Matelec FPC-30010, FPC-15002 Owner's Manual

Page 1
PUMP ON
FAULT
PUMP ON
FAULT
MAIN ISOLATOR
OFF
ON
DOC: FPC-30010 VER 1.0
PUMPCONTROL
Dual Pump Controller Installation and Operating Instructions
MODEL: FPC-30010
Page 2
2
Your Dual Pump Controller reects the superior quality and attention to detail in design, engineering and manufacturing that has distinguished MATelec Products for decades. The controller incorporates the very latest in micro-processor technology, ensuring you, the owner/operator, of many years of functional, reliable and ‘user friendly’ operation.
Please read this manual prior to installation and operation of the controller.
WELCOME TO DUAL PUMP CONTROL
SAFETY 2 CIRCUIT DIAGRAM 7
INSTALLATION 3 AT A GLANCE 8
Mounting Indicators
Connection Push Buttons
GETTING STARTED 4
Operations
Features
CONTENTS
SAFETY
Prior to Installation, ensure power supply is isolated.
Power supply must be Circuit Breaker Protected. (Qualied Electrician to determine appropriate amp rating.)
Electrical connection to the panel must be carried out in accordance with ‘Connection Instructions’, see page 3.
Addition or modications to the control panel are not permitted and will void warranty.
The controller is not intended for use by children or inrm persons without supervision.
Repairs to the Controller must only be carried out by a suitably qualied Electrician
WARNING: All electrical connections must be carried out by a suitably qualied and
registered electrician
Page 3
3
FRONT SIDE VIEW
Top
Bottom
Top
Bottom
3 FLOAT SWITCH SYSTEM
2 FLOAT SWITCH SYSTEM
WIRING CONNECTION DETAIL
FPC-30010
NO FLOAT SWITCH
CONNECTED TO INPUT 2
STOP
START
LEVEL
COMMON
N/O CLOSE ON RISE
BLUE NOT REQUIRED
STANDBY
HIGH
LEVEL
COMMON
N/O CLOSE ON RISE
BLUE NOT REQUIRED
240Vac
MAINS POWER
SUPPLY
E A N
Input 2
Stop
Level
Input 2
Stop
Level
Input 3
Start
Level
Input 4
High
Level
SUPPLY
240Vac 12Vdc Connections
INPUT SWITCHES
PUMP 2
PUMP 1
A N
PUMP 1 Earth
PUMP 1 PUMP 2
PUMP 2 Earth
STOP
LEVEL
COMMON
N/O CLOSE ON RISE
BLUE NOT REQUIRED
START
LEVEL
COMMON
N/O CLOSE ON RISE
BLUE NOT REQUIRED
HIGH
LEVEL
COMMON
N/O CLOSE ON RISE
BLUE NOT REQUIRED
240Vac
MAINS POWER
SUPPLY
SUPPLY
240Vac 12Vdc Connections
INPUT SWITCHES
PUMP 2
PUMP 1
PUMP 1 Earth
PUMP 1 PUMP 2
PUMP 2 Earth
Input 2
Stop
Level
Input 2
Stop
Level
Input 3
Start
Level
Input 4
High
Level
A N
E A N
A N A N
Mounting Frame/ Wall
PUMP ON
FAULT
PUMP ON
FAULT
MAIN ISOLATOR
OFF
ON
1. Controller enclosure must be mounted in a vertical position.
2. Ensure mounting method does not compromise enclosure weather proof rating.
3. Ensure access to main isolator is not restricted.
4. Ensure cables/conduits entering the panel have mechanical protection and that the penetrations are sealed and do not compromise the weather proof rating of the enclosure.
INSTALLATION
MOUNTING
Note: Controller must be earthed and all electrical connections must be carried out by a suitably qualied
Electrician. For Single Working Level Float Switch Applications, connect to “Start (Input 3)” terminals only, and NO bridge wire is required in “Stop (Input 2)” terminals.
CONNECTION
Page 4
4
This controller can perform control functions for most Dual Pump pumping applications. It is more than likely that the control parameters have already been set up for your particular application, however, hereunder you will nd details of the setup and conguration options.
DIP Switch
Position Function
1/2 Off/Off
Mode A: Standard typical oat switch conguration (Start,Stop and High Level). No Low Level
Off/On
Mode B: Standard conguration plus low level (Start,Stop and High Level).
On/Off
Mode C: Standard conguration plus Prime Loss enabled, on Low Level (Input 1)
On/On
Mode D: Pressure Pumping conguration (Lead, Lag and Low Pressure)
3 Off Operating Pump alternates each time a pump start is triggered, or after 30 minutes continuous running.
On Operating Pump alternates after 6 hours continuous running.
4 Off Anti-seize Timer disabled
On Anti-seize Timer 6 seconds every 7 days enabled
5 Off When placed in Manual Mode, pump remains in Manual Mode
On When placed in Manual Mode after 5 minutes the pump will revert to Auto
6 Off High Level Alarm automatically resets upon open circuit of high level input. High Level alarm
has 15 minute delay.
On High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay.
Mode A: Standard Conguration
Start/Stop/High Level operation. When the Pump Start input is closed contact (triggered), the Duty Pump will be turned on. The pump will remain on until both the Pump Start and Pump Stop Inputs have turned off (Open Circuited). Upon High Level, both pumps will run until the Pump Stop Input turns off.
Input Function
Input 1 Low Level Input 2 Pump Stop Input 3 Pump Start Input 4 High Level
Mode B: Standard Conguration plus Low Level Alarm
As per Mode A, except it has an active Low Level input. The Low Level input must be closed, for Pump Start and Pump Stop inputs to function. The High Level input however, will still override the Low Level and run both pumps. Input functions are as follows:
OPERATION
In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if either pump has not run for 4 hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. Input functions are as follows:
There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and “feature”options, as per the following table:
Input Function
Input 1 Standby Start Input 2 Pump Stop Input 3 Pump Start Input 4 High Level
Page 5
5
The basic logic on which a High or Low Level Alarm is determined, is set out in the Table below:
If there is a Low Level Alarm, then both Pumps will be locked out until the alarm is manually reset. This lockout will only be over ridden upon a High Level condition where both the Pump Start and High level inputs are closed.
Note that after a High level is triggered, the pumps will both run until the Pump Start and Stop inputs are opened
Mode C: Standard Conguration plus Prime Loss
Mode D: Pressure Pumping Conguration
Typical Operation Mode D:
As per Mode A, except Input 1 is connected to a prime loss/ow switch. If at any stage, after Pump Start, or whilst a pump is running, the Prime Loss input opens, for a continuous 2 minute period, a fault is immediately triggered for that pump and duty alternates. Input functions are as follows:
Duty Pump: Lead Pump Standby Pump: Lag Pump Input functions are as follows:
Pressure drops to 400kPa: Lead (for this cycle) Pump cuts in.
Pressure increases and Pump cuts out.
Cycle continues with duty (Lead and Lag) alternating between the two pumps.
If pressure continues to drop to 350kPa, the Lag Pump will cut in and remain running until Lead Pressure Switch opens circuit. Then duty alternates.
No faults are logged against the Lead Pump if the Lag Pump starts.
The controller has inbuilt timers for “Delayed” Start and Stop to obviate pump chatter. Upon Input 1 contact closure, the pump will not start (delay start) for 1 second and will not stop (minimum run time) for 10 seconds (or 11 seconds from close of Input contacts). This “run on” occurs even if Lead Pressure switch opens circuit during this initial period. If however run time exceeds 11 seconds, the pump will stop immediately upon “Open Circuit” occurring.
If the Lead Pressure Switch input closes circuit as well as he Low Pressure Switch input, both pumps will be turned on and the Low Pressure Timer will begin counting. If this condition exists for a period of 60 seconds, then both pumps are shut down and the system signals a level alarm. This would be typical of a Loss of Prime, or Burst main situation.
Pressure switches are normally Closed and Opened on High Pressure.
Prime Loss functions as per mode Mode C.
Input Function
Input 1 Prime Loss Input 2 Pump Stop Input 3 Pump Start Input 4 High Level
Input Function
Input 1 Prime Loss (BRIDGE IF NOT REQUIRED Input 2 Lead Pump Pressure Switch (set at say 400kPa) Input 3 Lag Pump Pressure Switch (set at say 350kPa) Input 4 Low Pressure Switch (set at say 200kPa)
Input 1 Input 2 Input 3 Input 4
Pump
State
Alarm
Low Level Pump Stop Pump Start High Level
Closed Open/Closed Open Open Off
-
Closed Open/Closed Closed Open On -
Closed Open/Closed Closed Closed Both On High Level (after Timeout)
Closed Open/Closed Open Closed Both On High Level (after Timeout)
Open Open/Closed Open Open Off -
Open Open/Closed Closed Open Off Low Level
Open Open/Closed Open Closed Off Low Level
Open Open/Closed Closed Closed Both On High Level (after Timeout)
Page 6
6
In pressure pump mode some of the optional features are disabled, including maximum run alternation, anti-seize and maximum idle timers
Mode ‘Current Loop’: Level Transducer (4-20mA) Conguration
In order to activate current loop mode the enclosure must be opened and jumper J10 moved to the “current loop enabled” position (as shown in the following picture). By selecting current loop input mode the pump start input can be connected to a 4-20mA loop powered pressure transducer. The pump start, stop and high level signals can then be received from the pressure transmitter instead of oat switches. In this mode the pump stop oat switch input will be ignored however the high level input will still operate as per normal so that a oat switch can be used as backup if desired. The start, stop and high level current set points will be pre-programmed into the software and therefore cannot be adjusted. The levels for a 0-4m transducer are Stop= 300mm, Start= 600mm and High= 1000mm.
Figure 1: APC6 PCB Layout and Current Loop Jumper
C
urrent Loop
E
nable Jumper
Maximum Run and Alternation Mode
With DIP Switch 3 set to “Off” the unit will alternate as usual each time a pump start condition occurs. Additionally, the controller will automatically alternate pump duty if a pump has been running continuously for 30 minutes (maximum run timer) Setting this DIP Switch to “On” will cause the controller to operate in “Circulation Mode” where duty will only alternate once the pump has run for 6 hours of accumulated time.
Anti-Seize Timer
With DIP Switch 4 set to “On”, the Anti-seize timer will automatically run the pumps for 6 seconds, every 7 days. This pump operation will completely override all inputs including the low level (if enabled). This feature will only run pumps that are set in Auto. This “Pump Run”, will alternate between Pump 1 and Pump 2. A pump that has been-locked out due to a fault will not run.
Manual Mode Timeout
With DIP Switch 5 set to “On” the pump will only remain in Manual Mode for 5 minutes, after which time, it automatically reverts to Auto.
High Level Alarm Reset
With DIP Switch 6 set to “Off”, the High Level Alarm will automatically reset once the High Level input opens circuit. The controller will also use the alternate High Level Alarm Delay. Typically used for Storm Water applications. High Level Alarm delay in this mode is 15 minutes. Setting this DIP Switch to “On”, will cause the High level Alarm to remain active until the controller is reset. The High Level Alarm will use the standard High Level Alarm activation delay. Typically used for Sewerage applications. High Level Alarm delay in this mode is 5 minutes.
Audible and Visual Alarm Test
Setting this DIP Switch to “On”, will cause the High level Alarm to remain active until the controller is reset. The High Level Alarm will use the standard High Level Alarm activation delay. Typically used for Sewerage applications. High Level Alarm delay in this mode is 5 minutes.
Fault Reset
To reset all faults on the controller, press and old the Mute/Reset button on the Keypad continuously for a period of 3 seconds until an acknowledgment beep is heard.
Pump Fault
A Pump Fault is indicated for two types of faults. A Thermal Overload will be indicated by way of a steady Fault Indicator Light when the overload opens the contact for 3 seconds. Prime loss will be indicated by ashing the pump fault light slowly.
Level Alarms
A High Level Alarm is indicated by way of a steady Level Alarm Indicator Light. A Low Level/Low pressure Alarm is indicated by way of a Flashing Level Alarm Light.
Auto Silencing Alarm Feature
The audible Alarm is programmed to sound for 5 minutes continuously, unless muted and will thereafter automatically silence and enter “Chirp” mode. In “Chirp” mode, the Audible Alarm will sound briey (2 seconds) every 5 minutes.
Page 7
7
7
CIRCUIT DIAGRAM
MODE
SELECT
INPUT2
INPUT1
4-20mA
- +
INPUT3 INPUT4
BMS/
REMOTE
STROBE
- +
SIREN
- +
POWER
12Vac
PUMP 1
PUMP 2
PUMP 2
FAULT
PUMP 1
FAULT
KEYPAD CONNECTION
PIN 1
500mA
DUAL PUMP CONTROLLER
COM-30089
240V 10A MAX
Australia
®
IMPORTANT: READ INSTALLATION AND OPERATION MANUAL BEFORE USE
TOL 1 TOL 2
TOL 1
TOL 2
A1 A2 A2
59 69 59 69
A1
A
N
E
CONTACTOR
COILS
PUMP 1
CONTACTOR 1
32amp
2 POLE
PUMP 1
ROTALOSI
32amp
2 POLE
PUMP 2
ISOLATOR
CONTACTOR 2
PUMP 2
2amp
CONTROL
CIRCUIT
BREAKER
ISOLATOR
SWITCH
STROBE BUZZER
TRANSFORMER
12Vac
12Vdc
240Vac
INPUT 2 SWITCH
INPUT 3 SWITCH
INPUT 4 SWITCH
12Vdc
12Vdc
MODE
SELECT
INPUT2
INPUT1
4-20mA
- +
INPUT3 INPUT4
BMS/
REMOTE
STROBE
- +
SIREN
- +
POWER
12Vac
PUMP 1
PUMP 2
PUMP 2
FAULT
PUMP 1
FAULT
KEYPAD CONNECTION
PIN 1
500mA
DUAL PUMP CONTROLLER
COM-30089
240V 10A MAX
Australia
®
IMPORTANT: READ INSTALLATION AND OPERATION MANUAL BEFORE USE
MODE
SELECT
INPUT2
INPUT1
4-20mA
- +
INPUT3 INPUT4
BMS/
REMOTE
STROBE
- +
SIREN
- +
POWER
12Vac
PUMP 1
PUMP 2
PUMP 2
FAULT
PUMP 1
FAULT
KEYPAD CONNECTION
PIN 1
500mA
DUAL PUMP CONTROLLER
COM-30089
240V 10A MAX
Australia
®
IMPORTANT: READ INSTALLATION AND OPERATION MANUAL BEFORE USE
PUMP ON
FAULT
PUMP ON
FAULT
Page 8
8
AT A GLANCE
PUMP ON
FAULT
PUMP ON
FAULT
INDICATORS PUSH BUTTONS
DISTRIBUTED BY: INSTALLATION DATE:
SERIAL NUMBER:
KEYPAD
MANUFACTURED BY MATelec AUSTRALIA EMAIL: info@matelecaustralia.com.au
MATelec reserves the right to alter technical specications without notice.
A quick reference to the
controller’s Keypad and
Indicator functions and
meanings.
POWER ON
Power is turned on.
LEVEL ALARM ON
A high level alarm has been present for the preset time.
FLASHING
A low level alarm is present.
ON STEADY
Pump switched on to run.
ON STEADY
A pump fault/overload has occurred.
FLASHING A prime loss
fault has occurred.
Silences the siren and if held down for 3 seconds, clears all faults
If selected (the LED indicator will conrm if on) the particular pump is set to Automatic Pumping Mode
Turns pump off
If selected (the LED indicator will conrm if on) the pump is set to Manual Pumping Mode
POWER ON
LEVEL ALARM
PUMP ON
FAULT
AUTO
MAN
OFF
MUTE/
RESET