Matrx MaxiMizer, MiniMizer Installation Manual

Page 1
10421100 Rev.D
Installation Guide for
Dental Vacuum Pumps
MaxiMizer/MiniMizer
1
™
145 Mid County Drive Orchard Park, New York 14127 716-662-6650
Toll-Free: Technical Support: Fax: E-mail:
3/4” NPT FITTING & HOSE CLAMP - CONNECT TO VACUUM LINE FROM OPERATORIES
WATERSUPPLY 1/2” SHUT-OFF VALVE
1/4” POLYFLOW TUBING
1/4” POLYFLOW CONNECTOR AND 1/2” NPT BUSHING
EXHAUST SILENCER
P-TRAP
LOW VOLTAGE CONTROL
1” ID HOSE
3/4” NPT FITTING & HOSE CLAMP
1” ID HOSE
Single Pump Installation with P-Trap Drain
Includes Hookup Kit 77000145
HOSE CLAMP
Site Requirements
"
" "
"
"
Ambient Temperature Range:
Cold Water:
Waste:
Electrical:
VacuumPiping:
40°- 104°F / 4° -40° C.
Provide heatingor ventilationas required.
See “Water Requirements”above.
Each vacuum pump location requires a 1-1/2" sewer linewith "P" trap terminatingwith 3/4" femaleNPT or a single standard utility floor sink. For platform-mounted unit draining toa P- trap, a1-1/4" female NPT terminationis needed.
A dedicated circuit is required for operation.
See “ElectricalSpecifications” above.
See “VacuumPiping Installation”, page3.
NOTE: Installations mustbe madeto all localcodes.
ELECTRICAL CONNECTION TO OUTLET OR BREAKER PANEL
12”/30cm
8-12” MAX (20-30cm)
28”/70cm APPROX.
WATER SUPPLY 1/2 NPT
ELECTRICAL HOOKUP
VACUUM PIPING 3/4 NPT
2” NPT PVC VENT TO OUTSIDE
OPTIONAL AIR/WATER SEPARATOR
Elevation View
2" PVC BY CONTRACTOR
ELECTRICAL CONNECTION TO OUTLET OR BREAKER PANEL
WATERSUPPLY 1/2” SHUT-OFF VALVE
1/4” POLYFLOW TUBING
LOW VOLTAGE CONTROL
AIR/WATER SEPARATOR
1/4” POLYFLOW CONNECTOR AND 1/2” NPT BUSHING
3/4 NPT
EXTENSION BY CONTRACTOR
1” HOSE WITH 3/4” NPT FITTING & HOSE CLAMP (EACH END)
3/4” NPT FITTING & HOSE CLAMP - CONNECT TO VACUUM LINE FROM OPERATORIES
1” ID HOSE
3/4” NPT FITTING & HOSE CLAMP
Single Pump Installation with Air/Water Separator
Includes Hookup Kit 77000145
OPTIONAL :DRAIN CONFIGURATION
AIR/WATERSEPARATOR INTO P-TRAP
VENT TO OUTSIDE
1” EXHAUST HOSE
Water Requirements
20-120 psi /
1.4-8.3 bar
Pressure Range 20-120 psi /
1.4-8.3 bar
35-80° F /
2-12° C
Water Temperature Range
35-80° F /
2-12° C
Electrical Specifications
1HP
NOMINAL: 115/230 VAC
MIN/MAX: 104-126 VAC 188-253 VAC
2HP
NOMINAL: 230 VAC
MIN/MAX: 188-253 VAC
Motor Horsepower
Single Phase Volts
Maximum Current / Pump
50/60 Hz
15.0 A
8.2/7.5 A
8.2/8.1 A
~
13.1/11.9 A
11.2/11.1A
60 Hz 115 VAC 60 Hz 208/230 VAC 50 Hz 208/230 VAC
20 A 20 AMinimum Circuit Breaker
Users SizingGuide
Listed below are the typical number of users that can be supported by MaxiMizers and MiniMizers. Dual pump and triple pump installations are used in large dental practices where redundancy and additional capacity is desired.
2 1/2
Single Unit
4
5
-
Dual Units Triple Units
8
12
This guide covers the following pump Models:
!
!
!
!
!
!
!
!
!
!
!
MAX 1000 (Single Unit, 1 HP) - P/N 77001460 MAX 2000 (Single Unit, 2 HP) - P/N 77001462 MAX 1000-2 (Dual Units, 1 HP) - P/N 77001468 MAX 2000-2 (Dual Units, 2 HP) - P/N 77001469 MAX 2000-3 (Triple Units, 2 HP) - P/N 77001472
MaxiMizer 1000 Platform - P/N 77001473 MaxiMizer 2000 Platform - P/N 77001474 MIN 1000 (Single Unit, 1 HP) - P/N 77001464 MIN 2000 (Single Unit, 2 HP) - P/N 77001466 MiniMizer 1000 Platform - P/N 77001475 MiniMizer 2000 Platform - P/N 77001476
PUMP SPECIFICATIONS INSTALLATION -Single pumps
FLOOR DRAIN
Physical Dimensions
MiniMizer/ MaxiMizer
2000
Height Width Depth Weight (Pump Only) Shipping Weight (with
accessories)
Single Pump Dual Pumps Triple Pumps
MiniMizer/ MaxiMizer
1000
15in/38cm
12in/31cm
14in/36cm
54lbs/24kg
70lbs/32kg
150 lbs / 68 kg
16.5 in / 42 cm
12in/31cm
14in/36cm
65lbs/30kg
76lbs/35kg
162 lbs / 74 kg
227 lbs /103 kg
24in/61cm
26.5 in / 67 cm
16in/40cm
212 lbs / 96 kg
Height Width Depth Shipping Weight
24in/61cm
26.5 in / 67 cm
16in/40cm
200 lbs / 91 kg
Dual Platform Unit
Use of devices or presence of the conditions listed adds to the user count as indicated:
Device
User Count
" " " " " "
High-volume Evacuator Outlet Saliva Ejector Hand Wash Station Nitrous Oxide Scavenger Main vacuum line approx. 50 ft (15 m) Branch vacuum line extending 50 ft (15 m) beyond main line
approx.
1
1/2
1
1/2
1 1
MiniMizer/ MaxiMizer
2000
MiniMizer/ MaxiMizer
1000
MiniMizer/ MaxiMizer
2000
MiniMizer/ MaxiMizer
1000
MiniMizer/
MaxiMizer
2000
MiniMizer/ MaxiMizer
1000
MiniMizer/ MaxiMizer
2000
MiniMizer/
MaxiMizer
1000
Page 2
WATERSUPPLY 1/2” SHUT-OFF VALVE
1/4” POLYFLOW CONNECTOR AND 1/2” NPT BUSHING
AIR/WATER SEPARATOR
1” HOSE WITH 3/4” NPT FITTING & HOSE CLAMP (EACH END)
VACUUM LINE TO OPERATORIES
1/4” POLYFLOW TUBING
LOW VOLTAGE CONTROL
3/4” CHECK VALVE(ALL INLETS)
ELECTRICAL CONNECTION TO OUTLET OR BREAKER PANEL
1” HOSE WITH 3/4” NPT FITTING & HOSE CLAMP (EACH END)
3/4” NPT EXTENSION BY CONTRACTOR
FLOOR DRAIN
VENT TO OUTSIDE
MaxiMizer Triple Units
Includes Triple Hookup Kit: 77000982 and Waste/Water/Vacuum Hookup Kit: 77000145
R e f e r S e r v i c i n g t o
Ref e r S erv ic i ng to
Q u a l if i e d S e r v i c e P e r
s o n n e l
Qualifi
e d Service
Personnel
C
A
U
T
I
O
N
!
S H O C K H A Z A R D
C
AUT
I
ON!
SH OC K HA Z AR D
R e f e r S e r v i c in g to
Re fer Servi
cing
t o
Q u a l if i e d Se rv ic e P e r so n n e l
Qu a l i fi e d S erv i ce P e rs on n e l
C A U T I O N ! S H O C K H A Z A R D
CA U T I ON!
SHOCK
HAZ
AR D
R e f e r S e r v ic in g t o
Ref er S ervi c i n g to
Q u a li f ie d S e r vi c e P e
rs o n n e l
Qu a li fi ed Servi
c e P e rson
n el
C
A
U
T
I
O
N
!
S H O C K H A Z A R D
CAUT
I
ON!
SHO
CK
HAZ
A RD
Recommended Triple MaxiMizer Hookup to
Air/Water Separator
Air / Water Separator P/N 77000246
1 1/4 NPT
1 1/4” WYE
3/4 x 1 1/4 NPT BUSHING
1” HOSE WITH 3/4” NPT FITTING & HOSE CLAMP (EACH END)
2
INSTALLATION -Dual/Triple pumps
ELECTRICAL CONNECTION TO OUTLET OR BREAKER PANEL
VACUUM LINE TO OPERATORIES
LOW VOLTAGE CONTROL
EXHAUST SILENCER
1/4” POLYFLOW TUBING
WATERSUPPLY 1/2” SHUT-OFF VALVE
1/4” POLYFLOW CONNECTOR AND 1/2” NPT BUSHING
1” HOSE WITH 3/4” NPT FITTING & HOSE CLAMP (EACH END)
3/4” CHECK VALVE(ALL INLETS AND OUTLETS)
CONNECT TO COMMON P-TRAP DRAIN (AS SHOWN), OR SEPARATEP­TRAPS
1” HOSE WITH 3/4” NPT FITTING & HOSE CLAMP (EACH END)
MaxiMizer Dual Units Installed with P-Trap Drain
R e f e r S e r v i c i n g t o
Refer
Servi
c ing
t o
Q u a l i f ie d S e r v i c e P
e r s o n n e l
Q u alified
Servi
c e Personnel
C
A
U
T
IO
N
!
SH O C K H A Z A R D
C
A
UTION!
SHO
C K HA Z A R D
R e f e r S e r v ic in g t o
Refer
S ervi c ing
t o
Q u a l i fi e d S e r v i ce P
e r s o n n e l
Qua
l i fied
S e r v ice P ersonne
l
C
A
U
T
IO
N
!
S H O C K H A Z A R D
CAUT
I
O
N
!
S HOCK
HAZA
R D
R e f e r S e r v i c in g to
Ref er Servi
cin g to
Q u a l i f ie d S e r v i ce P
e r s o n n e l
Qualified
Servic
e P ersonnel
C
A
U
T
I
O
N
!
S H O C K H A Z A R D
C
A
UTION!
S H O CK
HAZA
R D
Triple MaxiMizer with P-Trap Installation
TO DRAIN
MaxiMizer Dual Units Installed with Air/Water Separator
Includes Dual Hookup Kit: 77000034 (Max 1000-2) 77000950 (Max 2000-2) and Waste/Water/Vacuum Hookup Kit: 77000145
Includes Dual Hookup Kit: 77000034 (Max 1000-2) 77000950 (Max 2000-2) and Waste/Water/Vacuum Hookup Kit: 77000145
10421100 Rev.D
WATER SUPPLY 1/2 NPT
ELECTRICAL HOOKUP
2” NPT PVC VENT TO OUTSIDE
Elevation View - Dual Vacuum Pumps
28”/70cm APPROX.
8-12” MAX (20-30cm)
WATER SUPPLY 1/2 NPT
12”/30cm
OPTIONAL AIR/WATER SEPARATOR
3/4” NPT CHECK VALVE
ELECTRICAL
HOOKUP
3/4” NPT CHECK VALVE
Page 3
1 2 3 4 5 6 7 8
9 10 11 12
Trunk Line Pipe Sizing
3/4
1
3/4
1 1-1/4 1-1/4 1-1/2 1-1/2 1-1/2
2
2
2
Number of User Counts
Pipe Size (NPT) PVC Schedule 40 or Copper Type K, L or M
3
INSTALLATION -Platform pumps
10421100 Rev.D
Platform-Mounted Dual MaxiMizers
Includes Hookup Kit 77000849 (MaxiMizer) or 77000863 (MiniMizer)
1 1/2” VACUUM LINE FROM OPERATORIES
INLET CONNECTION
2" PVC BY CONTRACTOR
1” EXTENSION BY CONTRACTOR
AIR/WATER SEPARATOR
FLOOR DRAIN
FLOOR DRAIN WITH
AIR/WATERSEPARATOR
1 1/2” EXHAUST HOSE
VENT TO OUTSIDE
ADAPTER, 1 1/4 MNPT x 1 1/2 SLIP
3/8" POLYFLOW TUBING
WATERSUPPLY 1/2" SHUTOFF VALVE
ALTERNATE EXHAUST CONNECTION
3/8" POLYFLOWx 1/4 MNPT CONNECTOR (2)
BUSHING 1/4 x 1/2 NPT
HOSE CLAMP
P-TRAP DRAIN WITH
AIR/WATERSEPARATOR
VENT TO OUTSIDE
1 1/2” EXHAUST HOSE
P-TRAP DRAIN
1 1/2” EXHAUST HOSE
ELECTRICAL HOOKUP BOX
VACUUM PIPING 1 1/4” NPT
OPTIONAL AIR/WATER SEPARATOR
28”/70cm APPROX.
12”/30cm
11-13” MAX (28-33cm)
WATER SUPPLY 1/2 NPT
(2) INDEPENDENT BRANCH CIRCUIT LEADS INTO SINGLE GANG BOX THROUGH TOP KNOCKOUTS
Elevation View - Platform Pump Installation
3/4"3/4"3/4"3/4"
1/4” POLYFLOW TUBING TO VACUUM PIPING
OPTIONAL PILOT RELAY
TO CONTROL PANEL
MIN. SLOPE 1/4"/10FT.
3/4"
SERVICE LINES: 3/4” PIPE TRUNK LINE: 3/4” PIPE FOR FIRST 2 OPERATORIES; INCREASE SIZE INCREMENTALLYFOR 4, 6, 8, 10 AND 12 OPERATORIES (SEE CHART BELOW)
TO OPERATORIES
Operatory VacuumPipingInstallation:
Service andtrunk vacuum linesshould besized according to the number of user counts given in the Pipe Sizing table. PVC piping is preferred for all installations. Copper pipe is required onlyfor returnplenum installations.
Control Wiring:
MaxiMizers are furnished standard with a low voltage relay for remote operation. A Matrx CP Series control panel may be installed to provide utility switching and monitoring. For information on control panels available, see the Matrx Dental EquipmentCatalog.
CONTROL
PANEL
SWITCH
RED
BLUE
WHT
RED
BLUE
WHT
18/3 JACKETED BELL WIRE
REMOTE CONTROL
PANEL
LOW VOLTAGE CONTROL LEADS
VACUUM PIPING AND CONTROL WIRING
Pilot Relay Wiring
Dual Pump Control Wiring:
Remote control wiring for dual pump installations may be installed in one of the following ways:
Control pumps from two separate switches at the control panel by using two runs of18/3 jacketedwire.
Control pumps from a single switch atthe control panel by installing a pilot relay (Matrx P/N 77000361). Connect low voltageleads asshown.
"
"
3/4"3/4"1"1"
1 1/2” EXHAUST HOSE
Page 4
145 Mid County Drive Orchard Park, New York 14127 716-662-6650
800-847-1000
888-279-1260
716-662-8440
Toll-Free: Technical Support: Fax: E-mail:
10421100 Rev.D
4
EVACUATION FILTER INSTALLATION
Evacuation Filter Installation Detail
For part number 77000338 and 77000038
Elbow Extension (not included with kit)
Panel Mounts To Wall Surface With Screws And Anchors Provided
Drill 3/16” Hole For Anchors
1/2”or 3/4”Copper or PVC. Strap to Wall Stud.
3/4” NPT