Mastervolt whisper 6, whisper 10 Installation Manual

Page 1
INSTALLATION MANUAL FOR MOBILE APPLICATIONS
WHISPER 6 /10
- 3000 RPM -
Mobile diesel generating set 230V / 50Hz
Digital Diesel Control
V5 August 2009
Art.nr. 50261121
Page 2
TABLE OF CONTENTS
2 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
Copyright © 2009 Mastervolt. All rights reserved. Reproduction, transfer, distribution or storage of part or all of the contents in this d ocument in an y form wit hout the prior written permission of Mastervolt is prohibited.
Page 3
TABLE OF CONTENTS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 3
TABLE OF CONTENTS:
1
INTRODUCTION..............................................................................................................................................................4
1.1 General .............................................................................................................................................................. 4
1.2 Generating sets for vehicles............................................................................................................................... 4
1.2.1 Marine and mobile generators...........................................................................................................4
1.2.2 Why two radiators:............................................................................................................................. 5
1.2.3 Why the alternator should be cooled by water...................................................................................5
2 INSTALLATION............................................................................................................................................................... 6
2.1 General .............................................................................................................................................................. 6
2.2 Location..............................................................................................................................................................6
2.3 Instructions for optimal sound and vibration insulation....................................................................................... 7
2.3.1 Further recommendations .................................................................................................................7
2.4 Ventilation........................................................................................................................................................... 7
2.4.1 General..............................................................................................................................................7
2.4.2 Air strainer element ........................................................................................................................... 8
2.5 Connections .......................................................................................................................................................8
2.5.1 Fuel supply...................................................................................................................................... 10
2.5.2 Radiator cooling ..............................................................................................................................12
2.5.3 Dry exhaust system.........................................................................................................................16
2.5.4 Electrical installation (12 Volt) ......................................................................................................... 18
2.5.5 AC power system (230 Volt)............................................................................................................21
3 INSTALLATION SPECIFICATIONS.............................................................................................................................. 22
3.1 General ............................................................................................................................................................ 22
3.2 Commission table............................................................................................................................................. 22
3.3 Technical data..................................................................................................................................................23
3.4 Installation materials.........................................................................................................................................24
4 DIAGRAMS & DRAWINGS ........................................................................................................................................... 29
4.1 Layout generator control with 230VAC fan....................................................................................................... 29
4.2 Layout generator control with 12VDC fan......................................................................................................... 30
4.3 Layout generator control with 24VDC fan......................................................................................................... 31
4.4 Wiring colours................................................................................................................................................... 32
4.5 AC wiring diagram 230V / 50Hz .......................................................................................................................33
4.6 Electrical diagram radiator fan control 230VAC................................................................................................34
4.7 Electrical diagram radiator fan control 12 / 24 VDC.......................................................................................... 35
4.8 Wiring diagram electronic governor.................................................................................................................. 36
4.9 Remote control panel drawings........................................................................................................................ 37
4.10 Dimensions....................................................................................................................................................... 38
Page 4
INTRODUCTION
4 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
1 INTRODUCTION
1.1 GENERAL
This installation manual applies to the installation of the Mastervolt Whisper 6 / 10 -3000RPM mobile diesel generating set, first launched in August 2008. This manual is valid for the following models:
Part number Description
51102020 Whisper 6, 230V 3000rpm
Mobile / keel cooling
51102026 Whisper 6, 230V 3000rpm
Mobile / keel cooling -ungrounded
51104020 Whisper 10, 230V 3000rpm
Mobile / keel cooling
51104026 Whisper 10, 230V 3000rpm
Mobile / keel cooling -ungrounded
For other models see our website: www.mastervolt.com
WARNING
A warning symbol draws attention to special warnings, instructions or procedures which, if not strictly observed, may result in damage or destruction of equipment, severe personal injury or loss of life.
DANGER
This danger symbol refers to electric danger and draws attention to special warnings, instructions or procedures which, if not strictly observed, may result in electrical shock which will result in severe personal injury or loss of life.
WARNING! Before working (installation) on the system read the section safety instructions in the user’s manual
1.2 GENERATING SETS FOR VEHICLES
1.2.1 Marine and mobile generators
Whisper Generators originate from the marine sector. But there are also specially designed Whispers available for mobile applications, suitable for supplying power on board of vehicles to use professional apparatus and equipment, strong lightning and air conditioning etc. The cooling system and exhaust system on vehicles is completely different from standard marine systems. Standard marine generators are cooled by seawater that nowhere exceeds 30° Celsius and is seldom warmer than 20° Celsius in the northern territories. Cold seawater is pumped through the alternator, through the heat exchanger and is injected in the exhaust. The exhaust gasses are therefore cooled and rubber exhaust hose can be used.
On vehicles the engine and alternator are individually cooled by radiator with an electric (12V/24V or 230V) driven fan. The radiators can be fitted below, on top or in the side of the vehicle.
The exhaust is of the dry type and includes a stainless flexible bellow and high quality mufflers.
Never use rubber exhaust hose, neither fibreglass nor plastic exhaust parts in a dry exhaust system as applied on vehicles.
Figure 1: Typical vehicle application radiator side mounted
Page 5
INTRODUCTION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 5
Figure 2: Typical vehicle application radiator top mounted
Figure 3: Typical vehicle application radiator bottom mounted
1.2.2 Why two radiators:
The optimum engine operating temperature is between 87° and 92° Celsius. The radiator reduces the temperature of the cooling liquid by only 5°C to 12°C. The returning “cold” coolant therefore has a minimum temperature of approx. 75° Celsius. The alternator should be kept as cool as possible. In practice an alternator starts getting less efficient above 40° Celsius. It is hardly possible to cool down the cool ant of the alternator below 40° by using a radiator. When a vehicle is in the sun on a parking place the ambient temperature itself could be 40° Celsius. Because of the divergence in the working temperature of engine and alternator it will be clear that it is not possible to combine the cooling of the engine and alt ernator in one radiator system. Furthermore it will be clear that it is very difficult to cool an alternator optimally with the aid of a radiator in conditions with high ambient temperatures.
1.2.3 Why the alternator should be cooled by water
For normal industrial use alternators are cooled by air. This requires a flow of air through the alternator of many m3 per minute. With the air, the noise comes out into the open. Generators on vehicles can only made silent by full enclosure in a sound shield canopy. The o nly opening in the Whisper canopy is the inlet for combustion air. For that reason the alternator is cooled by water. Although coolin g the alternator by circulating water through a radiator is not ideal; it is much better than by air. Therefore aircooled alternators are rarely used in vehicles
Page 6
INSTALLATION
6 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
2 INSTALLATION
Figure 4: Schematic installation diagram
2.1 GENERAL
To ensure reliability and durability of the equi pment, it is very important that the installation is carried out with the utmost care and attention. To avoid problems, such as temperature problems, noise levels, vibration, etc. the instructions set out in this manual must be followed and all installation work must be carried out professionally.
2.2 LOCATION
When looking for a proper place for a generator in a vehicle all relevant aspects have to be taken into account
Accessibility
Solid foundation
Space to mount the radiator (Refer to par. 2.5.2)
Space to mount the exhaust (Refer to par. 2.5.3)
A way to fit the fuel lines
Since Whisper generating sets have extremely compact dimensions, they can be installed in tight locations. Please consider that even almost maintenance-free machinery must still remain accessible. When selecting the location area in which to mount the generating set, make sure there is sufficient room to carry out any maintenance work. The unit must be easily accessible on the service side and on the distribution si de to have access to the V-belt All models can be serviced from one side. Oil filling can b e done on the service side and on the top. Cooling liquid can be filled via the expansion tanks. The top of the engine (rocker cover) has to be accessible for adjustment of the valve clearance.
Please also note that in spite of the automatic oil pressure sensor it is still essential that the oil level is checked regularly.
Page 7
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 7
2.3 INSTRUCTIONS FOR OPTIMAL SOUND AND VIBRATION INSULATION
Position the generating set as low as possible in the vehicle. The generating set is secured to the base frame by means of flexible engine mountings. This frame is mounted in the vehicle with additional vibration dampers. When it is possible to mount the unit directly on the chassis of the vehicle this has advantages in preventing vibrations by resonance.
2.3.1 Further recommendations
Whisper generating sets are standard equipped with a sound cover. This sound cover has been designed to give effective sound insulation. For optimum sound and vibration dampening, the following factors should be considered.
1 Most important is the structure on which the generator
is placed to be stiff. Directly below the rubber mountings the structure should be supported vertically to the chassis of the vehicle.
2 In larger vehicles a separate and insulated space for
the generator will help to damp the noise even further
3 Avoid mounting the generating set in close proximity
to thin walls or floors that may cause resonance.
4 Sound dampening is extremel y poor if the generating
set is mounted on a light weight flimsy surface such as plywood which will only amplify vibrations. If mounting on a thinner surface cannot be avoided, this should be at least be reinforced with stiffening struts or ribbing. If possible, holes should be drilled or cut through the surface to help reduce the resonance. Covering the surrounding walls and floors with a heavy coating plus foam will certainly improve the situation.
5 Never connect the base of the generating set directly
to walls or tanks.
2.4 VENTILATION
2.4.1 General
The generating set normally draws air from the engine room. Engine rooms with natural ventilation must have vent openings of adequate size and location to ena ble the generating set to operate without overheating. To allow an ample supply of air within the temperature limits of the generating set an opening of at least 100 cm2 is required. A "sealed" engine compartment must have a good extraction ventilator to maintain reasonable engine room temperatures. High temperature of intake air reduces engine performance and increases engine coolant temperatures. Air temperatures above 40°C reduce the engine power by 2% for each 5°C of rise. To minimise these effects the engine room temperature must not be more than 15ºC above the outside ambient air temperature. Apply a combination of ventilators, blowers and air intake ducting to meet the temperature limit. The air inlet ducts should run to the bottom of the engine room to clear fumes from the bilge and to circulate fresh air. Air outlets should be at the top of the engine room to remove the hottest air. An engine room blower should be used as an extraction ventilator to remove air from the engine room. In cases where it is impossible to meet the above mentioned temperature limit by using machine room ventilation, connections are to be made for an air inlet directly to the enclosure. With these connections the generating set can be directly connected to an air duct. Air inlets should be louvered, where appropriate, to protect the engine room and to protect the generating set from water spray. As an extra precaution, the fitting of a cowl ventilator with a cover box located as high as possible, is recommended.
Figure 5: Mounting of the Whisper generating set. X = wrong, V = OK
Page 8
INSTALLATION
8 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
Figure 6: Mounting of the air strainer element
2.4.2 Air strainer element
Applying a generator in a vehicle, where combustio n air is taken in from below the vehicle, there is often much dust, sand and dirt in the air. For these applications Mastervolt prescribes the installation of an air strainer element. This air strainer element is in the standard suppl y, but not yet mounted as often the best place to mount it will be different in any installation. To install the air strainer element one has to find the best place somewhere on the canopy. Figure 6 shows the recommended place, but the filter can be mounted everywhere, even on the bottom, hanging down. Use sealant or kit between the flange and the surface.
ATTENTION!
In any case it is necessary to open a hole for air inlet!
2.5 CONNECTIONS
The generating set comes with all supply lin es and output cable (i.e. electric cables, coolant connections, exhaust, fuel lines etc.) already connected to the engine and generator. The supply lines are fed through the capsule’s front base. The connections are marked as shown in figure 7 All electrical connections, cable types and sizes must comply with the appropriate national regulations. Supplied cables are rated for ambient temperatures up to 70°C. If the cables are required to meet higher temperature requirements, they must be run through conduits.
ATTENTION!
Before working (installation) on the system read the section safety instructions
50230006 A IR CLEA NER + ADAPTER
50230005 A DAPTER
50230003 A IR CLEANER
WHEN NO T USING THE FILTER, THIS HOLE SHOULD BE OPENED
Page 9
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 9
Fig. 7 Connections Whisper 6 and 10 for mobile applications
01 Coolant generator in 02 Battery positive (+) 03 Fuel out Ø8mm 04 Fuel in Ø8mm 05 Battery negative (–) 06 Coolant engine out 07 Coolant engine in 08 Coolant generator out
10 Expansion tank 11 Exhaust 1½” 12 AC power output 13 Remote control
Page 10
INSTALLATION
10 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
2.5.1 Fuel supply
1 FUEL TANK
Fuel tanks should be made of appropriate material such as (stainless) steel or plastic. Steel tanks should not be galvanised or painted inside. Condensation can occur in metal tanks when temperature changes. Therefore, water accumulates at the bottom of the tank and provisions should be made for the drainage of this water. The tank will need a filling connection, a return connection and an air ventilation connection which will require protection against water entry. Some official regulations do not allow connection points at the base of the fuel tank; connections are to be made at the top of the tank with internal tubing down to a few cm above the bottom of the tank. Using the existing fuel tank of the car-engine the fitting should be carried out with extra care. Both a supply line and a return line should be installed and go into the tank from the top. Interference of the two systems (car engine and generator engine) shou ld be avoided.
Do NOT connect the fuel lines to the lines of the vehicles engine fuel supply.
Driving the tank empty below the level of the suction pipe of the generator could make it necessary to bleed the fuel system.
2 FUEL LIFT PUMP
The generating set itself is equipped with a fuel lift pump; therefore the tank can be installed at a lower level than the generating set. See figure 8. The maximum suction he ight is 1 m. If the pump has to lift the fuel higher than one meter an external fuel lift pump must be installed. The control board is already prepared to connect an extra fuel pump. When using a second electric fuel supply pump, it is recommended to mount a loose supplied pump close to the tank and mount it in an angle or vertical to prevent air bubbles to block the system. The pump will become quite hot and should be mounted out of touch. (Refer to fig. 13) The pump makes clicking noises and therefore could be mounted on rubber mountings. When the clicking noises of the pump are not acceptable an other noiseless pum p is available as an option
Figure 8: Fuel supply (fuel tank is above the generating set)
1 Fuel return 2 Fuel supply 3 Prefilter / Water separator (optional) 5 Fuel Tank
Page 11
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 11
A
1
3
2
5
4
Figure 9: Fuel supply (fuel tank is below the generating set)
1 Fuel return 2 Fuel supply 3 Prefilter / Water separator (optional) 4 Extra fuel lift pump (optional) 5 Fuel tank
Figure 10: Fuel line assembly with vertical mounted pump and fuel lift pump mounted in an angle
Page 12
INSTALLATION
12 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
3 FUEL PIPES
When the tank is above the generating set (figure 8) we recommend ending the return line on the top of the tank. When the return is on the top - in case of a leakage the return line cannot overflow because of siphoning. One will only need a fuel cock in the fuel supply line. When the tank is below the generating set we recommend ending the return line on the bottom of the tank (A) below the inlet of the supply line.
Both supply and return fuel pipe lines should be appropriate material and 8 mm outer diamet er tubing. The quality of the tubing of fuel pipes could be submitted to local regulations depending on the application of the vehicle. The fuel pipes can be plumbed to the flexible hoses which are on the generating set and have a conn ection to fit to 8 mm pipe. This fuel lines fulfils CE standards and are according to ISO 7840 A2. It is important to avoid bends in the pipes, as they could trap air bubbles. The return pipe should never be connected to the suction pipe. The return line should be of 8 mm diameter and go straight back via the top to the bottom of the tank. When the return is too narrow, has too many bents and goes back to the bottom of the fuel tank, the back-pressure could be too high. This results in irregular running of the engine. When the engine runs irregular, one can check if back-pressure is the problem by disconnecting the return line just outside the canopy and draining it in a canister. When the engine runs smooth now, the return piping has to be changed. It could also help to install a second (electrical 12V) fuel lift pump.
4 FUEL FILTERS
A fine fuel filter is installed which requires maintenance. Mastervolt advises to install an extra fuel filter/ water fuel separator near the fuel tank. Before starting your generating set for the first time follow the fuel system bleeding procedure in the users manual.
2.5.2 Radiator cooling
1 GENERAL INSTRUCTIONS
The radiators can be mounted below the floor, in the side or on the roof of the vehicle. Wherever the radiators are mounted the well functioning of the system depends on the well circulation of the coolant. Roof mounted radiators bring the most risk for circulation problems, because air trapped in the radiators or a low level of the coolant, will immediately affect the cooling capacity of the radiators. It is recommended to keep the radiators as close as possible to the unit. The piping should be fitted as direct as possible. When the radiators are above the engine, the piping should be fitted below the top of the radiators! (refer to figure 11). Bents in the piping, that can trap air bubbles, should be avoided or ventilated (refer to figure 12)
Figure 11: Air traps should be avoided
Piping should not be fitted above the radiator!
OK
Page 13
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 13
Figure 12: Ventilating an air trap
Special attention should be paid to the ventilation of the systems. Each installation system is standard supplied with an expansion tank for the coolant, which is also use d to release air bubbles and makes it possible to add coolant into the system in an easy way. This expansion tank should be at the highest point of the system and mounted as high as possible.
Most cooling problems originate from air traps blocking the circulation of the engine coolant.
Figure 13. Alternator cooling system: open expansion tank with overflow pillar.
For the alternator cooling system we use an open -non pressurised- system. Therefore the 12 mm overflow pillar on the expansion tank should stay open (figure 13). A piece of hose can be used to drain redunda nt liquid that is thrown out because of the expansion of the liquid in the system. When open the expansion tank can easily releas e air that is ventilated by the different connections. As the capacity of the alternator cooling system is very small, also the initial filling can be done via the expansion tank. It could be necessary to refill the tank a few times. The pump of the alternator cooling system is self-priming and this makes the system less sensitive for air traps.
For the engine we use a pressurised system. The 12 mm connection on the top is closed. Wherever the radiators are mounted it is necessary to ventilate the exhaust manifold of the engine. The exhaust manifold has a 8 mm connection to ventilate the manifold. There is an 8 mm high pressure and high temperature resistant hose in the delivery to connect the hose connection on the side of the manifold with the expansion tank (refer to figure 7).
Initially the engine cooling system can be filled via the cap on the exhaust manifold of the engine. However when the radiator is above the engine one can only fill the system to the level of the manifold. Additional filling has to be done via the expansion tank. For large engine cooling systems with long pipes or for extra reserve there is an extra large expansion tank with a content of 7 litres and an alarm for low coolant level th at can be supplied as an option (refer to figure 14).
Figure 14: 7 litres optional expansion tank with low level alarm.
Page 14
INSTALLATION
14 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
When mounting the radiators it is important to take care that the outgoing connection, which is the connection to the engine inlet, is on the top position (refer to figure 15 detail A) and is connected to the expansion tank. Also when the radiator is mounted flat at the bottom of the vehicle the outgoing connection is connected to the expansion tank. This is the best way to have the system release air and to add liquid when necessary.
The expansion tank must be fitted in the outlet of the radiator = the inlet pipe of the engine
Figure 15. Outgoing connection connected to the expansion tank
When both radiators are flat mounted on the roof, the expansion tanks should be mounted a little higher. (refer to figure 16 detail B).
Figure 16: Low profile radiator assembly on the roof
Most cooling problems originate from air traps blocking the circulation of the engine coolant.
It is very important to use good quality heat resistant hose and fittings. Therefore it is strongly advised to use Mastervolt installation kits
A
side mount
bottom mount
B
top mount
Page 15
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 15
2 HOW AND WHERE TO MOUNT THE RADIATORS
The radiator kit includes rubber mountings to prevent vibrations to be transferred to the body of the vehicle (figure 17). Due to the difference between vehicles general instructions are not available. One has to find out where the best place for mounting is. For OEM customers Mastervolt can supply a special customised installation kit.
Figure 17. Radiator on rubber mountings
Bottom mounted radiators
When bottom mounted the radiator should not be the lowest point of the vehicle to avoid damage. A free flow of air should be guaranteed. When horizontal mounted, the fan should be on top, which causes a flow of air downwards. Often it is possible to find a place where extra space above the fan helps to create a free flow of air. It is recommended to make a shield below the radiator to catch stones and dirt and operates as a spoiler. The distance between the radiator and the shield should be at least 50 mm. Sometimes it is possible to build the radiators and shield on a sub frame that is mounted below the vehicle as a module.
Measures have to be taken to prevent the hot air circulating and reducing the capacity of th e radiators. Refer to figure 18
Figure 18: Bottom mounted radiators with shield
Figure 19. Making use of the space below the floor to get an optimal flow of air through the radiators.
Side mounted radiators
Most effective and easy is to mount the radiator in the side of the vehicle, if possible below the level of t he top of the engine. A louvered grid should protect the radiator from rain and objects, but must not block the airflow. The fan should be inwards which causes the air to blo w outwards. A disadvantage of having the radiator in the side is possibly more noise of the electric fan and a flow of air that could be felt by people passing by. A free flow of air should be guaranteed. The ventilation connection of the cooling system that goes to the expansion tank, should be in the outgoing coolant flow on top of the radiator.
Figure 20: Side mounted radiator
side mounted
air flo
w
Page 16
INSTALLATION
16 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
Roof mounted radiators
The radiators on the roof is often the best option from the point of view of keeping the noise of the fans away from people and it will give the best result in dissipating the heat. However, often this option conflicts with the possible need to keep the vehicle as low as possible. An other disadvantage is that the piping has to go through the roof which requires provisions to be waterproof. Also negative is that roof mounted radiators are more sensitive for air traps (see figure 11). When having enou gh space it would be ideal to have the radiators vertically mounted on the roof. Note that the expansion tank should be above the radiator. When having the radiators horizontally mounted on the roof (refer to figure 21) enough space (50 mm) should be between the roof and the radiator fan to have a free flow of air. When the radiators are roof mounted there should be protection against weather conditions. To avoid damage while the vehicle is driving at high speed, the use of a spoiler could be necessary.
Figure 21: Two examples of top mount radiators
3 TWO SPEEDS FAN (OPTIONAL)
To keep the noise as low as possible the fans of the radiators can run at two different speeds. As option a control box is available which can be used to drive the fans with two speeds, depending on the load of the generator. When using 12/24V DC to drive the fans (see chapter 4.7), in normal mode the electric motors of the fans are connected in series and run at low speed. In this mode they almost produce no noise. Only when necessary
- this is controlled by thermostat switches - the fans are
switched in parallel and will blow at full speed.
The same is achieved with 230 V fans with help of a transformer (refer to the connection diagrams in paragraph
4.6).
However, when not strictly necessary, we recommend using the standard fan control instead of the t wo speeds fan control, in order to keep the system as simple as possible.
2.5.3 Dry exhaust system
1 GENERAL REMARKS
A dry exhaust muffler system should be as effective in silencing the exhaust as a wet marine exhaust system when applying the right mufflers. However noise could be generated by vibrations in the mufflers and be transferred to the chassis. Tacit factors like the length of specific pipe sections could be important. It is very difficult to take these factors into account.
Figure 22: Dry exhaust systems on vehicles
The standard Mastervolt exhaust kit contains the materials to perform a professional installation. In the kit is a stainless steel flexible bellow (hose) to allow for expansion and to prevent vibrations to be transferred. Rubbers are supplied to mount the mufflers flexible. The insulation blanket for the flexible bellow and the resonance muffler are also very effective in damping vibrations. Still it could be that additional measures has to be taken like an e xtra clamp in a vibrating section of pipe, insulation bl ankets on other parts of the system and possibly even additional mufflers.
When the exhaust is led through the roof of a vehicle, measures has to be taken to prevent rainwater to enter the system. Special rain caps are available as an option.
Figure 23. Ways to prevent water to get in
horizontal
vertical
Page 17
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 17
A negative feature of a dry exhaust system is the heat radiated by its components. Measures are taken to overcome the heat problem: The exhaust bent to bring the exhaust out of the canopy is cooled by water. Insulation blankets are included in the exhaust kit to insulate the flexible bellow and the first muffler. When a dry exhaust has its outlet on the roof, all the pip es inside the vehicle has to be insulated.
The exhaust pipes will be very hot and all accessible pipes and mufflers are dangerous to people when not insulated.
There are companies that are specialised in insulating hot pipes and fancy systems are available to make it good looking. However it is also possible to do it yourself by winding fibreglass or Rockwool around the pip es and seal it with aluminium tape.
2 THE STANDARD DRY EXHAUST SYSTEM
The standard exhaust system contains:
On the generator set:
An insulated exhaust bent
In the exhaust installation kit:
A stainless steel shielded flexible bellow.
One resonance muffler
One absorption muffler
Clamps and rubbers to mount the system flexible
Fittings, bents and pipes to make the different
connections
Blankets for thermal and sound insulation.
The mufflers are high quality industrial mufflers that are much more effective, robust and durable than mufflers made for automotive use.
3 INSTALLATION OF THE EXHAUST
Before determining the location of the generator set one has to consider how to get away with the exhaust. Often one can find space below the vehicle between the chassis to mount the mufflers. The outlet should blow the fumes away from the doors to avoid a nasty smell. When the gasses are in the flow of air blowing from the radiators this will help to avoid the fumes to be noticed. Under no condition the fumes should be sucked into the flo w of air into the radiators. In wind still conditions a light smell of exhaust fumes around the vehicle will not be avoidable. To bring the exhaust to the top of the vehicle gives the best results on noise and smell. However, when the pipes go through the vehicle they should be insulated and around the hole in the roof should be a col lar to prevent rainwater to leak in. Both mufflers could be on the roof or one of them or both could be below the vehicle. In general it is better to have the mufflers wide apart: the resonance muffler close to the generator and the absorption muffler on the end of the line. A short pipe (30cm) should be on the far end after the absorption muffler. The absorption muffler has no flow direction and could be mounted both ways. The resonance muffler should be mounted according to the indication on the muffler itself.
The resonance muffler should be fitted according to direction of the gas flow indicated.
In the kit are clamps to mount the exhaust pipes to stainless steel bars. These bars should be mounted to the chassis of the vehicle. It is recommend to use rubber mountings whenever possible. However take care that the heat conducted through the brackets will not affect the rubber. Refer to figure 24 how to mount the rubber in a safe way. When any doubt an extra safe guard could b e constructed from steel wire or chain.
Figure 24. Mounting bracket in rubber with safe guard
Page 18
INSTALLATION
18 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
2.5.4 Electrical installation (12 Volt)
1 DIGITAL DIESEL CONTROL SYSTEM
The electrical control system is standard in 12 Volt with negative earth. Non- earth return is available as an option.
All electrical wiring has been prepared on the generating set to the control panel prior to despatch from the factory. The engine is controlled by a very advanced microprocessor based system: Digital Diesel Control. The “black box” containing the microprocessor is located on top of the alternator. A local control panel is on the generating set.
Remote control
A remote control panel also containing a microprocessor is in the delivery. A 15 m intermediate 8-pole communic ation cable is in the standard supply as well (refer to figure 25). If necessary an optional longer (up to 30m / 100ft) intermediate cable can be connected if the standard lengt h does not suit the required distance. When a longer distance than 30m / 100ft is required, consult the Mastervolt service department for advice.
Figure 25 Remote control cable
One can mount the control panel after drilling a hole in the dashboard using the plastic cover. Refer to the dimensional drawings in chapter 4. The panel without the plastic cover fits the Mastervision modular panel system.
More remote control panels (slave panels) can b e put in parallel by using the modular connectors on the back of the units. As a slave one can use the same panel offering all functions again. It is also possible to use an old or new type slave panel only to start and stop the generator. Old type remote panels and system panels can be connected by means of the green connector.
Pay attention to the colour codes as indicated in figure 26 when fitting cable to the green connector. Some software versions in old system panels (supplied before Ma y 2004) could conflict with the software in the DDC and an update of the software of the system panel could be necessary. When this is the case consult to the Mastervolt service department for advice.
When using the factory settings, installation is very simple: just plug the remote cable into the remote and the generator is ready to use. Refer to figure 26.
WIRING C OLOURS
RED GREEN BROWN YELLOW PINK PURPLE BLUE WHITE
GREY/ PI NK GREY
RED/BLUE
BLACK
MAX. 150 m A
WARNING RELAY
REMOTE CABLE
REMOTE CABLE
2
1
5
4
3
8
7
6
11
10
9
12
SENSE BAT. 2
121110987654321
Whisper Re mote Panel
WRP/2
J3
Figure 26 Remote box terminals
Acoustic alarm or warning lamp
One can connect an external max.150 mA relay to generate an acoustic warning or applying a warning lamp etc. Be aware of polarity as some relays has a diode inside and should be connected plus to plus en minus to minus as indicated. Refer to figure 26.
Page 19
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 19
Connection for emergency stop / fire alarm switch
To connect an emergency stop button or to stop the generator automatically in case of a fire alarm, you can use the bypass connection between fastons J7 and J18 on the backside of the local control panel. See figure 27. To do so, remove this bypass connection and then replace it by an emergency switch or a potential free fire alarm switch with normally closed contacts
Fig. 27: Connection for emergency stop / fire alarm switch
Automatic starting and stopping
Automatic start/stop Mastervolt cannot be held responsible for damage caused by the unattended running generator using the auto-start/stop mode or interval mode.
Using the auto-start/stop (interval) mode the generator can start unexpectedly. When working on the electrical system, the 3 Amp fuse must be removed from the control panel and the battery plus cable must be removed from the battery.
In the delivery are warning stickers to stick on several parts of the electric installation (transfer switch, distribution box, etc.) to warn for automatic start)
The Mastervolt Digital Diesel Control system offers several options for automatic starting and stopping.
Access to this menu and other menus could be blocked. For de-blocking and setting up this options refer to the APPENDIX of the DDC user’s manual.
One of these options is to monitor a second battery (not being the starter battery) to start the generator automatically when the voltage of this battery drops belo w a certain setting. Other names for this second battery are “auxiliary battery”, “service battery”, ”users battery” or “consumers battery”. We will refer to this battery as “the second battery”(BAT2). In some menus the starter battery could be indicated as “the first battery” (BAT1). A sense wire to monitor the second battery should be connected (attention polarity!) to the connector on the back of the remote panel. Refer to fig. 29. The sense wires must be connected directly on the second battery before a main switch and be protected by a 3 Amps fuse. (Monitoring the generator starter battery does not require an extra sense connection)
Settings
When one want to apply other settings than the factory settings refer to the DDC users manual, especially to the APPENDIX.
2 STARTER BATTERY
For starting, the Whisper requires a 12V starter battery with the following capacity:
Model Minimum capacity
Whisper 6 60Ah Whisper 10 60Ah
The generating set can be connected with the main engine battery or have its own battery. We strongly recommend the use of a separate battery for the generating set and to keep the wiring system for the vehicle engine and the domestic DC supply system completely separate and individually connected to separate batteries.
230VAC
IVO 12/10
A
B
12V
+-
Figure 28: Starter battery
However, the negative of all the batteries on the vehicle should be interconnected to avoid difference in the voltage level of the earth on different places causing trouble to electronic devices which might be in the system. The above recommendation is not valid for vehicles having the starter battery of the vehicle engine or other auxiliary
Remove bypass between J7 - J18
Normal operation
Alarm / emergency
local control panel (rear view)
Page 20
INSTALLATION
20 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
equipment positive grounded. When this is the case an expert should be consulted. A battery switch may be used to interrupt the positive connection. The starter battery is charged by the alternator on the engine. An additional battery charger will help to keep the battery in good condition when the generating set is not used. A battery charger is not included in the standard supply. A high efficiency battery charging unit can be ordered from Mastervolt which is able to charge both the vehicles’s main battery and the starter battery. Also a small charger can be used to charge the starter battery only, such as the IVO SMART 12/10. A battery switch and a charger are included in the battery installation kits, art. no. 50230210 (70Ah) or 50230220 (160Ah)
3 12V OR 24V DC TO DRIVE THE FAN
When applying 12V or 24 V DC to drive the fan of the radiators the fan should be wired with minimum 4 mm2 cable according to the wiring diagram. The negativ e return wire should be of the same diameter. The return current should never be lead over the chassis. The consumption of power by the 12V DC powered fan makes it necessary to install an additional 30 Amps battery charger to prevent the starter battery to be drained. A much larger battery (170Ah at least) is required. The battery charging winding in the generating set is not capable of powering the fan. Neither is the small charger that is included in the battery kit. Mastervolt supplies high quality battery chargers that continuously supply the rated power. Chargers of other suppliers are often rated to other standards and give the rated current (Amps) only for a short period if at all. To avoid the need of an extra heavy battery charger a 230 Volt fan on the radiator is recommended. One should realize that the power for the fan must be decucted from the output power of the generating set.
4 OTHER RECOMMENDATIONS AND WARNINGS
The battery should be secured for poor road conditions and the terminals should be insulated. For extra safety the battery can be enclosed in a wooden, plastic, fiberglas etc. (non metal) box. Even when the earth return system is applied a negative battery cable should be use d and the vehicle should not to be used as a conductor. The battery cables are supplied in a standard length of 1.5 m, if longer cables are required a larger cross sectional area should be considered to compensate for voltage reduction.
When two batteries are used in series to provide a 24 Volt supply system, never take off 12 Volt (starting) power from one of these batteries. This will result in severe damage to both batteries within a short time.
Disconnect the battery leads if electrical welding is to be carried out, otherwise damage will be caused to the diodes of the alternator.
As explosive hydrogen gases may be discharged during charging, the battery should be located in a well ventilated room. Ensure that the supplied battery cable connectors are properly fitted and never remove during or shortly after charging as sparking can occur, which may ignite the hydrogen gasses.
Page 21
INSTALLATION
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 21
2.5.5 AC power system (230 Volt)
The electric power supplied by the generator is of a high voltage and dangerous to people. Before working (installation) on the system read the sections on safety in the users manual.
Realise hat people are not used to have 230V available on a vehicle. Put warning signs on wall sockets and on junction boxes. Instruct non-regular users of the vehicle. Warn maintenance personal of garages that do service on the vehicle.
Generators used on vehicles that are operated in a hazardous environment have often to fulfil special regulations and additional measures have to be taken accordingly.
Be sure that all electrical installations (including all safety systems) comply with all required regulations of the local authorities. All electrical safety/shutdown and circuit breaking systems have to be installed onboard as the generating set itself cannot be equipped with such equipment for every possible variation. The vehicle’s power supply system should be suitable and safe for the AC voltage which is applied and the power that will be generated. Special attention has to be paid on dividing the system in branches which are fused individually. It is absolutely essential that each and every circuit in the on-board electrical system is properly installed by a qualified electrician.
1 FUSE
An output fuse (between the generating set and the electrical installation) should be installed to protect the installed electrical system. The following maximum single phase output current applies:
Model Maximum single phase
output current
Whisper 6 25 Amps Whisper 10 40 Amps
The fuses must be of the slow reacting type. For electrical motors connected to the system, a motor protection switch must be installed
2 GROUNDING
The AC alternator windings are not grounded. The housing of the alternator and all other metal parts are grounded To make a connection between “neutral” and “ground” is necessary as part of a specific insulation failure protection system. It is possible that the electric installation in the vehicle must be protected against insulation failures. Methods of protection are subjected to rules that can be different depending on the use of the vehicle and local standards. In the standard marine manual is more information, but this is according CE regulations for boats. Vehicles are subject to different regulations depending on the application of the vehicle. Experts in this field should be consulted
3 CABLE
For the power cable we recommend the use of 3 wire single phase oil resistant cable with a sufficient cross sectional area. One wire for earth is included. For long cables it is recommended to apply cables with a larger cross section (refer to ISO 13297 annex A)
4 TRANSFER SWITCH
A power source selector switch much be installed bet ween the generating set and the vehicle’s electrical supply system. This switch must ensure that all AC consumers can be switched off at once. This switch should also be installed to keep the generating set and shore (grid) power systems separate. Transfer switches - to switch over from shore to vehicle or from generating set to inverter - should be well designed to switch over all wires including neutral (and not only phases or line) and there should be provisions with the aid of timers to prevent relays from clattering.
Mastervolt recommends the installation of a Mass Systemswitch as the power source selector. This works automatically when the generating set is not running the input remains in the shore position and as soon as the generating set is running the Mass Systemswitch switches automatically after 10 seconds delay time over to the generating set position.
In all situations the transfer switches between shore, inverter and generator should switch both neutral and L1. Of course this is the case when using a Mastervolt Mass Systemswitch.
Page 22
INSTALLATION SPECIFICATIONS
22 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
3 INSTALLATION SPECIFICATIONS
3.1 GENERAL
1 Make a hole for combustion air in the sound shield.
Mount an air inlet filter (if required)
2 Mount the generating set directly, without additional
vibration dampers, on a solid surface. 3 Mount the cooling system for the engine 4 Mount the cooling system for the alternator 5 Connect exhaust system. 6 Connect ‘fuel supply line’ to the water separator/ fuel
filter. 7 Connect ‘fuel return line’ to the fuel tank. 8 Connect remote panel (just plug in). 9 Connect the AC cable from the AC box to the power
source selector (or Mass Systemswitch). 10 Connect the positive and negative poles from the 12V
starter battery to the battery cables. 11 Connect the power supply of the radiators 12 Install a Mastervolt battery charger. (optional)
3.2 COMMISSION TABLE
1 Check if a hole for combustion air intake is in the
sound shield. Also check if an air inlet filter for
combustion air is necessary and has been installed 2 Check if the cooling system for the engine is properly
installed. Note that air traps must be avoided. 3 Check if the cooling system for the alternator is
properly installed. Note that air traps must be avoided. 4 Check if the exhaust system is properly installed.
Check maximum length of exhaust hose, diameter of
exhaust piping. 5 Check all coolant connections. 6 Check the AC cables and the grounding. 7 Check if an AC breaker is installe d before or after the
power source selector. When there is only a circuit
breaker, use it to disconnect the generating set from the grid.
8 Check all DC c onnections, check if the battery switch/
circuit breaker is closed.
9 Open the fuel valve. C heck if there are no air leaks in
the fuel supply line, and check if the lift of the fuel is less than 1 meter. Check if there is no air in the water
fuel separator. 10 Check if the air intake in the canopy is not blocked. 11 Check the oil level and colour of the oil. Check the
coolant level of both the alternator cooling and the
engine cooling 12 To bleed the fuel system: push the “Start” button on
the local control (not on the remote panel) and hold at
least 5 seconds and as long as necessary to bleed
the system. 13 Start the engine by pushing the start button 14 Check when t he generating set is running, the delay
of 5 to 10 seconds in the power source selector
transfer. 15 Check voltage and frequency under ‘no load’
conditions. 16 Check voltage and frequency under ‘full load’
conditions. 17 Check if the battery charger of the generating set is
working (max. 14.5 Volt). 18 Close the sound shield and check the noise level. 19 Stop the generating set and check th e engine again
for leakages of oil, fuel or coolant.
Installation checklist available on our website: www.mastervolt.com. Commissioning form available on our website: www.mastervolt.com..
Page 23
INSTALLATION SPECIFICATIONS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 23
3.3 TECHNICAL DATA
WHISPER 6 AND 10
Model Whisper 6 Whisper 10
Dimensions (l x w x h) 69.0 x 52.5 x 58.0 cm 80.5 x 52.5 x 58.0 cm Weight including sound shield 200 kg (440Lbs) 240kg (530Lbs) Max. operation angle 25° 25° Remote panel 15 m cable Digital Diesel Control System Battery capacity min. 12V / 60Ah 12V / 60Ah Fuel consumption 1-2.5 litre/hour, load dependent 1-4 litre/hour, load dependent Combustion air consumption 0.95 m3/min. 1.43 m3/min. Model fuel pump Electrical driven 12V Electrical driven 12V Max lift fuel pump 1m 1m Cooling Radiator cooling Radiator cooling Cooling pump Mastervolt self priming raw water impeller pump, PTO driven Model cooling pump M M Alternator synchronous brushless, maintenance free, water cooled Voltage regulation capacitor capacitor Output power at 50Hz, power factor cos phi = 1 5 kW* 9 kW* Battery charger (alternator including regulator): 40 Amps 40 Amps * Note that this value must be reduced by the power to drive the cooling fans of the radiators.
Page 24
INSTALLATION SPECIFICATIONS
24 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
3.4 INSTALLATION MATERIALS
BATTERY INSTALLATION KIT 70 Ah
no qty article no description dimensions 51 1 62000700 Mastervolt AGM Battery 12V/70Ah 70Ah 52 1 43011000 battery charger IVO SMART 12/10 53 1 68060100 battery terminal + M8 54 1 68060200 battery terminal – M8 55 1 68456902 isolation cap 56 1 68456914 isolation cap 57 1 79009005 battery switch 250 Amp 58 4 6503002508 cable connectors M8x25
TOTAL 50230210 BATTERY INSTALLATION KIT 70 Ah
FUEL KIT
no qty article no description dimensions 41 2 50221203 Straight coupling 8 mm 42 1 50230090 Fuel strainer/water separator M14x1.5 mm 43 2 50221618 Parallel male stud coupling M14 - 8 mm 44 2 50221644 Reducing male nipple M14-M16 60 gr. 45 2 50221615 Hose connection 8 mm 46 2 50221616 Nut coupling M16x1.5 mm 47 1 50221252 Nipple hose pipe 8 mm 48 4 50221522 Hose clamps 10-16 mm 49 2 50221632 Gasket ring 14x20x1.5 mm
TOTAL 50230205 FUEL KIT
OPTIONAL INSTALLATION MATERIALS
no qty article no description dimensions 50 1 50222020 copper fuel pipe 6x8 mm 51 1 50220063 fuel hose 8x16 mm
Page 25
INSTALLATION SPECIFICATIONS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 25
Included are all fittings to fit copper pipes 8 mm outer diameter or rubber fuel hoses 8 mm inner diameter, or both
Figure 29: Installation materials battery and fuel kit
Page 26
INSTALLATION SPECIFICATIONS
26 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
DRY EXHAUST KIT 1½”
no qty article no description 61 1 50220043 Exhaust hose SS 500mm fem./male 1½” 62 1 50220042 Insul. blanket 3 5x60 exhaust hose 1½’ 63 1 50230523 Absorbtion muffler steel 1½” 64 1 50230524 Ressonance muffler steel 1½” 65 1 50230525 Insul. blanket 8 0x75 muffler SDHC 1½” 66 2 50221403 Pipe nipple 1½”x300mm galvanised 67 2 50221423 Parallel male coupling 1½” galvanised 68 2 50221413 Straigt coupling f/f 1½” galvanised 69 3 50221663 U-clamp 48 mm M10 70 3 50221664 Bracket U-clamp 25cm M10/48mm passivated 71 6 50211406 Washer SP M10 72 6 50211447 Washer spring SP M10 73 6 50211466 Nut hexogonal SP M10 75 1 50221473 Elbow 90 degr m/f gavalvanised 1½”
TOTAL 50201875 DRY EXHAUST KIT 1½”
RADIATOR COOLING KIT ALTERNATOR 230VAC
no qty article no description 31 1 50230304 Radiator cooler AP 300/2 E 230VAC 32 2 50221103 Straight reducer m/f 1”-3/4” 33 1 50221063 Male nipple 3/4” 34 1 50221043 TEE fittings 3/4” 35 3 50221004 Male hose co nnection 3/4x20 38 1 50212405 Temperature switch 35-45 degr 39 4 50201121 Vibration mounting 30x25 40 4 50211152 Bolt he xagonal ZP M8x16 41 8 50211465 Nut hexogonal SP M8 42 8 50211405 Washer SP M8 43 8 50211445 Washer spring SP M8 44 8 50220011 Hose vac um SAE100 R4 (3/4”) 19x31,5mm 45 6 50221502 Hose clamp stainless19-29 46 8 50221599 Hose support 35x15 mm galvanised 47 1 50230529 Bracket expansion tank for 50230531 47 1 50230531 Expansion tank 20 mm 47 1 50230532 Cap tank 0502 30531
TOTAL 50201878 RADIATOR COOLING KIT ALTERNATOR 230VAC
RADIATOR COOLING KIT ALTERNATOR 12VDC Same as article no. 50201878, except:
no qty article no description 31 1 50230302 Radiator cooler AP 300/2 E 12VDC
TOTAL 50201872 Radiator cooling kit alternator 12VDC
RADIATOR COOLING KIT ALTERNATOR 24VDC Same as article no. 50201878, except:
no qty article no description 31 1 50230303 Radiator cooler AP 300/2 E 24VDC
TOTAL 50201868 Radiator cooling kit alternator 24VDC
Page 27
INSTALLATION SPECIFICATIONS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 27
Figure 30: radiator cooling kit engine, exhaust kit and radiator cooling kit alternator
Page 28
INSTALLATION SPECIFICATIONS
28 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
RADIATOR COOLING KIT ENGINE 230VAC no qtt article no description 1 1 50230304 Radiator cooler AP 300/2 E 230VAC 2 2 50221502 Hose clamp stainless19-29 3 1 50221064 “Male nipple 1” 4 1 50221044 “TEE fitting 1” 5 2 50221010 Male hose connection 1x25 6 1 50221103 “Straight reducer m/f 1”-3/4” 7 1 50221004 Male hose connection 3/4x20 8 1 50212409 Temperature switch 87-82 degr 9 4 50201121 Vibration mounting 30x25 10 4 50211152 Bolt he xagonal ZP M8x16 11 4 50211465 Nut hexogonal SP M8 12 8 50211405 Washer SP M8 13 8 50211445 Washer spring SP M8 14 6 50220012 “Hose vac um SAE100 R4 (1”) 25,4x38mm” 15 4 50221503 Hose clamp stainless 26-38 16 8 50221599 Hose support stainless 35x12 mm 17 1 50230529 Bracket expansion tank for 50230531 17 1 50230531 Expansion tank 20 mm 17 1 50230532 Cap tank 0502 30531 18 1.5 50220011 “Hose vacum SAE100R4 (3/4”) 19x31,5mm 21 1 50221532 Hose clamp stainless mini 9-11
TOTAL 50201879 Radiator cooling kit engine 230VAC
RADIATOR COOLING KIT ENGINE 12VDC Same as article no. 50201879, except:
no qtt article no description 31 1 50230302 Radiator cooler AP 300/2 E 12VDC
TOTAL 50201871 Radiator coolin g kit engine 12VDC
RADIATOR COOLING KIT ENGINE 12VDC Same as article no. 50201879, except:
no qtt article no description 31 1 50230303 Radiator cooler AP 300/2 E 24VDC
TOTAL 50201880 Radiator coolin g kit engine 24VDC
Page 29
DIAGRAMS & DRAWINGS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 29
4 DIAGRAMS & DRAWINGS
4.1 LAYOUT GENERATOR CONTROL WITH 230VAC FAN
Figure 31: Layout generator control for with 230VAC radiator fan
Optional control for two speeds fans.
See chapter 4.6
ALTERNATOR TEMP.
S
WIT
C
H
Page 30
DIAGRAMS & DRAWINGS
30 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
4.2 LAYOUT GENERATOR CONTROL WITH 12VDC FAN
Figure 32: Layout generator control with 12VDC radiator fan
ALTERNATOR TEMP.
SWITCH
Optional control for two speeds fans.
See chapter 4.7
Page 31
DIAGRAMS & DRAWINGS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 31
4.3 LAYOUT GENERATOR CONTROL WITH 24VDC FAN
Figure 33: Layout generator control with 24VDC radiator fan
ALTERNATOR TEMP.
SWITCH
Optional control for two speeds fans. See chapter 4.7
Page 32
DIAGRAMS & DRAWINGS
32 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
4.4 WIRING COLOURS
Cable code number colour cross section
battery > starter motor red 25 mm2 starter motor > DDC 1 red 6 mm2 starter motor > LCP 13 red 2,5 mm2 battery > ground black 25 mm2 ground > LCP ground (GND) 2 black 4 mm2 DDC > glow plugs 3 brown 4 mm2 DDC > starter solenoid 4 yellow 2,5 mm2 LCP > fuel lift pump + 5 brown 1,5 mm2 LCP > fuel lift pump - 15 black 1,5 mm2 DDC > LCD 5 grey 1,5 mm2 DDC > oil pressure switch 6 purple 1 mm2 LCP > oil pressure switch 6 purple/black 1 mm2 DDC > water temperature switch 7 blue 1 mm2 LCP >water temperature switch 7 blue/black 1 mm2 DDC > exhaust temperature switch 8 blue/green 1 mm2 LCP > exhaust temperature switch 8 blue/rose 1 mm2 DDC > fuel solenoid (hold) 9 green 1,5 mm2 DDC > fuel solenoid (pull) 20 pink 1,5 mm2 DDC > fuel solenoid (com.) 17 black 1,5 mm2 B+ terminal alternator > starter motor 21 red 6 mm2 DDC >R terminal alternator 18 wit 1,5 mm2 DDC > L terminal alternator 19 orange 1,5 mm2 DDC > current measuring transformer 11 black 1 mm2 DDC >current measuring transformer 11 red 1 mm2 DDC > LCP 12 black 1,5 mm2 DDC > LCP 14 red 1,5 mm2 DDC > LCP 16 red/green 1,5 mm2 DDC > generator AC output 33 brown 1 mm2 DDC > generator AC output 33 blue 1 mm2
Page 33
DIAGRAMS & DRAWINGS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 33
4.5 AC WIRING DIAGRAM 230V / 50HZ
Figure 34: AC wiring diagram
Page 34
DIAGRAMS & DRAWINGS
34 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
4.6 ELECTRICAL DIAGRAM RADIATOR FAN CONTROL 230VAC
TERMINAL BLOCK
GENERATOR CONTACT
PUMP (PCB)
THERMOSTAT GENERATOR
THERMOSTAT ENGINE
RADIATOR COOLER
GENERATOR
BATTERY
230VAC
ENGINE
RADIATOR COOLER
GENERATOR
12VDC
M
230VAC
M
230VAC
5A
16
CU1,5
+1-
2
CU0,75
80-70?C
CU0,75
45-35?C
CU0,75
6
-
35A45 87
CU1,5
230VAC
CU1.5
6,3A116,3A
12 1413 15
5A
CU1.5
DIMENTION BOX: 270x270x180 MM
JUNCTION BOX AIR FANS
12VDC K1 K2
230/115VAC 200VA
TRAFO
230VAC
Figure 36: Electrical diagram fan control using 230V AC radiator fans – with two speeds fans (optional)
FUSE 5A
FUSE 6.3A
FUSE 6.3A
FUSE 5A
FUSE 5A
15 16
5 6
7
8
13 14
11
1
4
2
3
K2
K1
K2
K1
BAT. +12V
PUMP
+12V
GENERATOR 230VAC (L1)
K1
BAT.
–12V
GENERATOR 230VAC (N)
230VAC
230VAC
45-35°C80-70°C
THERMOSTAT COOLER
ENGINE GENERATOR
RADIATOR COOLER
ENGINE
RADIATOR COOLER
GENERATOR
K2
12
A2A2
A1 A1
11
11
14
14
12
41
41
42
44
44
230V
120V
115V
110V
0
0
TRANSFORMER
230V/115VAC
200VA
400V
M M
GENERATOR
L1
N
MAIN CIRCUIT BREAKER
AC LOAD
CIRCUIT BREAKER
AIR FANS
6A
Figure 35: Electrical diagram for standard fan
control using 230V AC radiator fans
Page 35
DIAGRAMS & DRAWINGS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 35
4.7 ELECTRICAL DIAGRAM RADIATOR FAN CONTROL 12 / 24 VDC
PUMP (PCB)
GENERATOR CONTACT
THERMOSTAT ALTERNATOR
THERMOSTAT ENGINE
ALTERNATOR
RADIATOR COOLER
RADIATOR COOLER
ENGINE
BATTERY
TERMINAL BLOCK
M
M
M
M
CU0,75
80-70∞C
CU4
CU0,75
45-35∞C
CU0,75
+
4
+1-2-
356+7
CU2,5
CU2.5
-8+9-
10
JUCTION BOX AIR FANS
FUSE 20/40A
K3
21435768
K1
10
9
K2
DIMENIONS BOX: 160x160x90 MM
Figure 37: Electrical diagram fan control using 12V or 24V DC radiator fans (optional)
FUSE 20/40A
+ BAT.
THERMOSTAT COOLER
ENGINE GENERATOR
CONTROL PANEL
PUMP 2
1
1
9
4
3
2
6
7
5
8
10
K1
K2
K3
K1
K2
K3
45-35°C
80-70°C
M
M
2
1
2
3
4
5
5
3
1
2
5
3
RADIATOR COOLER
ENGINE GENERATOR
– BAT.
Page 36
DIAGRAMS & DRAWINGS
36 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
4.8 WIRING DIAGRAM ELECTRONIC GOVERNOR
Figure 38: Electronic governer.
In addition to the mechanical governor, the W hisper 6 and 10 are standard equipped with an electronic governor. A governor keeps the speed (RPM=Rotations Per Minute) of the engine at a fixed value. The RPM of the engine correlates with the frequency of the electrical output (1500 RPM =50 Hz) of the alternator. Under full load the RPM of the Whisper models that have only a mechanical governor can drop 75 RPM (=2.5 Hz) at full load and will go further down or collapse when further loaded. However the engines with the electronic governor will keep the RPM and frequency at the set value. As the voltage is related to the frequency, the voltage will be more stable as well. The RPM represents power and the alternator performs better as well on a higher speed. Whisper models with an electronic governor will bring more power. So the electronic governor offers three advantages: a more stable frequency and voltage and more power.
The electronic governor system contains two parts:
1 The actuator controls the eng ine speed. This actuator
replaces the standard hold solenoid that is on all other
mechanical controlled Whisper engines. The actuator
controls the RPM directly on the fuel rack inside the
fuel pump without levers and other mechanical
transmissions. 2 A microprocessor keeps the speed at the set value by
controlling the actuator. The microprocessor is
programmed at the Mastervolt factory and many
parameters are set to perform well. It should not be
necessary to make adjustments. When adjustments
are necessary this can only be done with the he lp of
an interface to a computer and special software to get
access to the microprocessor.
The Mastervolt electronic governor does not need a pickup device in the flywheel housing that counts the passing tooth of the flywheel and determines the exact RPM of the engine, because the processor uses the 50 Hz of the AC output voltage as a reference.
Page 37
DIAGRAMS & DRAWINGS
EN/ Whisper 6 / 10 - 3000RPM for mobile applications / August 2009 / Copyright © 2009 Mastervolt / Août 2009 37
4.9 REMOTE CONTROL PANEL DRAWINGS
Figure 39: Whisper remote panel
The remote panel comes in a carton that can be used as a template to drill the mounting hole
Page 38
DIAGRAMS & DRAWINGS
38 Copyright © 2009 Mastervolt / August 2009 / Whisper 6 / 10 - 3000RPM for mobile applications / EN
4.10 DIMENSIONS
Figure 40: Outer dimensions (mm) Whisper 6 and 10
CONNECTIONS WHISPER 6 WHISPER 10 BOX DIMENSIONS WHISPER WHISPER 6
• exhaust: 1 ½” 1 ½” • length 69.0 cm (26.0’)
• fuel hose: 5/16” (8 mm) 5/16” (8 mm) • width 52.5 cm (20.7’)
• radiator alternator: 3/4” (19 mm) 3/4” (19 mm) • height 58.0 cm (22.8’)
• radiator engine: 1” (25.4 mm) 1¼” (32 mm) • weight 200 kg (440 Lbs)
• battery +: AW G 2 (25 mm2) AWG 2 (25 mm2)
• battery -: AWG 2 (25 mm2) AWG 2 (25 mm2)
POWERCABLES ISO 13297 annex A BOX DIMENSIONS WHISPER WHISPER 10
• 3 x AWG 12 (4 mm2) (not included) • length 80.5 cm (31.7’)
• width 52.5 cm (20.7’) REMOTE CONTROL: • height 58.0 cm (22.8’)
• 15 meter (45 ft) 8 wire communication cable (included) • weight 240 kg (530 Lbs)