10421100 Rev.D
Installation Guide for
Dental Vacuum Pumps
MaxiMizer/MiniMizer
1
™
145 Mid County Drive
Orchard Park, New York 14127
716-662-6650
800-847-1000
888-279-1260
716-662-8440
matrx@matrxmedical.com
Toll-Free:
Technical Support:
Fax:
E-mail:
3/4” NPT FITTING & HOSE
CLAMP - CONNECT TO
VACUUM LINE FROM
OPERATORIES
WATERSUPPLY
1/2” SHUT-OFF
VALVE
1/4” POLYFLOW
TUBING
1/4” POLYFLOW
CONNECTOR
AND 1/2” NPT
BUSHING
EXHAUST
SILENCER
P-TRAP
LOW
VOLTAGE
CONTROL
1” ID HOSE
3/4” NPT FITTING
& HOSE CLAMP
1” ID
HOSE
Single Pump Installation with P-Trap Drain
Includes Hookup Kit 77000145
HOSE
CLAMP
Site Requirements
"
"
"
"
"
Ambient Temperature Range:
Cold Water:
Waste:
Electrical:
VacuumPiping:
40°- 104°F / 4° -40° C.
Provide heatingor ventilationas required.
See “Water Requirements”above.
Each vacuum pump location requires a 1-1/2"
sewer linewith "P" trap terminatingwith 3/4" femaleNPT or
a single standard utility floor sink. For platform-mounted
unit draining toa P- trap, a1-1/4" female NPT terminationis
needed.
A dedicated circuit is required for operation.
See “ElectricalSpecifications” above.
See “VacuumPiping Installation”, page3.
NOTE: Installations mustbe madeto all localcodes.
ELECTRICAL CONNECTION
TO OUTLET OR BREAKER
PANEL
12”/30cm
8-12” MAX
(20-30cm)
28”/70cm
APPROX.
WATER
SUPPLY
1/2 NPT
ELECTRICAL
HOOKUP
VACUUM
PIPING
3/4 NPT
2” NPT PVC
VENT TO
OUTSIDE
OPTIONAL
AIR/WATER
SEPARATOR
Elevation View
2" PVC BY
CONTRACTOR
ELECTRICAL CONNECTION
TO OUTLET OR BREAKER
PANEL
WATERSUPPLY
1/2” SHUT-OFF
VALVE
1/4”
POLYFLOW
TUBING
LOW
VOLTAGE
CONTROL
AIR/WATER
SEPARATOR
1/4” POLYFLOW
CONNECTOR
AND 1/2” NPT
BUSHING
3/4 NPT
EXTENSION BY
CONTRACTOR
1” HOSE WITH
3/4” NPT FITTING
& HOSE CLAMP
(EACH END)
3/4” NPT FITTING & HOSE
CLAMP - CONNECT TO
VACUUM LINE FROM
OPERATORIES
1” ID HOSE
3/4” NPT FITTING
& HOSE CLAMP
Single Pump Installation with Air/Water Separator
Includes Hookup Kit 77000145
OPTIONAL :DRAIN CONFIGURATION
AIR/WATERSEPARATOR INTO P-TRAP
VENT TO
OUTSIDE
1” EXHAUST
HOSE
Water Requirements
20-120 psi /
1.4-8.3 bar
Pressure Range 20-120 psi /
1.4-8.3 bar
35-80° F /
2-12° C
Water Temperature
Range
35-80° F /
2-12° C
Electrical Specifications
1HP
NOMINAL:
115/230 VAC
MIN/MAX:
104-126 VAC
188-253 VAC
2HP
NOMINAL:
230 VAC
MIN/MAX:
188-253 VAC
Motor Horsepower
Single Phase Volts
Maximum Current / Pump
50/60 Hz
15.0 A
8.2/7.5 A
8.2/8.1 A
~
13.1/11.9 A
11.2/11.1A
60 Hz 115 VAC
60 Hz 208/230 VAC
50 Hz 208/230 VAC
20 A 20 AMinimum Circuit Breaker
Users SizingGuide
Listed below are the typical number of users that can
be supported by MaxiMizers and MiniMizers. Dual
pump and triple pump installations are used in large
dental practices where redundancy and additional
capacity is desired.
2 1/2
Single Unit
4
5
-
Dual Units
Triple Units
8
12
This guide covers the following pump
Models:
!
!
!
!
!
!
!
!
!
!
!
MAX 1000 (Single Unit, 1 HP) - P/N 77001460
MAX 2000 (Single Unit, 2 HP) - P/N 77001462
MAX 1000-2 (Dual Units, 1 HP) - P/N 77001468
MAX 2000-2 (Dual Units, 2 HP) - P/N 77001469
MAX 2000-3 (Triple Units, 2 HP) - P/N 77001472
MaxiMizer 1000 Platform - P/N 77001473
MaxiMizer 2000 Platform - P/N 77001474
MIN 1000 (Single Unit, 1 HP) - P/N 77001464
MIN 2000 (Single Unit, 2 HP) - P/N 77001466
MiniMizer 1000 Platform - P/N 77001475
MiniMizer 2000 Platform - P/N 77001476
PUMP SPECIFICATIONS INSTALLATION -Single pumps
FLOOR DRAIN
Physical Dimensions
MiniMizer/
MaxiMizer
2000
Height
Width
Depth
Weight (Pump Only)
Shipping Weight (with
accessories)
Single Pump
Dual Pumps
Triple Pumps
MiniMizer/
MaxiMizer
1000
15in/38cm
12in/31cm
14in/36cm
54lbs/24kg
70lbs/32kg
150 lbs / 68 kg
16.5 in / 42 cm
12in/31cm
14in/36cm
65lbs/30kg
76lbs/35kg
162 lbs / 74 kg
227 lbs /103 kg
24in/61cm
26.5 in / 67 cm
16in/40cm
212 lbs / 96 kg
Height
Width
Depth
Shipping Weight
24in/61cm
26.5 in / 67 cm
16in/40cm
200 lbs / 91 kg
Dual Platform Unit
Use of devices or presence of the conditions
listed adds to the user count as indicated:
Device
User Count
"
"
"
"
"
"
High-volume Evacuator Outlet
Saliva Ejector
Hand Wash Station
Nitrous Oxide Scavenger
Main vacuum line approx. 50 ft (15 m)
Branch vacuum line extending
50 ft (15 m) beyond main line
approx.
1
1/2
1
1/2
1
1
MiniMizer/
MaxiMizer
2000
MiniMizer/
MaxiMizer
1000
MiniMizer/
MaxiMizer
2000
MiniMizer/
MaxiMizer
1000
MiniMizer/
MaxiMizer
2000
MiniMizer/
MaxiMizer
1000
MiniMizer/
MaxiMizer
2000
MiniMizer/
MaxiMizer
1000