Mastervolt Whisper 3.5 3000 RPM, Whisper 3.5 User Manual

Page 1
USERS MANUAL
WHISPER 3,5
- 3000 RPM -
Marine diesel generating set 230V / 50Hz
Digital Diesel Control
V5. May 2006
Art.nr. 50200302
Page 2
CONTENTS
2 May 2006 / WHISPER 3,5 / EN
This manual applies to the Mastervolt Whisper 3,5 marine generating set controlled by Digital Diesel Control. First launched in April 2004. For earlier models refer to other manuals available on our website: www.mastervolt.com
CONTENTS:
1
INTRODUCTION..............................................................................................................................................................4
1.1 General .............................................................................................................................................................. 4
1.2 Service and maintenance................................................................................................................................... 4
1.3 Guarantee.......................................................................................................................................................... 4
1.4 Liability............................................................................................................................................................... 5
1.5 Identification....................................................................................................................................................... 5
1.5.1 Nameplate......................................................................................................................................... 5
2 INFORMATION................................................................................................................................................................ 6
2.1 Safety.................................................................................................................................................................6
2.1.1 General..............................................................................................................................................6
2.1.2 Electrical safety ................................................................................................................................. 6
2.1.3 Earth insulation failures.....................................................................................................................6
2.1.4 Installation.........................................................................................................................................7
2.1.5 Operation........................................................................................................................................... 7
2.1.6 Fire and explosion............................................................................................................................. 7
2.1.7 Chemicals.......................................................................................................................................... 7
2.2 TRANSPORT, LIFTING AND STORAGE........................................................................................................... 8
2.3 THE WHISPER 3,5 ............................................................................................................................................ 8
2.3.1 Features............................................................................................................................................8
2.3.2 Remote control.................................................................................................................................. 8
2.3.3 Documentation .................................................................................................................................. 8
2.3.4 Accessories included in the standard delivery...................................................................................8
2.4 Components....................................................................................................................................................... 9
2.4.1 Main components to identify..............................................................................................................9
2.4.2 Generator control panel...................................................................................................................10
2.4.3 Remote control panel ...................................................................................................................... 10
2.5 Technical Information.......................................................................................................................................10
2.5.1 AC alternator................................................................................................................................... 10
2.5.2 Engine.............................................................................................................................................10
2.5.3 Digital Diesel Control system........................................................................................................... 10
2.5.4 Battery charger................................................................................................................................11
2.5.5 Alarms and shut down..................................................................................................................... 11
2.5.6 Control............................................................................................................................................. 11
2.5.7 Remote control................................................................................................................................ 11
2.5.8 Hour counter.................................................................................................................................... 11
2.5.9 Load indicator..................................................................................................................................11
2.5.10 Fuel specification............................................................................................................................. 11
2.5.11 Oil information................................................................................................................................. 11
2.5.12 Technical data................................................................................................................................. 12
2.5.13 Wiring codes and colours................................................................................................................13
2.5.14 Lay out control PCB.........................................................................................................................14
2.5.15 Electrical diagram 230 V AC / 50 Hz ............................................................................................... 15
Page 3
CONTENTS
EN / WHISPER 3,5 / May 2006 3
3 OPERATION.................................................................................................................................................................. 16
3.1 General ............................................................................................................................................................ 16
3.2 Operating Instructions ...................................................................................................................................... 16
3.2.1 Summarised operating instructions (daily use)................................................................................16
3.2.2 Extended operating instructions ...................................................................................................... 16
4 MAINTENANCE............................................................................................................................................................. 19
4.1 Alternator..........................................................................................................................................................19
4.2 Engine.............................................................................................................................................................. 19
4.2.1 Preliminary instructions ................................................................................................................... 19
4.2.2 Bleeding fuel lines ........................................................................................................................... 19
4.2.3 Valve clearance...............................................................................................................................19
4.2.4 Replacing fuel filter.......................................................................................................................... 20
4.2.5 Cleaning oil strainer......................................................................................................................... 20
4.3 Regular maintenance ....................................................................................................................................... 20
4.3.1 Maintenance schedule..................................................................................................................... 21
4.3.2 Putting out of service....................................................................................................................... 21
5 TROUBLE SHOOTING.................................................................................................................................................. 22
5.1 Alternator/ electrical faults ................................................................................................................................ 22
5.1.1 General............................................................................................................................................22
5.1.2 Trouble shooting table..................................................................................................................... 22
5.2 Engine faults..................................................................................................................................................... 23
5.2.1 General............................................................................................................................................23
5.2.2 Trouble shooting table..................................................................................................................... 23
5.2.3 Warnings......................................................................................................................................... 26
5.2.4 Service address............................................................................................................................... 26
5.3 Special procedures alternator........................................................................................................................... 26
5.3.1 Residual voltage check / excitation procedure ................................................................................ 26
5.3.2 Testing rotary rectifier diodes .......................................................................................................... 26
5.3.3 Winding resistant values.................................................................................................................. 27
5.3.4 Meggering ....................................................................................................................................... 27
5.4 Special procedures engine............................................................................................................................... 27
5.4.1 Setting the RPM .............................................................................................................................. 27
5.4.2 Tightening torques........................................................................................................................... 27
5.4.3 Measuring exhaust backpressure.................................................................................................... 27
5.4.4 Disassembling instructions.............................................................................................................. 28
6 SPARE PARTS LIST..................................................................................................................................................... 29
MAINTENANCE LOG ............................................................................................................................................................... 31
Page 4
INTRODUCTION
4 May 2006 / WHISPER 3,5 / EN
1 INTRODUCTION
1.1 GENERAL
The Whisper 3,5 Marine Diesel Generating set is manufactured and marketed by Mastervolt. It is important to read this manual before installing and operating the generating set. Both safety and durability rely very much on the correct identification, installation and a good understanding of ratings, features, design, maintenance and operation procedures. The information, specifications, illustrations and statements contained within this publication are given with our best intentions and are believed to be correct at the time of going to press. Our policy is one of continued development and we re­serve the right to amend any technical information with-out prior notice. Whilst every effort is made to ensure the accuracy of the particulars contained within this publication neither the manufacturer, distributor, or dealer in any circumstances shall be held liable for any inaccuracy or the consequences thereof.
WARNING
A warning symbol draws attention to special warnings, instructions or procedures which, if not strictly observed, may result in damage or destruction of equipment, severe personal injury or loss of life.
DANGER
This danger symbol refers to electric danger and draws attention to special warnings, instructions or procedures which, if not strictly observed, may result in electrical shock which will result in severe personal injury or loss of life.
1.2 SERVICE AND MAINTENANCE
Regular service and maintenance should be carried out according to the directions in this manual. For service and maintenance one can appeal to the manufacturer or the dealers.
1.3 GUARANTEE
Mastervolt guarantees that this generating set has been built according to good workmanship, according to the specifications in this manual and according to European Community safety regulations.
During production and prior to delivery, all of our generating sets are tested and inspected.
The functioning of this generating set is subject to guarantee. The period and conditions of this guarantee are laid down in the general conditions of delivery as registered with the Chamber of Commerce and Industries in Amsterdam number 33279951 and are available on request. Some aspects of our warranty scheme are given here in more detail: The guarantee period is two years, limited to 1000 running hours. Warrantee does not cover failures that are caused by misuse, neglect or a faulty installation.
Example 1. Faulty installation: Seawater entering the engine is the most common cause of damage to combustion engines in boats. (Both to propulsion and generator engines.) The entry of water must be avoided under all conditions. Be aware that the conditions in blue water sailing can be extreme. Refer t o the installation manual for instructions but remember these are for guidance only as many factors influence the installation of a generator. The ultimate responsibility will always be with the owner to ensure a safe and comp liant installation. If in doubt ask!
DAMAGE CAUSED BY THE INGRESS OF WATER IS NEVER COVERED BY WARRANTEE
Example 2: Misuse: Long term running with no load or too little load c an cause the exhaust to get choked with soot or carbon. Cleaning the exhaust is not covered by warrantee.
Example 3: Neglect Sometimes the seal of the raw water pump starts leaking. Mostly this begins with a little drip and slowly gets worse. Regular visual inspection of the generator is necessary to prevent damage to occur from a leaking water pump. When one find serious damage after weeks of neglect warrantee claims will not be honoured.
Example 4: Neglect Whisper generators have an option for an auto start/stop mode or interval mode. Mastervolt cannot be held responsible for damage caused by the unattended running generator.
Page 5
INTRODUCTION
EN / WHISPER 3,5 / May 2006 5
Warranty means that faulty parts are repaired or replaced free of charge. If necessary the whole generator unit will be exchanged. Labour necessary to complete repairs on board a vessel executed by an authorized service engineer is covered, but is limited to a reasonable number of hours and reasonable rates in relation to the actual repair work that has to be done. Travel expenses and travel hours are not covered. Also not covered is the labour required to take a generator out of a boat or for reinstallation. There is no cover for labour needed to get access to the generator, for example to remove equipment or bulkheads etc. Goods to be delivered under warrantee will be invoiced. Only after the faulty goods are returned will the invoice be credited. Payment in advance may be required or guaranteed by credit card. If after the faulty goods are returned, it is indicated that the failure was not covered by warranty a credit will not be issued. For example if a Printed Circuit Board is returned with clear damage caused by seawater, warranty will be refused. Freight costs to deliver spares by normal mail or carriers is covered under warranty. Special services like express mail, overnight delivery etc. are not covered. Taxes and duties are not covered. For shipments to remote off shore areas any additional costs incurred over normal carriage will be invoiced to the customer. The cost for returning faulty goods is not covered under warranty.
Additional agreements could be part of the contract of delivery.
If any problem arises which could be subject of guarantee, procedures should be followed as described in the guarantee certificate, unauthorised repairs could lead to further damage and violate the guarantee conditions.
Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in this user’s manual and the supplementary installation manual, then damage may occur and the generating set may not fulfil its specifications. In all these cases the guarantee may become invalid
1.4 LIABILITY
Mastervolt does not accept responsibility for damage, injuries or casualties which are the result of operation of the generating set in specific conditions which brings dangers which could not be foreseen, or could be avoi ded by additional measures. Mastervolt does not accept
liability for damage due to use of the ge nerator, possible errors in the manuals and the results thereof.
Automatic start/stop Mastervolt cannot be held responsible for damage caused by the unattended running generator using the auto-start/stop mode or interval mode.
1.5 IDENTIFICATION
Before using this generating set it is very important to identify the set correctly. To communicate for service or ordering parts it is also essential to correctly identify the generating set. Also for the daily operation of the genera­ting set it is necessary that the operator knows the correct specifications.
1.5.1 Nameplate
All required identification data are on the nameplate.
1 The identity of the generating set is given by the
SERIAL NUMBER. When this number is available the manufacturer can trace the specifications of the generating set. On the nameplate are also some basic features of the set:
2 POWER
The nameplate gives the nominal maximum continues load in kVA (= kW) calculated with power factor one. When calculating a load one should al ways take into account the power factor or cos phi of this load. The
Model Whisper 3,5 Article number 050900500 Serial number
Max. power 3,6 KVA cos phi =0,8
3 KVA cos phi = 1 Voltage 230V ± 5% Frequency 50 Hz Current 13A Phase Single phase Dimensions
L x W x H
505x400x500mm
Weight 97 kg
Fig 1: Nameplate
Page 6
INFORMATION
6 May 2006 / WHISPER 3,5 / EN
power should never exceed 3 kW. Power is rated at an ambient temperature of 40°C and a seawater temperature of 25ºC. For higher temperatures the generating set has to be derated.
3 VOLTAGE shows the nominal voltage.
This voltage should be within the specified tolerance at the nominal frequency.
4 FREQUENCY is shown in Hz and is determined by
the speed of the engine (RPM). 50 Hz correlates with 3000 rpm, 60 Hz correlates with 3600 rpm.
5 CURRENT shows the maximum current that is
acceptable at the specified frequency, voltage and power factor.
6 WEIGHT shows the net dry weight (approximately) in
kg. This is without fuel, oil, packing and external installation equipment
7 The CE symbol shows that the generating set is build
according to European Community safety regulations. This includes the regulations regarding the safet y of pleasure craft, machinery, electric safety and electric magnetic compatibility (EMC) and other relevant directives.
Safety also relies on the installation, application and circumstances. See also the remarks in this manual under SAFETY
Before changing a factory setting you are advised to consult the manufacturer. When the generating set you have to identify is not new you have to take into account the possibility that former users may have changed the settings. Check the settings (voltage, frequency, rpm) when there is any doubt.
2 INFORMATION
2.1 SAFETY
2.1.1 General
When correctly installed and used in normal circumstances this generating set fulfils EC safety regulations. This generating set could be part of an installation or could be used in a way that additional regulations of the EC or other authorities have to be taken into account.
Circumstances could make it also necessary to take additional measures. Be aware of wet conditions and hazardous environments caused by explosive gases etc
2.1.2 Electrical safety
The voltage of 230 Volt generated by this generating set is dangerous and if instructions and procedures are not strictly observed may result in electrical shock which will result in severe personal injury or loss of life.
Check all wiring at least once a year. Defects, such as loose connections, burned cables etc. must be repaired immediately.
Do not work on the electrical system if it is still connected to a current source. Only allow changes in your electrical system to be carried out by qualified electricians.
Connection and protection must be done in accordance with local standards.
Using the auto-start/stop (interval) mode the generator can start unexpectedly. When working on the electrical system, the 3 Amp fuse must be removed from the control panel and the battery plus cable must be removed from the battery.
Warning signs indicate parts which could be live.
2.1.3 Earth insulation failures
According to local regulations and depending on the application it could be necessary to take measures for protection against earth insulation failures. In the standard delivery “neutral” and “ground” are not connected. To make a connection between “neutral” and “ground” could be necessary as part of a specific insulation failure protection system.
Page 7
INFORMATION
EN / WHISPER 3,5 / May 2006 7
Small pleasure craft in Europe is submitted to The Recreational Craft Directive 94/25/EC. The guidelines of this directive refer to (ISO 13297). When the installation complies with this standard the “neutral” and “ground” should be connected on the generating set. (Refer to the electrical diagram, page 15)
In all situations the transfer switches between shore, inverter and generator should switch
both neutral and L1. Of course this is the case when using a Mastervolt Masterswitch. Be aware that insulation protection systems can be different for different applications and even within the shi p there could be different standards for different spaces. We did refer to the Recreational Craft Directive that applies to pleasure craft up to 24 m of length. Sometimes one has to comply with other standards such as the rules of certification societies like Lloyds Register of Shipping or Veritas, regulations for the protection of personal, building legislation, etc. It is of the greatest importance to have expert advice on this issue.
2.1.4 Installation
Whisper generating sets are not self contained and have to be properly installed in enclosed areas such as a machine room.
Installation includes measures to be taken to
outlet exhaust fumes which contain carbon
monoxide and are extremely dangerous. Carbon monoxide (CO) is an invisible odourless gas. Inhalation produces headache, nausea or death. Installation includes measures for proper ventilation, safe electric connections, safe installation of the starting battery, proper fitting of the cooling system and fuel pipes etc. Refer to the installation manual.
2.1.5 Operation
The Whisper 3,5 generating set does not have any external moving parts like fans and V-belts and therefore is very safe.
Nevertheless take note of the signs on the generating set which show symbols in a triangle indicating danger.
The generating set should be operated by authorised personnel only.
Be aware of hot parts and especi ally parts of the exhaust system.
If the generating set is unsafe, fit danger notices and disconnect the battery negative (-) lead so that it cannot be started until the condition is corrected.
Do not attempt to operate the generating set with a known unsafe condition. Disconnect the battery negative (-) lead prior to attempting any repairs or cleaning inside the enclosure.
Always consult the manual before carrying out maintenance.
Do not ch ange the settings without consultin g the manufacturer. Keep a record of setting changes in this manual.
2.1.6 Fire and explosion
Fuels can be flammable. Proper handling limits the risk of fire and explosion.
Avoid refilling the fuel tank while the engine is running. When oil or fuel is leaking do not use the generating set.
Do not run the engine close to explosives or gasses.
Hydrogen gas generated by charging batteries is explosive. Ensure for proper ventilation. Do not smoke or allow sparks, flames, or other sources of ignition around batteries.
Keep a fire extinguisher on hand.
Poor electrical connections or using wiring which
is not suited for the rated currents can cause overheating and possibly fire.
2.1.7 Chemicals
Fuels, oils, coolants, and battery electrolyte can be hazardous to personnel if not treated properly. Do not swallow or have skin contact with these liquids. Do not wear clothing that has been contaminated by fuel or lubricating oil.
Gaskets may be manufactured from asbestos. Particles of this material should not be inhaled as this may result in fatal diseases.
Page 8
INFORMATION
8 May 2006 / WHISPER 3,5 / EN
On no account allow any unprotected skin to come into contact with the injector spray as the fuel may enter the blood stream with fatal results.
Engines may be fitted with seals or O-rings manufactured from "viton" or similar material. When exposed to abnormal high temperatures in excess of 400°C an extremely corrosive acid is produced which cannot be removed from the skin. If signs of decomposition are evident, or if in doubt, always wear disposable heavy duty gloves.
2.2 TRANSPORT, LIFTING AND STORAGE
When lifting the generating set avoid any risk of personal injuries, do not stand un-der the generating set..
Use soft slings to avoid damage
Included in the delivery is a lifting eye, onl y to be
used to take the generator out of the capsule. Do not use to lift the set including the capsule and certainly not including the steel foundation plate !
After transporting the generating set check for damage before installation.
Long term storage can have detrimental effects on engine and alternator. The engine shoul d be put through an engine preservation procedure. (Refer to the maintenance chapter)
The alternator windings tend to condense. To minimise condensation, store the generating set in a dry and warm storage area.
After removing the generating set from long term storage perform an insulation check. (Refer to the alternator maintenance paragraph for procedures)
While th e battery is stored it should be recharged every 12 weeks.
2.3 THE WHISPER 3,5
2.3.1 Features
This generating set includes a diesel engine which is connected by close coupling to an alternator in a sound attenuated capsule. The set is mounted on a steel base frame and mounted securely on anti vibration mounting pads to the capsule base. All cables and hoses ar e guided through the capsule’s left side. The set is not self contained and is only operable after proper installation using additional accessories and installation materials. Installation accessories are listed in the installation manua l and are available through the supplier of the genera-ting set. The full automatic Digital Control is based on microprocessor technology. Several automatic start/stop functions can be programmed and monitored (refer to Digital Diesel Control users manual).
2.3.2 Remote control
The full automatic remote control panel including 15 mtr cable comes as standard with the Wisper 3,5.
2.3.3 Documentation
Included in the delivery is this users manual (number:
50200302) an installation manual (number: 50200311) and a users manual for DCC (number: 50200261). Not included in the standard delivery but available as options are:
Parts manual; number: 50200180
Workshop manual; number: 50200170
However in this manual there is a list of important parts for maintenance and spare parts as well as a chapter on maintenance and problem solving.
2.3.4 Accessories included in the standard delivery
Fuel filter
Fuel lift pump
Lifting eye
Special hose connector for measuring exhaust
backpressure (Refer to paragraph 5.4.3).
Page 9
INFORMATION
EN / WHISPER 3,5 / May 2006 9
2.4 COMPONENTS
2.4.1 Main components to identify
1 Air inlet; 2 Starter motor; 3 Battery connection (positive); 4 Battery connection (negative); 5 AC 230 V wiring; 6 AC 230 V output connection box; 7 Fuel filter; 8 Fuel pipe inlet; 9 Fuel pipe return; 10 Bypass hose air vent; 11 Cooling water in; 12 Exhaust manifold (water cooled); 13 Thermo-switch exhaust; 14 Glow plug; 15 Injector; 16 Valve cover; 17 Decompression handle; 18 Oil filler cap; 19 Solenoid fuel valve; 20 Electric fuel lift pump; 21 Cooling water pump; 22 Oil pressure pump; 23 Fuel pressure pump 24 Oil pressure switch; 25 Oil sump pump; 26 Exhaust connection; 27 Fuel return; 28 Oil filler cap/ oil level indicator; 29 Control panel; 30 Capacitor; 31 Fuse 1; 32 Fuse 2; 33 Remote control cable; 34 Stop solenoid; 35 Oil strainer cover; 36 Start button; 37 Digital Diesel Control unit; 38 RPM set screw; 39 Oil temp switch; 40 Plug screw; 41 Heat exchanger.
Fig. 2: Overview Whisper 3,5.
18
19 27
25
40 23
38
37 30
29 31 32
36
34 24
28
1 39
14
2
41
20
7
26 3
9 4
10 11
6
1 17
15 16
12 13
3 4
21 22
35 33
20 5
8
Page 10
INFORMATION
10 May 2006 / WHISPER 3,5 / EN
2.4.2 Generator control panel
Fig. 3: Control panel. 1 Fuse 3A; 2 Fuse 3A; 3 Start/stop button.
Fig... 4: Digital Diesel Control unit
2.4.3 Remote control panel
1 Start button; 2 Stop button; 3 Select button; 4 Set button; 5 Failure lamp; 6 Generator load indicator. 7 Display
2.5 TECHNICAL INFORMATION
2.5.1 AC alternator
The single phase alternator is directly coupled, one bearing, brushless, rotating field design, t wo poles (3000 RPM) and self regulating. Residual magnetism causes a small voltage over the stator windings and allows a current to flow in the windings, which is magnified because of the feed back effect between rotor and stator. The field windings in th e rotor are short-circuited over a diode to rectify the current. A capacitor over an additional winding in the stator which is at an angle with the power-winding keeps the voltage stable within 5 % at the specified rpm and provides voltage fall off with speed, preventing over-excitation at low engine speeds and softening the effect of load switching to relieve the burden on the engine. Further technical data on the design of the alternator can be found in drawings and diagrams in this manual.
2.5.2 Engine
The Whisper 3,5 generating set is based on the Kubota OC60 1 cylinder diesel engine. The engine is indirectly injected. The engine is oil cooled and the oil is cooled by a heat exchanger and raw water. The heat exchanger and all other parts which are in direct contact with the raw (sea) water are made of seawater resistant material like naval brass and gunmetal. The engine has been specially adapte d for the Mastervolt application and is very different from the standard engine supplied for industrial applications!
2.5.3 Digital Diesel Control system
The standard electrical engine control system is 12 Volt negative earth, non earth return (ungrounded) is available as optional. Check your identification data to determine which system is applied. The system is designed according to the "energise to run" system. The Digital Diesel Control is a very advanced microprocessor based full automatic system. Besides automatic start the system offers many monitoring options. Refer to the separate Digital Diesel Control users manual. The microprocessor unit is located on top of the alternator.
1
2
3
3A 3A
Fig. 5: Digital Diesel remote control panel.
1 2 6 5
3 4 7
Page 11
INFORMATION
EN / WHISPER 3,5 / May 2006 11
2.5.4 Battery charger
There is an extra winding in the alternator generating 6 Amp 12 V. This current is rectified on the control PCB to charge the battery. Both the current and the voltage are regulated.
2.5.5 Alarms and shut down
In the event of malfunctioning this will be indicated by the failure light and details will be shown on the display the engine will be shut down. There are three functions guarded: oil pressure, oil temperature and exhaust temperature. Exhaust temperature too high indicates the cooling water to be blocked. All alarm switches are closed when no malfunction occur. A contact is cut in the event of an alarm. This means that the generating set will not work when the alarm switches are broken or there is a loose wire. The system therefore is intrinsically safe. The panel will display details about the alarm.
2.5.6 Control
The generating set can be operated by push buttons on the panel on the alternator or by the remote control. By pushing the start button the control system is activated and will start the engine automatically. Pushing the ST OP button will stop the engine and the electrical system will be deactivated. Stopping the engine is executed by the ‘pull’ solenoid, at the same time the fuel valve solenoid will shut off.
2.5.7 Remote control
All wiring connections from the remote control to the board are made by plug in connectors. An intermediate communication cable is in the standard supply. If necessary an optional longer 8 wire cable can be connected if the standard length does not suit the required distance. Numerous remote control units can be put in parallel by using the connectors on the back of the units. (Refer to installation instructions)
2.5.8 Hour counter
The remote control offers several timer functions that helps to schedule maintenance.
2.5.9 Load indicator
On the remote control the load will be indicated on the display and by the LED-bar. The load is measur ed by a current transformer on the alternator.
2.5.10 Fuel specification
The engine must only be used with diesel fuel oil which conforms to the standards for use in modern diesel engines. Fuel free from water and contaminants is of the utmost importance.
2.5.11 Oil information
1 Specification:
The oil must be suitable for oil changes as specified in the maintenance chapter. The Kubota engine must be run on heavy duty lubricating oil meeting the requirements of API class CC or CD.
It is very important to use the correct oil specification. Very often local oil suppliers recommend a higher class, because they assume that a higher class is allowed. This is not the case. One should not follow these recommendations. Using the wrong specification will cause high oil consumption.
2 Oil viscosity:
We recommend a multigrade oil 15W40.
3 Oil capacity:
Excluding the oil cooler the content of the crankcas e is 1,3 l. including the oil cooler it is 1,5 l. Do not overfill with lubricating oil as this m ay have a detrimental effect on engine performance.
4 Oil pressure
Minimum at idle 49 Kpa (0,5 kgf/cm2 - 7psi).
Normal at 3000 rpm between 147 and 4 90 Kpa
(1,5 up to 5 kgf/cm2 - 21 up to 71 psi).
Minimum at 3000 rpm 98 Kpa (1,0 kgf/cm 2 - 14 psi).
Page 12
INFORMATION
12 May 2006 / WHISPER 3,5 / EN
2.5.12 Technical data
GENERAL
Model WHISPER 3,5 RPM 3000 Alternator water cooled, synchronous Engine Kubota diesel, model OC60 (Japan) Number of cylinders 1 Displacement 276 cm3 Bore X stroke 72x68 mm Combustion air consumption 0,38 m3/min.. at nominal RPM Continuous power engine 3 kW nett. Cooling system Indirect cooling by raw water. Cooling water pump pto driven Mastervolt self priming impeller pump, type K Fuel lift pump engine electric pump (12 V DC), additional pump available upon request Starting battery (optional) 55-90 Ah Fuel consumption 0.7-1.4 litre/hour, load dependent Control Digital Diesel Control including automatic start/stop
ELECTRICAL SPECIFICATIONS
Output voltage 230V 50 Hz alternating current (AC) single phase Output rating 3,6 KVA cos phi = 0,8; 3 KVA = 3 kW cos phi = 1 Voltage tolerance ± 5% Frequency tolerance ± 5% Alternator brushless, two pole, synchronous
MECHANICAL SPECIFICATIONS
Supply includes generating set, built into tugged GRP sound shield with steel bas e frame, m ounte d
on rubber anti vibration mounts Dimensions hxwxd 500x505x405 mm Colour top white, bottom green Weight 97 kg including sound shield Max. installation angle 25 degrees Standard supplies Digital Diesel Control, remote panel (15 m cable) Optional mobile (vehicle) version, non earth return, spare part kits
Page 13
INFORMATION
EN / WHISPER 3,5 / May 2006 13
2.5.13 Wiring codes and colours
number colour cable code no
cross section battery > starter motor red 16 mm2 starter motor > DCC 1 red 6 mm2 starter motor > LCP 13 red 2,5 mm2 battery > ground black 16 mm2 ground > LCP ground (GND) 2 black 2,5 mm2 DDC > glow plug 3 brown 4 mm2 DDC > starter solenoid 4 yellow 2,5 mm2 LCP > fuel lift pump + 5 brown 1,5 mm2 LCP > fuel lift pump – 15 black 1,5 mm2 DDC > LCD 5 grey 1,5 mm2 DDC > oil pressure switch 6 purple 1 mm2 LCP > oil pressure switch 6 purple/black 1 mm2 DDC > oil temperature switch 7 blue 1 mm2 LCP > oil temperature switch 7 blue/black 1 mm2 DDC > exhaust temperature switch 8 blue/green 1 mm2 LCP > exhaust temperature switch 8 blue/rose 1 mm2 DDC > fuel valve solenoid 9 green 1,5 mm2 DDC > stop solenoid 20 pink 2,5 mm2 DDC > current measuring transformer 11 black 1 mm2 DDC > current measuring transformer 11 red 1 mm2 DDC > LCP 19 orange 1,5 mm2 DDC > LCP 12 black 1,5 mm2 DDC > LCP 14 red 1,5 mm2 DDC > LCP 16 red/green 1,5 mm2 DDC > generator AC output 33 brown 1 mm2 DDC > generator AC output 33 blue 1 mm2 LCP > battery charger winding generator 10 red 1 mm2 LCP > battery charger winding generator 10 red 1 mm2
DDC=Digital Diesel Control Unit LCP=Local Control Panel
Page 14
INFORMATION
14 May 2006 / WHISPER 3,5 / EN
2.5.14 Lay out control PCB
Fig 7: Lay out control PCB
Page 15
INFORMATION
EN / WHISPER 3,5 / May 2006 15
2.5.15 Electrical diagram 230 V AC / 50 Hz
Fig 8: Electrical diagram 230V
EARTH AND NEUTRAL CONNECTED
Page 16
OPERATION
16 May 2006 / WHISPER 3,5 / EN
3 OPERATION
3.1 GENERAL
The generating set is operational after full installation and filling up with: fuel, engine lubricating oil and cooling liquid, filling the starter battery with acid, connecting the battery to earth and connecting the digital remote control panel.
1 Filling cap 2 Minimum oil level 3 Maximum oil level Fig. 9:
3.2 OPERATING INSTRUCTIONS
3.2.1 Summarised operating instructions (daily
use)
Routine "pre-start" checks: 1 Check oil level (refer to fig. 9). 2 Engine cooling system (all valves open). 3 Power source selector switch (off/shore
power/generator power). Switch to power source switch "OFF", or switch off all consumers in the usual way. If a MASTERSWITCH is installed, this operates
automatically. 4 Switch on battery switch (when installed). 5 Fuel valve: open.
Starting:
Push the start button to initiate the full automatic
starting procedure. You can monitor the procedure on
the display.
In operation checks: 1 Check for abnormal noise or vibration 2 Check the voltage 3 Check sea water flow at exhaust outlet 4 Power source selector switch (off/shore
power/generator power). Switch to power source generator. If a MASTERSWITCH is installed, this operates automatically.
5 Before loading the generating set up to maximum,
have it run warm. Continuous load should be restricted to 70 % of maximum load.
Stopping generator: 1 Switch off all electrical devices (consumers). If the
generating set has been running under full load for a longer period, do not shut it down abruptly. Reduce the electrical load to about 30% of the rated load (i.e. 30% of 3 kW is approx. 1000W) and let it run for
approx. 5 minutes. 2 Press the STOP button. 3 Close the inlet sea water cock. 4 Switch to an other 230V power source, if available. If
a Masterswitch is installed, this is done automatically.
3.2.2 Extended operating instructions
Check when starting the first time or after a longer perio d of rest: 1 If there is any damage caused by transport or
installation. 2 Check if installation conforms to the installation
instructions. 3 Ensure the generating set is free to turn without
obstruction. 4 Check all hoses and hose connections for leaks. 5 Check all cables and cable end terminal connections. 6 Check the engine and generator mounting bolts.
Routine "pre-start" checks: 1 Check engine oil level.
The generator switches off in the event of insufficient
oil-pressure. Even when the oil level is too low the oil
pressure can be high enough. Do not run the
generator with the oil below the lowest mark in the,
because a smaller volume of oil will become
contaminated considerably quicker than a larger
volume. Therefore we recommend daily oil-checks.
Check oil level prior to starting the engine or at least 5
minutes after the engine has stopped. 2 Check sea water cocks. Do not forget the valve of the
water outlet in case of a water/exhaust gas separator.
Page 17
OPERATION
EN / WHISPER 3,5 / May 2006 17
3 Check the water strainer. 4 Check for leaks. 5 Regular ly check the siphon vent in the cooling water
supply.
6 If no MASTERSWITCH is used: Switch main Power
Source Selector switch to "OFF" or switch off all devices.
7 Switch on the battery switch.
Starting the generator:
By pushing the start button briefly the electric system is activated, the fuel lift pump starts pumping and the starting procedure will begin. (By pushing the stop button the system is deactivated)
The Whisper 3,5 can even be started with an almost discharged battery using the cylinder compression release handle. The engine can then be rotated easily ("turned over") as the valves are opened i.e. in the decompression position. You can also use the decompression handle to readjust the valve clearance and to fill the cooling system with anti freeze for conservation in winter time.
A restart protection prevents starting the engine when it is already running, which could cause damage.
In the event of starting problems (numerous attempts are made), close the sea-water inlet cock while cranking to prevent the outlet system and engine to fill up with water.
During the starting process, the cooling water pump is driven with the engine. The cooling water is discharged t o the exhaust outlet, because the engine does not run, the exhaust pressure is not high enough to expel this water. Open the valve directly when the engine starts to prevent damaging the impeller. Water in the cylinder will cause serious damage to the engine. For instance; a bent piston rod or a cracked cylinder head. In fact water in the cylinder is the main cause for engine damage in pleasure craft.
Checks once the generator is in operation:
1 Check for abnormal noise or vibration. 2 Check the voltage.
Fig. 10: Decompression handle
3 Check coolant flow.
Always check immediately after starting the generator
if cooling water flows at the exhaust outlet. If this is
not the case, check the cooling water pump. After
having become acquainted with the generator you will
be able to recognise the coolant flowing throug h the
system by listening for the noise of the water which is
expelled.
Be aware that especially in harbours the coolant water inlet can easily be blocked by floating objects.
4 Power source selector switch (off/shore
power/generator power). Switch to power source
generator. If a MASTERSWITCH is installed, this
operates automatically.
Before loading the generating set up to maximum,
have it run warm. The first 50 hours of running the
continuous load should be restricted to 70 % of maxi-
mum load. Running for long periods at no load or light
load in the first 50 hours can cause cylinder glazing
and high oil consumption.
Engine load during longer operation: Please ensure that the generating set is not overloaded. Overloading occurs when the electrical load (demand) is so high that the generator cannot be turned around properly by the diesel engine. Overloading causes the engine to run rough, while using oil and excessive fuel and producing soot by the exhaust. The engine can even stop.
The generator should therefore only be loaded at the maximum rated power for short periods (2-3 hours) only!
Page 18
OPERATION
18 May 2006 / WHISPER 3,5 / EN
The high peak current is meant for the ability to start electrical devices that need a high current for starting especially electric motors and compressors (from a still stand state). In order to prolong the generating set’s life expectance, the nominal electrical demand on the system should be about 80% or the rated generating set’s maximum load. Please note this when switching on your electrical devices! Nevertheless, the Whisper 3,5 is designed so as not to overheat, even under extreme conditions.
Do not run the generator for very long periods at no load or at very low load. When this is necessary do load the generator at least one hour in 10 hours for minimum 70%. Long term running at too low load will cause the exhaust to be choked by carbon.
Never remove the battery while the engine is running or any electrical cable while the battery is connected in the circuit. Only disconnect the battery with the engine stopped and all switches in "OFF" position
Stopping the generating set:
1 Avoid stopping of the gen erator abruptly after a long
period of operation at high load! Doing so, you av oid unnecessary thermal load to your generating set! Act as follows: Prior to switching off the generating set, decrease the generator load (i.e. turn off most electrical users) and let the generator run at low load for approx. 5 minutes to allow the engine to get properly cool ( the influe nt sea water must flow through the system in order to cool the engine).
If the generator is operating in a hot environment and
you do not act as given above, the excessive heat in
the engine can trip the "high temp" alarms. In that
case, a restart of the engine is not possible for some
time. It is also recommended to switch off electrical
users prior to stopping the generator because of the
voltage drop that occurs as the engine comes to a
halt. Such voltage drops may cause damage to
electric motors, compressors (in refrigerators or air
conditioners etc.).
2 Press the STOP button.
3 Close the inlet sea water cock.
4 Switch to an other 230V power source, if available. If
a Masterswitch is installed, this is done automatically.
If the engine is not running and ‘failure’ and ‘charging’ LED is blinking, reset by stop button, otherwise it will drain the start battery
Page 19
MAINTENANCE
EN / WHISPER 3,5 / May 2006 19
4 MAINTENANCE
4.1 ALTERNATOR
The alternator does not require any maintenance. Periodic inspection and cleaning is recommended, depending on environmental conditions. However when the alternator has been idle for a long period attention to winding condition is recommended. The condition of windings can be assessed by measurement of insulation resistance to earth. The CAPACITOR should be disconnected during this test. A 500V ‘megger’ or similar instrument should be used. The insulation resistance to earth of all windings should be in excess of 1.0 MOhm. Should the insulation resistance be less than this value, drying out the generator windings is essential. Drying out can be carried out by direct warm air from a fan heater or similar apparatus into the generator air inlets or outlets. All bearings are greased for life and not regreasable.
4.2 ENGINE
4.2.1 Preliminary instructions
All regular maintenance can be carried out when the en­closure is open. For repairs we recommend to take out the generating set to a workshop. The enclosure can be completely removed by taking out the bolts form the aluminium bars below the bottom of the capsule. When oil and dirt have gathered in the enclosure measures have to be taken to avoid spilling oil and polluting the environment.
The first service on the engine should be carried out after 25 hours of its life. This also applies after a major over­haul. In the first 25 hours the engine should receive special attention: Long periods of light or no load running in the first 25 hours may lead to cylinder glazing and high oil consumption.
For the same reason it is of the greatest importance to use the right oil specification
The first time starting up or after running out of fuel it could be necessary to prime the fuel system.
4.2.2 Bleeding fuel lines
Ensure there is sufficient fuel. The Whispers are self bleeding. Push the start button activating the electric system and activating the fuel pump. When more time is
needed to bleed, push “start” and hold on the local control panel (so not on the remote panel). Hold as long as necessary to bleed the system.
Fig. 11: Self bleeding fuel lines
4.2.3 Valve clearance
Tightening torques, refer to § 5.4.2. When the engine is in cold condition both valves shoul d have a clearance between 0.14 and 0.18 mm. The adjustment has to be done at T.D.C. of the compression stroke. Using a pocket light one can check the position of the flywheel (refer to picture 12). By using the decompression handle one can crank the engine easily with a screwdriver to put the marks in line. Confirm that the valves do not move up or down when the crankshaft is turned about 20 degrees in normal and reverse direction of rotation. If the rocker arms move the piston is on the T.D.C. of the intake or exhaust stroke. In such a case turn the crankshaft 360° in the direction of engine rotation again. The piston is now at T.D.C. of the compression stroke. After readjustment one should crank the engine for 20 rotations and check the valves again.
Fig. 12: Valve clearance
Page 20
MAINTENANCE
20 May 2006 / WHISPER 3,5 / EN
4.2.4 Replacing fuel filter
Filter change depends on contamination of the fuel, but should be done however, at least every 1000 running hours. Before changing the filter, clamp off the supply line. Remove the hoses from filter and attach them on the new filter again. The arrow on the filter housing indicates the direction of the flow. A clogged filter results in a lack of output of the generating set.
4.2.5 Cleaning oil strainer
The oil strainer is behind a plug on the bottom of the engine. In the strainer is a magnet to catch the metal parts which are in the lubricating oil. Once per 1000 hours or when the oil is contaminated one can clean the strainer by washing it with petrol or a solvent. A green rubber plu g in the capsule gives access to the strainer. Before taking out the plug one should sump the oil. Use tissues to avoid spilling oil in the capsule.
4.3 REGULAR MAINTENANCE
CHECK DAILY:
Oil level (see fig. 13) Take care the oil level is never below the mark.
Hoses for loose connections or deterioration.
Water inlet filter.
1 Filling cap 2 Minimum oil level 3 Maximum oil level Fig. 13:
AFTER FIRST 50 HOURS:
Change oil. Have the engine run until it is on temperature an d stop it. Drain oil by the sump pump into a suitable retainer and fill up with fresh oil. Start the engine again and have it run for 5 minutes. Stop the engine again and pause for a few minutes to let the oil gather in the crankcase. Check the level again and add oil when necessary.
Check and tighten nuts, bolts, and unions, paying particular attention to the fuel system.
Check the valve clearance.
Observe the exhaust at the normal full load. The
exhaust must be free from soot. Do not allow the engine to run with a dirty exhaust without investigating the cause as this may result in an expensive breakdown.
Check siphon breaker valve or air vent on a regular basis. When the air vent it not working properly the engine can fill up with water by siphoning. Water in the combustion chamber causes serious damage to the engine.
EVERY 150 HOURS:
Change oil.
Check the battery acid level.
Check battery terminals for corrosion
Check impeller raw water pump (durability
depends on the purity of the sea water. In sandy water and warm water wear will increase). When replacing the impeller the gasket between the pump case and the cover should be replaced as well. So when ordering a spare impeller order a gasket as well. Remove the cover to get access to the impeller. Remove the old impeller with the help of two screwdrivers. Install the new impeller and add some grease. Turn the blades in the direction of rotation of the pump i.e. anti clockwise looking at the impeller.
EVERY 300 HOURS:
Replace the impeller of the raw water pump.
Check valve clearance.
Page 21
MAINTENANCE
EN / WHISPER 3,5 / May 2006 21
EVERY 1000 HOURS:
Replace the fuel filter Replacement depends on the condition of the fuel. We recommend replacement every 1000 hours. Isolate the fuel supply and change the element.
Clean the oil strainer.
EVERY 2000 HOURS:
Check lubricating oil pressure
Clea n and check or replace fuel injector nozzles
and check injection pressure.
Check the air filter element: The air is taken in via the cover on the alternator. Below this cover is a spongy material which filters the air and holds some electrical components which are cooled by the inlet air. This filter does not require regular maintenance. Only in very dusty circumstances this filter should be cleaned. The spongy material can be washed in solvent or replaced.
Check the cooling system: The engine oil is indirectly cooled by raw water via an oil cooler/ heat exchanger. The alternator is cooled by seawater which is pumped by the PTO driven impeller pump through the cooler elements in the generator housing. All parts of the cooling system are of corrosion free and seawater resistant materials such as brass and gunmetal. In case of gathering of dirt in the system it could be cleaned by compressed air. When overhauling the engine one could clea n the parts thoroughly or replace.
When the generator set runs less than 100 hours a year the oil should be changed yearly
4.3.1 Maintenance schedule
Check oil level daily Check water strainer daily Change oil 150 hours Check air vent 150 hours
Check impeller water pump 150 hours Check valve clearance 300 hours Replace impeller water pump 300 hours Replace fuel filter 300 hours Clean the oil strainer 1000 hours Check injector and injection pressure 2000 hours Check inlet air filter 2000 hours
4.3.2 Putting out of service
When not using the generating set for a longer period it is recommended to execute an engine preservation procedure.
1 Clean the engine.
2 Loosen the fuel suction pipe and fuel retur n and put
them in a can with preservation diesel fuel. Start the engine and run the engine warm.
3 Drain the hot engine oil and refill with preservation oil.
4 Stop the engine and loosen the inlet of the ra w water
pump. Drain the water from the water lock. Lift the valves by the decompression handle to avoid the engine from starting and crank the engine having the raw water inlet sucking anti freeze from a can until the pump, heat exchanger and manifold are full.
5 Disconnect the batter y and store it in a place free of
frost and dry and charge it regularly.
6 Close inlet- and outlet openings with tape.
7 Protect the generating set against the influences of
bad weather conditions.
This method of preservation will be sufficient for 6 months. Repeat steps 2, 3, and 4, every 6 months. Change oil before using the engine again.
Page 22
TROUBLE SHOOTING
22 May 2006 / WHISPER 3,5 / EN
5 TROUBLE SHOOTING
5.1 ALTERNATOR/ ELECTRICAL FAULTS
Beware of parts which are live!
Remove 3 Amp. Fuse in the control panel while working on the generator to prevent the engine from starting
5.1.1 General
If any problem should occur, check basic conditions and examine all external wiring, switch gear and circuit breakers. Also check if measuring instruments give the correct value. If in doubt, measure directly on the alternator terminals with an independent instrument.
This should only be carried out by an experienced electrician. Check if the engine is running correctly at 3000 (50 Hz) RPM according to its settings and does as well under load. A RPM drop of 5% at full load is acceptable. There-fore a no load setting should be at 3150 RPM = 52.5 Hz or 3750 RPM = 62.5 Hz. Under no circumstances should the RPM under full load be below 2940 RPM = 49 Hz or 3540 = 59 Hz. When the problem is in the RPM refer to the engine fault finding paragraph. Digital Diesel Control system will help to indicate failures and display causes.
5.1.2 Trouble shooting table
PROBLEM CAUSE SOLUTION
Circuit breaker "off" or faulty fuse
Check switches and fuses and measure directly on the alternator to exclude external causes.
Low engine RPM.
Check the engine RPM and adjust (refer to special procedures).
Loss of residual magnetism.
Check the residual magnetism and flash the alternator (refer to special procedures).
Capacitor loose or broken.
Check by independent excitation if the problem is in the capacitor or in the windings.
No output (Voltage) at all
Rotor diodes broken.
Check the diodes in the rotor (refer to special procedures) The Whisper 3,5 has two diodes in the rotor. It happens very rarely that both are broken. When only one diode is broken the voltage will be low but will not varnish completely.
No load at all or very low load.
Switch on a load and check voltage.
Engine is not reaching the rated RPM.
Refer to special procedures to readjust RPM.
Defective capacitor.
Check capacitor and replace if necessary (refer to special procedures).
Generator output voltage too low when no load is on it (less than 210V).
Defective diode (one of the two)
Check the diodes in the rotor and replace (refer to special procedures).
Generator is overloaded.
Switch off a load; (part off) consumers.
Engine is not reaching the rated RPM.
Refer to engine RPM problems
Generator output voltage too low under load (less than 210V). In no load condition it is ok
Defective capacitor
Check capacitor and replace if necessary (refer to special procedures).
Engine is running too fast (RPM too high).
Check engine speed and adjust (refer to special (more than 245V).procedures).
Over-energising due to defective capacitors
Check capacitor specification and replace capacitors if necessary.
Generator voltage too high, (more than 245V)
Presence of a strong capacitive load (leading power factor)
Compensate for this capacity and seek for experts advice.
Page 23
TROUBLE SHOOTING
EN / WHISPER 3,5 / May 2006 23
PROBLEM CAUSE SOLUTION
Disturbances on the electrical system/ user side.
Check if electrical load is fluctuating
Generator voltage fluctuates.
Engine runs irregularly.
When engine runs irregularly refer to section: "Engine runs irregularly".
Generator is not able to start an electric motor
If the generator is unable to supply enough power to start an electric motor (230V), this is usually because this motor draws too much current during starting
Check the electric motor’s current draw required for starting. This should not exceed 70% of the rated generator output current. This could be remedied by providing stronger capacitors to the motor or using a "soft-start". Inquire at your nearest Mastervolt dealer or directly at the manufacturer, Mastervolt in the Netherlands.
5.2 ENGINE FAULTS
Remove 3 Amp. fuse in the control panel while working on the generator to prevent the engine from starting.
5.2.1 General
Most electrical problems relating to Voltage or Frequency are due to wrong engine speed. Note that RPM and Hz are basically the same. Use the problem solving table to find the cause. When there is no obvious cause one can adjust the RPM (refer to special procedures). The Digital Diesel Control s ystem will help to indicate failures and display causes.
When the engine is not cranking well starting problems almost always originate from battery problems or poor battery cable connections. When the engine is cranking, well starting problems almost always originate from lack of fuel or air bubbles in the fuel pipes.
When the engine does not start instantly, prolonged cranking can fill up the exhaust system with cooling water because of the water injected exhaust. When the water enters the cylinder through the valves this will bring severe damage to the engine. When the engine does not start and repeated cranking is necessary shut off the seawater inlet. Open the valve immediately after the engine has started. A failure code is displayed when a hardware failure at the generator is detected.
failure code problem
COMMUNICATION
Communication error between the panel end the generator
LOW START BAT
Starter battery voltage too low
ALTERNATOR
No output battery charging voltage
EXHAUST TEMP
Exhaust temperature is too high
WATER TEMP
Coolant temperature is too high
OIL PRESSURE
Oil pressure failure
LOW VOLTAGE
Generator AC output voltage is too low
HIGH CURRENT
generator is in overload
FREQUENCY
output frequency of the generator is too low
5.2.2 Trouble shooting table
PROBLEM CAUSE SOLUTION
Almost certainly this is an electrical problem or the engine is locked by water in the cylinder or there is other severe damage. Display will indicate low battery voltage.
Check on water in the cylinder and further damage by cranking while lifting the valves with the decompression handle. When there is water in the cylinder, then deactivate the control system, disconnect the battery, remove the glow plug. Crank the engine to remove the water through the opening of the glow plug. Check oil on the presence of water and change oil. Find out how the water entered the cylinder (check the air vent). Take precautions to prevent it from happening again. When there is no mechanical malfunction the problem must be an electric malfunction.
Diesel engine fails to crank, the starter makes clicking noises, or the engine cranks very slowly
Starter battery switched "OFF".
Check position of the battery switch and switch "ON".
Page 24
TROUBLE SHOOTING
24 May 2006 / WHISPER 3,5 / EN
PROBLEM CAUSE SOLUTION
Starter battery voltage insufficient (battery too weak).
Check battery voltage. Recharge the battery. Inspect battery terminals and cables for a good electrical connection (inspect against corrosion, tattered wires, etc.) During the normal starting process, the battery voltage drops to 11V (with a fully charged battery). If the voltage does not drop during starting, the electrical connection is faulty. If the battery voltage drops lower than 11V, then the battery has been discharged too deep.
Starter broken
Repair the starter motor
To thick engine lubricating oil.
Change oil for a lower viscosity.
Out of fuel or faulty fuel, water in the fuel.
Fill up with fuel or replace with better quality.
Fuel inlet solenoid valve is not opening.
Check wire connections and circuitry to solenoid. (Refer to DC wiring diagram)
Fuel lift pump is not working.
Fuel filter is blocked.
Air in fuel lines.
Check fuel filter and fuel lift pump: clean or replace if necessary. Bleed air from fuel system (refer to maintenance section).
Low compression because of dirty valves.
Clean valves. Take off the injection bent and inspect the outlet port. When little rust in the port clean the valve by taking off the valve spring and rotate until rust is removed. When the outlet port is strongly affected by rust, the exhaust system is not properly installed (refer to paragraph 5.4.3). Contact Mastervolt service department for advice.
Wrong valve clearance.
Adjust valve clearance,
Starter is turning engine smoothly, but engine fails to start
Blocked injector.
Have the injector tested and cleaned if necessary.
Unsuitable contaminate d fuel
Lack of fuel.
Fill up with fuel or replace by better quality.
Choked fuel filter.
Check fuel filter and fuel lift pump: clean or replace if necessary.
Faulty fuel lift pump.
Check and repair
Choked air filter.
Lack of air.
Check the air intake
Choked exhaust system, exhaust chocked rubber exhaust hose kinked.
Check the exhaust hose
Air in the fuel pipes
Bleed air from fuel system (refer to maintenance section).
Blocked injector.
Have the injector tested and cleaned if necessary.
Wrong valve clearance.
Adjust valve clearance.
Engine runs irregularly.
Temporarily hunting (this will disappear when engine has run in).
Too much oil.
Drain oil to proper level.
Lack of fuel.
Check fuel supply system: fuel pump and filter.
Lack of intake air.
Check air intake.
Choked exhaust system, exhaust blocked, rubber exhaust hose kinked.
Check exhaust system.
Generator overloaded by over- energising.
Reduce the electrical load (switch off some consumers).
Generator over energised.
Check that the proper capacitor type is installed and that it is connected correctly.
Defective generator (windings, bearings or other)
Generator must be sent to manufacturer for repair of damaged bearing or winding.
Engine speed drops
Damaged engine
Repair by Mastervolt service
Page 25
TROUBLE SHOOTING
EN / WHISPER 3,5 / May 2006 25
PROBLEM CAUSE SOLUTION
Engine does not stop on command
• Loss of control
Faulty Digital Diesel Control unit. Stop the engine manually by the stop handle. Check wire connections to stop solenoid. Check solenoid valve function. Replace if necessary.
Engine exhaust smokes
Faint blue smoke - generally the result of light load
Increase load.
Heavy blue smoke - caused by lubricating oil: Overfull oil sump or worn cylinder bore, stuck broken or worn rings.
Check the oil level. Check the compression.
Black smoke –incomplete combustion caused by: Overload, choked air filter, inlet temperature too high, unsuitable fuel or water in fuel.
Check the fuel . Check for overload.
Engine starts, but stops after 10 up to 30 seconds
Protection system stops the engine; this can be caused by oil pressure failure, lack of cooling water (exhaust temperature alarm). Overload, loose wire or faulty alarm switch. Digital Diesel Control will help to indicate failure.
Refer to paragraph 2.5.5. and 3.2.2 for information on the alarm system. Bypassing the switches can help to confirm the failure.
Overload or short circuit.
Switch off the consumers and test for short circuit.
Lack of fuel.
Check fuel supply system: fuel lines, pump, filter, valves, tank level, etc.
Oil pressure low. (oil pressure switch tripped).
Check oil level. Check engine’s oil pressure and have it repaired by Mastervolt.
Excessive heat in cooling system (thermo-switch tripped).
Lack of cooling water (exhaust switch tripped).
Impeller broken.
Cooling water blocked.
Water strainer blocked.
Air or water in the fuel.
Blocked air or fuel filter.
Check cooling water system flow: water pump, inlet water filter, coolant flow.
Loss of compression by wear out or damage.
Repair by Mastervolt service.
Engine stops by itself
Overload or short circuit.
Switch off the consumers and test for short circuit.
Generator is being overloaded. Digital Diesel Control will indicate “overload”.
Check electrical load and switch off some consumers
Insufficient intake air.
Choked air filter.
Check intake air paths and filter, clean and replace if necessary.
Fuel injector faulty.
Replace injector.
Valve clearance incorrect.
Readjust valve clearance
Poor fuel quality.
Use better quality diesel.
Poor quality lubricating oil.
Use better quality oil.
Sooty, black exhaust.
Continuous running with very low load.
Increase load and have the engine run for a few hours
• Wrong measurement. Check if the load is measured correctly. Does the Amp meter show the correct value? When calculating the load by multiplying voltage and amps this should be done by using the exact values, taking into account the power factor of the consumers. When any doubt, measure the power directly with an appropriate instrument.
Overfull oil sump.
Bring the oil to the correct level
Choked fuel filter.
Replace the fuel filter.
Loss of power
Choked air filter.
Check air inlet openings; clean air filter.
Page 26
TROUBLE SHOOTING
26 May 2006 / WHISPER 3,5 / EN
PROBLEM CAUSE SOLUTION
Exhaust blocked.
Check the exhaust system.
Injector blocked.
Have the injector checked.
Loss of compression, sticking.
Have the compression measured.
damaged piston ring.
Clean or replace the rings.
Wear out of cylinder.
Have the compression measured and have the engine overhauled.
Overload.
Take away the overload.
Low oil level.
Fill up with oil.
Water inlet system blocked.
Check the cooling system thoroughly.
Broken impeller.
Water strainer choked
Heat exchanger choked.
Over-temperature
Engine stops very slowly
• Engine should stop within 20 seconds
Stop solenoid is faulty an engine is stopped by after pushing stopping button fuel shut off valve
5.2.3 Warnings
Generator must be shut off immediately if:
• Motor RPM suddenly rises or drops.
• Unusual noise comes from generating set.
• Exhaust gases suddenly colour dark.
• Engine failure warning light is on
5.2.4 Service address
If you cannot correct a problem with the aid of the mal­function table, contact your Mastervolt Service Centre or Mastervolt Amsterdam for an extended service list, tel: INT +31-20-3422100.
5.3 SPECIAL PROCEDURES ALTERNATOR
5.3.1 Residual voltage check / excitation procedure
When residual magnetism disappears there is no residual voltage. Residual magnetism can disappear after the generating set being out of service for a long period or suffered a short circuit. This can be solved by char ging the capacitor ("flashing") independently with a small 9 Volt battery. This can be done while the engine is stationary and the wiring is connected.
If the generating set battery is used for flashing one must take care. A short circuit can cause heavy sparking, fire and injuries
When flashing does not bring back voltage, the capacitor(s) should be renewed. When this does not help, the rotating rectifier diodes should be tested and a winding resistant test should be executed.
5.3.2 Testing rotary rectifier diodes
The diodes in the rotor can be checked with a multimeter. When both diodes are faulty the alternator will not generate any voltage. When only one diode is faulty the alternator will generate about half the normal voltage. The flexible lead connected to the diode should be disconnected at the terminal end, and the forward and reverse resistance checked. A healthy diode will indicate a very high resistance (infinity) in the reverse direction, and a low resistance in the forward direction. A faulty diode will give a full deflection reading in both directions with the test meter on the 10,000 ohms scale, or an infinity reading in both directions. The problem can also be in a faulty surge suppressor which is a metal-oxide varistor connected across the diodes, or the ESD capacitor. Replace the diodes, the suppressors and the capacitors.
Fig. 14.
Page 27
TROUBLE SHOOTING
EN / WHISPER 3,5 / May 2006 27
5.3.3 Winding resistant values
If after establishing and correcting any fault on the capacitor and diodes output is still low when separately excited, then the main rotor, stator and exciter stator winding resistance should be checked as the fault must be in one of these windings. The respective leads must be disconnected before taking the readings. Resistance values should be within 10% of the values given in the table below:
Resistance 50Hz
Resistance both main stator windings in series
1.2 Ohm
Resistance both rotor windings
2.1 Ohm
Resistance battery charger windi ng
0.15 Ohm
Resistance exciter stator winding
2.4 Ohm
5.3.4 Meggering
One can try to measure resistance between the housing and the windings with a multimeter which should read infinity. When readings are infinity but a fault is suspected one can do a high voltage resistance test (MEGGERING) This procedure should be carried out by an expert
5.4 SPECIAL PROCEDURES ENGINE
5.4.1 Setting the RPM
RPM is set by the manufacturer and should not need readjustment! However a very slight offset after running in could occur. RPM can be measured by a frequency meter. Before readjustment check any other explanation for the wrong speed. Engine speed is set at the factory at nominal 3000 (50 Hz) RPM. A RPM drop of 5% at full load is acceptable. Therefore a no load setting should be at ± 3150 RPM = 52.5 Hz. Under no circumstances should the
RPM be under full load below 2940 RPM = 49 Hz. When no cause can be found for a wrong speed, the s etting can be adjusted: It is very important to identify the correct setting assembly (refer to fig. 16).The screw is to be locked in position with the lock-nut.
5.4.2 Tightening torques
Valve clearance, refer to Maintenance, §4.2.3. Cylinder head screws M10x1,5: 51,9 to 56,8 Nm; 5,3 to 5,8 kgf-m. Rocker arm bracket mounting: M8 x 1,25: 23,5 to 27,4 Nm; 2,4 to 2,8 kgf-m.
5.4.3 Measuring exhaust backpressure
The exhaust system must be of adequate size -1 5/8”/ 40 mm no more-no less -and maximal length (refer to installation manual). This is true for all generators, but specially for the Whisper 3,5, because this small engine has a small gas flow that easily can be blocked by a wate r trap in the exhaust system. When any doubt; backpressure has to be measured. An easy way to measure for back-pressure is to use a water column. A water column can be made visible in a plastic tube alo ng a yardstick and fitting the end to a hose connection to fit in the adaptor on the injection bent after removing the exhaust temperature switch. The bent A hanging down should not be to short helping to damp the pulsating effect of the gas discharge that is characteristic for a one cylinder engine. The water column should be no more than 24 inches (60 cm.) of water (0,87 PSI - 0,06 bar)
1 Varistor (420V); 2 EMC capacitors (4,7nF - 630V); 3 Diodes (25A - 1200V). Fig15
Fig16: Setting assembly
Page 28
TROUBLE SHOOTING
28 May 2006 / WHISPER 3,5 / EN
5.4.4 Disassembling instructions
It could be necessary for repair or checks to disassemble the generating set. One can take off the white cover easily for regular maintenance and inspection. For further repair or inspection one can take off the upper green part as well. Following instructions will help:
1 When the generating set has to be taken out of its
enclosure we strongly advise not to do this in a narrow space on a boat, but to take out the complete set and take it to a workshop.
2 To take out the generator all connections have to be
taken off. The outgoing hose on the oil cooler is most difficult to get to, but can be reached from above by taking off the cover which is on the cylinder head of the engine. By taking out 4 screws from the aluminium bars the generating set will come loose from the capsule.
3 The easiest way to get the generator out of its capsule
is by lifting the set using the lifting eye and removing the capsule downwards.
4 The cooler elements are welded to the alternator
housing with silver and cannot be disassembled. How-ever one can take off the complete alternator housing.
5 Before the alternator can be taken off one has to take
out the fitting to the oil cooler to be able to take off the aluminium housing. All cables and wiring have to be loosened first.
6 The rotor can be taken off by removing the bolt which
goes through the shaft (normal clockwise threaded). The end of the shaft is specially threaded to push off the rotor from the conic stub shaft, which is on the flywheel, using a 6-mm rod of 165-mm length and a M10 bolt.
7 Reassembling the generating set one should take
care of alignment, cleaning the surfaces between engine and alternator and tighten the bolts crosswise and gradually.
8 Use Loctite 577 to seal the fittings, which should first
be cleaned and made free of oil and grease. Test the generating set first outside its capsule and check very carefully for leakages before putting it back in its enclosure.
Fig 17: Measuring exhaust backpressure
0
4
Page 29
SPARE PARTS LIST
EN / WHISPER 3,5 / May 2006 29
6 SPARE PARTS LIST
A parts manual in English is available as an option number: 50200180(* **). A work shop manual in English is available as an option number: 50200170(***).
We recommend the following spares for service and maintenance.
Kit A: parts for regular maintenance parts marked(*) article no 50201260
Kit B: parts for maintenance + spare parts: all parts marked (*)+(**) article no 50201261
Kit C: parts for "world travellers" all parts marked (*)+(**)+(***) article no 50201262
ARTICLE NO DESCRIPTION
50209030 Fuel filter (*) 50201031 Fuel lift pump (**) 50201051 Fuel valve solenoid (**) 50221609 Banjo eye fuel valve (**) 50201034 Copper washer connection bolt, M10 x 16 (**) 50201035 Copper washer, M12 x 18 (**) 50202048 Stop solenoid (***) 50201250 Raw water pump complete Mastervolt type K (***) (refer to fig. 17) 50209011 Impeller + gasket (3,4,5) (*) 50201012 Cover type K (**) (2) 50209018 Bolts cover (**) (1) 50201251 Pump repair kit A consisting of:
- Shaft (13)
- Bearings (2 pcs.) (10)
- O-ring (9)
- Seals (2 pcs.) (8)
- Clips (1 set) (11, 12) 50209010 Pump repair kit B (**)(same as repair kit A excluding the shaft) 50201220 Oil cooler complete with appendages (***) 50201225 Oil pipes and fittings (***) 50201222 Water hoses with clamps (***) 50201060 Capacitor xx micro-farad (**) xx = give value when ordering 50209132 Measuring coil (***) 50201290 Rotary diodes (2 pcs) (including varistors and capacitors (**) 50201085 Alternator bearing including O-ring (**) 50209100 Digital Diesel Control unit (black box) (***) 50209104 Local control panel on the engine (***) 50212154 Fuses 3 Amps (*) 50212170 Fuses 10 Amps (*) 50201066 Wiring loom complete (***) 50209102 Digital Diesel Remote Control panel (***) 50209133 Cable remote control 15 mtr, including connectors 50202034 Gasket valve cover (**) 50202030 Cylinder head gasket kit 50202036 Overhaul gasket kit + seal kit (***) 50202040 Glow plug (**) 50202050 Nozzle injector (**) 50202160 Fuel pump (high pressure) complete (***) 50209051 Silicone O-ring sound shield cover (**)
More extensive parts list on the internet: MASTERVOLT.COM (fast moving parts)
Page 30
SPARE PARTS LIST
30 May 2006 / WHISPER 3,5 / EN
Fig. 18 Waterpump type K
Page 31
MAINTENANCE LOG
EN / WHISPER 3,5 / May 2006 31
MAINTENANCE LOG
first service after 50 hours: hour counter: remarks
next service (every 150 hours) hour counter:
Page 32
Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands
Tel : + 31-20-3422100 / F ax : + 31-20-6971006
www.mastervolt.com / info@mastervolt.com
Loading...