Matrix M100, M100V Instructions Manual

1.0 SPECIFICATIONS .....................................................................3
1.1 High Altitude Operation .......................................................... 3
2.0 INSTALL ATION REQUIREMENTS .............................................4
2.1 Location ................................................................................ 5
3.0 VENTING .................................................................................. 6
Attachi ng Ve nt Pipi ng to Boiler ..................................................... 6
3.1 Vent Pipe Material..................................................................7
3.2 Venting Config uratio ns...........................................................7
3.3 Venting Rules and Guidelines.................................................9
3.4 Venting Clearances..............................................................10
3.5 Determining Vent Lengths ....................................................10
3.6 Outdoor Venting...................................................................11
4.0 CONDENSATE DRAIN ............................................................ 12
5.0 INSTALLING GAS PIPING .......................................................13
5.1 Installation...........................................................................13
5.2 Testing and settings.............................................................13
6.0 BOILER PLUMBING................................................................15
6.1 Plumbing (Minimum Requirements).......................................16
6.2 Matrix Boiler Connectio ns.....................................................17
6.3 Hydronic Heating Additions (Optional)...................................17
7.0 DOMESTIC HOT WATER SYSTEM ..........................................23
7.1 Operation and Set-up...........................................................23
7.1.2 Matrix DHW with Storage...................................................25
8.0 WIRING...................................................................................26
8.1 Field Wiring to Matrix............................................................26
8.2 Matrix Factory Wiring Sche matic...........................................27
9.0 CONTROL SETUP...................................................................29
9.1 Controller Displays...............................................................29
9.2 Operation and Set-up...........................................................30
9.3 Outdoor Sensor Oper at ion....................................................32
10.0 MATRIX BLOWER OPERATION............................................33
10.1 Forced Air Heating .............................................................33
10.2 Duct Sizing........................................................................ 34
11.0 HEAT RECOVERY VENTILATION.........................................35
11.1 Ventilatio n Needs...............................................................35
11.2 Types of Installation........................................................... 36
11.3 Damper Box ......................................................................37
11.4 Condensate Drain..............................................................37
11.5 HRV Balancing ..................................................................38
12.0 LIGHTING BOILER................................................................40
12.1 Initial Start-Up ....................................................................40
12.2 Re-Lig hting Unit .................................................................40
12.3 Turn Off Appliance .............................................................40
13.0 T ROUBLE SHOOTING .......................................................... 41
Matrix
Matrix Boiler Only
VERSION DATE: 2-7-08
14.0 SEQUENCE OF OPERATION................................................45
15.0 INSTALLATION CHECKLIST.................................................46
16. 0 ANNUAL MAINTE NANCE AND INSP ECTION ........................47
16.1 Combustion Chamber Cleaning ..........................................47
16.2 HRV/Air Hand ler Maintena nce ............................................47
17.0 PARTS LIST..........................................................................48
18.0 WARRANTY.......................................................................... 49
US Models
Matrix Installation a nd Operatio n Instructions
WARNING
THIS APPLIAN CE I NCORPOR ATES A CERTIFIED LO W PRESSURE BOIL ER, WHICH M UST OPPERATE W ITH A SUST AINED W ATE R PRESS URE. F AILURE TO MAINTAIN W ATE R PRESS URE W ILL D AM AGE T HE UN IT
AND VOID THE WARRANTY.
CAUTION
IT IS T HE RESPON SIBIL IT Y OF T HE HOM EOW NER TO KEEP T HE VENT TERM INAL CLE AR OF SNO W AN D ICE.
CAUTION
CERTIFIED C ARBO N M ONIXIDE D ETECTORS MUST BE INSTALLED ( SEE SECTION 2.0)
2
Matrix Installation a nd Operatio n Instructions
1.0 SPECIFICATIONS
Table 1. 1 Gener al Spec i fic at ions
Model
M100 25-150
M100V 25-150
Input MBH
Output
MBH
23-
139
23-
139
Steady State
Efficiency %
95 92.7 20x16 18x18 300-1200 400-1600 - 53-28-38 3” 95 92.7 20x16 18x18 300-1200 400-1600 70-150 53-28-38 3”
AFUE
%
Supply
Plenum
inches
Return
Plenum
inches
Airflow
Heating
CFM
Airflow
Cooling
CFM
Ventilatio n
CFM
Dimensions
H-W-D
Vent/Air
Size
1.1 High Altitude O per at ion
The Matrix is designed to operate to capacity
Figur e 1.1 Maximum Capacity vs. Altitud e
160
in installations at 2000 feet of elevation or less. As elevations higher than 2000 feet have less dense air, the uni t is not capable of
150
providing its specified capacity. (See Chart).
140
In Cana da:
De-rate by 5% for altitudes between 2000 and 4500 feet. For altitudes above 4500 feet
Input ( M bh)
130
consult with local authorities.
In US A:
120
De-rate by 4% for every 1000 feet over 2000 feet.
110
0-2000 3000 4000 5000 6000 7000 8000 9000 10000
Elevation (ft)
CAUTION
AT ELEVATIONS GREATER THAN 2000 FEET, THE COMBUSTION OF THE MATRIX MUST BE CHECKED WIT H A CALI BRATED CO MBU STION T EST ER TO ENS URE SAFE AND R ELIAB LE OPE RATION. CONS ULT SECTIO N 5.20 FO R INST RUCTIONS ON ADJU STING T HE INPUT TO PRO VIDE PROPER OPERATION.
IT IS THE INSTALLERS RESPONSIBILITY TO CHECK THE COMBUSTION, AND TO ADJUST THE COMBUSTION IN ACCORDANCE TO SECTION 5.20
3
Matrix Installation a nd Operatio n Instructions
2.0 INSTALLATION REQUIREMENTS
The installation of your NY Thermal Matrix gas furnace/boiler must conform to the requirements of your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where required by the Authority, the installation must confor m to the standard for “Controls and Safety Devices for Automatically Fired Boilers ANSI/ASME CSD-1.
IMPORTANT
Carbon Monoxide Detectors
Many jurisdictions require the installation of carbon monoxide detectors in buildings where a sidewall vented fuel-bur ning appliance is inst alled. In stallers m ust abide by local co de requ ire ments regard ing the installation of CO detectors. The use of a certified carbon monoxide detector is recommended but not required by NT I.
IMPORTANT
“IN THE STATE of M ASSACHUSETTS ONLY”
(a)For all horizontally vented gas fueled equipme nt installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing pl umber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipme nt is to be installed and on each additional level of the dwelling, building or structure served by the equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the i nstallation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requireme nts of this subdivision can not be met at the time of completion of installation,
the owner shall have a period of 30 days to comply with the above requirements; provided, however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of ei ght (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size,
GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”. (A plate is included with the boiler)
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b)EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
…..Next Page
4
Matrix Installation a nd Operatio n Instructions
….Continued.
(c)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYS TEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting s ystems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
ATTENTION
The Matrix is se t t o operate with Natural Gas; LP Co nversion Kit Part No. 82650- 1 is i ncluded with e ac h furnace and
must be installed before operating with Propane. Liquefied Petroleum (LP) propane gas is heavie r than air; it is imperative that your boiler is not installed i n a pit or si mila r lo ca t io n that wi ll pe r mit he a v ie r t ha n a i r ga s t o co llect . Lo ca l Code s may re qu i re a pp lia nces f ue led wit h LP g a s be provided with an approved means, of removing unburned gases from the room.
Check your local codes for this requirement.
2.1 Location
In all cases, the Matrix must be installed indoors, in a dry location, such that the gas components are protected from dripping or spraying water or rain, during operation and servicing. T he boiler location ambient temperature is mai ntai ned to a mi ni mum of
50°F. Determi ne the best location of the vent termination, and if possible locate the appliance as close to the termination point as possible. Ensure that the desired appliance location is not subjected to flooding or high moisture levels, for damage to the appliance will occur, voiding your NY THERMAL warranty.
LIQUIFIED PE TROL EUM (LP) PROPANE
IMPORTANT
CLEARANCES
For proper and saf e installation adhere to the f ollowing c learances t o com bust ib les:
Furnace Casing = 0" Floor = Combustible Flue Pipe: Boxed in or enclosed = 2”
The f ollowing are the minimum clearances r ecommended f or ser vicing:
Front = 24” Back = 6"( opt ional return plenum locati on) Top = 12" Sides = 24" Bottom = 0”
In free air = 0”
5
Matrix Installation a nd Operatio n Instructions
p
3.0 VE NTING
The NY Thermal Matrix is a high efficiency condensing gas furnace/boiler utilizing induced power venting. Exhaust gases are to be vented directly outdoors, using the venting me thod detailed in this section. Under no conditions, may this unit vent gases into a masonry chimney, unless it is vacant, and utilizes Matrix approved venting material as illustrated in the figures in this section.
Attaching Vent P ipi ng t o Boi ler
It is extremely important for the inta ke and exhaust piping to be adapted to the appropriate size immediately upon exiting the boiler cabinet. The Matrix comes with a 3” male PVC fitting to connect the air intake port of the boiler. The Matrix exhaust connection is 3” male PVC, use approved cement to connect to venting system. Check t he fl ue outlet gasket for prop er i nser ti on and sea ling prior to and after attachi ng the ve nting. Ensure the venting system does not apply a load or stain on the flue outlet of the boiler (recommend using two elbows to create a “swing joint” as shown above).
Fig ur e 3.1 Venting Const r uction
It is recommended that two elbows be used, so that the slope of the hori zontal exhaust vent does not affect the vertical
lumb of the pipe connected to the boiler. Slope all horizontal indoor exhaust vent ing ¼” to ½” per linear foot.
It is recommended to have a collection point for condensation in the intake venting. Condensation can then be drained to an open house dr ain or condens ate pump.
Drain line from intake must have an appropriate trap or shut off valve to avoid siphoning.
IMPORTANT
The vent connection and piping must be perfectly aligned to the furnace connection. AND MUST NOT APPLY ANY W EIGHT OR LATERAL FORC E TO T HE FLU E BOX. NTI do es not warrant y damages to t he flu e box.
6
Matrix Installation a nd Operatio n Instructions
p
3.1 Vent Pipe Mat erial
IMPORTANT
Field supplied piping and fittings are required to complete the installation. Selection of the vent pipe material must be based upo n the Local codes and regulations. The Matrix is certified to oper ate under all conditions using the following vent ing material:
Exhaust Vent Pip ing:
The first 3 feet of the exhaust venting must be readily accessible for inspect ion. In Canada all exhaust pipe, fittings and cement must comply with ULC S636 (As per ULC S636, only CPVC can be used). In U.S. exhaust pipe and fittings must comply with ANSI/ASTM D1784 and DF441 for PVC and CPVC respectively. Cement and primer must comply with ANSI/ AST M D2564 and F493 for PVC a nd CPVC respectively.
1. 3 ” PVC Sch.40 ( US only, not per mitted in Ca nada) .
2. 3 ” CPVC Sch.40.
Air Supply Pipe:
1. 3 ” ABS.
2. 3 ” PVC Sch.40.
3.2 Venting Confi gur at ions
See Chart f or m aximum l engt hs
See Chart for max i m um l engths
3.2.1 Two-Pipe Vent Termination
Fig ur e 3.2 Two-Pi pe Vent Ter m i nati on
Coupling and elbow to be against wal l
– ½ ” play is acceptable
Exhaust
Intake
The ver tical portion of the exhaust termination does not require insulation, if less than 5 feet in total length
12” Plus Snow allow ance
Example 12+19=31
Must insert
lastic bird
screen
Apply Plate Here
Gas Vent Direct ly Below
Keep Free of Obstruc t ions
Exhaust
Intake
Out sid e W all”
Window
Exhaust
36”
18”
4”-12” or great er than 36”
Intake
12” Plus Snow Allo wance Min”
7
Matrix Installation a nd Operatio n Instructions
p
p
w
Apply
(
g
3.2.2 Concent r ic Vent Termination (No longer appr oved for Canada)
Fig ur e 3.3 Conc e nt ric Vent Ter mina t i on
Plate Here
Gas Vent Directly Belo Keep Free of Obstruc t ions
48” min.
4” or greater than 24”
Minim um 12”
lus snow
allowance
36” min.
Exhaust
Inlet air
Note: inlet pipe must always be connected to the boiler.
Must insert
lastic bird
screen
Support (Fie ld installed)
Inlet air
Use NTI part # 82666 or York part # 1CT0303 Instructions included with vent terminal contain more detailed assembly and installation instructions. Clearances and requirements of this manual supersede those of the instructions incl uded with the vent terminal. Terminal must be cemented together during installation.
Exhaust
Must be 1” from wall
3.2.3 Roof Vent ing
Figure 3.4 Roof Vent i n
Roof weat her seal Flashing (field supplied)
18”
12” Plus Snow
Support
Field supplied)
Note: inlet pipe must always be connected
8
Matrix Installation a nd Operatio n Instructions
IMPORTANT
USE OF EXI STING CHIMNEY
It is permissible to run vent pipe t hrough an exist i ng chimney as long as:
1. The chim ney is not to be used by any other appliance.
2. Flue gases don’t enter the vacant chim ney.
3. O nly Trinit y c er t ified venti ng materials are used, see Sect ion 3.1.
4. Vent lengths are within the maximums specified.
3.3 Venting Rules and G uide lines
1. It is highly recommended that the vent termi nal be located where it will not be exposed to normal prevailing winds.
2. The exhaust mus t be a minimum of 18” above the air inlet, and the air inlet must always be a minimum of 12” plus snow allowance above any surface that will support snow. (Two feet plus snow allowance is highl y recommended). Consult your weather office, for the maximum typical snowfall for your region. Example: New Brunswick Canada the typical maximum snowfall is 19”, Thus in figures of Section 3.3, the inlet must be (12”+19”) = 31” off the ground, the exhaust mus t be (31”+18”) = 49”. The horizontal distance between the inlet and exhaust must be a minimum of 4” center to center. If the horizontal distance between the inlet and exha ust is more then 12”, increase the vertical separation by the same amount. Example: If horizontal separation is 24”, a minimum vertical separation of 30” is required (24”-12”=12”), so increase mini mum vertical separation by 12”), (18”+12”=30”). If horizontal distance is greater then 6’, no additional vertical spacing is required. Vertical separation is never required to be greater then 36”.
3. Under normal operating conditions this appliance will produce a plume of white gases, and sho uld be taken into consideration when selecting an adequate location. A 3’ diameter stainless, plastic, or vinyl shield can be used to flash the exterior of the residence.
4. If the horizontal distance between the inlet and exhaust is more then 12”, increase minimum vertical separation by the same
amount. (If horizontal distance is greater then 6’, no additional vertical spacing is required). Example, horizontal separation
equal to 24” require s a mi nimum ve rtical separation of 18”+(24”-12”) =30”. (Vertical separat ion is neve r re quired t o be greater then 36”)
5. Elbows on outside of wall must be no greater than ½” away from the wall. All indoor exhaust piping mus t be on a slope back to the boiler a minimum of ¼” per linear foot of vent. For applications where excessive condensation is possible ½” per linear foot is recommended. (See figure after #11. Recommended way to have plumb pipe connection to boiler.)
6. Exhaust vent pipe can be secured to the wall for more rigidity.
7. In all roof applications the discharge must point away from the pitch of the roof.
8. Install adequate flashing where the pipe enters the roof, to prevent water leakage.
9. Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
10. For installations that exit the wall below grade. Excavate site as shown in figure, to a point below where the pipes are to exit. Ensure tha t the wall is fully sealed where the pipes penetrate the wall. The vent piping MUST be secured to the side of the building above grade, as shown, to provide rigidity. NTI provides a mounting bracket, PN:82075, for securing the exhaust pipes. Ensure that the vent clearances are maintained (Inlet mi nimum 12” plus snow allowance from grade, exhaust outlet 18” mi nimum above inlet)
11. Install the vent screens provided into both the inlet and exhaust vent terminal elbows. The screen must be on the outside of the last elbow. Install the screen into the female opening of the elbow. Then cut a s mall piece of pipe to sandwich the screen into the elbow. NOTE be sure that the small piece of pipe cut, does not extend past the end of the elbow. Two screens are provided in the package.
12. It is extremely important that the intake and exhaust piping be adapted to the appropriate size immediately upon exiting the boiler cabinet.
13. All interior vent pipe shall be supported a minimum of every 36”.
Figure 3.5 Installing Venting Below Grade
9
Matrix Installation a nd Operatio n Instructions
3.4 Venting Clearances
These are code restrictions for the location of the Flue gas vent ter minal. Compliance doesn’t insure a satisfactor y installation; good common sense must also be applied.
The vent terminal shall not t er minate:
1. Directly above a paved sidewalk or a paved driveway that is located between two buildings, and that serves both buildings;
2. Less than 7 feet above grade where located adjacent to a paved walkway or driveway located on public property.
3. Within 3' (three feet) of a window or door that can be opened, or non-mechanical air supply inlet to any building.
4. Within 6’ of a mechanical air supply inlet to any building, or roof eve containing soffit openings.
5. Above a meter/regulator assembly withi n 3' horizontally of the vertical centerline of the regulator.
6. Within 3' horizontally of any gas service regulator vent outlet up to a height of 15’.
7. Less than 30” plus snow allowance above grade, or any surface that will support snow, ice, or debris. The exhaust must be a minimum of 18” above the air inlet, and the air inlet must always be a mi nimum of 12” plus snow allowance above any surface that will support snow. (Two feet plus snow allowance is highly recommended). Consult your weather office, for the maximum typical snowfall for yo ur regi o n.
8. Underneath a wooden verandah, porch, or deck.
9. Underneath cement verandah, porch, or deck, unless both ends are open and the exhaust pipe is installed at least 24” under the deck floor.
10. So situated that the flue gases are directed towards brickwork, siding, or other construction, in such a manner that may caus e damage fro m heat or co ndensate from the fl ue gas es.
11. Less than 3’ from an inside corner of an L-shaped structure (including walls and fences).
12. Install the warning plate “Gas Vent Di re c t ly B e lo w” 4 feet above the location of the air inlet pipe, so it is visible from at least
eight (8) feet away (Plastic Label included in the Installation Manual Package – see figure).
3.5 Deter mining Vent Lengt hs
Use the following chart to determi ne the maximum amount of vent pipe that can be used. This chart calculates, sweep and 45º elbows, and 90º elbows at 5 equivalent feet. Note: chart shows allowable equivalent vent lengths for intake and exhaust vents separately, thus an M100V operating on Natural Gas can be installed with 105 equivalent feet of intake venting and 105 equivalent feet o f exhaus t venti ng.
IMPORTANT
The length of one vent p ipe (intake or exha ust) ma y not exceed t he lengt h of the other vent pipe by mor e then 20 equivalent f eet .
The thr ee 90° elbows of t he exterior vent piping (two outlet, and one inlet) do not have to be included, as they are taken into considerat ion in t he vent calculations.
Propane Gas (LP) maximu m vent length cannot exceed 50 equivalent f eet .
Table 2 Maximum Vent Lengt h
Number of Elbows or 45's
Model
M100
M100V
Vent
Type
3"Natural 105 1009590858075706560 3" LP 50 45 40 35 30 25 20 15 10 5
Gas
Max. Equiv.
Length
123456789
10
Matrix Installation a nd Operatio n Instructions
3.6 Out door Vent ing
Vent piping outside the Building is permitted under the following conditions:
The maximum length outside the building is 20 feet. (Outdoor length must be included in the overall vent length calculation.) All normal termina tion clearances are maintained. All exterior exhaust vent pipes are insulated with 3.5”-ID, ½”-
thick, Closed Cell Foamed Polyolefin Tubing i.e., “Tundra Seal Plus” or equivalent.
The pipe is supported every 24” The exhaust and inlet are sloped back to the boiler ½ ” elevation for every foot.
Fig ur e 3.6 O utd oor Venting
Support s every 24”
Exhaust
Inlet
Apply Plate Here
Gas Vent Direct ly Below
Keep Free of Obstruc t ions
Maximum of 20 feet is permitted for outside a building
usin g 3” pipe ONLY.
12” plus all owance above grade for snow
11
Matrix Installation a nd Operatio n Instructions
4.0 CON DE NS ATE DRAIN
This unit produces water as a product of combustion. Much of this water condenses on the heat exchanger and in the venting system. All exhaust piping must be on a slope back to the boiler ¼” per linear foot of vent. Steps must be taken to ensure that condensate does not collect in the venting system. Condensate must be drained from the boiler into a household drain.
WARNING
FAILURE TO PROPERLY CONNECT THE CONDENSATE LINE WILL CAUSE COMBUSTION GASES TO ENTE R THE ROOM, POSSIBLY C AUSING SERIOUS INJ URY T O OCCUPANTS O R DEATH.
Note: c hec k with your munici pality, or l ocal ga s co mpa ny to determine i f disposal of combustion condensate is permitted. In the State of Massachusetts the condensate must be neutralized prior to entering a drain.
The following are important notes that must be taken into consideration when constructing the condensate system:
DO NO T run condensate line outside. A frozen or blocked drain will cause the
condensate to fill the combustion chamber. This will result in a no heat condition, as the unit will shut down, and damage to the flame sensor, and components can occur.
NEVER use copper, steel, or galvanized piping in the construction of the
condensate system (condensate is very corrosive and will wrought most me tals). When a condensate pump is used or required, select a pump that is designed for residential furnaces.
Fig ur e 4.1 Cond ens at e Drain Plumbi ng
Condensate Drain From Boiler
Nipple mu st be cut.
Drain must be open t o allow overfl ow if
blocked
Drain must include trap
12
Matrix Installation a nd Operatio n Instructions
5.0 INSTALLING GAS PIPING
5.1 Installation
Fig ur e 5.1 G as Inlet Connection
Refer to the current National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation
codes, and local codes for gas piping requirements and sizing.
It is hig hly recomme nded to use flexibl e gas pipe, the gas valve and blower cannot support the weight of piping. I f piping is used, ensure that the valve supports NO WEIGHT
Gas cock shut Off Valve to be "T" type h an d le
Pipe size runnin g t o t he unit depends on:
Length of pipe.
Number of fittings.
Type of gas.
Gas valve
Maximum inp ut requirement of all gas
appliances in the residence.
Ensure that:
Flexible gas pipe is used (if acceptable by
local codes). The gas valve and blower cannot support the weight of piping, leading to blower vibration and damaged components. If rigid piping is used, ensure that the valve supports NO WEIGHT
You plan the installation so that the piping does not interfere with the vent pipe, or the removal of the valve, burner, and
serviceable components.
The Boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying,
rain etc.) during installation and servicing.
The gas piping is large enough for all the appliances in the home. No appreciable drop in line or manifold pressure should
occur when any unit (or combination of units) lights or runs.
Al ways use a pipe- thr eading compo und t ha t i s resistant to pr opa ne (LP) gas s olvent actio n. Us e spar ingl y to all male
threads, starting at two threads from the end. Over doping or applying dope to the female end, can result in a blocked gas
line. DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the valve or motor can occur. Install a manual “equipme nt Shut-Off Valve” as shown. Valve must be listed by a nationally recognized testing lab.
5.2 T esting and sett ings
Gas line and regulator(s) must be able to support a line pressure at the gas valve of 4-9”w.c for Natural Gas and 9-12”w.c for LP while running at maximum rate. Matrix gas valves are equipped with two bleed ports to measure Line and Manifold pressure.
Note: Line pressure adjustments can only be made at the gas regulator, NOT AT THE GAS VALVE.
WARNING
IF L INE PRE SS URE EXCE EDS ½ PS I (14 INC HES W. C. ) CO MPL ET ELY DISCO NN ECT L INE T O GAS VALV E. THIS EXCESSIVE PRESSURE CAN DAMAGE VALVE, CAUSING A LEAK RESULTING IN FIRE OR
EXPLOSION.
13
Matrix Installation a nd Operatio n Instructions
The gas valve is equipped with a throttle/input adj ustment
Fig ur e 5.2 Set ting Com bust ion
screw. The input screw “MUST NEVER BE ADJUSTED” without verifying proper combustio n with a calibrated combustion analyzer.
Manifold
Input Screw
out
Gas IN
Air In
Line Pressure
CAUTION
The M atrix is tested w ith Natural Gas having a heat ing value of 1020 BTU p er cubic foot . For areas with lower heating valu es, a combusti on t est is required to obtain optimum operation.
Using a calibrated flue gas anal yzer, check the combustion and compare it with the acceptable requirements. The test should be performed at maximum fan speed (“Gas Input Value”).
Adjusting Combustio n - Use the input screw to adjust the amount of gas available for combustion. Increasing gas increases CO
and CO2. Reducing gas decreases CO and CO2.
CO – At maximum fan speed, the CO reading is
the most critical to the safe operation of the boiler. The CO should be no higher than 175 PPM at any condition. If the CO is over 140 PPM, the input should be reduced until the CO is less than 140 PPM or the CO2 is reduced to 8% (9% for LP Gas). If the CO is over 140 PPM and the CO2 is less than 8% (9% for LP Gas), contact NTI for assistance.
CO – At minimum fan speed, should be checked, and the CO should be less than the reading recorded at high fan speed. The CO
at low fan speed must not be at least as high as the CO2 recorded at high fan speed, but not more then 9.5% (10.5% for LP Gas).
Table 5. 1 Normal Range of Combust i on Pr oduct s
(At maximum fan speed, 240)
Natural Propane Carb o n Dioxid e CO2 % 8-9.5* 9-10.5* Carbon M onoxide CO ppm 25-175* 25-175* NOX ppm 10-50 10-50
*Note: On colder days CO2 should be closer to the lower number, on warmer days it should be closer to the higher number. CO should be highest at the maximum firing rate.
2
Figure 5.3 Gas Input Screw Adjustment
Input Screw
valve. Ful ly open to close is approximately 17 turns. Typical adjustment for Natural Gas is 0-1 full turns in or out. Typical adjus tment fo r LP Ga s is 0-3 full t urns i n or out (aft er conversion is perform ed).
Is a m ultiple turn needle
ATTENTION
IF FOR ANY RE ASON T HE INPUT SCREW IS ADJUS TED, A “COM BUST ION ANALYZER” MUST BE USED TO ENSURE SAFE AND PROPER OPE RATION.
Input Screw Adjustment
Decrease gas Turn Clockwise
In crease gas Turn counterclockwise
14
Matrix Installation a nd Operatio n Instructions
O
OCCU
6.0 BOILER PLUMBING
WARNING
THIS APPLIANCE CONSISTS OF A “LOW-MAS S” BOILER AND MUST HAVE ADEQUAT E WATER FLOWING T HROUGH IT WHENEVER THE BURNER IS ON. FAILURE T O DO T HIS WILL DAMAGE THE UNIT AND VOID THE WARRANTY. PLUMBING MUST INCORPORATE A PRESSURE REGULATI NG FILL VALVE AND PRESSURE R ELIEF VA LVE.
WARNING
HYDRONIC SYSTEMS, OLD AND NEW, MUST BE FLUSHED TO REMOVE SEDIMENT, FLUX, FILINGS, ETC. FAILURE TO DO SO WILL SERIOUSLY DAMAGE THE BOILER, VOIDING WARRANTY. (CLEAN WITH FERNOX CLEANER F3, NTI PART NUMBER: 83449.)
WARNING
WATER WIT H A TOTAL HARDNESS GREATER THEN 100PPM (6 GR AINS/GALLON) MAY RESULT IN HEAT EXCHANGER FAILURE AND WILL VOID YOUR NT I WARR ANTY. TREAT ALL SYST EMS WITH FERNOX PROTECTOR F1 (NTI PART NUMBER: 83448), WHICH IS INCLUDED WITH THE MATRIX PACKAGE.
WARNING
THE BOILER FITTINGS CAN’T SUPPORT ANY WEIGHT. SUPPORT ALL OF THE PLUMBING SYSTEM EXTERNALLY.
DO NOT APPLY TORQUE TO T HE PLUMBING FITT INGS. HOLD THE FITTING WHEN INST ALLING,
THERWISE DA MAGE TO TH E UNIT WILL
R.
CAUTION
This app liance is des igned to o perat e in res ident ial and co mmercia l heating syste ms, and is not int ended for:
1. Out door installations, or unheated spaces, which can cause freezing.
2. Process heat in g of pot able water , or any ot her fluids.
3. Un-pressur ized, and gravity f eed heat ing systems.
4. Heating systems with very low pressures or flow.
IMPORTANT
1. Underst and and f ol low the plumbing requirements provided in t his section.
2. Keep serviceability in mind when instal ling plu mb ing around the fur nace cabinetr y.
3. Install f itt ings that will allow the system to be flushed if needed duri ng annual check-ups.
4. Add inhibitor, Fernox Protector F1 (NTI Part Number: 83448), to the system water to help prevent limestone and magnetite depos its, and galvan ic corrosion. Bottle provided wil l treat an average 100-
liter (26 US gallon) system.
15
Loading...
+ 34 hidden pages