Mastervolt MPPT Solar ChargeMaster 25 Installation Manual

Page 1
MPPT Solar ChargeMaster 25
BATTERY SOLAR CHARGE REGULATOR
USER AND INSTALLATION MANUAL
Ga om deze handleiding in andere talen te downloaden naar onze website:
Um diese Anleitung in anderen Sprachen herunterzuladen, besuchen Sie bitte unsere Website:
Pour télécharger ce manuel dans d'autres langues, consultez notre site Web :
Para descargar este manual en otros idiomas, visite nuestro sitio web:
Per scaricare questo manuale in altre lingue, visitare la pagina del prodotto sul nostro sito Web:
www.mastervolt.com
NL
DE
FR
ES
IT
Page 2
2
MPPT Solar ChargeMaster 25 – User and Installation Manual

OVERVIEW

1. Power switch (Section 3.5)
2. Solar indicator LED (Section 3.6)
3. Charge indicator LED (Section 3.6)
4. Fault indicator LED (Section 3.6)
5. LCD-display (Section 3.6)
6. PV input
7. Battery connection
8. Load output
9. Grounding terminal
10. Temperature sensor jack
11. Identification label (Section 2.7)
Figure 1: Overview
Page 3
MPPT Solar ChargeMaster 25 – User and Installation Manual
3
TABLE OF CONTENTS:
1 IMPORTANT SAFETY INSTRUCTIONS ......................................................................................................................... 4
1.1 General .............................................................................................................................................................. 4
1.2 Explosive gases ................................................................................................................................................. 4
1.3 Warnings regarding the use of batteries ............................................................................................................. 4
1.4 Warning regarding life support applications ....................................................................................................... 4
2 GENERAL INFORMATION .............................................................................................................................................. 5
2.1 Use of this manual .............................................................................................................................................. 5
2.2 Liability ............................................................................................................................................................... 5
2.3 Warranty ............................................................................................................................................................. 5
2.4 Disclaimer........................................................................................................................................................... 5
2.5 Correct disposal of this product .......................................................................................................................... 5
2.6 Use of pictograms .............................................................................................................................................. 5
2.7 Identification label ............................................................................................................................................... 5
3 OPERATION .................................................................................................................................................................... 6
3.1 General .............................................................................................................................................................. 6
3.2 Maintenance ....................................................................................................................................................... 6
3.3 Three Step charge algorithm .............................................................................................................................. 6
3.4 Overview ............................................................................................................................................................ 7
3.5 POWER switch ................................................................................................................................................... 7
3.6 LEDs and LCD display ....................................................................................................................................... 8
4 INSTALLATION ................................................................................................ ............................................................... 9
4.1 Unpacking .......................................................................................................................................................... 9
4.2 Environment ....................................................................................................................................................... 9
4.3 Wiring and fuses ................................................................................................................................................. 9
4.4 Specifications of the PV array ............................................................................................................................ 9
4.5 Connection of loads .......................................................................................................................................... 10
4.6 Things you need ............................................................................................................................................... 12
4.7 Connection ....................................................................................................................................................... 12
4.8 Commissioning after installation ....................................................................................................................... 14
4.9 Use in combination with Mastervolt MLI battery ............................................................................................... 15
4.10 Software version ............................................................................................................................................... 16
4.11 Decommissioning ............................................................................................................................................. 16
4.12 Storage and transportation ............................................................................................................................... 16
4.13 Re-installation ................................................................................................................................................... 16
5 TROUBLE SHOOTING .................................................................................................................................................. 17
6 TECHNICAL DATA ........................................................................................................................................................ 18
6.1 Specifications ................................................................................................................................................... 18
6.2 Dimensions....................................................................................................................................................... 19
Page 4
4
MPPT Solar ChargeMaster 25 – User and Installation Manual

1 IMPORTANT SAFETY INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS
WARNING!
Read the entire manual before using the Solar ChargeMaster. Keep this manual in a secure place. This chapter describes important safety and operating instructions for use of a Solar ChargeMaster.

1.1 GENERAL

1 Before using the Solar ChargeMaster (SCM), read all
instructions and cautionary markings on the SCM and the batteries.
2 To reduce the risk of electric shock – Do not expose the SCM
to rain, snow, spray, moisture, excessive pollution and condensing circumstances. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the SCM in a non-ventilated room, as overheating may result.
3 Use of an attachment or spare part not recommended or
sold by Mastervolt may result in a risk of fire, electric shock, or injury to persons.
4 The SCM is designed to be permanently connected to a PV
array and DC electrical system. Installation of, and work on the SCM, may be carried out only by a qualified and trained personnel, consistent with the locally applicable standards and regulations.
5 Make sure that all wiring is properly installed and in good
electrical condition; and that wire sizes are large enough for the ampere ratings of the SCM. Check the wiring on a regular base, at least once a year. Do not use the SCM when the wiring is undersized or damaged.
6 Do not operate the SCM if it has received a sharp blow, been
dropped, or otherwise damaged in any way; take it to a qualified serviceman.
7 Except for the connection compartment, the SCM may not
be opened or disassembled. There are no serviceable parts inside the cabinet. Take it to a qualified, authorized and trained serviceman when service or repair is required. Incorrect reassembly may result in a risk of electric shock or fire.
8 Two primary energy sources are present: a PV array and
batteries. To reduce risk of electric shock, disconnect the SCM from both energy sources before attempting any maintenance or cleaning. Turning off controls will not reduce this risk.
9 This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
10 When the PV array is exposed to light, it supplies a DC
voltage to the SCM which can be dangerous to touch. For this reason, use of an external DC-switch is strongly recommended. Alternatively, before attempting any maintenance or cleaning the PV-array should be protected from light exposure, e.g. by covering the PV modules.
11 The SCM is provided with a grounding terminal. Grounding
and all other wiring must comply with local codes and ordinances.
12 Short circuiting or reversing polarity will lead to serious
damage to batteries, SCM, wiring as well as accessories. Fuses cannot prevent damage caused by reversed polarity and the warranty will be void.
13 In case of fire, you must use the fire extinguisher which is
appropriate for electrical equipment.
14 If applied in a marine application in the United States,
external connections to the SCM shall comply with the United States Coast Guard Electrical Regulations (33CFR183, Sub part I).

1.2 EXPLOSIVE GASES

1 TO REDUCE RISK OF BATTERY EXPLOSION, FOLLOW THESE
INSTRUCTIONS AND THOSE PUBLISHED BY BATTERY MANUFACTURER AND MANUFACTURER OF ANY EQUIPMENT YOU INTEND TO USE IN VICINITY OF THE BATTERY. REVIEW CAUTIONARY MARKING ON THESE PRODUCTS.
2 DANGER: To reduce the risk of explosion – Never use the
SCM in situations where there is danger of gas or dust explosion or in areas in which ignition-protected equipment is required.

1.3 WARNINGS REGARDING THE USE OF BATTERIES

1 Consider having someone close enough by to come to your
aid when you work near a lead-acid battery.
2 Have plenty of fresh water and soap nearby in case battery
acid contacts skin, clothing, or eyes.
3 Wear complete eye protection and clothing protection. Avoid
touching eyes while working near battery.
4 If battery acid contacts skin or clothing, wash immediately
with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 10 minutes and get medical attention immediately.
5 NEVER smoke or allow a spark or flame in vicinity of battery
or engine.
6 Be extra cautious to reduce risk of dropping a metal tool onto
battery. It might spark or short-circuit battery or other electrical part that may cause explosion.
7 Do not wear watches, bracelets, necklaces or other metal
objects when working on batteries.
8 Only use SCM for charging a LEAD-ACID or Mastervolt MLI
batteries and the supply of users attached to these batteries, in permanent systems. Do not use SCM for charging dry-cell batteries that are commonly used with home appliances.
9 NEVER charge a frozen battery. 10 Excessive battery discharge and/or high charging voltages
can cause serious damage to batteries. Do not exceed the recommended limits of discharge level of your batteries.
11 If it is necessary to remove a battery, always remove
grounded terminal from battery first. Make sure all accessories are off, so as not to cause an arc.
12 Be sure that the area around battery is well ventilated while
battery is being charged. Refer to the recommendations of the battery manufacturer.
13 Batteries are heavy and may become a projectile if involved
in an accident! Ensure adequate and secure mounting and always use suitable handling equipment for transportation.

1.4 WARNING REGARDING LIFE SUPPORT APPLICATIONS

Mastervolt products are not designed to be used as component of medical equipment, unless negotiated in the form of a written agreement between customer and/or manufacturer and Mastervolt. Such agreement will require the equipment manufacturer either to contract additional reliability testing of the Mastervolt parts and/or to commit to undertake such testing as a part of the manufacturing process. Furthermore, the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arising from the use of the Mastervolt parts in the life support equipment.
Page 5

2 GENERAL INFORMATION

2.1 USE OF THIS MANUAL

This manual serves as a guideline for the safe and effective operation, maintenance and possible correction of minor malfunctions of the Solar ChargeMaster 25. This manual is only valid for the following model:
Part number
Model
131902500
MPPT Solar ChargeMaster 25
This model is further referred to as Solar ChargeMaster. All the specifications, provisions and instructions contained in this manual apply solely to standard versions of the Solar ChargeMaster delivered by Mastervolt.

2.2 LIABILITY

Mastervolt can accept no liability for:
Consequential damage resulting from the use of the Solar ChargeMaster.
Possible errors in the included manual and the consequences of these.
Use that is inconsistent with the purpose of the product.

2.3 WARRANTY

The Mastervolt product warranty covers the Solar ChargeMaster for the first two years after the purchase date, on the condition that the product is installed and used according to the instructions in this manual.
Installation or use that do not comply with these instructions may result in under performance, damage or failure of the product and may void this warranty. The warranty is limited to the cost of repair and/or replacement of the product. Costs of labor or shipping are not covered by this warranty.

2.4 DISCLAIMER

Our products are subject to continual development and improvement. Therefore, additions or modifications to the products may cause changes to the technical data and functional specifications. No rights can be derived from this document. Please consult our most current Terms & Conditions of Sale.

2.5 CORRECT DISPOSAL OF THIS PRODUCT

This product is designed and manufactured with high quality materials and components, which can be recycled and reused. Dispose of according to WEEE.
Act according to your local rules and do not dispose of your old products with your normal household waste. The correct disposal of your old product will help prevent potential
negative consequences to the environment and human health.

2.6 USE OF PICTOGRAMS

Safety instructions and warnings are marked in this manual and on the product by the following pictograms:
CAUTION!
Special information, commands and prohibitions in order to prevent damage.
WARNING
A WARNING refers to possible injury to the user or installer or significant material damage to the Solar ChargeMaster if the installer / user does not (carefully) follow the stated procedures.
Read this manual before installation and use.
This product has been declared conform the EC directives and standards.
Degree of protection: IP23. The product is protected against touch by fingers and water spray < 60 degrees from vertical.

2.7 IDENTIFICATION LABEL

Figure 2: Identification label The identification label is located at the right-hand side of
the Solar ChargeMaster (see Figure 1). Important technical information required for service, maintenance & secondary delivery of parts can be derived from the identification label.
CAUTION!
Never remove the identification label. This will void the warranty.
Serial number
EO20A0678
Device version “A”
Part number
Page 6
6
MPPT Solar ChargeMaster 25 – User and Installation Manual

3 OPERATION

3.1 GENERAL

The Mastervolt Solar ChargeMaster is a fully automatic battery charger which converts power from photovoltaic (PV) array to a regulated battery voltage. The PV array connected to the Solar ChargeMaster is operated at its optimum voltage to obtain an optimal yield (Maximum Power Point tracking). The Solar ChargeMaster will automatically adjust itself to a 12V or a 24V system. Under normal circumstances the Solar ChargeMaster remains switched on with the PV-array and batteries connected.
When power from the PV array is enough, the Solar ChargeMaster will initiate the charging process.
WARNING
The Solar ChargeMaster has no on/off switch. Charging will be initiated as soon as power from the PV-array becomes available.
The Solar ChargeMaster is protected against overload, short circuit, overheating and under and over voltage.
CAUTION!
The Solar ChargeMaster is not protected against:
Excessive overvoltage on the Solar input;
Surges inducted by lightning.

3.2 MAINTENANCE

No specific maintenance to the Solar ChargeMaster is required. Examine your electrical installation on a regular base, at least once a year. Defects such as loose connections, damaged wiring etc. must be corrected immediately. If necessary, use a soft clean cloth to clean the casing of the Solar ChargeMaster. Do not use any liquids or corrosive substances, such as solvents, alcohol, petrol or abrasive components.
In the event of decommissioning, refer to section 4.11

3.3 THREE STEP CHARGE ALGORITHM

See Figure 3. Battery charging is accomplished in three automatic stages: BULK, ABSORPTION and FLOAT.
Figure 3: Three step charge system
BULK: At this stage the charger delivers its maximum current for quick charging from 0 to 80%.
ABSORPTION: The charger has reached its maximum charge voltage and the charge current will slowly decrease until the battery is charged up to 100%.
FLOAT: This stage begins once the battery is fully charged. The battery remains in fully charged state.
By installing the battery temperature sensor, the charge voltages are automatically adapted for deviating temperatures.
Figure 4: Temperature compensated charging See Figure 4. When the battery temperature is low, the
charge voltage increases. On the other hand, when the battery temperature is high, the charge voltage is decreased. Overcharge and gassing are prevented this way. This will extend the life of your batteries.
Page 7
MPPT Solar ChargeMaster 25 – User and Installation Manual
7

3.4 OVERVIEW

Figure 5: Operation of the Solar ChargeMaster

3.5 POWER SWITCH

POWER switch operation
Meaning
Press shortly
Activate LCD-display (see text below)
1 second
Switch on Solar ChargeMaster again after a fault or error situation
1 second
Mute audible alarm
>5 seconds
Battery type setting, see section 4.8.2
INPUT
Actual input power from PV-array (Watts)
BATTERY TYPE
Battery type setting;
see section 4.8.2
ERROR
An error code is displayed in case of a fault condition
CHARGING CURRENT
Actual output current of the Battery Output (Amps)
LOAD
Actual load connected to the Load Output (Watt)
OVERLOAD
Highlighted or blinking in case of overload
POWER switch
See section 3.5
BATTERY VOLTAGE
Actual battery voltage (Volts)
BATTERY CAPACITY
Estimation of the battery state of charge;
WIRING FAULT
Highlighted in case of error in the wiring;
Fault indicator LED
A fault condition is detected; see section 3.6
Charge indicator LED
The batteries are being charged; see section 3.6
Solar indicator LED
PV Power is available; see section 3.6
LCD Display
See section 3.6
Page 8
8
MPPT Solar ChargeMaster 25 – User and Installation Manual

3.6 LEDS AND LCD DISPLAY

LED indication
LCD indication
Audible alarm*
Meaning
Blue
Green
(Off)
--
(Off)
Normal operation, batteries are being charged.
(Off)
(Off)
(Off)
(Off)
(Off)
Irradiation on the PV modules is insufficient (for instance during night time). The Solar ChargeMaster is in sleep mode to reduce power drain from the batteries. The display can be activated temporally by pressing the POWER switch shortly. The display will be deactivated automatically after 1 minute.
(Off)
(Off)
(Off)
(Off)
(Off)
No power from the PV-modules. Check wiring to PV­modules if the Solar ChargeMaster is switched off during daytime. Check for loose connections or incorrect polarity.
(Off)
(Off)
Yellow
--
(Off)
Reversed polarity on the PV-input. Check PV array wiring.
(Off)
(Off)
Red
--
(Off)
Reversed polarity on the Battery connection. Check battery wiring.
(Off)
(Off)
Orange
--
(Off)
Reversed polarity on the PV-input and Battery connection. Check wiring.
--
--
--
OVERLOAD
blinking
Every 2 seconds
Overload on Load output (110%). Reduce connected load.
--
--
--
blinking
Every second
Low battery voltage. Reduce load connected to the batteries and charge batteries.
--
--
--
F0
Continuously
Power from PV-modules is OK, but battery voltage too low (< 8.5V @ 12V / <17V @ 24V). Check batteries.
--
--
--
F1
Continuously
Overcharge, battery voltage is too high. The charger will automatically cut off output. Check batteries.
--
--
--
F2 +
OVERLOAD
Continuously
Overload on Load output (130%). The charger will automatically cut off the output. Reduce connected load.
--
--
--
E1 +
ERROR
Continuously
Voltage from PV-modules is too high. Check PV-array.
--
--
--
E2 +
ERROR
(Off)
MLI Ultra battery only: Stop charge event generated. Refer to user’s manual of the MLI Ultra battery.
--
--
--
E3 +
ERROR
Continuously
Battery temperature too high. Check batteries.
--
--
--
E4 +
ERROR
Continuously
Battery temperature too low. Check batteries.
* The audible alarm can be muted by holding the POWER switch pressed for 1 second. ** Refer to section 4.8.2 for battery type settings.
Page 9
MPPT Solar ChargeMaster 25 – User and Installation Manual
9

4 INSTALLATION

During installation, commissioning and maintenance of the Solar ChargeMaster, the Important Safety Instructions are applicable at all times.

4.1 UNPACKING

The delivery includes the following items:
Solar ChargeMaster;
Battery temperature sensor;
Modular cable assembly (see section 4.9);
This User’s manual
Important Safety Instructions
After unpacking, check the contents for possible damage. Do not use the product if it is damaged. If in doubt, contact your supplier.

4.2 ENVIRONMENT

Obey the following stipulations during installation:
The Solar ChargeMaster is designed for indoor use only.
Ambient operating temperature: -20°C ... 55°C / -4°F 131°F (power de-rating above 40°C / 104°F to decrease the internal temperature).
Humidity: 5-95%, non-condensing.
The Solar ChargeMaster must be mounted to a vertical,
solid and heat-resistant surface, with the connecting cables downwards.
Do not expose the Solar ChargeMaster to excessive dust, aggressive environments, ammonia or salt.
Make sure that the hot air that is developed during operation can be discharged. The Solar ChargeMaster must be mounted in such a way that obstruction of the airflow along the heatsink on the backside of the casing will be prevented.
The Solar ChargeMaster requires a minimum of 20 cm/8" of clearance on every side to ensure safety and proper ventilation.
Do not locate the Solar ChargeMaster in the same compartment as the batteries.
Do not install the Solar ChargeMaster straight above the batteries because of possible corrosive Sulphur fumes.
Although the Solar ChargeMaster fully complies with all applicable EMC limits, it may still cause harmful interference to radio communication equipment. If such interference appears, it is recommended to increase the separation between the Solar ChargeMaster and the equipment, to relocate the receiving antenna or to connect the equipment to a circuit different from that to which the Solar ChargeMaster is connected.

4.3 WIRING AND FUSES

WARNING
The wire and fuse sizes stated in this manual are given as guideline only. Always comply with all local rules and regulations.
Keep in mind that high current will pass through the DC wiring. Keep the cable length as short as possible, this will keep the system efficiency as high as possible. The recommended minimum cross sections of the wiring are:
Connection Minimum DC Cable cross section
<2m / 6ft length
2 - 4m / 6 - 12ft
PV input
6mm² / AWG10
10mm² / AWG8
Battery
6mm² / AWG10
10mm² / AWG8
Load
6mm² / AWG10
10mm² / AWG8
Use boot lace ferrules on the wire ends. These ferrules must be crimped with a proper crimping tool. Use the following wire colors for DC wiring:
Wire color
Meaning
Connect to:
Red
Positive
+ (POS)
Black
Negative
– (NEG)
Lay the positive and negative cables next to each other to limit the electromagnetic field around the cables. The negative battery cable should be connected directly to the negative post of the battery bank or the ground side of a current shunt. Do not use the chassis frame as the negative conductor. Tighten securely. The positive battery cable must be fused and connected to the positive post of the battery bank.
The recommended DC fuses are:
Connection
DC fuse
Battery fuse
40A
Load fuse
40A

4.4 SPECIFICATIONS OF THE PV ARRAY

WARNING
When the PV array is exposed to light, it supplies a DC voltage to the Solar ChargeMaster which can be dangerous to touch. For this reason, use of an external DC­switch is strongly recommended. Alternatively, before attempting any maintenance or cleaning the PV-array should be protected from light exposure, e.g. by covering the PV modules.
CAUTION!
Do not connect Solar ChargeMasters in parallel on the side of the PV array.
Page 10
10
MPPT Solar ChargeMaster 25 – User and Installation Manual
The Solar ChargeMaster can be used with any PV array configuration that satisfies the following requirements:
Maximum open circuit PV voltage: 75 V DC;
The open circuit voltage from the PV array must be
5Volts higher than the battery voltage.
CAUTION!
Never connect voltages higher than specified to the PV-input, as this will cause permanent damage to the Solar ChargeMaster.
Configuration examples for PV-arrays consisting of monocrystalline or polycrystalline PV-modules:
Battery voltage U
NOM
= 12V
Panel type Number of panels
in series
parallel
36 cells
1 up to 3
Max. 360Wp
60 cells
1
Max. 360Wp
72 cells
1
Max. 360Wp
Battery voltage U
NOM
= 24V
Panel type Number of panels
in series
parallel
36 cells
2 up to 3
Max. 720Wp
60 cells
1
Max. 720Wp
72 cells
1
Max. 720Wp
Note: The Solar ChargeMaster will automatically limit the
input current and power to its specified rating (see section 6.1). Excess power will not be converted.

4.5 CONNECTION OF LOADS

Depending on the energy system in which the Solar ChargeMaster is used, there are two options to connect the electrical load to the Solar ChargeMaster:
To the Load output on the Solar ChargeMaster, or
Directly to the battery.

4.5.1 Load connected to the Load output

See Figure 6 for a typical installation diagram. The Load
output is provided with a protection circuit that switches off
the connected load automatically in case of overload or if the battery voltage is too low. This kind of installation is typically used when the PV-modules are the only source of electrical power to charge the battery. Characteristics:
Maximum DC-load: 25A
Under voltage disconnect: 10.5V
Under voltage reconnect: 11.0V

4.5.2 Load connected to the battery

If the maximum load will exceed 25 Amps or if the battery will also be charged by other energy sources, such as a battery charger or an alternator, the electrical load shall be connected to the battery directly. See Figure 7 for a typical installation diagram. In this situation the battery is no longer protected against too low battery voltages. Installation of additional undervoltage protection circuits may be necessary.
Figure 6: Load connected to the Load output on the Solar ChargeMaster
Battery temperature sensor
BATTERY
Load
Battery fuse
Load fuse
PV-array
External DC-switch
(see section 3.4)
Page 11
MPPT Solar ChargeMaster 25 – User and Installation Manual
11
Figure 7: Load connected directly to the battery
Above schematics are to illustrate the general placement of the Solar ChargeMaster in a circuit. They are not meant to provide detailed wiring instructions for any particular electrical installation.
Battery temperature sensor
BATTERY
Load
Battery fuse
Load fuse
PV-array
External DC-switch
(see section 3.4)
Page 12
12
MPPT Solar ChargeMaster 25 – User and Installation Manual

4.6 THINGS YOU NEED

Make sure you have all the parts you need to install the Solar ChargeMaster:
Solar ChargeMaster (included);
Battery temperature sensor with cable and plug
(included);
DC cables to connect the Solar ChargeMaster; see section 4.3 for specifications;
DC-fuse holder with a DC-fuse, to be integrated in the positive DC-cable to the battery; see section 4.3.
Screws / bolts (Ø 4mm max.) (with plugs) to mount the Solar ChargeMaster to a surface;
Batteries;
Appropriate and reliable cable terminals, strain reliefs,
battery terminals and boot lace ferrules.
We recommend as a minimum tool kit:
Phillips screw driver nr.2 or flat blade screw driver 5 mm to fix the DC-cables;
Tools to fix the screws / bolts with plugs to mount the Solar ChargeMaster to a surface.

4.7 CONNECTION

4.7.1 General

WARNING
Let installation work be done by a licensed electrician. All electrical systems must be disconnected from any power source during the entire installation!
CAUTION!
Short circuiting or reversing DC polarity may lead to damage to the Solar ChargeMaster, the cabling and/or the terminal connections.
Follow all steps of the installation instructions in order of succession as described.
CAUTION!
Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore, tighten all connections well, in order to limit transition resistance as far as possible. Use cables of the correct size. Use additional strain reliefs to prevent the transmission of stress to the screw connectors.
CAUTION!
The negative connections of the Solar ChargeMaster are common and therefore have the same electrical potential. If grounding is required, always do this on the negative wires. Use one grounding point only.
Note: If the battery temperature remains within 15-25°C,
connection of the battery temperature sensor is optional.
Page 13
MPPT Solar ChargeMaster 25 – User and Installation Manual
13

4.7.2 Installation step by step

1
Mark the position of the four mounting spots.
Then fix the casing to the wall.
Figure 8
2
Fit boot lace ferrules to all DC-cables.
Connect the wiring of the Load-output (see section 4.5). Integrate a fuse holder in the positive load wire, but do not place the fuse yet.
Figure 9
3
Connect the wiring to the battery.
Integrate a fuse holder in the positive battery wire, but do not place the fuse yet.
Figure 10
4
Attach the battery temperature sensor to the
casing the battery. Plug the temperature sensor cable into the Temperature sensor jack.
Figure 11
5
Connect the PV array
WARNING
Risk of shock! When the PV array is exposed to light, it supplies a dangerous DC voltage. See section 4.4.
Figure 12
6
If grounding is required, connect the
grounding terminal to the central grounding point of the electrical installation; see Figure 1, item 10. See also section 4.7.1
Check all wiring: positive to +, negative to –.
See also Figures 6 and 7 for wiring examples. If OK, continue with section 4.8 for commissioning of the Solar ChargeMaster.
7
Page 14
14
MPPT Solar ChargeMaster 25 – User and Installation Manual

4.8 COMMISSIONING AFTER INSTALLATION

4.8.1 Commissioning step-by-step

CAUTION!
Check the polarity of all wiring before commissioning: positive connected to positive (red cables), negative connected to negative (black cables).
1 If all wiring is OK, place the DC-fuse between the Solar
ChargeMaster and the load.
2 Then place the DC-fuse between the Solar
ChargeMaster and the battery.
WARNING
When placing this fuse, a spark can occur, caused by the capacitors used in the Solar ChargeMaster. This is particularly dangerous in places with insufficient ventilation, due to the gassing of the batteries an explosion can occur. Avoid having flammable materials close by.
3 The Solar ChargeMaster will initiate the charging
process if the voltage from the PV array is 5VDC higher than the battery voltage; see chapter 3.
Note: If the Solar ChargeMaster does not switch on, press
the POWER switch for 1 second.

4.8.2 Battery type setting

The Solar ChargeMaster is suitable for charging the following battery types: Flooded lead acid, AGM, Spiral, Gel, Traction batteries and Mastervolt Li-Ion batteries (MLI).
WARNING
The MLI charging voltages on this charger fit the Mastervolt Li-ion (MLI) batteries but do not necessarily fit other Li-ion batteries! See also section 4.9. Always follow the instructions provided by the battery manufacturer!
CAUTION!
Invalid settings of the Solar ChargeMaster can cause serious damage to your batteries and/or the connected load! Adjustments of settings may be undertaken by authorised personnel only.
Note: If your Solar ChargeMaster is not new, you must
consider that former users may have changed the settings.
The actual setting for Battery type is shown on the display during normal operation mode. See Figure 13.
Indication
Battery type
01
Flooded
02
AGM
03
Gel
04
Traction
05
Mastervolt MLI (see section 4.9)
Figure 13: Battery type setting To change the Battery type setting:
Hold the POWER button (Figure 1) pressed until the Battery type indication starts blinking;
Press the POWER button shortly to scroll through the Battery type settings as described above;
Hold the POWER button pressed until the Battery type indication stops blinking to confirm the desired setting.
When the POWER button is not touched for 10 seconds, the Solar ChargeMaster will return to the normal operation mode without changing a setting.
Page 15
MPPT Solar ChargeMaster 25 – User and Installation Manual
15

4.9 USE IN COMBINATION WITH MASTERVOLT MLI BATTERY

If the Solar ChargeMaster is used in combination with a Mastervolt MLI Ultra type Li-ion battery, charging is stopped if the MLI Ultra battery generates the Stop charge event.
Additional things you need:
MasterBus Multipurpose Contact Output;
Modular cable assembly (included in the delivery of the
Solar ChargeMaster).
Follow next additional steps to install the Solar ChargeMaster in combination with a Mastervolt MLI type Li­ion battery (see Figure 14):
1 Do not use the battery temperature sensor. Instead
plug the loose provided modular cable assembly into the Temperature sensor jack;
2 Connect the other side of this cable assembly to the
Multipurpose Contact Output as indicated;
3 Connect the DC main wiring and other components as
indicated;
4 Connect the MasterBus cabling between the devices
as indicated;
5 Add a MasterBus control panel to the MasterBus
network;
6 Configure the following Stop Charge event at the Li-ion
battery:
Configuration
Event 1 (obligatory)
Event source
Stop Charge
Event target
INT DC Relay
Event command
Activate
Event data
Copy
7 Adjust setting for Battery type to Mastervolt MLI (see
section 4.8.2);
8 Continue with the “Commissioning” section in the
manual of the MLI Ultra battery.
Li-ion battery
Loads
Battery fuse in positive battery line
DC positive cable
Safety relay
DC negative cable
MasterBus Multipurpose Contact Output via modular cable assembly
connected to the Solar ChargeMaster
MasterBus cable
MasterBus terminator
Figure 14: Use of the Solar ChargeMaster in combination with a Mastervolt MLI Ultra battery
Page 16
16
MPPT Solar ChargeMaster 25 – User and Installation Manual

4.10 SOFTWARE VERSION

To check the version of the installed software:
Hold the POWER button (Figure 1) pressed until the
Battery type indication starts blinking;
The version of the installed software is shown at the
right upper side of the display (Figure 15);
After 10 seconds the Solar ChargeMaster returns to the
normal operation mode.
Battery type (blinking)
Software version
Figure 15: Software version

4.11 DECOMMISSIONING

To put the Solar ChargeMaster out of operation, follow these instructions in order of succession:
1 Switch off all loads that are connected to the Solar
ChargeMaster;
2 Disconnect the PV array by switching off the switch
between the PV-array and the Solar ChargeMaster (or protect the PV-array from light exposure, e.g. by covering the PV modules);
3 Remove the DC-fuse between the Solar ChargeMaster
and the battery;
4 Remove the DC-fuse between the Solar ChargeMaster
and the load;
5 Check with a suitable voltage meter whether the
Battery connection and the LOAD output of the Solar ChargeMaster are voltage free;
6 Disconnect the negative cable to the PV array from the
terminal block of the Solar ChargeMaster. Isolate the
core of the wire with insulating tape; 7 Do the same for the positive cable to the PV array; 8 Disconnect all other remaining wiring.
Now the Solar ChargeMaster can be demounted in a safe way.

4.12 STORAGE AND TRANSPORTATION

When not installed, store the Solar ChargeMaster in the original packing, in a dry and dust free environment. Always use the original packing for transportation. Contact your local Mastervolt Service Centre for further details if you want to return the apparatus for repair.

4.13 RE-INSTALLATION

To reinstall the Solar ChargeMaster, follow the instructions as described in this chapter (chapter 4).
Page 17
MPPT Solar ChargeMaster 25 – User and Installation Manual
17

5 TROUBLE SHOOTING

If you cannot solve a problem with the aid of this chapter, contact your local Mastervolt Service Centre. See www.mastervolt.com/technical-support. Make sure you have the following information present if you must contact your local Mastervolt Service Center to solve a problem:
Article and serial number; see section 2.7.
Software version; see section 4.10.
Malfunction
Possible cause
What to do
No output voltage and/or current
Solar ChargeMaster was switched off due to a previous fault situation
Press POWER-button for one second to switch on the Solar ChargeMaster again
Check section 3.6 for an overview of fault indications of the LEDs and the LCD display
Display shows
OVERLOAD or error
code E1, E2, E3, E4, F0, F1 or F2
Check section 3.6 for an overview of fault indications of the LEDs and the LCD display Fault indicator LED
illuminated
Check section 3.6 for an overview of fault indications of the LEDs and the LCD display
Audible alarm active
Press POWER switch for 1 second to mute the alarm. Check section 3.6 for an overview of fault indications of the LEDs and the LCD display
No display
The Solar ChargeMaster is in sleep mode
Press the POWER switch shortly to activate the display
Output voltage too low, charger supplies maximum current
Load that is connected to the batteries is larger than charger can supply.
Reduce load taken from the batteries.
Batteries not 100% charged
Measure battery voltage. After some time, this will be higher.
Wrong battery type setting
Check settings (see section 4.8.2).
Charge current too low
Batteries almost fully charged
Nothing, this is normal when the battery is almost fully charged.
High ambient temperature
Nothing; if ambient temperature is above 40°C / 104°F the charge current is automatically reduced.
Low irradiation on the PV-array.
Check PV-array, check for shading.
Battery not fully charged
Current to load is too high
Reduce load taken from the batteries.
Charge time too short
Use an additional battery charger
Battery temperature too low
Use the battery temperature sensor.
Defective or worn-out battery
Check battery and replace if necessary.
Wrong battery type setting
Check settings (see section 4.8.2).
Battery is discharged too fast
Battery capacity reduced due to sulphation or due to plate corrosion
Charge and recharge a few times, this might help. Check battery and replace if necessary.
Batteries are too warm, gassing
Defective battery (short circuit in cell)
Check battery and replace if necessary.
Battery temperature too high
Use the battery temperature sensor.
Wrong battery type setting
Check settings (see section 4.8.2).
Page 18
18
MPPT Solar ChargeMaster 25 – User and Installation Manual

6 TECHNICAL DATA

6.1 SPECIFICATIONS

Model
MPPT Solar ChargeMaster 25
Article no.
131902500
Nominal battery voltage (U
NOM
)
12V and 24 V (Auto detection)
PV-INPUT
@ U
NOM
= 12V
@ U
NOM
= 24V
Maximum connected PV power
360Wp
720Wp
Maximum input PV power*
300W
600W
Full power voltage MPPT range
15 V ~ 66 V
30 V ~ 66 V
Absolute maximum PV Voltage
75VDC
75VDC
MPP tracking
Yes, integrated MPP tracker
Start-up voltage:
Battery voltage + 3VDC
Maximum PV input current
18ADC
EU efficiency
>97%
Peak static power conversion efficiency
>98%
Static MPPT efficiency
>99%
BATTERY OUTPUT
@ U
NOM
= 12V
@ U
NOM
= 24V
Maximum charge current (I
MAX
)
25 A
25 A
Charge voltage, Absorption:
14.25V (Traction: 14.45V)
28.5V (Traction: 28.9V)
Charge voltage, Float;
13.25V (AGM, gel: 13.8V, MLI: 13.5V)
26.5V (AGM, gel: 27.6V, MLI: 27.0V)
Battery temperature compensation
30 mV/°C
60 mV/°C
DC consumption (at night):
5mA
5mA
DC consumption (on, no charging):
<110mA
<80mA
Charge algorithm:
Three step (Bulk, Absorption, Float)
Battery types**:
Flooded, AGM, Gel, Traction, Mastervolt MLI.
LOAD OUTPUT
@ U
NOM
= 12V
@ U
NOM
= 24V
Maximum output current
25 A, max 36A peak for 1 sec.
25 A, max 36A peak for 1 sec.
Under voltage disconnect
10.5V
21.0V
Under voltage reconnect
11.0V
22.0V
GENERAL
Galvanic isolation between PV and battery
No, common negative conductor
Dimensions in mm [inch] (h x w x d):
135 x 190 x 73 mm [5.3 x 7.5 x 2.9 inch]; see also section 6.2
Weight:
1 kg
Operating Temperature Range
–20°C ≤ T
AMB
≤ +55°C [–4°F ≤ T
AMB
≤ 131°F]
Full Power Temperature range
–20°C ≤ T
AMB
≤ +40°C [–4°F ≤ T
AMB
≤ 104°F] (no power de-rating)
Non-operating Temperature range
–40°C T
AMB
+75°C [–4°F ≤ T
AMB
≤ 167°F] (storage temperature)
Relative Humidity
5% to 95% non-condensing
Protection degree
IP23
MasterBus connectivity
No
Terminals:
Screw terminals, max. wire size 10mm2
* Automatic limitation of input power; excessive power will not be converted ** Refer to section 4.8.2 for battery type settings.
Specifications are subject to change without prior notice.
Page 19
MPPT Solar ChargeMaster 25 – User and Installation Manual
19

6.2 DIMENSIONS

Figure 16: Dimensions of the Solar ChargeMaster in mm [inches]
Page 20
Europe, Middle East & Africa
Customer Service
T: +31 (0) 20 34 22 100 E: info@mastervolt.com
Technical Support
T: +31 (0) 20 34 22 100 E: ts@mastervolt.com
Location & Shipping
Mastervolt Snijdersbergweg 93 1105 AN Amsterdam The Netherlands
Americas & Caribbean
Customer Service
T: +1 800 307 6702, Option 1 E: orderentry@marinco.com
Technical Support
T: +1 800 307 6702, Option 2 E: tsusa@mastervolt.com
Location & Shipping
Power Products, LLC N85 W12545 Westbrook Crossing Menomonee Falls, Wisconsin 53051 United States
Asia Pacific
Customer Service
T: +64 9 415 7261 Option 1 E: enquiries@bepmarine.com
Technical Support
T: +64 9 415 7261 Option 3 E: technical@bepmarine.com
Location & Shipping
BEP Marine 42 Apollo Drive Rosedale, Auckland 0632 New Zealand
Copyright © 2019 Mastervolt. All rights reserved.
Reproduction, transfer, distribution or storage of part or all of the contents in this
document in any form without the prior written permission of Mastervolt is prohibited.
Loading...