920 47 8.051 86 2.059 125 0.674
9 41.840 48 7.745 87 1.996 126 0.658
10 39.870 49 7.453 88 1.934 127 0.640
11 38.010 50 7.173 89 1.875 128 0.623
12 36.240 51 6.905 90 1.818 129 0.607
13 34.570 52 6.648 91 1.736 130 0.592
14 32.980 53 6.403 92 1.710 131 0.577
15 31.470 54 6.167 93 1.658 132 0.563
16 30.040 55 5.942 94 1.609 133 0.549
17 28.680 56 5.726 95 1.561 134 0.535
18 27.390 57 5.519 96 1.515 135 0.521
19 26.170 58 5.320 97 1.470 136 0.509
Note: The informations above are only for reference.
33
Appendix 3: form for indoor/outdoor unit’s air exhaust temperature sensor numerical value of resistance
Tem p . (° C ) Resistance (kΩ) Tem p. (° C) Resistance (k)Tem p . (° C ) Resistance (kΩ) Temp. (°C ) Resistance (kΩ)
-29 853.500 10 98.000 49 18.340 88 4.754
-28 799.800 11 93.420 50 17.650 89 4.609
-27 750.000 12 89.070 51 16.990 90 4.469
-26 703.800 13 84.950 52 16.360 91 4.334
-25 660.800 14 81.050 53 15.750 92 4.204
-24 620.800 15 77.350 54 15.170 93 4.079
-23 580.600 16 73.830 55 14.620 94 3.958
-22 548.900 17 70.500 56 14.090 95 3.841
-21 519.600 18 67.340 57 13.580 96 3.728
-20 486.500 19 64.330 58 13.090 97 3.619
-19 458.300 20 61.480 59 12.620 98 3.514
-18 432.000 21 58.770 60 12.170 99 3.413
-17 407.400 22 56.190 61 11.740 100 3.315
-16 384.500 23 53.740 62 11.320 101 3.220
-15 362.900 24 51.410 63 10.930 102 3.129
-14 342.800 25 49.190 64 10.540 103 3.040
-13 323.900 26 47.080 65 10.180 104 2.955
-12 306.200 27 45.070 66 9.827 105 2.872
-11 289.600 28 43.160 67 9.489 106 2.792
-10 274.000 29 41.340 68 9.165 107 2.640
-9 259.300 30 39.610 69 8.854 108 2.568
-8 245.600 31 37.960 70 8.555 109 2.498
-7 232.600 32 36.380 71 8.268 110 2.431
-6 220.500 33 34.880 72 7.991 111 2.365
-5 209.000 34 33.450 73 7.726 112 2.302
-4 198.300 35 32.090 74 7.470 113 2.241
-3 199.100 36 30.790 75 7.224 114 2.182
-2 178.500 37 29.540 76 6.998 115 2.124
-1 169.500 38 28.360 77 6.761 116 2.065
0 161.000 39 27.230 78 6.542 117 2.069
1 153.000 40 26.150 79 6.331 118 2.015
2 145.400 41 25.110 80 6.129 119 1.963
3 138.300 42 24.130 81 5.933 120 1.912
4 131.500 43 23.190 82 5.746 121 1.863
34
5 125.100 44 22.290 83 5.565 122 1.816
6 119.100 45 21.430 84 5.390 123 1.770
7 113.400 46 20.600 85 5.222 124 1.725
8 108.000 47 19.810 86 5.060 125 1.682
9 102.800 48 19.060 87 4.904 126 1.640
Via Gettuglio Mansoldo
(Loc. La Macia) 37040 Arcole
Verona, Italy
Tel. +39 - 045.76.36.585 r.a.
Fax +39 - 045.76.36.551 r.a.
www.maxa.it
e-mail: maxa@maxa.it
Loading...