Mastervolt whisper 12 ultra User Manual

Page 1
USERS MANUAL
WHISPER 12 ULTRA
- Three phase - 1500 RPM -
Marine diesel generating set 230/400V-50 Hz
MASTERVOLT Snijdersbergweg 93, 1105 AN Amsterdam The Netherlands Tel.: +31-20-3422100 Fax.: +31-20-6971006 www.mastervolt.com
V5. December 2008
Art.nr. 50200341
Page 2
TABLE OF CONTENTS
2 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
Copyright © 2008 Mastervolt. All rights reserved. Reproduction, transfer, distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited.
TABLE OF CONTENTS:
1 INTRODUCTION..............................................................................................................................................................4
1.1 General .............................................................................................................................................................. 4
1.2 Service and maintenance................................................................................................................................... 4
1.3 Guarantee .......................................................................................................................................................... 4
1.4 Liability ............................................................................................................................................................... 5
1.5 Identification ....................................................................................................................................................... 5
1.5.1 General.............................................................................................................................................. 5
1.5.2 Identification plate ............................................................................................................................. 6
2 INFORMATION................................................................................................................................................................ 7
2.1 Safety ................................................................................................................................................................. 7
2.1.1 General.............................................................................................................................................. 7
2.1.2 Electrical safety ................................................................................................................................. 7
2.1.3 Earth insulation failures ..................................................................................................................... 7
2.1.4 Installation ......................................................................................................................................... 7
2.1.5 Operation........................................................................................................................................... 8
2.1.6 Fire and explosion ............................................................................................................................. 8
2.1.7 Chemicals.......................................................................................................................................... 8
2.2 Transport, lifting and storage.............................................................................................................................. 9
2.3 The Whisper 12 ULTRA Three Phase ................................................................................................................ 9
2.3.1 Features ............................................................................................................................................ 9
2.3.2 Remote control .................................................................................................................................. 9
2.3.3 Documentation .................................................................................................................................. 9
2.3.4 Accessories included in the standard delivery...................................................................................9
2.4 Components ..................................................................................................................................................... 10
2.4.1 Main components to identify............................................................................................................ 10
2.4.2 Generator control panel................................................................................................................... 12
2.4.3 Remote control panel ...................................................................................................................... 12
2.5 Technical Information ....................................................................................................................................... 12
2.5.1 AC alternator ................................................................................................................................... 12
2.5.2 Engine ............................................................................................................................................. 13
2.5.3 Digital Diesel Control system........................................................................................................... 13
2.5.4 Battery charger................................................................................................................................ 13
2.5.5 Alarms and shut down..................................................................................................................... 13
2.5.6 Monitoring........................................................................................................................................ 13
2.5.7 Control............................................................................................................................................. 13
2.5.8 Remote control ................................................................................................................................ 13
2.5.9 Hour counter.................................................................................................................................... 13
2.5.10 Load indicator.................................................................................................................................. 13
2.5.11 Fuel specification............................................................................................................................. 14
2.5.12 Oil information ................................................................................................................................. 14
2.5.13 Cooling liquid................................................................................................................................... 14
2.5.14 Technical data ................................................................................................................................. 15
2.5.15 Wiring codes and colours ................................................................................................................ 16
2.5.16 Lay out control wiring....................................................................................................................... 17
2.5.17 Electrical diagrams AC connections (alternator models with 6 wires) ............................................. 18
Page 3
TABLE OF CONTENTS
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 3
2.5.18 Electrical diagrams AC connections (alternator models with 12 wires)............................................ 20
2.5.19 Diagram electronic governor ........................................................................................................... 22
3 OPERATION.................................................................................................................................................................. 23
3.1 General ............................................................................................................................................................ 23
3.2 Operating Instructions ...................................................................................................................................... 23
3.2.1 Summarised operating instructions (daily use)................................................................................ 23
3.2.2 Extended operating instructions ...................................................................................................... 23
4 MAINTENANCE............................................................................................................................................................. 26
4.1 Alternator.......................................................................................................................................................... 26
4.2 Engine .............................................................................................................................................................. 26
4.2.1 Preliminary instructions ................................................................................................................... 26
4.2.2 Bleeding fuel lines ........................................................................................................................... 26
4.2.3 Valve clearance............................................................................................................................... 26
4.2.4 Replacing fuel filter .......................................................................................................................... 26
4.2.5 Replacing oil filter ............................................................................................................................ 27
4.2.6 Readjustment V-belt ........................................................................................................................ 27
4.3 Regular maintenance ....................................................................................................................................... 28
4.3.1 Maintenance schedule..................................................................................................................... 29
4.3.2 Putting out of service ....................................................................................................................... 29
5 TROUBLE SHOOTING.................................................................................................................................................. 30
5.1 Alternator/ electrical faults ................................................................................................................................ 30
5.1.1 General............................................................................................................................................ 30
5.1.2 Trouble shooting table ..................................................................................................................... 30
5.2 Engine faults..................................................................................................................................................... 32
5.2.1 General............................................................................................................................................ 32
5.2.2 Trouble shooting table ..................................................................................................................... 32
5.2.3 Warnings ......................................................................................................................................... 35
5.2.4 Service address............................................................................................................................... 35
5.3 Special procedures alternator........................................................................................................................... 35
5.3.1 Automatic voltage regulator............................................................................................................. 35
5.3.2 Residual voltage check / excitation procedure (flashing)................................................................. 36
5.3.3 Testing rotary rectifier diodes .......................................................................................................... 36
5.3.4 Winding resistant values.................................................................................................................. 36
5.3.5 Meggering ....................................................................................................................................... 37
5.4 Special procedures engine ............................................................................................................................... 37
5.4.1 Setting the RPM .............................................................................................................................. 37
5.4.2 Adjusting valve clearance and retightening the cylinder head bolts. ............................................... 37
5.4.3 Measuring exhaust backpressure.................................................................................................... 38
5.4.4 Disassembling instructions .............................................................................................................. 38
6 SPARE PARTS LIST..................................................................................................................................................... 40
MAINTENANCE LOG ............................................................................................................................................................... 42
Page 4
INTRODUCTION
4 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
1 INTRODUCTION
1.1 GENERAL
The Whisper 12 ULTRA Three Phase Marine Diesel Generating set is manufactured and marketed by Mastervolt. It is important to read this manual before installing and operating the generating set. Both safety and durability rely very much on the correct identification, installation and a good understanding of ratings, features, design, maintenance and operation procedures. The information, specifications, illustrations and statements contained within this publication are given with our best intentions and are believed to be correct at the time of going to press.
All of the specifications, provisions and instructions contained in this manual apply solely to standard versions of the Mastervolt Whisper 12 ULTRA generating set. This manual is valid for the following models:
Part nr. Version Description
51107305 B Whisper 12 Ultra Three Phase
230V-400V 1500rpm
51107306 B Whisper 12 Ultra Three Phase
230V-400V 1500rpm-ungrounded
See 1.5 for identification of the generator set. For other models see other manuals available on our website: www.mastervolt.com
Our policy is one of continued development and we re­serve the right to amend any technical information without prior notice. Whilst every effort is made to ensure the accuracy of the particulars contained within this publication neither the manufacturer, distributor, or dealer in any circumstances shall be held liable for any inaccuracy or the consequences thereof.
WARNING
A warning symbol draws attention to special warnings, instructions or procedures which, if not strictly observed, may result in damage or destruction of equipment, severe personal injury or loss of life.
DANGER
This danger symbol refers to electric danger and draws attention to special warnings, instructions or procedures which, if not strictly observed, may result in electrical shock which will result in severe personal injury or loss of life.
1.2 SERVICE AND MAINTENANCE
Regular service and maintenance should be carried out according to the directions in this manual. For service and maintenance one can appeal to the manufacturer or the dealers.
1.3 GUARANTEE
Mastervolt guarantees that this generating set has been built according to good workmanship, according to the specifications in this manual and according to European Community safety regulations. During production and prior to delivery, all of our generating sets are tested and inspected.
The well functioning of this generating set is subject to guarantee. The period and conditions of this guarantee are laid down in the general conditions of delivery as registered with the Chamber of Commerce and Industries in Amsterdam number 33279951 and are available on request. The guarantee period is two years, limited to 1000 running hours. Some aspects of our guarantee scheme are given here in more detail:
Guarantee does not cover failures that are caused by misuse, neglect or a faulty installation.
Example 1. Faulty installation: Seawater entering the engine is the most common cause of damage to combustion engines in boats (both to propulsion and generator engines). The entry of water must be avoided under all conditions. Be aware that the conditions in blue water sailing can be extreme. Refer to the installation manual for instructions but remember these are for guidance only as many factors influence the installation of a generator. The ultimate responsibility will always be with the owner to ensure a safe and compliant installation. If in doubt ask!
DAMAGE CAUSED BY THE INGRESS OF WATER IS NEVER COVERED BY GUARANTEE
Example 2: Misuse: Long term running with no load or too little load can cause the exhaust to get choked with soot or carbon. Cleaning the exhaust is not covered by guarantee.
Page 5
INTRODUCTION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 5
Example 3: Neglect Sometimes the seal of the raw water pump starts leaking. Mostly this begins with a little drip and slowly gets worse. Regular visual inspection of the generator is necessary to prevent damage to occur from a leaking water pump. When one find serious damage after weeks of neglect guarantee claims will not be honoured.
Example 4: Neglect Whisper generators have an option for an auto start/stop mode or interval mode. Mastervolt cannot be held responsible for damage caused by the unattended running generator.
Guarantee means that faulty parts are repaired or replaced free of charge. If necessary the whole generator unit will be exchanged. Labour necessary to complete repairs on board a vessel executed by an authorized service engineer is covered, but is limited to a reasonable number of hours and reasonable rates in relation to the actual repair work that has to be done. Travel expenses and travel hours are not covered. Also not covered is the labour required to take a generator out of a boat or for reinstallation. There is no cover for labour needed to get access to the generator, for example to remove equipment or bulkheads etc.
Goods to be delivered under guarantee will be invoiced. Only after the faulty goods are returned will the invoice be credited. Payment in advance may be required or guaranteed by credit card. If after the faulty goods are returned, it is indicated that the failure was not covered by guarantee a credit will not be issued. For example if a Printed Circuit Board is returned with clear damage caused by seawater, guarantee will be refused. Freight costs to deliver spares by normal mail or carriers is covered under guarantee. Special services like express mail, overnight delivery etc. are not covered. Taxes and duties are not covered. For shipments to remote off shore areas any additional costs incurred over normal carriage will be invoiced to the customer. The cost for returning faulty goods is not covered under guarantee.
Additional agreements could be part of the contract of delivery.
If any problem arises which could be subject of guarantee, procedures should be followed as described in the guarantee conditions, unauthorised repairs could lead to further damage and violate the guarantee conditions.
Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in this user’s manual and the supplementary installation manual, then damage may occur and the generating set may not fulfil its specifications. In all these cases the guarantee may become invalid. Use original spareparts only!
1.4 LIABILITY
Mastervolt does not accept responsibility for damage, injuries or casualties which are the result of operation of the generating set in specific conditions which brings dangers which could not be foreseen, or could be avoided by additional measures. Mastervolt does not accept liability for damage due to use of the generator, possible errors in the manuals and the results thereof.
Automatic start/stop Mastervolt cannot be held responsible for damage caused by the unattended running generator using the auto-start/stop mode or interval mode.
1.5 IDENTIFICATION
1.5.1 General
Before using this generating set it is very important to identify the set correctly. To communicate for service or ordering parts it is also essential to correctly identify the generating set. Also for the daily operation of the genera­ting set it is necessary that the operator knows the correct specifications.
Page 6
INTRODUCTION
6 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
1.5.2 Identification plate
All required identification data are on the identification plate. For location of the identification plate see figure 1
: 1060 x 575 x 635mm
: 2006YEAR OF MANUFACTURING
The Netherland s Tel. + 31 (0)20 3422100
Snijdersbergweg 93, 1105 AN Amsterdam
Manufacturer : Mastervolt b.v.
WEIGHT : 380 kg
DIMENSIONS
PHASE
: Three Phase
: 3 x 19ACURRENT
FREQUENCY : 50Hz
: 230 / 240VVOLTA GE
MAX.POWER : 12kW (kVA) cos = 1
: SERIAL NO
ARTICLE NO : 51107305
: Whisper 12 ULTRAMODEL
Fig. 1: Location of the identification plate.
1 The identity of the generating set is given by the
SERIAL NUMBER.
Example:
When this number is available the manufacturer can trace the specifications of the generating set. On the identification plate are also some basic features of the set:
2 POWER
The identification plate gives the nominal maximum continues load in kVA (= kW) calculated with power factor one. When calculating a load one should always take into account the power factor or cos phi of this load. The power should never exceed the
nominal power as shown on the identification plate. Power is rated at an ambient temperature of 40°C and a seawater temperature of 25ºC. For higher temperatures the generating set has to be derated.
3 VOLTAGE shows the nominal voltage.
This voltage should be within the specified tolerance at the nominal frequency and a balanced load. The Whisper 12 ULTRA Three Phase can be connected as 3-phase 230/400Volt (STAR) or as 3-phase 230Volt (DELTA). The alternator is not designed and rated for single phase applications. For single phase applications Mastervolt offers another model that has dedicated windings. The nameplate indicates the connection as made in the factory; BE AWARE THAT THE CONNECTIONS COULD BE RECONNECTED BY FORMER USERS
4 FREQUENCY is shown in Hz and is determined by
the speed of the engine (RPM). 50 Hz correlates with 1500 rpm. Mastervolt offers generators for 1800 rpm 60 Hz applications as well. When necessary a Whisper 12 Tri Phase model can be reconnected and set for 60 Hz applications. A 60 Hz special manual is available upon request.
5 CURRENT shows the maximum current that is
acceptable at the specified frequency, voltage and power factor. The indicated current is the current between two phases that can be taken of three times.
6 WEIGHT shows the net dry weight (approximately) in
kg. This is without fuel, oil, packing and external installation equipment
7 CE-marking: the “CE” symbol shows that the
generating set is build according to European Community safety regulations. This includes the regulations regarding the safety of pleasure craft, safety of machinery, electric safety and electric magnetic compatibility (EMC) and other relevant directives.
Safety also relies on the installation, application and circumstances. See also the remarks in this manual under SAFETY Before changing a factory setting you are advised to consult the manufacturer. When the generating set you have to identify is not new you have to take into account the possibility that former users may have changed the settings. Check the settings (voltage, frequency, rpm) when there is any doubt.
SERIAL NO: : W822B001
version “B”
Page 7
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 7
2 INFORMATION
2.1 SAFETY
2.1.1 General
When correctly installed and used in normal circumstances this generating set fulfils EC safety regulations. This generating set could be part of an installation or could be used in a way that additional regulations of the EC or other authorities have to be taken into account.
DANGER Warning signs draw attention to special warnings, instructions or procedures which, if not strictly observed, may result in electrical shock which will result in severe personal injury or loss of life.
Circumstances could make it also necessary to take additional measures. Be aware of wet conditions and hazardous environments caused by explosive gases etc
2.1.2 Electrical safety
The voltage of 230 / 400 Volt generated by this generating set is dangerous and if instructions and procedures are not strictly observed may result in electrical shock which will result in severe personal injury or loss of life.
Check all wiring at least once a year. Defects, such as loose connections, burned cables etc. must be repaired immediately.
Do not work on the electrical system if it is still connected to a current source. Only allow changes in your electrical system to be carried out by qualified electricians.
Connection and protection must be done in accordance with local standards.
Using the auto-start/stop (interval) mode the generator can start unexpectedly. When working on the electrical system, the 3 Amp fuse must be removed from the control panel and the battery plus cable must be removed from the battery.
Warning signs indicate parts which could be live.
2.1.3 Earth insulation failures
According to local regulations and depending on the application it could be necessary to take measures for protection against earth insulation failures. In the standard delivery “neutral” and “ground” are not connected. To make a connection between “neutral” and “ground” could be necessary as part of a specific insulation failure protection system. Small pleasure craft in Europe is submitted to The Recreational Craft Directive 94/25/EC. The guidelines of this directive refer to (ISO 13297). When the installation complies with this standard the “neutral” and “ground” should be connected on the generating set.
Be aware that insulation protection systems can be different for different applications and even within the ship there could be different standards for different spaces. We did refer to the Recreational Craft Directive that applies to pleasure craft up to 24 m of length. Sometimes one has to comply with other standards such as the rules of certification societies like Lloyds Register of Shipping or Veritas, regulations for the protection of personal, building legislation, etc. It is of the greatest importance to have expert advice on this issue.
In all situations the transfer switches between shore, inverter and generator should switch both neutral (N) and all phase lines (L1, L2 and L3).
2.1.4 Installation
Whisper generating sets are not self contained and have to be properly installed in enclosed areas such as a machine room.
Installation includes measures to be taken to outlet exhaust fumes which contain carbon
monoxide and are extremely dangerous. Carbon monoxide (CO) is an invisible odourless gas. Inhalation produces headache, nausea or death. Installation includes measures for proper ventilation, safe electric connections, safe installation of the starting battery, proper fitting of the cooling system and fuel pipes etc. Refer to the installation manual.
Page 8
INFORMATION
8 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.1.5 Operation
External moving parts like fans and V-belts are covered by the soundshield and therefore the Whisper 12 ULTRA is very safe when the soundshield is closed.
Nevertheless take note of the signs on the generating set which show symbols in a triangle indicating danger.
When service has to be carried out while the engine is running, be aware of moving parts like V-belts.
The generating set should be operated by authorised personnel only.
Be aware of hot parts and especially parts of the exhaust system and the cooling system.
If the generating set is unsafe, fit danger notices and disconnect the battery positive (+) lead so that it cannot be started until the condition is corrected.
Do not attempt to operate the generating set with a known unsafe condition. Disconnect the battery positive (+) lead prior to attempting any repairs or cleaning inside the enclosure.
Always consult the manual before carrying out maintenance.
Do not change the settings without consulting the manufacturer. Keep a record of setting changes in this manual.
2.1.6 Fire and explosion
Fuels can be flammable. Proper handling limits the risk of fire and explosion.
Avoid refilling the fuel tank while the engine is running. When oil or fuel is leaking do not use the generating set.
Do not run the engine close to explosives or gasses.
Hydrogen gas generated by charging batteries is explosive. Ensure for proper ventilation. Do not smoke or allow sparks, flames, or other sources of ignition around batteries.
Keep a fire extinguisher on hand.
IN CASE OF FIRE, DO NOT OP EN SOU NDSHIELD. TO AVOID SERIOUS INJURY OR D EA TH FR OM FIRE
IMMEDI ATELY DISCHARGE ENTI RE CONTENTS OF GASEOUS
SHUT DOWN ENG INES, GENERATO R SETS AND BLO WERS.
PORTAB LE FIRE E XTINGUISHER THRO UGH THIS PORT.
THROUG H
HERE
FIRE EXTINGUISHER PO R T :
BREAK
Fig. 2: Fire extinguisher port.
In case of fire do not open the soundshield. To avoid serious injury or death from fire, shut down engines, generator sets and blowers. Break through the label which is indicated by BREAK THROUGH HERE and then immediately discharge entire contents of gaseous portable fire extinguisher through the fire extinguisher port. On the generating set this fire extinguisher port is indicated by the label as shown in figure 2.
Poor electrical connections or using wiring which is not suited for the rated currents can cause overheating and possibly fire.
2.1.7 Chemicals
Fuels, oils, coolants, and battery electrolyte can be hazardous to personnel if not treated properly. Do not swallow or have skin contact with these liquids. Do not wear clothing that has been contaminated by fuel or lubricating oil.
Gaskets may be manufactured from asbestos. Particles of this material should not be inhaled as this may result in fatal diseases.
On no account allow any unprotected skin to come into contact with the injector spray as the fuel may enter the blood stream with fatal results.
Engines may be fitted with seals or O-rings manufactured from "viton" or similar material. When exposed to abnormal high temperatures in excess of 400°C an extremely corrosive acid is produced which cannot be removed from the
Page 9
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 9
skin. If signs of decomposition are evident, or if in doubt, always wear disposable heavy duty gloves.
2.2 TRANSPORT, LIFTING AND STORAGE
When lifting the generating set avoid any risk of personal injuries, do not stand under the generating set.
Use soft slings to avoid damage
On the engine are two hoist eyes which can be
used to take the generator out of the capsule. They can also be used to lift the complete generating set including the capsule.
After transporting the generating set check for damage before installation.
Long term storage can have detrimental effects on engine and alternator. The engine should be put through an engine preservation procedure. (Refer to the maintenance chapter)
The alternator windings tend to condense. To minimise condensation, store the generating set in a dry and warm storage area.
After removing the generating set from long term storage perform an insulation check. (Refer to the alternator maintenance paragraph for procedures)
While the battery is stored it should be recharged every 12 weeks.
2.3 THE WHISPER 12 ULTRA THREE PHASE
2.3.1 Features
This generating set includes a diesel engine which is connected by close coupling to an alternator in a sound attenuated capsule. The set is mounted on a steel base frame and mounted securely on anti vibration mounting pads to the capsule base. All cables and hoses are guided through the capsule’s sides. The set is not self contained and is only operable after proper installation using additional accessories and installation materials. Installation accessories are listed in the installation manual and are available through the supplier of the generating set. The full automatic Digital Control is based on microprocessor technology. Several automatic start/stop functions can be programmed and monitored (refer to Digital Diesel Control users manual).
2.3.2 Remote control
The full automatic remote control panel including 15 mtr cable comes as standard with the Whisper generating set.
2.3.3 Documentation
Included in the delivery is:
This users manual (number: 50200341)
An installation manual (number: 50200381)
An users manual for DCC (number: 50200261).
A quick reference guide for DDC (number
50200275)
Not included in the standard delivery but available as options are:
Parts manual; number: 50200185
Workshop manual; number: 50200172
However in this manual there is a list of important parts for maintenance and spare parts as well as a chapter on maintenance and problem solving.
2.3.4 Accessories included in the standard delivery
Expansion tank, hose and fittings
Special hose connector for measuring exhaust
back pressure (refer to paragraph 5.4.3)
Page 10
INFORMATION
10 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.4 COMPONENTS
2.4.1 Main components to identify
Fig. 3 Frontleft view main components Whisper 12 Ultra – Three phase.
Fig. 4: Rear view main components Whisper 12 Ultra – Three phase.
01
04
03
02
05
06
07
08
09
10
12
13
14 15
16
01 Identification plate 02 Digital Diesel Control
(DDC) 03 Control panel 04 Fuses 05 Fuel injector (4x) 06 Glowplug (4x) 07 Expansion tank Ø8mm 08 Bypass cooling water out
Ø20mm 09 Bypass cooling water in
Ø20mm 10 Exhaust hose Ø51mm 12 Remote control 13 AC power output 14 Fuel injection pump 15 Fuel solenoid 16 Engine oil filter
17 Exhaust manifold
(watercooled) 18 Alternator (12VDC) 19 Engine coolant pump 20 V-belt 21 Raw water pump 22 Cooling water injection
bend 23 Rubber engine mounting 24 Starter motor solenoid 25 Starter motor 26 Heat exchanger
Page 11
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 11
Fig. 5: Front right view main components Whisper 12 Ultra – Three phase
Fig. 6: Top View main components Whisper12 Ultra – Three phase
28
38
37
41
27
29
39
40
30
36
35
34
33
32
31
42 Hoist eye rear 43 Air cleaner element 44 Failsafe
45
Temperature switch
exhaust 46 Filler cap engine coolant 47 Rocker cover 48 Filler cap engine oil
49
Temperature switch
coolant 50 Thermostat housing
27 Engine speed adjusting
screw
28 Injection pump air
bleeding screw 29 Engine serial number 30 Oil sump handpump 31 Fuel filter 32 Coolant drain plug 33 Engine oil pressure switch 34 Engine oil dipstick 35 Hoist eye front 36 Fuel lift pump 37 Battery negative (–)
25mm² 38 Battery positive (+)
25mm² 39 Raw water inlet Ø20mm 40 Fuel in Ø8mm 41 Fuel out Ø8mm
Page 12
INFORMATION
12 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.4.2 Generator control panel
Start / Stop
Remove fuse
Internal fuel pump Fuse 3A
befo re main tenan c e
Digital Di esel Control Fuse 3A
A ux ilia r y Fuse 10A
Ex tern al Fuel Pump Fuse 3A
O b serve instruc tion s in th e manu al
Rep lac e fuses with sam e type a nd ratin g
Whispe r Digita l Diesel Oper a t ion Unit
Fig: 7 Control panel.
Fig. 8 Digital Diesel Control unit
2.4.3 Remote control panel
04
03
02
01
05
07
06
01 Generator load indicator 02 Failure LED 03 Start button 04 Stop button 05 Display 06 Select button 07 Set button
Fig. 9: Digital Diesel remote control panel
2.5 TECHNICAL INFORMATION
2.5.1 AC alternator
The tri phase synchronous alternator is directly coupled, one bearing, brushless, rotating field design, 6 or 12 wire (depending on the alternator model), four pole, (1500 RPM) and regulated by an Automatic Voltage Regulator (AVR). The exciter stator has a residual magnetism, which guarantees self-exciting of the generator on start-up (that thereby generates a residual voltage of about 10% nominal voltage).
Fig. 10 Automatic Voltage Regulator (AVR).
The AVR, powered by an auxiliary circuit on the main stator, acts on the exciter stator indirectly controlling the field generated by the main rotor by means of the sequence exciter rotor - diode bridge - main rotor. The voltage regulator controls and keeps constant the average voltage of one phase. The voltage setting on the AVR can be adjusted with the help of a trimmer “V” (See par.5.3.1) A frequency control progressively deactivates the machine when the drive motor speed drops below a pre-set, adjustable threshold preventing over-excitement at low operating speeds and abating the load engage effects on the engine. The AVR works only within limits of the set frequency 50 Hz. When operating below the lower limit of 46 Hz ± 1 Hz the AVR will stop regulating to avoid overloading the exciter coil. When applying the generator set at 60 Hz the AVR is re-adjustable as well. To operate at 60 Hz the engine RPM and Digital Diesel Control settings must also be changed. For the USA market a dedicated manual is available for 60 Hz applications. Please refer to the Mastervolt service centre for specific instructions to convert the generating set to 60 Hz. It is not possible to take off the full power from the Whisper 12 ULTRA Three Phase by reconnecting the alternator to
Page 13
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 13
single phase (or dual voltage 60 Hz). Mastervolt offers dedicated single phase and dual voltage 60 Hz generators
Fig. 11 AVR Setting-components and terminals
The power comes from 6 or 12 wires (depending on the alternator model) that can be connected in Star or Delta arrangements to take off different voltages. For tri phase 230/400V, the alternator should be connected in a Star arrangement. For three phase 230V, the wires should be connected in a Delta arrangement. Further technical data on the connections of the alternator can be found in drawings and diagrams in this manual. See section 2.5.17 (6 wires) or section 2.5.18 (12 wires).
2.5.2 Engine
The Whisper 12 ULTRA generating set is based on the Mitsubishi S4S2 4 cylinder 4 stroke diesel engine. The engine is indirectly injected. The engine is water cooled and the cooling liquid is cooled by a heat exchanger and raw water. The heat exchanger and all other parts which are in direct contact with the raw (sea) water are made of seawater resistant material like naval brass and gunmetal. The engine has been specially adapted for the Mastervolt application and is very different from the standard engine supplied for industrial applications!
2.5.3 Digital Diesel Control system
The standard electrical engine control system is 12 Volt negative earth, non earth return (ungrounded) is available as optional. Check your identification data to determine which system is applied. The system is designed according to the "energise to run" system. The Digital Diesel Control is a very advanced microprocessor based full automatic system. Besides automatic start the system offers many monitoring options. Refer to the separate Digital Diesel Control users manual. The microprocessor unit is located in the black box on top of the alternator (see figures 3 and 8)
2.5.4 Battery charger
On the engine is an alternator generating 50 Amp 12V. This current is rectified to charge the battery. The voltage is regulated at ±14.4V.
2.5.5 Alarms and shut down
In the event of malfunctioning this will be indicated by the failure LED, details will be shown on the display and the engine will be shut down. There are three functions guarded: oil pressure, oil temperature and exhaust temperature. Exhaust temperature too high indicates the cooling water to be blocked. All alarm switches are closed when no malfunction occur. A contact is cut in the event of an alarm. This means that the generating set will not work when the alarm switches are broken or there is a loose wire. The system therefore is intrinsically safe. The panel will display details about the alarm.
2.5.6 Monitoring
Refer to the operating of the Digital Diesel Control
2.5.7 Control
The generating set can be operated by push buttons on the panel on the alternator or by the remote control. By pushing the START button the control system is activated and will start the engine automatically. Pushing the STOP button will stop the engine and the electrical system will be deactivated.
2.5.8 Remote control
All wiring connections from the remote control to the board are made by plug in connectors. An intermediate communication cable is in the standard supply. If necessary an optional longer 8 wire communication cable can be connected if the standard length does not suit the required distance. Numerous remote control units can be put in parallel by using the connectors on the back of the units. (Refer to installation instructions)
2.5.9 Hour counter
The remote control offers several timer functions that help to schedule maintenance.
2.5.10 Load indicator
On the remote control the load will be indicated on the display and by the LED-bar. The load is measured by current transformers on the alternator. All phases are monitored and overload of all phases or just one or two phases will provoke an alarm or even shut down when the alarm is ignored.
Page 14
INFORMATION
14 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.5.11 Fuel specification
The engine must only be used with diesel fuel oil which conforms to the standards for use in modern diesel engines. Fuel free from water and contaminants is of the utmost importance.
2.5.12 Oil information
1 Specification:
The oil must be suitable for oil changes as specified in the maintenance chapter. The Mitsubishi engine must be run on heavy duty lubricating oil meeting the requirements of API class CC, CD, CF or CF_4.
It is very important to use the correct oil specification. Very often local oil suppliers recommend a higher class, because they assume that a higher class is allowed. This is not the case. One should not follow these recommendations. Using the wrong specification will cause high oil consumption.
2 Oil viscosity:
We recommend a multigrade oil 15W40.
3 Oil capacity:
Excluding the oil filter the content of the crankcase is
5.2 l. Including the oil filter it is 5.7 l. Note that the engine may contain some residual oil due to testing at the factory.
While filling, check the lubricating oil level by means of the engine oil dipstick. Do not overfill with oil as this may have a detrimental effect on engine performance.
4 Oil pressure
Minimum at idle 98kPa (1 kgf/cm² - 14psi) (1 bar).
Normal at 1500 rpm ±350kPa (3.5 kgf/cm² - 50
psi) (3.5 bar).
2.5.13 Cooling liquid
The engine is cooled by cooling liquid. The capacity of this system of the Whisper 12 ULTRA is 7.6 litres.
Always use coolant which is compatible with aluminum components of the cooling system. Do not mix coolants with different kinds of chemical compound, as this may cause congelation of the coolant. In case of doubt refresh the content of the entire cooling system.
We recommend not using water but cooling liquid that is marketed for the use in combustion engines. Cooling liquid protects the engine against frost to minus 25° C. Also it protects the engine block against corrosion. One can fill the engine via the filling cap on the exhaust manifold. Fill up till the level is just below the filling cap. When the engine is on temperature the liquid will expand and the redundant liquid will be pressed into the expansion tank. This tank has to be filled up till the mark. When cooling liquid is not available clean fresh water could be used with an additive of anti freeze. When using water with anti freeze the right mixture has to be calculated according to the information of the supplier of the anti freeze. When the cooling is based on keel cooling or radiator cooling the capacity of these coolers and piping has to be taken into account calculating the right mixture. The cooling liquid in the engine is pressurised and has a boiling point above 100° C. The temperature switch in the thermostat housing switches at 110° C. When keel cooling or radiator cooling is applied the cooling system is not pressurised. There should be a special cap on the manifold without valves leaving the connection to the expansion tank open. Refer to the manual on keel cooling and radiator cooling.
Page 15
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 15
2.5.14 Technical data
GENERAL
Model WHISPER 12 ULTRA
RPM 1500
Alternator 3 phase synchronous (air cooled)
Engine Mitsubishi diesel, model S4L2 (Japan)
Number of cylinders 4
Displacement 1758 cm3
Bore X stroke 78x92 mm
Combustion air consumption 1.8 m³/min.
Continuous power engine 12 kW
Cooling system indirect cooling by raw water, 18-22 l/min.
Cooling water pump PTO driven Mastervolt self priming impeller pump, type M12
Fuel lift pump engine electric pump (12 V DC), additional pump available upon request
Starting battery (optional) 85 Ah 12V
Fuel consumption 2-5.5 litre/hour, load dependent
Control Digital Diesel Control including automatic start/stop
ELECTRICAL SPECIFICATIONS
Output voltage 230/400V 50 Hz alternating current (AC) three phase,
re-connectable to three phase 230V
Output rating: 12 kVA = 12kW at power factor cos phi = 1
Voltage tolerance ± 2% (balanced load)
Frequency tolerance ± 1% (electronic governor)
Alternator Air cooled, brushless, four pole, 6 or 12 wire, synchronous
Voltage regulation: AVR
MECHANICAL SPECIFICATIONS
Supply includes Sound shield with steel base, mounted on rubber anti vibration mounts. (Generator
set without sound shield is optional)
Dimensions hxwxd 106 x 57.5 x 63.6 cm
Colour Metallic silver / grey
Weight 380 kg including sound shield
Max. installation angle 25 degrees
Standard supplies Digital remote panel (+15 m cable), fuel filter, fuel lift pump, user and installation
manuals
Optional: Installation kits, mobile (vehicle) version, non earth return (ungrounded), spare
part kits, PTO to drive a hydraulic pump
Page 16
INFORMATION
16 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.5.15 Wiring codes and colours
number colour cross section
battery > starter motor red 25 mm2
starter motor > DDC 1 red 6 mm2
starter motor > LCP 13 red 2,5 mm2
battery > ground black 25 mm2
ground > LCP ground (GND) 2 black 4 mm2
DDC > glow plug 3 brown 4 mm2
DDC > starter solenoid 4 yellow 2,5 mm2
LCP > fuel lift pump + 5 brown 1,5 mm2
LCP > fuel lift pump - 15 black 1,5 mm2
DDC > LCP 5 grey 1,5 mm2
DDC > oil pressure switch 6 purple 1 mm2
LCP > oil pressure switch 6 purple/black 1 mm2
DDC > water temperature switch 7 blue 1 mm2
LCP > water temperature switch 7 blue/black 1 mm2
DDC > exhaust temperature switch 8 blue/green 1 mm2
LCP > exhaust temperature switch 8 blue/pink 1 mm2
DDC > fuel solenoid (hold) 9 green 1,5 mm2
DDC > fuel solenoid (pull) 20 pink 2,5 mm2
DDC > fuel solenoid (com.) 17 black 2,5 mm2
B+ terminal alternator > starter motor 21 red 6 mm2
DDC >R terminal alternator 18 white 1,5 mm2
DDC > L terminal alternator 19 orange 1,5 mm2
DDC > current measuring transformer AC1 66 black 1 mm2
DDC > current measuring transformer AC1 66 red 1 mm2
DDC > current measuring transformer AC2 77 black 1 mm2
DDC > current measuring transformer AC2 77 red 1 mm2
DDC > current measuring transformer AC3 88 black 1 mm2
DDC > current measuring transformer AC3 88 red 1 mm2
DDC > LCP 12 black 1,5 mm2
DDC > LCP 14 red 1,5 mm2
DDC > LCP 16 red/green 1,5 mm2
DDC > generator AC output AC1 33 brown 1 mm2
DDC > generator AC output AC1 33 blue 1 mm2
DDC > generator AC output AC2 44 brown 1 mm2
DDC > generator AC output AC2 44 blue 1 mm2
DDC > generator AC output AC3 55 brown 1 mm2
DDC > generator AC output AC3 55 blue 1 mm2
DDC=Digital Diesel Control Unit LCP=Local Control Panel
Page 17
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 17
2.5.16 Lay out control wiring
Fig 12: Electrical Diagram control wiring Whisper 12Ultra – three phase
Page 18
INFORMATION
18 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.5.17 Electrical diagrams AC connections (alternator models with 6 wires)
Only valid for alternator models with 6 wires
Fig 13a: Electrical Diagram 230 / 400 V AC / 50 Hz three phase (Star configuration)
Page 19
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 19
Only valid for alternator models with 6 wires
Fig 13b: Electrical Diagram 230 V AC / 50 Hz three phase (Delta configuration)
Page 20
INFORMATION
20 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.5.18 Electrical diagrams AC connections (alternator models with 12 wires)
Only valid for alternator models with 12 wires
Fig 14a: Electrical Diagram 230 / 400 V AC / 50 Hz three phase (Star configuration)
Page 21
INFORMATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 21
Only valid for alternator models with 12 wires
Fig 14b: Optional configuration modes of the AC wiring for alternator models with 12 wires
Page 22
INFORMATION
22 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2.5.19 Diagram electronic governor
In addition to the mechanical governor, the Whisper 12 Ultra Three Phase is standard equipped with an electronic governor. A governor keeps the speed (RPM=Rotations Per Minute) of the engine at a fixed value. The RPM of the engine correlates with the frequency of the electrical output (1500 RPM =50 Hz) of the alternator. Under full load the RPM of the Whisper models that has only a mechanical governor can drop 75 RPM (=2.5 Hz) at full load and will go further down or collapse when further loaded. However the engines with the electronic governor will keep the RPM and frequency at the set value. As the voltage is related to the frequency, the voltage will be more stable as well. The RPM represents power and the alternator performs better as well on a higher speed. Whisper models with an electronic governor will bring more power. So the electronic governor offers three advantages: a more stable frequency and voltage and more power.
The electronic governor system contains two parts: 1 The actuator controls the engine speed. This actuator
replaces the standard hold solenoid that is on all other
mechanical controlled Whisper engines. The actuator controls the RPM directly on the fuel rack inside the fuel pump without levers and other mechanical transmissions.
2 A microprocessor keeps the speed at the set value by
controlling the actuator. The microprocessor is programmed at the Mastervolt factory and many parameters are set to perform well. It should not be necessary to make adjustments. When adjustments are necessary this can only be done with the help of an interface to a computer and special software to get access to the microprocessor.
The Mastervolt electronic governor does not need a pickup device in the flywheel housing that counts the passing tooth of the flywheel and determines the exact RPM of the engine, because the processor uses the 50 Hz of the AC output voltage as a reference.
(When this manual was not supplied with the generator and there is a pick up on your generator than you have another model than referred to in this manual. Refer to our website for the correct manual.)
Fig 15: Diagram electronic governer
Page 23
OPERATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 23
3 OPERATION
3.1 GENERAL
The generating set is operational after full installation and filling up with: fuel, engine lubricating oil and cooling liquid, connecting the battery to earth and connecting the digital remote control panel.
Fig. 16:
3.2 OPERATING INSTRUCTIONS
3.2.1 Summarised operating instructions (daily use)
Routine "pre-start" checks:
1 Check oil level (refer to fig. 16). 2 Water inlet (all valves open). 3 Power source selector switch (off/shore
power/generator power). Switch to power source switch "OFF", or switch off all consumers in the usual
way. 4 Switch on battery switch (when installed). 5 Fuel valve: open.
Starting:
Push the start button to initiate the full automatic
starting procedure. You can monitor the procedure on
the display.
In operation checks:
1 Check for abnormal noise or vibration 2 Check the voltage 3 Check sea water flow at exhaust outlet 4 Power source selector switch (off/shore
power/generator power). Switch to power source generator.
5 Before loading the generating set up to maximum,
have it run warm. Continuous load should be restricted to 70 % of maximum load.
Stopping generator:
1 Switch off all electrical devices (consumers). If the
generating set has been running under full load for a longer period, do not shut it down abruptly. Reduce the electrical load to about 30% of the rated load and
let it run for approx. 5 minutes. 2 Press the STOP button. 3 Close the inlet sea water cock. 4 Switch to an other AC power source, if available.
3.2.2 Extended operating instructions
Check when starting the first time or after a longer period of rest:
1 If there is any damage caused by transport or
installation. 2 Check if the installation conforms to the installation
instructions. 3 Ensure the generating set is free to turn without
obstruction. 4 Check all hoses and hose connections for leaks. 5 Check all cables and cable end terminal connections. 6 Check the engine and generator mounting bolts.
Routine "pre-start" checks:
1 Check engine oil level.
The generator switches off in the event of insufficient
oil-pressure. Even when the oil level is too low the oil
pressure can be high enough. Do not run the
generator with the oil below the lowest mark in the,
because a smaller volume of oil will become
contaminated considerably quicker than a larger
volume. Therefore we recommend daily oil-checks.
Check oil level prior to starting the engine or at least 5
minutes after the engine has stopped.
1 2
1 Maximum oil level 2 Minimum oil level
Page 24
OPERATION
24 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
2 Check sea water cocks. Do not forget the valve of the
water outlet in case of a water/exhaust gas separator. 3 Check the water strainer. 4 Check for leaks. 5 Regularly check the siphon vent in the cooling water
supply. 6 Switch main Power Source Selector switch to "OFF"
or switch off all devices. 7 Switch on the battery switch.
Starting the generator:
By pushing the start button briefly the electric system
is activated, the fuel lift pump starts pumping and the
starting procedure will begin (by pushing the Stop
button the system is deactivated).
The first time starting up or after running out of fuel it
could be necessary to prime the fuel system. (Refer to
bleeding fuel system instructions in the maintenance
chapter).
A restart protection prevents starting the engine when it is already running, which could cause damage.
In the event of starting problems (numerous attempts are made), close the sea-water inlet cock while cranking to prevent the outlet system and engine to fill up with water.
During the starting process, the cooling water pump is driven with the engine. The cooling water is discharged to the exhaust outlet, because the engine does not run, the exhaust pressure is not high enough to expel this water. Open the valve directly when the engine starts to prevent damaging the impeller. Water in the cylinder will cause serious damage to the engine. For instance; a bent piston rod or a cracked cylinder head. In fact water in the cylinder is the main cause for engine damage in pleasure craft.
Checks once the generator is in operation:
1 Check for abnormal noise or vibration. 2 Check the voltage. 3 Check coolant flow.
Always check immediately after starting the generator
if cooling water flows at the exhaust outlet. If this is
not the case, check the cooling water pump. After
having become acquainted with the generator you will
be able to recognise the coolant flowing through the
system by listening for the noise of the water which is
expelled.
Be aware that especially in harbours the coolant water inlet can easily be blocked by floating objects.
4 Power source selector switch (off/shore
power/generator power). Switch to power source generator. Before loading the generating set up to maximum, have it run warm. The first 50 hours of running the continuous load should be restricted to 70 % of maxi­mum load. Running for long periods at no load or light load in the first 50 hours can cause cylinder glazing and high oil consumption.
Engine load during longer operation:
Please ensure that the generating set is not overloaded. Overloading occurs when the electrical load (demand) is so high that the generator cannot be turned around properly by the diesel engine. Overloading causes the engine to run rough, while using oil and excessive fuel and producing soot by the exhaust. The engine can even stop.
The generator should therefore only be loaded at the maximum rated power for short periods (2-3 hours) only! The high peak current is meant for the ability to start electrical devices that need a high current for starting especially electric motors and compressors (from a still stand state).
In order to prolong the generating set’s life expectancy, the nominal electrical demand on the system should be about 70% or the rated generating set’s maximum load. Please note this when switching on your electrical devices! Nevertheless, the Whisper 12 ULTRA is designed so as not to overheat, even under extreme conditions.
Do not run the generator for very long periods at no load or at very low load. When this is necessary do load the generator at least one hour in 10 hours for minimum 70%. Long term running at too low load will cause the exhaust to be choked by carbon.
Never remove the battery while the engine is running or any electrical cable while the battery is connected in the circuit. Only disconnect the battery with the engine stopped and all switches in "OFF" position
Page 25
OPERATION
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 25
Stopping the generating set:
1 Avoid stopping of the generator abruptly after a long
period of operation at high load! Doing so, you avoid
unnecessary thermal load to your generating set!
Act as follows:
Prior to switching off the generating set, decrease the
generator load (i.e. turn off most electrical users) and
let the generator run at low load for approx. 5 minutes
to allow the engine to get properly cool (the influent
sea water must flow through the system in order to
cool the engine).
If the generator is operating in a hot environment and
you do not act as given above, the excessive heat in
the engine can trip the "high temp" alarms. In that
case, a restart of the engine is not possible for some
time. It is also recommended to switch off electrical
users prior to stopping the generator because of the
voltage drop that occurs as the engine comes to a halt. Such voltage drops may cause damage to electric motors, compressors (in refrigerators or air conditioners etc.).
2 Press the STOP button.
3 Close the inlet sea water cock.
4 Switch to an other 230V/400V power source, if
available.
If the engine is not running and ‘failure’ and ‘charging’ LED is blinking, reset by stop button, otherwise it will drain the start battery
Page 26
MAINTENANCE
26 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
4 MAINTENANCE
4.1 ALTERNATOR
The alternator does not require any maintenance. Periodic inspection and cleaning is recommended, depending on environmental conditions. However when the alternator has been idle for a long period attention to winding condition is recommended. The condition of windings can be assessed by measurement of insulation resistance to earth. (See 5.3.5 Meggering). All bearings are greased for life and not regreasable.
4.2 ENGINE
4.2.1 Preliminary instructions
All regular maintenance can be carried out when the enclosure is open. When oil and dirt has gathered in the enclosure measures have to be taken to avoid spilling oil and polluting the environment. The first service on the engine should be carried out after 50 hours of its life and after a major overhaul. In the first 50 hours the engine should receive special attention:
Long periods of light or no load running in the first 50 hours may lead to cylinder glazing and high oil consumption.
For the same reason it is of the greatest importance to use the right oil specification
The first time starting up or after running out of fuel it could be necessary to prime the fuel system.
4.2.2 Bleeding fuel lines
The system is self bleeding. The first time starting up or after running out of fuel it could be necessary to prime the fuel system. 1 Ensure there is sufficient fuel. 2 Release the fuel bleed screw (1). See fig. 17. 3 Push the start button activating the electric system
and activating the fuel pump. When more time is needed to bleed, push “start” and hold on the local control panel (so not on the remote panel) Hold as long as necessary to bleed the system.
4 Retighten the fuel bleed screw (1) when no further air
bubbles are expelled.
Fig. 17: Bleeding fuel lines 1 = Fuel bleeding screw
4.2.3 Valve clearance
When the engine is in cold condition both valves (inlet and outlet) should have a clearance between 0.25 mm. The adjustment has to be done at TDC (refer to § 5.4.2).
4.2.4 Replacing fuel filter
Filter change depends on contamination of the fuel, but should be done however, at least every 300 running hours. Before changing the filter, clamp off the supply line. Remove the hoses from filter and attach them on the new filter again. The arrow on the filter housing indicates the direction of the flow. A clogged filter results in a lack of output of the generating set.
Page 27
MAINTENANCE
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 27
4.2.5 Replacing oil filter
The oil filter is in front of the service side. Replacement has to be executed according to the schedule in this manual. Drain the oil using the sump pump and put some tissues under the filter.
A smeer of oil has to be put on the seal of the filter before fitting the filter. The filter should be fastened manually: when the rubber touches the metal turn 3/4 further.
4.2.6 Readjustment V-belt
The alternator bracket allows for readjust of the V-belt. Deflections should be 10 mm (refer to fig. 20)
Fig. 20
10 mm
Fig. 18
Fig. 19
Page 28
MAINTENANCE
28 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
4.3 REGULAR MAINTENANCE
CHECK DAILY:
Oil level (see fig. 21)
Take care the oil level is never
below the mark. Do not add oil
when the level is still above
the mark
1 Minimum oil level 2 Maximum oil level
Fig. 21:
CHECK DAILY:
Level cooling liquid
Hoses for loose connections or deterioration.
Water inlet filter.
AFTER FIRST 50 HOURS:
Change oil and replace the oil filter. Have the engine run until it is on temperature and stop it. Replace the oil filter. Drain oil by the sump pump into a suitable retainer and fill up with fresh oil. Start the engine again and have it run for 5 minutes. Stop the engine again and pause for a few minutes to let the oil gather in the crankcase. Check the level again and add oil when necessary.
Check and tighten nuts, bolts, and unions, paying particular attention to the fuel system.
Observe the exhaust at the normal full load. The exhaust must be free from soot. Do not allow the engine to run with a dirty exhaust without investigating the cause as this may result in an expensive breakdown.
Check air vent on a regular basis. When the air vent it not working properly the engine can fill up with water by siphoning. Water in the combustion chamber causes serious damage to the engine.
Check and readjust V-belt.
Check the electrical connections.
EVERY 150 HOURS:
Change oil.
Check the battery acid level (not applicable when
Mastervolt batteries are used).
Check battery terminals for corrosion
Check and readjust V-belt
Check impeller raw water pump (durability
depends on the purity of the sea water. In sandy water and warm water wear will increase).
When replacing the impeller the gasket between the pump case and the cover should be replaced as well. So when ordering a spare impeller order a gasket as well. Remove the cover to get access to the impeller. Remove the old impeller with the help of two screwdrivers. Install the new impeller and add some grease. Turn the blades in the direction of rotation of the pump i.e. anti clockwise looking at the impeller.
EVERY 300 HOURS:
Replace the impeller of the raw water pump.
Retighten the cylinder head bolts and adjust the
valve clearance. (Refer to § 5.4.2).
Replace the oil filter.
Replace the fuel filter
Replacement depends or the condition of the fuel. We recommend replacement every 300 hours. Isolate the fuel supply and change the element.
EVERY 1000 HOURS:
Replace the V-belt.
Retighten cylinder head bolts/adjust + valve
clearance.
EVERY 2000 HOURS:
Check lubricating oil pressure
Clean and check or replace fuel injector nozzles
and check injection pressure.
Check the air filter element: The air is taken in via the cover on the alternator. Below this cover is a spongy material which filters the air and holds some electrical components which are cooled by the inlet air. This filter does not require regular maintenance. Only in very dusty circumstances this filter should be cleaned. The spongy material can be washed in solvent or replaced.
Check the cooling system: The engine cooling liquid is indirectly cooled by raw water via a heat exchanger. The alternator is cooled by seawater which is pumped by the PTO driven impeller pump through the cooler elements in the generator housing. All parts of the cooling
1 2
Page 29
MAINTENANCE
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 29
system are of corrosion free and seawater resistant materials such as brass and gunmetal. In case of gathering of dirt in the system it could be cleaned by compressed air. When overhauling the engine one could clean the parts thoroughly or replace.
When the generator set runs less than 100 hours a year the oil should be changed yearly
4.3.1 Maintenance schedule
Check oil level daily
Check water inlet filter daily
Check the level of the cooling liquid daily
Change oil and oil filter after first 50 hours
Check and tighten nuts, bolts, etc. after first 50 hours
Check exhaust after first 50 hours
Check air vent after first 50 hours
Check and readjust V-belt after first 50 hours
Check electrical connections after first 50 hours
Change oil 150 hours
Check battery 150 hours
Check air vent 150 hours
Check and readjust V-belt
150 hours
Check impeller water pump 150 hours
Replace impeller water pump 300 hours
Retighten cylinderhead bolts and readjust valve clearance
300 hours
Replace oil filter 300 hours
Replace fuel filter 300 hours
Retighten cylinderhead bolts , adjust valve clearance 1000 hours Replace the V-belt 1000 hours
Check lubricating oil pressure 2000 hours
Check injector and injection pressure 2000 hours
Check inlet air filter 2000 hours
Check cooling system 2000 hours
4.3.2 Putting out of service
When not using the generating set for a longer period it is recommended to execute an engine preservation procedure.
1 Clean the engine.
2 Loosen the fuel suction pipe and fuel return and put
them in a can with preservation diesel fuel. Start the engine and run the engine warm.
3 Drain the hot engine oil and refill with preservation oil.
4 Stop the engine and take loose the inlet of the raw
water pump. Drain the water from the water lock. Crank the engine having the raw water inlet sucking anti freeze from a can until the pump, heat exchanger and manifold are filled.
5 The coolant can stay in the engine
6 Disconnect the battery and store it in a place free of
frost and dry and charge it regularly.
7 Close inlet- and outlet openings with tape.
8 Protect the generating set against the influences of
bad weather conditions.
This method of preservation will be sufficient for 6 months. Repeat steps 2, 3, and 4, every 6 months. Change oil before using the engine again.
Page 30
TROUBLE SHOOTING
30 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
5 TROUBLE SHOOTING
5.1 ALTERNATOR/ ELECTRICAL FAULTS
Beware of parts which are live!
Remove 3 Amp. Fuse in the control panel while working on the generator to prevent the engine from starting
A failure code is displayed when a hardware failure at the generator is detected
5.1.1 General
If any problem should occur, check basic conditions and examine all external wiring, switch gear and circuit breakers. Also check if measuring instruments give the correct value. If in doubt, measure directly on the alternator terminals with an independent instrument. This should only be carried out by an experienced electrician. If during these measurements the engine immediately stops after starting and an error code is displayed at the remote control panel ( “AC VOLTAGE”), one can start the
generator by means of a “service start” at the service menu (see paragraph “service start” of the user’s manual of the Digital Diesel Control). By doing this, the generator will keep running for 2 minutes before it stops. This offers you the possibility to carry out measurements to investigate the cause of the failure.
Check if the engine is running correctly at 1500 RPM (50 Hz) according to its settings and does as well under load. A RPM drop of 1% at full load is acceptable. Therefore a no load setting should be at 1515 RPM = 50.5 Hz. Under no circumstances should the RPM under full load be below 1485 RPM = 49.5 Hz. When the problem is in the RPM refer to the engine fault finding paragraph. Digital Diesel Control system will help to indicate failures and display causes
CAUTION!
If the voltage is set any higher than its maximum limit, the generator may be damaged.
Failure code Problem
COMMUNICATION Communication error between the panel and the generator LOW START BAT Starter battery voltage too low ALTERNATOR No output battery charging voltage EXHAUST TEMP Exhaust temperature is too high WATER TEMP Coolant temperature is too high OIL PRESSURE Oil pressure failure AC VOLTAGE Generator AC output voltage is either too high or too low HIGH CURRENT Generator is in overload FREQUENCY Output frequency of the generator is too low
5.1.2 Trouble shooting table
PROBLEM CAUSE SOLUTION
Circuit breaker "off" or faulty main fuse
Faulty fuse of the AVR
Check switches and fuses and measure directly on the alternator to exclude external causes. Check fuse of the AVR
Low engine RPM.
Check the engine RPM and adjust (refer to special procedures).
Loss of residual magnetism.
Check the residual magnetism and flash the alternator (refer to special procedures).
Faulty AVR
Check by independent excitation if the problem is in the AVR or in the windings and replace AVR if necessary (see special procedures).
No output (Voltage) at all
Rotor diode(s) broken.
Check the diodes in the rotor (refer to special procedures). The Whisper 12 ULTRA Three Phase has six diodes in the rotor.
Generator output voltage too
Engine is not reaching the rated RPM. Refer to special procedures to readjust RPM.
Page 31
TROUBLE SHOOTING
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 31
PROBLEM CAUSE SOLUTION
Faulty AVR. When slightly too low, adjustment could be necessary
Try to readjust AVR. Check by independent excitation if the problem is in the AVR or in the windings and replace AVR if necessary (see special procedures).
low when no load is on it (less than 225V between phase and neutral).
Defective diode(s)
Check the diodes in the rotor and replace (refer to special procedures).
Unbalanced load; check the voltage of the other phases. When the voltages are different this is caused by an unbalanced load.
Bring load in balance. When slightly out of balance, remove the sense wires to the phase with the highest load and check if the voltage on the other phases is not too high.
Engine is not reaching the rated RPM. Possibly too much load or engine problems (lack of fuel)
Switch off a load; (part off) consumers See to engine RPM problems
Generator output voltage too low under load (less than 225V between phase and neutral). In no load condition it is OK
Faulty AVR or readjustment necessary
Try to readjust the voltage Check by independent excitation if the problem is in the AVR or in the windings and replace AVR if necessary (see special procedures).
Generator output voltage too high without load, (more than 235V between phase and neutral)
Over-energising due to defective AVR or wrong AVR setting
Check AVR, readjust and replace AVR if necessary (see special procedures)..
Generator output voltage too high with load, (more than 235V between phase and neutral) In no load condition it is OK
Unbalanced load
Bring load in balance. When slightly out of balance, remove the sense wires to the phase with the highest load and check if the voltage on the other phases is not too low.
Disturbances on the electrical system/ user side.
Check if electrical load is fluctuating
AVR reacts on fluctuating load
Do not apply strong fluctuating loads
Generator voltage fluctuates.
Engine runs irregularly.
When engine runs irregularly see section: "Engine runs irregularly" at the “Engine faults” paragraph.
Generator is not able to start an electric motor
If the generator is unable to supply enough power to start an AC electric motor, this is usually because this motor draws too much current during starting
Check the electric motor’s current draw required for starting. This should not exceed the rated generator peak output current. This could be remedied by using a "soft-start". Inquire at your nearest Mastervolt dealer or directly at the manufacturer, Mastervolt in the Netherlands.
Page 32
TROUBLE SHOOTING
32 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
5.2 ENGINE FAULTS
Remove 3 Amp. fuse in the control panel while working on the generator to prevent the engine from starting.
5.2.1 General
Most electrical problems relating to Voltage or Frequency are due to wrong engine speed. Note that RPM and Hz are basically the same. Use the problem solving table to find the cause of a wrong engine speed. When there is no obvious cause one can adjust the RPM (refer to special procedures). When the engine is not cranking well, starting problems almost always originate from battery problems or poor battery cable connections.
When the engine is cranking, well starting problems almost always originate from lack of fuel or air bubbles in the fuel pipes.
When the engine does not start instantly, prolonged cranking can fill up the exhaust system with cooling water because of the water injected exhaust. When the water enters the cylinder through the valves this will bring severe damage to the engine. When the engine does not start and repeated cranking is necessary shut off the seawater inlet. Open the valve immediately after the engine has started.
A failure code is displayed when a hardware failure at the generator is detected.
Failure code Problem
COMMUNICATION Communication error between the panel end the generator LOW START BAT Starter battery voltage too low ALTERNATOR No output battery charging voltage EXHAUST TEMP Exhaust temperature is too high WATER TEMP Coolant temperature is too high OIL PRESSURE Oil pressure failure AC VOLTAGE Generator AC output voltage is either too high or too low HIGH CURRENT Generator is in overload FREQUENCY Output frequency of the generator is too low
5.2.2 Trouble shooting table
PROBLEM CAUSE SOLUTION
Diesel engine fails to crank, it does not react at all, or the starter makes clicking noises, or the engine cranks very slowly
Almost certainly this is an electrical problem. One other possibility is that the engine is locked by water in the cylinders or there is other severe damage. Display will indicate “LOW START BAT”.
Check on water in the cylinder and further damage by cranking. When there is water in the cylinder, then deactivate the control system, disconnect the battery, remove the glow plugs. Crank the engine to remove the water through the opening of the glow plugs. Check oil on the presence of water and change oil. Find out how the water did enter the cylinder (check the air vent). Take precautions to prevent it from happening again. When there is no mechanical malfunction the problem must be an electric malfunction.
Starter battery switched "OFF".
Check position of the battery switch and switch "ON".
No reaction at all
Faulty fuse on control panel
Replace fuse
Starter battery voltage insufficient (battery too weak).
Check battery voltage. Recharge the battery. Inspect battery terminals and cables for a good electrical connection (inspect against corrosion, tattered wires, etc.)
No reaction or clicking noises, or slow cranking
To thick engine lubricating oil.
Change oil for a lower viscosity.
Page 33
TROUBLE SHOOTING
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 33
PROBLEM CAUSE SOLUTION
Wiring control system faulty
During the normal starting process, the battery voltage drops to 11V (with a fully charged battery). If the voltage does not drop during starting, the electrical connection is faulty. If the battery voltage drops lower than 11V, then the battery has been discharged too deep.
Starter motor faulty
Repair the starter motor
Out of fuel or faulty fuel, water in the fuel.
Fill up with fuel or replace with better quality.
Fuel solenoid is not working.
Check if solenoid comes in; if not check wire connections and circuitcy to solenoid (see DC wiring diagram).
Fuel lift pump is not working.
Fuel filter is blocked.
Air in fuel lines.
Check fuel filter and fuel lift pump: clean or replace if necessary. Bleed air from fuel system (see maintenance section).
Wrong valve clearance.
Adjust valve clearance,
Low compression because of dirty valves.
Clean valves. Take off the injection bent and inspect the outlet port. When little rust in the port clean the valve by taking off the valve spring and rotate until clean. When the outlet port is strongly affected by rust, the exhaust system is not properly installed (see paragraph
5.4.3). Contact Mastervolt service department for advice.
Blocked injector.
Have the injector tested and cleaned if necessary.
Starter is turning engine smoothly, but engine fails to start
Loss of compression by wear out or damage
Repair by Mastervolt service
Unsuitable contaminated fuel
Lack of fuel.
Fill up with fuel or replace by better quality.
Choked fuel filter.
Check fuel filter and fuel lift pump: clean or replace if necessary.
Disturbances on the electrical system/ user side.
Check if electrical load is fluctuating.
Faulty fuel lift pump.
Try the pump by manual operation. Repair when faulty or replace
Choked air cleaner.
Lack of air.
Check the air intake
Choked exhaust system, exhaust blocked, rubber exhaust hose kinked.
Check the exhaust hose
Air in the fuel pipes
Bleed air from fuel system (see maintenance section).
Blocked injector.
Have the injector tested and cleaned if necessary.
Faulty electronic governor
Replace faulty parts. Contact Mastervolt service department for advice
Wrong valve clearance.
Adjust valve clearance.
Temporarily hunting (this will disappear when engine has run in).
Engine runs irregularly.
Ongoing hunting caused by faulty electronic governor
Replace faulty parts. Contact Mastervolt service department for advice
Faulty electronic governor
Replace faulty parts. Contact Mastervolt service department for advice
Too much oil.
Drain oil to proper level.
Lack of fuel.
Check fuel supply system: fuel pump and filter.
Lack of intake air.
Check air intake.
Choked exhaust system, exhaust blocked, rubber exhaust hose kinked.
Check exhaust system.
Generator overloaded
Reduce the electrical load (switch off some consumers).
Engine speed drops
Defective generator (windings, bearings or other)
Generator must be sent to manufacturer for repair of damaged bearing or winding.
Page 34
TROUBLE SHOOTING
34 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
PROBLEM CAUSE SOLUTION
Damaged engine
Repair by Mastervolt service
Engine does not stop on command
Fuel solenoid is not switching off •
Loss of control
Faulty Digital Diesel Control unit. Stop the engine manually by the stop handle. Check wire connections to fuel solenoid. Check solenoid function. Replace if necessary
Faint blue smoke - generally the result of light load
Increase load.
Heavy blue smoke - caused by lubricating oil: Overfull oil sump or worn cylinder bore, stuck broken or worn piston rings.
Check the oil level. Check the compression.
Engine exhaust smokes
Black smoke –incomplete combustion caused by: Overload, choked air cleaner, inlet temperature too high, unsuitable fuel or water in fuel.
Check air cleaner Check the fuel . Check for overload.
Engine starts, but stops after 10 seconds
Protection system stops the engine; this can be caused by oil pressure failure, lack of cooling water (exhaust temperature alarm). Overload, loose wire or faulty alarm switch. Digital Diesel Control will help to indicate failure.
See paragraph 2.5.5. and 3.2.2 for information on the alarm system. Bypassing the switches can help to confirm the failure. When there is no real failure, it could be a faulty alarm switch
Overload or short circuit.
Switch off the consumers and test for short circuit.
Lack of fuel.
Check fuel supply system: fuel lines, pump, filter, valves, tank level, etc.
Oil pressure low. (oil pressure switch tripped).
Check oil level. Check engine’s oil pressure and have it repaired by Mastervolt.
Excessive heat in cooling system (thermo-switch tripped).
Lack of cooling water (exhaust switch tripped).
Impeller broken.
Cooling water blocked.
Water strainer blocked.
Air or water in the fuel.
Blocked air or fuel filter.
Check cooling water system flow: water pump, inlet water filter, coolant flow.
Loss of compression by wear out or damage.
Repair by Mastervolt service.
V-belt broken or loose.
Readjust or replace V-belt
Engine stops by itself (Digital Diesel Control will help to indicate failures)
Thermostat faulty
Check thermostat and replace
Generator is being overloaded. Digital Diesel Control will indicate “HIGH CURRENT”.
Check electrical load and switch off some consumers
Insufficient intake air.
Choked air cleaner.
Check intake air paths and filter, clean and replace if necessary.
Fuel injector faulty.
Replace injector.
Valve clearance incorrect.
Readjust valve clearance
Poor fuel quality.
Use better quality diesel.
Poor quality lubricating oil.
Use better quality oil.
Sooty, black exhaust.
Continuous running with very low load.
Increase load and have the engine run for a few hours
Wrong measurement. Check if the load is measured correctly. Does the Amp meter show the correct value? When calculating the load by multiplying voltage and amps this should be done by using the exact values, taking into account the power factor of the consumers. When any doubt, measure the power directly with an appropriate instrument.
Overfull oil sump.
Bring the oil to the correct level
Loss of power
Choked fuel filter.
Replace the fuel filter.
Page 35
TROUBLE SHOOTING
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 35
PROBLEM CAUSE SOLUTION
Choked air cleaner
Check air inlet openings; clean air cleaner.
Exhaust blocked.
Check the exhaust system.
Injector blocked.
Have the injector checked.
Loss of compression, sticking or damaged piston ring.
Have the compression measured. Clean or replace the rings.
Wear out of cylinder.
Have the compression measured and have the engine overhauled.
Overload.
Take away the overload.
Low level of cooling oil or air in the cooling system
Fill up with liquid and release air bubbles. Check if there are air blocks in the system; see the installation manual
Water inlet system blocked.
Broken impeller.
Water strainer choked
Heat exchanger choked.
Check the cooling system thoroughly.
Over-temperature
Faulty thermostat Check the thermostat or replace.
5.2.3 Warnings
Generator must be shut off immediately if:
Motor RPM suddenly rises or drops.
Unusual noise comes from generating set.
Exhaust gases suddenly colour dark.
Engine failure warning light is on
5.2.4 Service address
If you cannot correct a problem with the aid of the mal­function table, contact your Mastervolt Service Centre or Mastervolt Amsterdam for an extended service list, tel: INT +31-20-3422100.
5.3 SPECIAL PROCEDURES ALTERNATOR
5.3.1 Automatic voltage regulator
The voltage regulator has a ±2% voltage precision in the machine working range with distortion free loads. The phase voltage can be adjusted by trimmer “V” (see figure 22) from 185 to 290V. A fuse protects the regulator and generator against overloads and/or faults; a pocket has been provided on the edge of the board to hold a spare fuse (rapid type 20x5
3.15A). Another trimmer “ST” (stability) allows adapting the regulator to the generator parameters. The regulator has been built to suppress the voltage surges on releasing the load that are below 20% at nominal load.
AVR SETTINGS
To select the AVR settings access the control board after removing the cover. Most adjustments are factory set to ensure satisfactory results in the operating tests on commissioning. Further adjustments may be necessary to ensure optimum operation under specific working conditions. If the alternator has to operate at 50Hz the jumper “J” across the terminals marked “60Hz” has to be left in place, if it has to operate at 60Hz this jumper should be replaced. The output voltage can be changed by adjusting potentiometer “V”. Take the generating set to its nominal speed and turn until the required voltage is obtained.
Fig. 22. Automatic Voltage Regulator (AVR)
Setting the bottom speed at 50 (60)Hz: start up rotation of the generating set adjusting it to obtain a frequency of 46 (56)Hz. Turn trimmer “UF” until the voltage begins to drop. Restore nominal speed.
CAUTION
If the bottom speed is set at too low a frequency the generator may be damaged. On the other hand, too high a frequency can cause voltage drops with high load.
Page 36
TROUBLE SHOOTING
36 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
5.3.2 Residual voltage check / excitation procedure (flashing)
When residual magnetism disappears there is no residual voltage. Residual magnetism can disappear after the generating set being out of service for a long period or a short circuit. This can be solved by exciting the exciter field coil directly, disconnecting the AVR first. Put 12 Volt directly over the electronic regulator terminals taking polarity into account.
Fig.23: Residual voltage check / excitation procedure.
When using the starter battery fuse it and limit the current with a 30 Ohm resistor. Flashing can be done while the engine is running and the wiring is connected. When a variac (variable power supply) is available one should be able to control the voltage manually.
CAUTION
If the starter set battery is used for exciting one must take care. A short circuit can cause heavy sparking, fire and injuries.
When external excitation does not bring back voltage, the rotating rectifier diodes should be tested and a winding resistant test should be executed.
5.3.3 Testing rotary rectifier diodes
The diodes in the rotor can be checked with a multimeter. The diodes are integrated in a rectifier unit. When all diodes are faulty the alternator will not generate any voltage. When one or more diodes are faulty the alternator will produce too low voltage.
The flexible leads connected to the diodes should be disconnected at the terminal end, and the forward and reverse resistance checked. A healthy diode will indicate a very high resistance (infinity) in the reverse direction, and a low resistance in the forward direction. A faulty diode will give a full deflection reading in both directions with the test meter on the 10,000 ohms scale, or an infinity reading in both directions. In case of faulty diodes replace the rectifier unit. One can get access to the diode unit by taking off the backend cover of the alternator.
Fig.24: Rotating rectifier diodes.
5.3.4 Winding resistant values
If after establishing and correcting any fault on the AVR and diodes, and output is still low when separately excited, then the main rotor, stator auxiliary and exciter stator winding resistance should be checked as the fault must be in one of these windings. The respective leads must be disconnected before taking the readings. Resistance values should be within 10% of the values given in the table below:
Whisper 12 ULTRA Three Phase Alternator models with 6 wires
Resistance main stator windings
0.39 Ohm
Resistance rotor windings
2.4 Ohm
Resistance auxiliary winding
7.5 Ohm
Resistance exciter stator winding
24 Ohm
Resistance exciter rotor winding
3x 0.32 Ohm
Alternator models with 12 wires
Resistance main stator windings
0.33 Ohm
Resistance rotor windings
1.18 Ohm
Resistance auxiliary winding
3.85 Ohm
Resistance exciter stator winding
18 Ohm
Resistance exciter rotor winding
0.18 Ohm
Page 37
TROUBLE SHOOTING
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 37
5.3.5 Meggering
One can try to measure resistance between the housing and the windings with a multimeter which should read infinity. When readings are infinity but a fault is suspected one can do a high voltage resistance test (MEGGERING) This procedure should be carried out by an expert. The AVR should be disconnected during this test. A 500V ‘Megger’ or similar instrument should be used. The insulation resistance to earth of all windings should be in excess of 2 MOhm. Should the insulation resistance be less than this value, drying out the generator windings is essential. Drying out can be carried out by direct warm air (60-80ºC) from a fan heater or similar apparatus into the generator air inlets or outletst
5.4 SPECIAL PROCEDURES ENGINE
5.4.1 Setting the RPM
RPM is set by the manufacturer and should not need readjustment! When adjustments are necessary this can only be done with the help of an interface to a computer and special software to get access to the microprocessor. If readjustment of the RPM is necessary, please contact your Mastervolt Service Centre for advice:
5.4.2 Adjusting valve clearance and retightening the cylinder head bolts.
Both procedures have to be carried out with a cold engine. When both procedures are carried out be sure to retighten the cylinder head bolts before adjusting the valve clearance. When retightening the cylinder head bolts, drain the coolant by removing the drain plug (ref. to fig. 3 –
6).
Loosen the bolts slightly, remove the rocker assembly (the rocker arms, shaft, and stays) and then retighten the bolts to the specified torque in the numerical order illustrated (ref. to fig. 26).
Tightening torque cylinder head bolt: 88 ± 5 Nm Rocker stay tightening torque: 14.7 ± 2 Nm
Figure 26: Cylinder head bolts
The clearance of both (intake and exhaust) valves should be 0.25 mm in cold condition. Set the piston of the first cylinder to be adjusted to top dead centre (T.D.C.) of compression stroke.
The T.D.C. of compression stroke can be found by aligning the T.D.C. mark (notch) on the crankshaft pulley with the mark on the gear case (ref. to fig. 27). First align the T.D.C. mark for the No. 1 cylinder. Confirm that the valves do not move up or down when the crankshaft is turned about 20 degrees in normal and reverse direction of rotation.
Figure 27
If the rocker arms move piston no.1 is on the T.D.C. of the intake or exhaust stroke. In such case turn the crankshaft 360° in the direction of engine rotation again. No. 1 piston is now at T.D.C. of the compression stroke. After adjusting the valves of cylinder 1 adjust the valve clearance of the remaining cylinders in firing order 1 – 3 – 4 – 2. Turn the crankshaft 180 degrees clockwise from the T.D.C of cylinder 1 to the T.D.C of cylinder 3. and turn the crackshaft 180 degrees further clockwise to the TDC of cylinder 4 and adjust the valves. And again 180 degrees to adjust cylinder 2.
Mark on timing gearcase
IT (injection timing) mark
TDC mark piston 1 and 4
TDC mark piston 2 and 3
10 4 2 5
7
861 39
14 12 1 13
1
FRONT MOTOR
Page 38
TROUBLE SHOOTING
38 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
5.4.3 Measuring exhaust backpressure
The exhaust system must be of adequate size -2”/ 51 mm
- and maximal length (refer to installation manual). When
any doubt; backpressure has to be measured. An easy way to measure for back-pressure is to use a water column. A water column can be made visible in a plastic tube along a yardstick and fitting the end to a hose connection to fit in the adaptor on the injection bent after removing the exhaust temperature switch.
The bent A hanging down should not be too short helping to damp the pulsating effect of the gas discharge that is characteristic for a one cylinder engine. The water column should be no more than 27 inches (69 cm.) of water (1 PSI
- 0,07 bar)
5.4.4 Disassembling instructions
It could be necessary to disassemble the generating set for repair or checks. Following instructions will help:
1 The design of the Whisper 12 Ultra makes it possible
to do most repairs on the spot. The connections of the alternator are very accessible. The same is true for the diode of the rotor
2 The sound shield can be disassembled according to
exploded view below (figure 29)
3 To take the generating set out of the soundshield all
hose and cable connections have to be taken off. The set is fixed to its base by four rubber mountings and can be loosened by removing the four nuts from the bolts of these mountings and by removing the safeguards. The easiest way to get the generator out of its capsule is by lifting the set using the lifting eyes
4 One can take off the complete alternator housing.
Before the alternator can be taken off all cables and wiring have to be loosened first.
5 The rotor can be taken off by removing the bolt which
goes through the shaft (normal clockwise threaded). The end of the shaft is specially threaded to push off the rotor from the conic stub shaft, which is on the flywheel, using a 10mm rod of 245mm length and a M24x2 bolt.
6 Reassembling the generating set one should take
care of alignment, cleaning the surfaces between engine and alternator and tighten the bolts crosswise and gradually.
7 Use Loctite 577 to seal the fittings, which should first
be cleaned and made free of oil and grease.
8 Test the generating set first outside its soundshield
and check very carefully for leakages before putting it back in its enclosure.
Fig 28: Measuring exhaust backpressure
MAXIMUM
69cm
27INCHES
Page 39
TROUBLE SHOOTING
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 39
Figure 29: exploded view sound shield Whisper 12 Ultra Three Phase
Page 40
SPARE PARTS LIST
40 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
6 SPARE PARTS LIST
A complete parts manual in English is available as an option number: number: 50200383 (***) A work shop manual in English is available as an option number: 50200172 (***).
We recommend the following spares for service and maintenance.
• Kit A: parts for regular maintenance parts marked (*) article no. 50201360
• Kit B: parts for maintenance + spare parts: all parts marked (*)+(**) article no. 50201361
• Kit C: parts for "world travellers" all parts marked (*)+(**)+(***) article no. 50201362
ARTICLE NO DESCRIPTION
50209030 Fuel filter (*)
50201031 Fuel lift pump (***)
50205120 V-belt (*)
50203121 Oil filter (*)
50201450 Raw water pump complete Mastervolt type M12 (***) (refer to fig. 30)
50209011 Impeller (50209013) + gasket (50209012) (*)
50201401 Cover type M12 (**)
50209018 Bolts cover (**) (6 pcs.)
50201851 Pump repair kit A consisting of: Shaft (50201811), Bearings (2 pcs) (50209014), O-ring (50209017),
Seals (2 pcs.) (50209015), Clips (1 set) (50209019), O-ring (50201814)
50209010 Pump repair kit B (**)(same as repair kit A excluding the shaft(5021811) and O-ring (50201814))
50201413 Heat exchanger complete with appendages (***)
50201422 Water hoses with clamps (**)
50209132 Measuring coil (***) , 3 pieces
50212902 Rotary diode assembly (**) three phase
50212901 Voltage regulator
50209104 Local control panel (***)
50209099 Digital Diesel Control Unit (***) three phases
50212170 Fuses 10 Amps(*)
50212154 Fuses 3 Amps (*)
50212198 Fuses 20 x 5 / 3.15 Amps (**)
50201366 Wiring loom complete (***)
50209102 Digital Diesel Remote control panel (***)
130010915 Cable remote control 15 mtr, including connectors
50206033 Overhaul gasket kit / Seal kit (***)
50206030 Cylinder head gasket kit
50206040 Glow plug, 4pcs (**)
50203050 Nozzle injector, 4pcs (**)
50206045 Thermostat (**)
50206038 Gasket thermostat (**)
50206034 Gasket rocker cover (**)
More extensive parts list on the internet: MASTERVOLT.COM (fast moving parts)
Page 41
SPARE PARTS LIST
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 41
50201814 O-ring
50209015
Seal
50201450 RAW WA TER PUMP M 12
Screw impelle r
50209011 Impeller kit
Bea r ing
50209014
50209016 Circlip
50201811 Shaft
Male hose connector
50221031
Pump housing50201414
Seal
50209015
50209018 Screw co ver
Cover type M12
50201401
Gasket
50209012
Impe l ler K+ M
50209013
50221007
Male hos e connector
O-r ing
50209017
Bear ing
50209014
50209019 Circlip
50209019 Circlip
Figure 30: Raw water pump complete Mastervolt type M12
Page 42
MAINTENANCE LOG
42 Copyright © 2008 Mastervolt / December 2008 / WHISPER 12 ULTRA - Three Phase / EN
MAINTENANCE LOG
first service after 50 hours: hour counter: remarks
next service (every 150 hours) hour counter:
Page 43
NOTES
EN / WHISPER 12 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt 43
NOTES
Page 44