1 GENERAL INFORMATION
Congratulations! You are one step ahead to
install the most advanced battery monitor - the
Masterlink MICC from Mastervolt. This
instrument will tell you at a glance:
• Exact state-of-charge of your battery;
• System voltage and system charge- or
discharge current;
• Amp-hours consumed from the battery;
• Time of operation remaining until your
battery is empty.
•Remote operation of your inverter, your
battery charger or Mass Combi.
1.1 Use of this manual
This manual serves as a guideline for the safe
and effective operation, installation,
maintenance and possible correction of minor
malfunctions of the Masterlink MICC.
It is therefore obligatory that every person who
works with the Masterlink MICC must be
completely familiar with the contents of this
manual, and that he / she carefully follows the
instructions contained herein. The manual must
be immediately accessible to the user. This
manual has 16 chapters.
1.2 Guarantee Specifications
Mastervolt guarantees that this unit has been
built in accordance with the legally applicable
standards and specifications. Should work take
place, which is not in accordance with the
guidelines, instructions and specifications
contained in the user manual, damage may
occur and / or the unit may not fulfil its
specifications. All of these matters may mean
that the guarantee may become invalid.
1.3 Quality
During the production and prior to their delivery,
all our units are exhaustively tested and
inspected. The guarantee period is two years.
1.4 Validity of this manual
All of the specifications, provisions and
instructions contained in this manual apply
solely to the MASTERVOLT-delivered standard
versions of the Masterlink MICC.
1.5 Liability
MASTERVOLT can accept no liability for:
•Consequential damage due to use of the
Masterlink MICC.
•Possible errors in the manuals and the
results thereof.
CAREFUL!
Never remove the type and number
plate.
Important technical information required
for service, maintenance & secondary
delivery of parts can be found from the
type and number plate.
November 2004 / Masterlink MICC / EN 5
Page 6
2 SAFETY GUIDELINES &
MEASURES
2.1 Warnings and symbols
Safety instructions and warnings are marked in
this manual by the following symbols and
pictograms:
a procedure, circumstance, etc which
deserves extra attention.
CAREFUL
Special data, restrictions and rules with
regard to the prevention of damage.
WARNING
a WARNING refers to possible injury to
the user or significant material damage
to the MICC if the user does not
(carefully) follow the procedures.
2.2 Use for intended purpose
1 The Masterlink MICC is constructed as per
the applicable low voltage directive.
2 Use the Masterlink MICC only:
• in a technically correct condition;
• in a closed room, protected against rain,
moisture, dust and non condensing
circumstances;
•observing the instructions in the manual
WARNING Never use the Masterlink
MICC at locations where there is danger
of gas or dust explosion!
3 Use other than as mentioned under 2 is not
considered to be consistent with the
intended purpose. MASTERVOLT is not
liable for any damage resulting from the
above.
2.3 Organisational measures
The user must always:
• Have access to the user manual
• Be familiar with the contents of this manual.
This applies particularly to Chapter 2, Safety
Guidelines & Measures.
2.4 Warning for special dangers
1 Check the wiring at least once a year.
Defects such as loose connections, burnt
wiring etc. must be corrected immediately.
2 Do not work on the Masterlink MICC or the
system if it is still connected to a power
source. Only allow changes in your electrical
system to be carried out by qualified
electricians.
3 Installation must be done in accordance with
local standards.
4 The battery voltage can be dangerous. Use
caution and pay careful attention when
installing the Masterlink MICC. Avoid short
circuiting. Voltages above 34 V can be
dangerous.
6November 2004 / Masterlink MICC / EN
Page 7
3 INSTALLATION
3.1 Tools and equipment required
Installation of the Masterlink MICC involves only
eight wires and two 6 pole modular
communication cables (RJ12, cross wired). The
following sections describe a basic installation
such as you would find on an average boat, RV
or in a solar application.
First gather all the tools you need for the
installation of the Masterlink MICC.
We recommend as a minimum tool kit:
• A saw to make the panel cut-out
• A 10-mm drill to make holes for feeding
through the wiring between the panel, the
shunt and the batteries.
• A 14 mm spanner for shunt connections
• Wire stripper and crimper
• 2 mm and 5 mm flat blade screwdrivers.
A complete set of spanners, pliers and
wrenches may be helpful during the installation
of the Masterlink MICC.
3.2 Materials needed for installation
Make sure you have all the parts you need for
the job:
•A 500A/50mV shunt (supplied with the
Masterlink MICC)
•Cable(s) long enough to easily reach from
the batteries to the Masterlink MICC
(maximum length of the cables: 25 meters /
80ft.):
•Either: One cable 4x2x0,25 mm² shielded
twin twisted pair
•Or: One cable 2x0.25 mm² shielded
twisted pair and three normal 2-core
cables 2x0,25 mm²
•Two 6 pole modular communication cables
(RJ12, cross wired; see figure 1) to connect
the Masterlink MICC to the Mass Sinus
inverter and the Mass charger.
•Three inline fuse holders with 2 Amp fuses
(do not install the fuses before the
installation is completed).
•An as short as possible heavy-duty battery
cable to run from one shunt bolt to the main
battery. The size of this cable is usually
35-70 mm² but can vary depending on the
system. (Consult your Mastervolt dealer if
1 6 1 6
1 6 6 1
Figure 1: Modular cable, cross wired
the wire size is unknown.) This cable is
commonly available from your Mastervolt
dealer or at marine and auto shops.
• Cable terminals and cord end terminals.
• If an external low battery alarm is required: a
normal cable 2x0.25 mm². The maximum
Mastervolt
Description
part number
68 01 601100Cable 3x2x0.25 mm² twisted
current consumption of the relay must not
exceed 1A@30VDC.
3.3 Step by Step installation
During installation check also the
installation drawing on page 11.
Ideally you should install the Masterlink MICC
where it is possible to gain easy access to the
instrument. For good visibility avoid installing
the meter in direct sunlight. The maximum
(cable) distance between the meter and the
shunt must not exceed 25 meters / 80ft.
WARNING
Be sure that all the charging systems in
the installation are switched off or
removed and disconnect the plus and
minus connections from the main and
secondary (starter) batteries prior to
installation.
1. Make a cut out in the panel using the outline
drawings of chapter 15, or integrate the
Masterlink MICC in your Mastervision panel.
The minimum depth required for installing
the Masterlink MICC is 65 mm.
2. Make a hole in the black installation box on
the side where it is easy to enter the cable.
3. Install the shunt of the Masterlink MICC as
close as possible to the main battery, but
avoid the shunt being in contact with the
positive terminal of the batteries.
Special care must be taken that during
installation of the wiring, sharp bends of
the cables are avoided. Also be careful
not to run the cable on sharp edges that
could easily damage the cables and the
Masterlink MICC.
4. Run the twisted wired cable (2x 0,25 mm²)
between the shunt and the Masterlink MICC.
Be sure that the wires are long enough to be
connected at the left side of the shunt. The
shunt’s output voltage is very low (between 0
and 50mV) Therefore reliable connections
are essential. Prevent connections and
wiring from corrosion. Pay attention to the
correct connections (3 and 4) of the system
side and the battery side (see figure 3). The
maximum length of this cable must not
exceed 25 meters / 80 ft.
5. Run a normal cable (2x0,25 mm²) from pin 1
and 2 (power supply) of the Masterlink MICC
to the plus pole of the main battery
respectively system side of the shunt. Install
a fuse holder in the plus line. The maximum
length of this cable must not exceed 25
meters / 80 ft.
6. Run a normal cable (2x0,25 mm²) from pin 5
and 6 (service battery voltage sense) of the
Masterlink MICC to the plus pole of the main
battery respectively system side of the shunt.
Install a fuse holder in the plus line. The
maximum length of this cable must not
exceed 25 meters / 80 ft.
7. Run a normal cable (2x0,25 mm²) from pin 7
and 8 (start battery voltage sense) of the
Masterlink MICC to the plus respectively the
minus pole of the secondary battery. Install a
fuse holder in the plus line. The maximum
length of this cable must not exceed 25
meters / 80 ft.
Please note that the 2 Amp fuses
should only be installed after the
installation is completed.
Note: for the above mentioned cables
wires also a 8 wire cable (8x 0,25 mm²)
with twisted pair wires can be used (see
also chapter 3.2).
8November 2004 / Masterlink MICC / EN
Page 9
8. Run a 6 pole modular communication cable
(RJ12, cross wired) and connect the RJ12
connector to the socket on the right-hand
side (see figure 2: connector I) at the
backside of the Masterlink MICC.
To connect the other RJ12 connector to the
apparatus:
− Refer to the charger’s installation
manual to connect the RJ12 connecter.
−Mass Combi: You must connect the
RJ12 connecter to the “QRS-232” input
(Data bus connections) see figure 4.
9. Run another 6 pole modular communication
cable (RJ12, cross wired) and connect the
RJ12 connecter to the socket which is
marked with “Inv” (see figure 2: connector II)
at the back of the Masterlink MICC.
To connect the other RJ12 connector to the
apparatus:
− Refer to the inverter’s installation
manual to connect the RJ12 connecter.
−Option for the Mass Combi: Connect
the RJ12 connecter to the “REMOTE”
input (Data bus connections) see fig. 4.
NOTE: under normal circumstances
there is no need to install this
optional cable. If this cable is installed, the
total stand-by power consumption will be
reduced from 50mA to 30mA if the Mass
Combi is switched off by means of the
Inverter button on the Masterlink MICC
panel.
When installed, it is not possible to connect
the ICC remote control panel to the Mass
Combi.
II
I
Figure 2: Backside MICC panel
10. Connect the wires to the connection
terminals of the Masterlink MICC and mount
the panel with the four factory supplied nuts
and rings.
11. Connect the minus wire of the system to the
system side (see figure 3) of the shunt.
Charger
Inverter
3
Ç System side
È Battery side
4
– +
Secondary
battery
Load
– +
Main battery
Figure 3
12. Make a connection between the minus of the
secondary (starter) battery and the system
side (figure 3) of the shunt.
13. Connect the battery side of the shunt (figure
3) to the minus terminal of the main battery.
NOTE: if several minus cables are
connected to the minus terminal of the
main battery, all of these cables must
be connected to the system side of the
shunt. On the battery side only one
cable between shunt and main battery
is used.
14. Reconnect the positive terminals of the
batteries to the system.
15. Double check the wire connection of the
meter and install the three 2 amp fuses.
November 2004 / Masterlink MICC / EN 9
Page 10
Directly after power up by installing the two
2 amp fuses the LED.'s will light and after
approximately five seconds the display will
show the volt, amps, state of charge and the
time remaining of the main battery.
If this is not the case, check the wire
connections for errors. Consult to the trouble
shooting chapter if the wires are connected
correctly but the meter is not showing the
display (chapter 13).
3.4 Installation of an external alarm
The switching current of the alarm relay
(normally open contact) may never exceed
1A@30VDC. The switching contacts of the relay
are available on pin 9 and 10.
3.5 Connection of the charger and the
inverter
Always connect the cables between batteries
and charger and inverter, before you connect
the Masterlink MICC to the charger or inverter.
If it is necessary to disconnect batteries and
charger/inverter, then first disconnect Masterlink
MICC from the charger/inverter
For an appropriate operation of the Masterlink
MICC the “ON/OFF” switch of the inverter must
be set to the “REMOTE” position.
If you are using a Mass Combi then the
ON/OFF/CH. switch on the front of the Mass Combi must be set in the “ON” or “Ch. Position.
See chapter 4 of the manual of the Mass Combi.
Rear view of the Masterlink MICC panel
Connection compartment of the Mass Combi. See chapter 5 of the manual of
the Mass Combi.
AC CONNECTIONS
INPUT
GEN / SHORE
50A MAX 50A MAX 25A MAX
LNPE
OUTPUTOUTPUT
POWERSHORT BREAK
LNPE LNPE
1 - 2 - 3 - 4
+
25A
SHORT BREAK
PUSH TO RESET
Step 8: 6 pole modular cable
RJ12, cross wired
TEMP. SENS
POS
BATTERY
MASTERBUSREMOTEQRS232
NEG
+5A
Step 9: optional 6 pole modular
cable RJ12, cross wired
Figure 4: Connection between the Masterlink MICC panel and the Mass Combi
10November 2004 / Masterlink MICC / EN
Page 11
MASS INVERTER CHARGER CONTROL
Charger
Time-remain
03 hr 20 min
MASTERVOLT
-
Battery
Isolator
ALTERNATOR
+
INVERTER
Figure 5: installation drawing
1
d
e
r
i
w
s
s
o
r
c
e
l
b
a
c
e
t
o
m
e
r
r
e
t
r
e
v
n
I
1
*
*
MASTERVOLT
-
CHARGER
1
e
l
b
a
c
2
3
d
2
e
r
S
i
w
R
s
Q
s
r
o
r
e
c
g
r
a
h
C
*
*
1
+
r
o
n
d
i
n
d
d
u
n
e
o
r
u
i
r
o
u
g
r
q
s
g
i
e
r
s
s
'
s
e
p
a
i
s
h
h
a
c
S
C
n
C
o
i
t
D
u
s
b
i
u
r
n
t
i
s
i
M
d
V
m
0
5
/
A
0
0
5
t
n
u
h
S
12 or 24 vdc
- SERVICE SET +
12 or 24vdc
- START SET +
C
C
a
AC-present
Flo at
Vo lt - Am p
Absorption
1. + Power supply
2. - Power supply
3. Shunt load side
4. Shunt battery side
5. + Service battery voltage sence
INSTALATION DRAWING MASTERVOLT MASTERLINK MICC
Inverter
Select
6. - Service battery volage sence
8. - Start battery voltage sence
7. + Start battery voltage sence
10. low battery signal n.o.
9. Low battery signal n.o.
Fuse holder with fuses
s
I
k
h
M
c
t
i
a
j
h
w
t
i
e
e
w
n
r
i
o
d
w
h
e
i
p
l
e
e
p
n
l
p
o
e
t
u
h
s
p
e
r
t
e
l
o
o
e
c
n
t
6
s
e
r
r
o
e
o
t
c
w
e
t
6
f
m
f
o
5
o
s
2
t
s
f
s
r
i
o
e
s
t
n
e
m
o
u
m
c
m
e
X
i
l
x
b
d
a
a
n
m
a
C
*
*
November 2004 / Masterlink MICC / EN 11
Page 12
4 SYNCHRONISATION AND
SETTING THE BATTERY
CAPACITY
See also chapter 8.
4.1 Synchronisation
Although the meter is for many items "selflearning" it is necessary, for a quick start-up, to
set the meter according to the voltage and
capacity of the installed batteries.
To synchronise the meter with the installed
batteries, charge the batteries after the
installation of the Masterlink MICC for at least
24 hours with an appropriate charger to be sure
the batteries are 100% charged. After this time
the “FLOAT”-LED will be lit indicating the
battery is fully charged. The Masterlink MICC
can now be synchronised with the installed
battery.
4.2 Setting the battery capacity
The factory default for the battery capacity is set
at 200 Ah. For high accuracy of the “time
remaining” function and the “percentage
charged” indication, the meter must be set
according to the battery capacity installed. The
following steps will make sure that the right
battery capacity is set and the readings are as
accurate as possible.
Note: the capacity of the battery can
only be set if the batteries are 100 %
charged. The time remaining function
and the Ah consumed will be reset if the
battery capacity settings are changed.
Press the Select button for 5
Select
Ah-Time
seconds until the green Select
indication LED flashes.
Press the Ah-Time button
shortly to display the battery
capacity.
BATTERY CAP.
200 Ah È
Set-up
Adjust the required capacity of
the main battery by pressing
the Set-upbutton
Select
If the Select button is held for
five seconds, the arrow’s
direction in the right part of the
display will change. If the arrow is pointing
downwards (È) the set value can be changed
into lower values by means of the Set-up button. If the arrow is pointing upwards (Ç) the
set value can be changed into higher values.
If the battery capacity is set and no
buttons are used the Masterlink MICC
will reset to the users menu after 15
seconds.
For 12-volt systems the capacities of all the
installed batteries for the main battery bank can
be added. If a 24-volt battery system is used all
the capacities of the main battery bank are
added and divided by two.
Example:
A main battery bank with two batteries installed
of 12-volt 100 Ah each.
For a 12-volt system the battery capacity must
be set at 200 Ah. For a 24-volt system the
battery capacity must be set at 100 Ah.
The auxiliary (starter) battery capacity doesn’t
need not to be set.
4.3 Setting the battery voltage
Normally it will not be necessary to set the
battery voltage; the meter automatically detects
a 12 or 24-volt main battery system. Special
care must be taken that the battery must be
charged at least 50 % before power up. If this is
not possible or the state of charge of the battery
is unknown the battery voltage needs to be
adjusted.
12November 2004 / Masterlink MICC / EN
Page 13
Press and hold the Select
Select
button for 5 seconds until the
green Select indication LED
flashes.
Press the Select button five
Select
times shortly until “BATTERY
BANK” is displayed.
BATTERY BANK
24V
Set the required voltage of the
Set-up
main batteries using the Set-up
button.
The Masterlink MICC will now be synchronised
and set in accordance with the installed
batteries.
4.4 Activate Mass Combi setting
You only have to activate (ON) this setting if you
are using the Masterlink MICC in combination
with the Mass Combi. The default setting is
“OFF”.
This menu can be entered by
Select
holding the Select button for 5
seconds until the Select-LED is
flashing.
Now press the Set-up-button
Set-up
shortly to enter the “program
menu”
Press the Select button 4 times
Select
shortly until the “HFC MODE” is
displayed.
EXIT LEVEL
Select
->PRESS SET-UP
If this level is entered you can return to the user
menu by means of the Set-up button.
4.5 In case you are lost
Set-up Select
If it is necessary to reset to factory defaults, go
to the “PROGRAM LEVEL” by holding the
Selectbutton and Set-upbutton
simultaneously until both the Select-LED and
the Set-up-LED are flashing.
Next press the Set-up button
Set-up
shortly until “RESET
FACTORY” is displayed.
RESET HISTORY
PRESS SET 5sec
After holding the Set-up- button
Set-up
for 5 seconds the unit will be
reset to factory defaults.
HFC MODE
OFF
Select the required setting
Set-up
using the Set-up button.
November 2004 / Masterlink MICC / EN 13
Page 14
5 OPERATION
5.1 General
By means of the Masterlink MICC you can
switch on and off your inverter and charger
remote controlled and read the exact state-ofcharge of your battery.
The (dis)charge current is measured by means
of a shunt, and on demand made visible on the
display. From the starting point of fully charged
batteries, the Masterlink MICC calculates the
actual battery capacities. For this calculation the
measured (dis)charge currents are used as well
as assumptions about their effect on battery
capacity. The accuracy of the results of this
calculation depends on the correctness of these
assumptions. These assumptions are partly set
up by the user (possibly after a test) and partly
set up by the Masterlink MICC itself after a
number of charge/discharge cycles.
The operation of the Masterlink MICC can be
separated into three major parts: remote control
of the battery charger, remote control of the
inverter and retrieving information you’re your
batteries. (see figure 6)
5.2 Remote control of the battery charger
By pressing the “Charger”-
Charger
switch the battery charger can
be switched on/off. After a few
seconds the “Charger”-LED illuminates when
the charger is in operation (230V supply). The
“AC-present”-LED illuminates as well.
WARNING
Above operation is not applicable for
the chargers IVO Smart 12/25, 12/35,
12/40, 12/50 and 24/15, IVO Compact
12/25 and 24/10 and MASS 12/30,
24/15 and 24/25. When the charger is
switched off by means of the Masterlink
MICC (the Charger-LED is not
illuminated), the maximum output
current is reduced to 10%. To switch off
the battery charger completely, the
“ON-OFF”-switch of the battery charger
must be set to the “OFF”-position.
The meaning of the illuminating LEDs is
explained beneath. Refer to the charger’s users
manual for additional information about the
LCD-Display
Inverter
Select
Volt-Amp
Charger
Set-up
Ah-Time
A C B D
Figure 6: Operation of the Masterlink MICC
14November 2004 / Masterlink MICC / EN
Page 15
three-stage charge characteristic.
The LEDs A, B, C and D represent the following
information (see figure 6 for the references
indicated between brackets [ ]):
Bulk [A]: Main charge
Batteries are charged with full charger output
current at a voltage between 12V resp. 24V and
14.4V resp. 28.8V.
Absorption [B]: absorption charge
The batteries are almost (approx. 85%)
charged. Charging continues with decreasing
current until the batteries are full.
Float [C]: “trickle charge”
The batteries accept only a small current.
Voltage is lowered to 13.2V resp. 26.4V to keep
the battery fully charged without formation of
gases.
AC present [D]:
The AC-present –LED illuminates if the charger
is in operation (230V supply).
Besides the inverter there is an external 230V
AC source available.
5.3 Adjustment of the maximum charge
current
When the available current from the AC source
is limited (for instance to avoid the shore fuse
from tripping), the output current of the charger
can be reduced (and accordingly the AC-power
consumption of the battery charger):
Press the Select button for 5
Select
seconds until the green Select
indication LED flashes.
Press the Charger-button
Charger
shortly to display “CURRENT
CONT.”
CURRENT CONT.
100% Ç
Adjust the desired output
Set-up
current (10 – 100%) by
pressing the Set-upbutton
If the Select button is held for
Select
five seconds, the arrow’s
direction in the right part of the
display will change. If the arrow
is pointing downwards (È) the set value can be
changed into lower values by means of the Set-up button. If the arrow is pointing upwards (Ç)
the set value can be changed into higher
values.
After adjusting the output
Select
current to the desired value,
press the “Select”-button
shortly until “EXIT LEVEL” is displayed.
EXIT LEVEL
->PRESS SET-UP
Now it is possible to return to
Set-up
the user menu by means of the
Set-up-button. Also if none of
the buttons was used for 15 seconds the
Masterlink MICC returns to the users menu.
5.4 Adjustment of the Power sharing /
Power support level (Mass Combi
only).
When the available current from the AC source
is limited (for instance to avoid the shore fuse
from tripping), the maximum current can be
limited. In case of the Mass Combi you can
adjust the Power sharing / Power support* level.
Press the Select button for 5
Select
seconds until the green Select
indication LED flashes.
*See chapter 7.7 of the manual of the Mass
Combi to enable Power sharing / Power support
function.
November 2004 / Masterlink MICC / EN 15
Page 16
MICC User level
Direct access by pressing desired function button shortly
Set-up
Set-up
H01
Battery historical data
H01
Battery historical data
H02
H02
Deepest Discharge
Deepest Discharge
H03
H03
Peukert Exponet
Peukert Exponet
DEPT 1
DEPT 2
DEPT 3
I01
Inverter switch status
ON - OFF
V01
Voltage & Current
read out
Service Battery
V02
Voltage read out
Starter battery
T01
Battery Status
present in
% full
T02
Time remaing
present in
hours
T03
Battery Capacity
Consumed read out in
Ahr
ChargerAhr-timeVolt-ampInverterSelect =>
C01
Charger switch status
ON-OFF
DEPT 4
DEPT 5
DEPT 6
DEPT 6
DEPT 7
DEPT 7
Press the Charger-button
Charger
shortly to display “CURRENT
CONT.”
CURRENT CONT.
25A Ç
You can adjust the Power
Set-up
sharing / Power support level
between 2.5A and 25A in steps
of a 0.5A by pressing the Set-up button.
If the Select button is held for
Select
five seconds, the arrow’s
direction in the right part of the
display will change. If the arrow is pointing
downwards (È) the set value can be changed
into lower values by means of the Set-up button. If the arrow is pointing upwards (Ç) the
set value can be changed into higher values.
H04
H04
C.E.F.
C.E.F.
H05
H05
Numbers of
Numbers of
cycles detected
cycles detected
H6
H6
Software version
Software version
H07
H07
Error status
Error status
Figure 7: Set-up drawing (user level).
After adjusting the output
Select
current to the desired value,
press the “Select”-button
shortly until “EXIT LEVEL” is displayed.
EXIT LEVEL
->PRESS SET-UP
Now it is possible to return to
Set-up
the user menu by means of the
Set-up-button. Also if none of
the buttons was used for 15 seconds the
Masterlink MICC returns to the users menu.
5.5 Remote control of the Inverter
By pressing the “Inverter”-
Inverter
switch the inverter can be
switched on and off. After a few
seconds the “Inverter”-LED illuminates when the
inverter is in operation (AC-output).
16November 2004 / Masterlink MICC / EN
Page 17
5.6 User menu.
Functions like battery voltage, current
consumption and time-remaining are displayed
by means of the LCD display
This information can also used to control an
optional Battery Alarm relay. Refer to chapter 7,
8, 9 and 10 for adjusting and programming
functions of the Power System Control Panel.
For more information see also the setup drawing (figure 7). The numbers of
the mentioned levels correspond with
this drawing.
Battery voltage and current (V01)
VOLT & CHG.AMP
Volt-Amp
28.56V 29.3A
By pressing the Volt-Amp-button the LCD-
Display shows the main battery voltage and
current. If the battery is being charged, “VOLT &
CHG.AMP” is displayed. “VOLT & DIS.AMP”
means that the battery is being discharged with
the current that is displayed.
Voltage secondary (starter) battery (V02)
VOLT START BAT
Volt-Amp
28.53V
By pressing the Volt-Amp-button again, the
voltage of the secondary (starter) battery is
displayed. Please note that if no secondary
battery was installed, this function is not
available. The Masterlink MICC automatically
detects whether a secondary (starter) battery is
connected to the meter.
Battery status (T01)
BATTERY STATUS
Ah-Time
42%
By pressing the Ah-Time-button the LCDDisplay shows the state of charge of the main
battery as a percentage of the installed battery
capacity. This percentage gives an exact
indication of the state of charge of the battery.
This value is automatically compensated by the
charge efficiency factor (C.E.F.) and the
Peukert exponent (check chapter 11 for more
information about the C.E.F. and about the
Peukert exponent).
A battery is considered fully (100 %) charged if:
1. All of the Ah's discharged are charged back
into the battery plus 1 Ah (real counting
without CEF).
2. The charge-float voltage is met (the voltage
is usually set around 14.0/28.0 volt).
3. The charge-return current is met (the
charged current will be usually be set for 2 %
of the installed battery capacity).
If all the above parameters are met for a few
minutes, the reading of the Ah's consumed will
be reset to 100%.
Time remaining function (T02)
TIME REMAIN
Ah-Time
25 HR 14 MN
If you press the Ah-Time-button again, the
display shows how long the battery can be used
before it will be empty and needs to be
recharged. The remaining time is automatically
compensated with the Peukert exponent if the
battery is discharged above the 20h rating (see
chapter 11 for more information about the
Peukert exponent)
Ah consumed (T03)
CAP. CONSUMED
Ah-Time
- 86 Ah
If Ah-Time-button is pressed again, information
is shown on how many amp hours are
consumed from the battery. During charging this
value shows how many Ah's are still necessary
to bring the battery up to a
100 % state of charge (0 Ah consumed). This
value is compensated by the Charge Efficiency
Factor (C.E.F.).
November 2004 / Masterlink MICC / EN 17
Page 18
6 HISTORICAL DATA
To know the history of your battery can be very
useful. It will help you to check if the battery is
has the right capacity for the application, and
how long the battery can be used before it need
to be replaced. This can be done by reading the
number of cycles the battery has used, and the
efficiency (C.E.F.) of the battery. The memory
back up system of the MICC makes this data
available even if the power supply of the meter
removed or, if the battery completely discharged
to 0 volts.
For more information see also the setup drawing (figure 7). The numbers of
the mentioned levels correspond with
this drawing.
Battery history data (H01)
BATTERY HIS.
Set-up
To enter the historic data menu press the Setup button once. With the Select button you can
scroll trough a total of 6 information levels.
Deepest discharge (H02)
Select
By touching the Select-button once, the
deepest discharge of the battery is displayed.
This value lets you know the deepest discharge
of the battery since power up of the MICC or
after a historic data reset. For an optimum
lifetime of your battery it is advised not to
discharge a battery below 80 % of its rated
capacity. If a battery is frequently discharged
below this value, premature failure of the battery
can be expected.
DATA
DEEPEST DIS
99 Ah
Peukert exponent (H03)
PEUKERT EXP.
Select
1.27 P
The second level shows the Peukert exponent.
Standard batteries are rated for a 20-hour
discharge. This means that a 100 Ah battery
can supply 5 amps for 20 hours before a
voltage of 1,75 volt/cell (10,5 volt for 12-volt
batteries and 21 volt for 24-volt batteries) is
reached.
If the discharge current is higher, for example
10 amps the battery will not be able to supply
the full 100 Ah. In this case the voltage of
1,75 volt/cell or 10,5/21 volt is reached before
the battery has supplied its full 20-h rated
capacity. Frequently discharging the battery
below this voltage and/or capacity will shorten
the life of the battery dramatically.
The maximum time the battery can be used in
the above mentioned example is approx.
8 hour i.e. 80 Ah.
A German scientist Dr Peukert, has found an
exponent that can be used to calculate the
capacity of the battery, if it is used above its
20 h rating. This exponent is used by the MICC
to calculate the time the battery can be used
(time remaining function). The Peukert
exponent is also used to calculate the state of
charge in percentage.
In normal circumstances the Peukert exponent
is no needs to change, only if traction batteries
e.g. on a forklift, are used, and a high level of
accuracy is required. The Peukert exponent can
be changed in the program mode. See section
for how to calculate the Peukert exponent and
section how to set the MICC according to the
exponent found.
18November 2004 / Masterlink MICC / EN
Page 19
Charge Efficiency Factor C.E.F (H04)
C.E.F.
Select
90 %
The third level is the C.E.F (Charge Efficiency
Factor). Every combination of battery and
charger has an total efficiency. This means that
there must be more Ah charged into the battery
than are used. A standard wet type lead acid
battery has an efficiency of approx.
80 %, a gel type battery has an efficiency of
approx. 90 %. The efficiency of a battery is
improved after it has been used for 5-10 cycles.
For the rest of the lifetime of the battery the
efficiency will slowly decline depending on its
age and the number of discharge cycles. If an
efficiency of 70 % is reached, it will basically
mean that the battery is at the end of its lifetime
and needs to be replaced. The changing of the
efficiency means that it is necessary to calculate
the efficiency every charge and discharge cycle.
The C.E.F. is not only for the reading of the
charge and discharge information of the
MICC, but also for the calculation of the time
remaining function.
Number of cycles (H05)
NUMBER CYCLES
Select
10
The fourth level gives information about the
number of 35 % (low battery set point) cycles
used from the battery after the Masterlink MICC
was set up or after the Masterlink MICC was
reset to factory settings.
The number of cycles a battery can handle
depends strongly on the type of battery and its
quality. One cycle is reached if the battery is
discharged from 100 % state of charge down to
0 % followed by a charge up to 100 %. One
cycle is also reached if a battery is discharged
twice to 50 % and charged back to 100 % or
discharged four times 25 % and charged to
100 % etc.
A normal cranking battery can perform approx.
50-80 cycles before the end of its cycle life is
reached. A semi traction battery can perform
about 200-250 cycles and full traction batteries
can handle 1000-1500 cycles before the end of
their cycle lifetime is reached. The number of
cycles the battery is used together with the
C.E.F. of the battery gives a reasonable
indication about how long the battery can be
used before it needs to be replaced.
Every time the battery is discharged below
35 % of its rated capacity and charged back to
at least 85 % of its capacity, one cycle is
counted.
Software version (H06)
SOFTWARE VER.
Select
1.02
The fifth level of this menu displays the software
version installed in your MICC. This software
version can be used for future references.
Error status (H07)
ERROR STATUS
Select
NONE
The sixth level shows the error status (see the
low battery alarm settings for more information).
At this level it is possible to return to the user
menu by means of the Set-up button. Also if
none of the buttons are used for 15 sec the
MICC returns to the users menu.
November 2004 / Masterlink MICC / EN 19
Page 20
MICC Installer level
Hold select 2..4 sec untill led flashes and select the function below
Set-up
Set-up
F01
F01
Sleep mode
Sleep mode
On / Off
On / Off
F02
F02
Low Bat. Contact
Low Bat. Contact
On / Off
On / Off
F03
F03
LED is switch
LED is switch
On / Off
On / Off
F04
F04
HFC mode
HFC mode
On / Off
On / Off
F05
Exit level
DEPT 1
DEPT 2
DEPT 3
DEPT 4
DEPT 5
No function
level 1
M01
Set Low Voltage Level
Low Battery Signal
11vdc / 22vdc
M02
Set dischage Floor
35% of C.ahr
20% .. 50%
M03
Set level full charge
80% of C.ahr
70%..90%
M04
Set min. require run time
10 min
5 min .. 90 min
M05
Exit level
A01
Battery Capacity
200 ah
40 .. 9990 ah
A02
Average Time
Consumtion
0 minutes
0-10-20-30 minutes
A03
Return amps
6% of C.ahr
1%..10%
A04
Float level
13.1V / 26.2V
A05
Reset Ahr to 0000
Press setup
ChargerAhr-timeVolt-AmpInverterSelect =>
C01
Current Control
100% amp
10%..100%
C02
Exit level
DEPT 6
DEPT 6
DEPT 7
DEPT 7
SELECT & SETUP
DEPT 1
DEPT 2
DEPT 3
DEPT 4
A06
A06
Battery type
Battery type
12 /24V
12 /24V
A07
A07
Exit level
Exit level
Figure 8: Set-up drawing installer level
Program level - advanced settings
Hold select & setup 2 to 4 sec untill both leds flashes
ChargerAhr-timeVolt-ampInverter
No function
level 2
M06
Test Low Batt. mode
on - off
M07
Exit level
Change C.E.F. Manual
A08
Change Peukert
exponent 1,27
1,01 to 1,50
A09
actual read out
0.7... 0.99
A10
Exit level
No function
level 2
Set-up
Set-up
F06
Reset to factory setting
Reset to factory setting
Reset all historical data
Reset all historical data
F06
Press setup
Press setup
F07
F07
Press setup
Press setup
F08
F08
Exit level
Exit level
DEPT 5
DEPT 6
DEPT 6
Figure 9: Set-up drawing advanced settings
20November 2004 / Masterlink MICC / EN
Page 21
y
7 LOW BATTERY ALARM MENU
The Masterlink MICC checks the state of charge
of the battery continuously and gives an alarm
when the battery is reaching a low voltage set
point or a low discharge floor. The Masterlink
MICC is provided with a relay to control an
external alarm (check also chapter 3.4 for more
information).
To enter the Alarm menu hold
Select
Volt-Amp
100%
the Select button for 5 seconds
until the Select-LED flashes.
Now press the Volt-Amp button
to enter the low batter alarm
menu.
80%
With the Select button you can
now scroll through the levels of
Select
this menu and adjust several
alarm set points.
For more information see also the setup drawing (figure 8) and figure 10. The
numbers that are mentioned behind the
levels correspond with this drawing.
Note: If the Select button is held for
five seconds, the arrow in the right part
of the display will change. If the arrow is
pointing downwards (È) the set value
can be decreased by means of the Set-up button. If the arrow is pointing
upwards (Ç) the set value can be
increased.
Battery voltage
Battery status
11,0/22,0V
35%
status
Batter
Battery voltage
LOW BAT.DELAY (30s)
MAX RUN TIME (6h)
MIN RUN TIME (M04)
Battery alarm
FULL CHARGE (M03)
LOW BATTERY (M01)
DIS. FLOOR (M02)
Time
Figure 10: battery alarm settings
November 2004 / Masterlink MICC / EN 21
Page 22
Low battery alarm voltage set point (M01)
LOW BATTERY
Select
22.0V Ç
The MICC automatically detects a 12 or a
24-volt system. The factory default for the low
battery alarm is 11 volt if a 12-volt system is
used or 22 volt if a 24-volt system is used.
These values are correct if the battery is
discharged by the C 20 rate. If the discharged
rate is higher i.e. if the current is high, the low
voltage alarm may set slightly lower; for
example 10 / 20 volts. When the average
current is much lower than the C 20 rate this set
point can be set higher for example 12 / 24-volt.
For solar applications this voltage alarm can set
higher to avoid too deeply discharged batteries.
Low Ah set point (M02)
DIS.FLOOR
Select
35% Ç
At the second level of this alarm menu the alarm
can be set according to the Ah consumed. Battery
voltage is not always correct to set an alarm. The
voltage of a battery is not only affected by the
state of charge of the battery, but is also affected
by the load connected to the battery during
discharge. The alarm for the low Ah discharge
floor is factory set at 35 % of the total capacity of
the battery. For an average battery installation this
value is normally ok, but the alarm for low Ah can
be set according to the requirements of the
application. For solar applications this value is
often set to 50 % and for cyclic applications
(forklifts) the value is often set at 20 %.
Alarm delay
The alarm is delayed for 30 sec. This means
that if the voltage is lower than the setting for
low battery voltage, the alarm will be activated
after 30 seconds. This prevents the alarm being
activated during a small dip in the battery
voltage.
Low battery alarm "off" setting (M03)
FULL CHARGE
Select
80% Ç
The fourth level is used to reset the alarm if the
battery reaches 80% state of charge. This
means with the factory default settings of 35 %
for low alarm, and 80 % for switching of the
alarm, the alarm is activated if the Ah consumed
drops below 35 % and it is reset when the
batteries have been charged up to
80 % of their capacity. The value can be set
between 70 and 90 % according to the
requirements of the system.
Minimum alarm time setting (M04)
MIN RUN TIME
Select
10 MIN Ç
The fifth level of this alarm setting is used to set
the minimum time that the alarm will stay
activated. If for example the battery drops below
the settings for voltage and Ah but is charged
directly afterwards, the alarm will stay activated
for 10 minutes (factory setting) even if the
battery is charged above the settings for voltage
and Ah. This time can be adjusted between
5 and 90 minutes by means of the Set-up
button.
Maximum alarm time
The maximum alarm time is set for 6 hours and
used to set the maximum time the alarm will
stay activated. If for example the battery is
discharged below the settings for voltage and
Ah and will not be charged the alarm will stay
activated for a maximum of 6 hours.
Return to users menu (M05)
EXIT LEVEL
Select
->PRESS SET-UP
If this level is entered, it is possible to return to
the user menu by means of the Set-upbutton.
Also if none of the buttons are touched for
15 seconds, the Masterlink MICC will return to
the users menu.
22November 2004 / Masterlink MICC / EN
Page 23
8 INSTALL LEVEL
This menu is used to set the Masterlink MICC
according to the voltage and capacity of the
batteries installed.
To enter the install level press
Select
Ah-Time
Select
For more information see also the setup drawing (figure 8). The numbers of
the mentioned levels below correspond
with this drawing.
Note: If the Select button is held for
five seconds, the arrow in the right part
of the display will change. If the arrow is
pointing downwards (È) the set value
can be decreased by means of the Set-up button. If the arrow is pointing
upwards (Ç) the set value can be
increased.
Setting the battery capacity (A01)
Select
The first level is used for setting the battery
capacity. For an accurate reading of the time
remaining function, and the capacity consumed
in % of the installed capacity, this level must be
set according the capacity of the battery
installed. The set value is the capacity of the
battery with a 20 hour rating (C 20). If traction
batteries are installed with a different rating
such as C 10 or C 8, ask your battery supplier
what the capacity of the battery will be if the
battery is discharged according the 20-hour
rating and set the MICC according this value.
the Select button for 5 seconds
until the Select LED is flashing.
Next press the Ah-Time button
to enter the installer menu.
With the Select button you can
scroll through the levels of this
menu.
BATTERY CAP.
200 Ah È
For 12-volt systems the capacities of all the
installed batteries of the main battery bank can
be added. If a 24-volt battery system will be
used all the capacities of the main battery bank
are added and divided by two.
Example: a main battery bank with two batteries
installed of 12-volt 100 Ah each.
For a 12-volt system the battery capacity must
be set at 200 Ah. For a 24-volt system the
battery capacity must be set at 100 Ah.
The auxiliary (starter) battery capacity does not
need to be set.
Please note that the capacity of the
battery only can be set if the batteries
are 100 % charged. The time remaining
function and the Ah consumed are reset
if the battery capacity settings are
changed.
Average time for the time remaining function
(A02).
AVERAGE TIME
Select
10 MN È
With the second level it is possible to set the
average time for the time remaining function.
If this set point is set to 0 it means that the time
remaining is instantaneous and will give direct
information about how long the batteries can be
used in accordance with the load connected.
A more accurate and easier way to use value is
shown if the average reading is set to 10, 20 or
30 minutes. If this level is entered, the value can
be set by means of the Set-up button. The
factory default for this level is 10 minutes.
Setting the "charged" amperage (A03)
RETURN AMPS
Select
2.0% Ç
Another point that needs to be met before the
Masterlink MICC considers the battery fully
November 2004 / Masterlink MICC / EN 23
Page 24
charged is the number of amps flowing into a
fully charged battery. The more a battery is
charged the less current it requires. If this
current drops below 2 % of the installed battery
capacity (C 20 rating), the battery can be
considered as fully charged, provided the
charged voltage is met as well. If the battery
becomes a lot older (beyond its normal lifetime)
it might start to consume more current when the
battery is fully charged so the meter can not be
reset to zero and efficiency can not be
calculated correctly. This means that this set
point needs to be changed to a higher value if
old batteries are used which are beyond their
economical life but can not yet be replaced. The
"charged" amps can be changed between 1 and
10 % of the installed capacity and the factory
default is 2 %.
Setting the "charged" voltage (A04).
FLOAT LEVEL
Select
27.2V È
In order to check if the battery is fully charged
several parameters must be met before the
MICC will consider the battery fully charged.
One of the parameters is the minimum voltage
that must be reached. This voltage must be set
according to the lowest voltage of all the
charging devices in the system. This means for
example if the voltage of the battery charger is
14.25 volt and the alternator is 14 volt the
voltage must be set just below the lowest
voltage i.e. below 14 volt.
The above mentioned voltages are measured at
the output terminals of the charging system and
therefore it is necessary for these voltages to be
set approx. 0.4 volt lower to compensate for the
voltage drop in the wiring. In the above
mentioned example therefore the voltage must
be set for 13.6 volt.
Also this value will be automatically set for a
12 or a 24-volt system. The factory settings are
13,6 volts for a 12-volt system or 27,2 volt for a
24-volt system.
Resetting the Ah consumed (A05)
RESET AHR
Select
->PRESS SET-UP
With the fifth of this menu the consumed Ah can
be reset back to zero by the Set-up button for 5
sec. This will only be required if the MICC is out
of synchronisation caused by wrong settings or
if the batteries are replaced.
Only reset the consumed Ah's if you are
sure the batteries are 100 % charged.
Setting the battery voltage (A06)
BATTERY BANK
Select
24V
The last level is used to set the Masterlink
MICC according to the battery voltage of the
main battery. If the Masterlink MICC is powered
up with a full or at least a reasonably charged
battery, the MICC will automatically set the
voltage according to the nominal voltage of the
main battery system. If during power up of the
Masterlink MICC a 24-volt battery was
completely discharged i.e. the voltage was
below the 15 volts, the meter is set for the
wrong voltage. The right voltage can be set with
the Set-up button. The factory default setting is
12 volt.
Return to users menu (A07)
EXIT LEVEL
Select
->PRESS SET-UP
If this level is entered you can return to the user
menu by means of the Set-up button.
24November 2004 / Masterlink MICC / EN
Page 25
9 PROGRAM MENU
The Program menu is used to set the Masterlink
MICC according the users requirements.
This menu can be entered by
Select
Set-up
Select
For more information see also the setup drawing (figure 8). The numbers of
the mentioned levels below correspond
with this drawing.
Sleep mode (F01)
Select
The first level that can be set is the sleep mode.
For an even lower power consumption of the
MICC, as often required in solar applications,
the MICC can be set so that the backlight of the
display will be switched off if the buttons are not
used for 15 seconds. In this way the power
consumption is reduced till 28 mA. As soon as
one of the buttons will be touched the display
will be lit again for an easy reading of the
display. This function is very useful if smaller
battery capacities are used or in solar
applications where as low a possible power
consumption as possible is required. The sleep
mode can be switched on or off by means of the
Set-up button. The factory default setting is
"On".
Setting alarm function on or off (F02)
and holding the Select button
for 5 seconds until the SelectLED is flashing.
Now press the Set-up-button
shortly to enter the “program
menu”
With the Select button you can
scroll through the levels of this
menu.
SLEEP MODE
ON
With the second level it is possible to switch the
output of the alarm function on or off. The alarm
status will still be shown in the display but the
external alarm contact of the MICC will not be
activated (check chapter section for more
information about alarm settings). If this mode is
entered, the alarm function can be switched on
or off by means of the Set-up button. The
factory default for this level is off.
Adjustment of the charger/inverter LEDindication (F03)
LED IS SWITCH
Select
OFF
With the third and last level it is possible to
change the function of the LED-indication of the
charger and inverter buttons. Factory settings
for this function is ‘OFF’ which means that the
charger LED and the inverter LED will only
illuminate when the battery charger,
respectively the inverter are actually switched
on and that they are operating without failures.
With the Set-up button you can switch this
function to ‘ON’. When switched ON the
indication LED will illuminate as soon as the
Battery charger or the inverter is switched on by
means of the Charger-button, respectively the
Inverter-button. Then the LED will illuminate
immediately, whether the charger is operating
without failures or not.
Activate Mass Combi setting (F04)
You only have to activate (ON) this setting if you
are using the Masterlink MICC in combination
with the Mass Combi. The default setting is
“OFF”.
HFC MODE
Select
OFF
Return to users menu (F05)
EXIT LEVEL
Select
->PRESS SET-UP
If this level is entered you can return to the user
Select
LOW BAT CONT.
OFF
menu by means of the Set-up button.
November 2004 / Masterlink MICC / EN 25
Page 26
10 ADVANCED SETTINGS
After pressing and holding the Select and Setup buttons simultaneously for 5 seconds
several adjustments can be made to set the
Masterlink MICC according the users
requirements. However, under normal
circumstances these adjustments should not be
changed. Refer to figure 9 for more the set-up
drawing of these advanced settings. The
numbers below between brackets () correspond
with this drawing
CAREFUL!
Adjustments in the Advanced settings
menu can result in deviation in the
functioning of the MICC when
incorporated incorrectly. For more
information see also the set-up drawing.
10.1 Testing alarm function
At this level the low battery function can be
tested without draining the battery.
Select Set-up
By pressing the Select button, you can scroll to
the ‘EXIT-LEVEL’ If this level is entered you can
return to the user menu by means of the Set-up
button.
10.2 Exponent adjustment
With this menu the Peukert exponent and the
C.E.F. (Charge Efficiency Factor) can be in
accordance with the type of battery installed
(refer to chapter 11 for additional information)
It is advisable to only change these setting if
extended knowledge of the installed battery is
available.
Select Set-up
This menu can be entered by and holding the
Select and Set-up buttons simultaneously for 5
seconds until the Set-up and Select LEDs flash.
Setting the Peukert exponent (A08)
CHANGE PEUKERT
Ah-Time
1.27 P Ç
This menu can be entered by pressing and
holding the Select and Set-up buttons
simultaneously for 5 seconds until the Set-up
LED and the Select LED flash.
Testing alarm function (M06)
TEST LOW BAT
Volt-Amp
OFF
Press the Volt-Amp button to enter the menu
With the Set-up button you can toggle the alarm
function between ON and OFF, independently
of the state of charge, to test the alarm
functions.
Return to users menu (M07)
EXIT LEVEL
Select
->PRESS SET-UP
Press the Ah-Time button to enter the menu
With the Set-up button the value can be
changed from 1.01 to 1.50. The factory default
setting
is 1.27.
Note: If the Select button is held for
five seconds, the arrow in the right part
of the display will change. If the arrow is
pointing downwards (È) the set value
can be decreased by means of the Set-up button. If the arrow is pointing
upwards (Ç) the set value can be
increased.
Setting the Charge efficiency factor (A09)
In the second the C.E.F. (Charge Efficiency
Factor) can be changed. The C.E.F. is
26November 2004 / Masterlink MICC / EN
Page 27
recalculated automatically by the Masterlink
MICC every time the battery makes a cycle. The
calculated value is checked with the C.E.F. as
stored in the memory of the Masterlink MICC. If
the calculated value is differs from the stored
value, only 50% of the difference is
compensated. This is to avoid the C.E.F. being
changed too much by incorrect wrong settings
or an incorrect calculation of the MICC. For an
accurate calculation of the C.E.F., the
Masterlink MICC needs approx. 6-10 cycles
after power up.
If the C.E.F. of the battery is known, the C.E.F.
can be set manually to give an accurate reading
directly after power-up of the MICC, but even if
the C.E.F. is set manually, the Masterlink MICC
continues to calculate the C.E.F. and will
automatically adjust it if necessary.
The C.E.F. can be set by means of the Set-up
button between 70 and 90 %. The factory
default is set at 90 %.
Note: If the Select button is held for
five seconds, the arrow in the right part
of the display will change. If the arrow is
pointing downwards (È) the set value
can be decreased by means of the Set-up button. If the arrow is pointing
upwards (Ç) the set value can be
increased.
Return to users menu (A10)
EXIT LEVEL
Select
->PRESS SET-UP
If this level is entered you can return to the user
menu by means of the Set-up button.
10.3 Reset menu
The reset menu is used to reset the Masterlink
MICC to its factory settings and to reset all
historical data.
This menu can be entered by and holding the
Select and Set-up buttons simultaneously for
five seconds until the Set-up and Select LED’s
flash.
Return to the factory default settings (F06)
RESET FACTORY
Set-up
PRESS SET 5sec
Now press the Set-up button to enter the menu
With the first level of the reset menu the MICC
can be returned to the factory settings by
holding the Set-up button for 5 seconds.
Resetting the historical data (F07)
RESET HISTORY
Select
PRESS SET 5sec
If new batteries are installed, the historical data
of the old batteries needs to be erased to leave
only historical data from the newly installed
batteries. By holding the Set-up button for
5 seconds the old data will be erased and a new
cycle for historical data will be started.
Return to users menu (F08)
EXIT LEVEL
Select
->PRESS SET-UP
If this level is entered you can return to the user
menu by means of the Set-up button.
Select Set-up
November 2004 / Masterlink MICC / EN 27
Page 28
11 ADDITIONAL INFORMATION
11.1 The Peukert Exponent
Deep cycle battery capacity is usually stated as
a 20-hour discharge rate. A 100 Ah battery will
provide 5A for 20 hours. At discharge rates
above 5A the battery will not supply 100 Ah.
For example: if you are drawing 100A out of the
battery, it will last less than one half-hour.
A scientist named Peukert discovered this in
1897. The Peukert-equation describes the effect
of different discharging rates on the capacity of
a battery. This effect is that with increasing
discharge rate, the capacity of a battery
decreases. Table 3 and the examples give you
an idea of this effect and show how to estimate
a value for the Peukert exponent in your
situation. The Masterlink MICC uses Peukert’s
equation only for the calculation of Time
Remaining. The number in the display (in Ah) is
always the actual number of used Ah.
This means that if you discharge the battery
very fast, the Time Remaining can be zero
before the meter indicates that the total capacity
has been used.
Executing two discharge tests, one at a high
and one at a low discharge rate, which are
about the minimal and maximal discharge rate
for your situation, enables you to calculate a
value “n” for the Peukert exponent which fits
best to your situation. The Masterlink MICC
uses 1.27 as default value for “n”, which will
give good results for most batteries.
At low to moderate discharge rates, around the
20 hr discharge rate, the logarithmic effect of
the Peukert equation is small. At lower
discharge rates the effect is almost linear. For
this reason battery manufacturers specify the
capacity for a 20-hour discharge rate. Peukert’s
equation for battery capacity (Cp) reads:
Cp= I^n * t
log t2 - log t1
where n= ----------------------------
log I1 - log I2
By doing two discharge tests and knowing
I1 and I2 (discharge current in one of the two
tests), and t1 and t2 (time in hours of the two
tests) you can calculate n. For this calculation
you need a calculator that has a logarithmic
function. You can use Table 3 for a better
understanding of the effect of high discharge
rates on the capacity of your batteries. You can
use the table also to make an estimate of “n” of
a battery after only one discharge test. The
values in the table are based on a 100 Ah
battery, but can be used for any capacity you
like by applying the correct ratio
capacity/current. See the examples given.
Table 3: Percentage of available capacity from a 100 Ah battery at different discharge rates and different
values for “n” (= Peukert exponent).
Example 1
Suppose you have a 200 Ah battery. Now
discharge at a 50 A rate until the battery
reaches 1.75 V per cell (10.5V for a 12 V
battery). This would be equivalent to a
discharge rate of 25 A for a 100 Ah battery.
If the battery delivered 67% (134 Ah) the
appropriate Peukert’s exponent would be 1.25.
Example 2
A 100 Ah battery with a Peukert’s exponent of
1.3 will deliver only 41 % of its capacity (41 Ah)
when supplying a 100A load.
11.2 Time Remaining, CEF, & History.
The Charging Efficiency Factor (CEF) takes into
account the fact that batteries are not 100 %
efficient. You have to put in more energy than
you take out. All our meters learn the efficiency of the battery system. The CEF is
used to correct the rate at which Amp-hours are
counted back during charging. The CEF is also
displayed; a falling CEF is an indication of a
failing battery. Additionally, the historic data
available in the Meter includes the number
battery cycles, and the deepest discharge.
November 2004 / Masterlink MICC / EN 29
Page 30
12 GENERAL BATTERY
INFORMATION
The lifetime and performance of batteries
depend for a great deal on how they are cared
for and used. Below we have listed some
influences on the lifetime and some more
information about charging and calculating the
right capacity for your system.
Temperature
A high temperature is disastrous for the lifetime
of your batteries. If they are regularly subjected
to temperatures above 40°C you should relocate
them or supply forced fresh air ventilation.
Discharge
Regularly discharging below 20 % of battery
capacity has a negative effect on lifetime. For
long life of the batteries it is best not to
discharge the battery below 50 %.
Charging
Special care must be taken if wet type batteries
are used. During charging they produce
dangerous hydrogen gas. This means that
special care must be take for ventilation to avoid
the danger of explosion.
To keep their capacity batteries must be
charged fully regularly and the best way is to
use a three step regulated charger. To adjust
the charger according to the temperature of the
battery will increase the lifetime of the battery
significantly. Also a low voltage ripple will help
to extend the lifetime of the battery.
Mastervolt therefore recommends the use of the
Mastervolt Mass or IVO Smart chargers.
Charging a battery is simple if 230 V utility power
is regularly available. However using a generator
to charge the battery up to more than 85 % is not
efficient. The reason for this is that the charging
current is strongly reduced after reaching 8085% of the battery capacity. A rule of thumb can
be used that the last 20 % of charge of the
battery will take 3-4 hours. To keep the generator
time as short as possible batteries will not be
charged up to the full 100 % if a generator is
used to charge the batteries. Normally this will
not harm the battery as long if they are brought
back to a full 100 % at least every five to seven
days.
Real available capacity
The battery capacity given by the manufacturer
is based on the current the battery can deliver
when fully discharged during 20 hours. Using
the (not absolute) values for charging and
discharging mentioned above (50 % and
100 %) means that about 50 % of the capacity
as declared by the manufacturer is really
available for use. If you often use a generator
this can even be as low as 35 %
Choosing the best battery capacity for your
situation
If you are going to decide about the battery
capacity that you have to install it is good to keep
the above mentioned 50 % in mind. If the batteries
are often discharged at a higher rate than 5 % of
the battery capacity (C 20 rate) as given by the
manufacturer, it is also useful to take the Peukert
effect into account. The 50 % rule and Peukert
effect result both in larger battery sets as expected
after simply counting factory specifications.
However if you take both into account you will
miss the often heard disappointment about the
performance of batteries.
30November 2004 / Masterlink MICC / EN
Page 31
ADDITIONAL INFORMATION
13 TROUBLE SHOOTING AND ERROR CODES
13.1 Trouble shooting
Problem Possible cause What to do
No display function Error in the wiring Check wiring for errors especially power supply
(pin 1 and 2) (chapter 3.3 step 5)
No amp reading Error in the wiring Check wiring for errors especially between shunt
and pin 3 and 4 (chapter 3.3 step 4)
No volt reading Error in the wiring Check wiring for errors especially voltage sense
(pin 1, 2, 5 and 6) (chapter 3.3 step 6)
No voltage reading of
secondary battery
Amp reading not accurate Distortion on the shunt
Secondary battery not
or wrongly connected
wiring
Check the wiring to pin 7 and 8. Connect wire
between minus main battery and minus
secondary battery (chapter 3.3 step 7)
Replace wiring by twisted pair cable between the
shunt and pin 3 and 4. (chapter 3.3 step 4)
Rerun the wires and keep them away from
equipment that might cause noise
Time remaining function
indicating ------ during
discharge
Back light switches off
after 15 seconds
No accurate time
remaining function
Voltage /low Ah alarm not
functioning correctly
Voltage /low Ah alarm not
functioning correctly
External voltage /low Ah
alarm not functioning
correctly
Voltage /low Ah alarm not
functioning
Voltage reading shows
0,00
Power sharing / Power
support can not be
adjusted.
Shunt wiring reversed Check installation drawing and correct the wiring.
Pay extra attention to the distinction between
battery side and system side (chapter 3.3)
Unit in sleep mode Press one of the buttons or refer to chapter 9,
step F01 to disable the sleep mode.
Wrong setting of the
installed Ah
Wrong setting of the
parameters
Testing alarm function is
switched on
Wrong connection of
relay contact
Alarm setting in the off
position
Battery voltage below
Refer to chapter 8, step A01 for the correct setting
of the battery capacity.
Refer to chapter 7, for the correct setting of the
parameters.
Switch off the Testing alarm function (chapter
10.1, step M06)
Connect the external relay to the correct pins
(chapter 3.4)
Switch on the alarm function (chapter 10.1, step
F02)
Charge the battery
7 volt
Mass Combi setting not
activated.
Check and if necessary activate the Mass Combi
setting in the Masterlink MICC menu (see chapter
9 step F04).
Check and if necessary activate the Power
sharing / Power support function on the Mass
Combi. See also the manual of the Mass Combi.
November 2004 / Masterlink MICC / EN 31
Page 32
ADDITIONAL INFORMATION
13.2 Error codes
The following error codes are displayed when the Masterlink MICC detects a problem. The display
alternates between the selected monitoring function and the error code. The error code continues to
flash until the error is corrected.
Code Description Action
E1 Battery Temperature error, the batteries
are too warm to be charged safely.
The charger will stop charging until the battery
temperature is within the safe margin. Make sure that the
batteries are ventilated properly.
E2 DC error, automatic charger shut down
due to too low or too high DC Voltage
DC system voltage has dropped below 10.5V (12V
system), 21.0V (24V system), or has risen above 15.5V
(12V system), 31.0V (24Vsystem)
E3 Short-circuit of the charger output. Possible short-circuit on the output, The charge current
will be reduced to a quarter of the maximum value.
E4 Charger is too hot, automatic charger
shutdown due to too high temperature
The charger switches automatically on after it has cooled
down sufficiently. Make sure that the charger is ventilated
properly
E5 Charger switched off because of a
battery sense error
The battery voltage sense wires are connected wrong or
the charger has reached the maximum compensation
value. The charger compensates the voltage loss with a
maximum of 2,5V
E6 Inverter error. The inverter is in overload, reduce load. Inverter
temperature is too high, inverter will automatically switch
off and on if temperature has dropped sufficiently. Make
sure that the inverter is ventilated. DC supply voltage to
high switch off charger .
The following error code is displayed when the Masterlink MICC detects a communication problem with
the battery charger.
Code Description Action
NO COMM Communication error with the battery
charger. The battery charger is switched
off or the AC-input is disconnected.
Switch on the battery charger or adjust the
charger’s DIP-switch correctly (refer to the
charger’s operation manual, “ContMon”;
REMARK: When the ContMon function is enabled
while the battery charger is switched off, energy is
withdrawn from the battery connected to the
battery charger.
NO COMM Communication error with the battery
charger. The battery charger is
disconnected from the Masterlink MICC
Check the wiring of the 6 pole modular
communication cable (Chapter 3.2 and 3.3, step
9)
or connected by a wrong modular
communication cable (RJ12, cross wired)
32November 2004 / Masterlink MICC / EN
Page 33
ADDITIONAL INFORMATION
14 TECHNICAL DATA
Model Masterlink MICC
Article number 70403105
Function of instrument Battery monitor for 12 and 24 volt battery banks
Remote control for a Mastervolt inverter and battery charger or Mass