Mastervolt MASS SYSTEMSWITCH 10, MASS SYSTEMSWITCH 16 Installation Manual

Page 1
USER AND INSTALLATION MANUAL
To download this manual in other languages, please
visit our website: www.mastervolt.com
MASS SYSTEMSWITCH
Automatic AC transfer switch
Page 2
2
Mass Systemswitch 16 kW (230V) – User and Installation Manual
TABLE OF CONTENTS
1 GENERAL INFORMATION ........................................ 3
1.1 Use of this manual ........................................... 3
1.2 Guarantee Specifications ................................. 3
1.3 Quality ............................................................. 3
1.4 Validity of this manual ...................................... 3
1.5 Liability ............................................................. 3
1.6 DISCLAIMER ................................................... 3
2 SAFETY GUIDELINES AND MEASURES ................. 4
2.1 Use for intended purpose ................................ 4
2.2 Organisational measures ................................. 4
2.3 Warning of special dangers ............................. 4
3 HOW IT WORKS ........................................................ 5
3.1 Source priority ................................................. 5
3.2 AC inputs ......................................................... 5
3.2.1 Only inverter power available ............... 5
3.2.2 Shore power available .......................... 5
3.2.3 Generator power available ................... 5
3.3 AC outputs ....................................................... 5
3.3.1 Inverter only output (no break).............. 6
3.3.2 Short break output ................................ 6
3.3.3 Power output ........................................ 6
3.3.4 Generator only output ........................... 6
3.4 Monitoring and control ..................................... 6
3.4.1 Remote control panel (optional)............ 6
3.4.2 MasterBus (optional) ............................ 7
3.5 Load on inverter mode ..................................... 7
3.6 Automatic load on inverter mode ..................... 7
3.6.1 Traditional remote control panel ........... 7
3.6.2 MasterBus ............................................ 7
3.6.3 Example ............................................... 7
4 INSTALLATION .......................................................... 9
4.1 General ............................................................. 9
4.2 Environment ..................................................... 9
4.3 Tools required for installation ........................... 9
4.4 Mounting of the cabinet .................................... 9
4.5 Opening the connection compartment .............. 9
4.6 Wire cross section ............................................ 9
4.7 Ground connections ....................................... 10
4.8 Wiring ............................................................. 10
4.9 Inputs .............................................................. 11
4.10 Outputs ........................................................... 11
4.11 Remote panel (optional) ................................. 12
4.12 MasterBus (optional) ...................................... 12
4.13 Commissioning after installation ..................... 12
4.13.1 MasterBus (optional) ........................... 12
4.14 Decommissioning ........................................... 12
4.15 Storage and transportation ............................. 12
4.16 Re-installation ................................................. 12
5 MASTERBUS ............................................................ 13
5.1 What is MasterBus? ....................................... 13
5.2 Event based commands ................................. 13
5.3 How to set up a MasterBus network ............... 14
6 SPECIFICATIONS ..................................................... 15
6.1 Technical data ................................................ 15
6.2 Dimensions ..................................................... 16
6.3 MasterBus ...................................................... 17
6.3.1 Menu level 2: Monitoring ..................... 17
6.3.2 Menu level 3: History ........................... 17
6.3.3 Menu level 3: Configuration ................. 18
6.3.4 List of event sources ........................... 19
6.3.5 List of event commands ...................... 19
6.3.6 Personal settings and notes ................ 19
Page 3
Mass Systemswitch 16 kW (230V) – User and Installation Manual
3

1 GENERAL INFORMATION

The MASTERVOLT Mass Systemswitch is the heart of the AC installation. It is designed to take over manual switching between three different power sources. The Mass Systemswitch automatically transfers the available AC power source to the right outputs. Automatic switching between the power sources doesn’t only offer you more comfort; it also improves the safety on board. The switching between the power sources, which is done by means of relays, assures that no short-circuiting will occur.
The status of the Mass Systemswitch can be monitored by means of a Mastervolt remote control panel. The Mass Systemswitch is also compatible to be used in the MasterBus network: a decentralized data network, giving you full control over the entire electrical installation.

1.1 USE OF THIS MANUAL

This manual serves as a guideline for the safe and effective operation, installation, maintenance and possible correction of minor malfunctions of the Mass Systemswitch 16 kW.
It is therefore obligatory that every person who works with the Mass Systemswitch must be completely familiar with the contents of this manual, and that he / she carefully follows the instructions contained herein. The manual must be immediately accessible to the user.

1.2 GUARANTEE SPECIFICATIONS

Mastervolt guarantees that this unit has been built in accordance with the legally applicable standards and specifications. Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in the user manual, damage may occur and / or the unit may not fulfil its specifications. All these matters may mean that the guarantee may become invalid.

1.3 QUALITY

During the production and prior to their delivery, all our units are exhaustively tested and inspected. The guarantee period is two years.

1.4 VALIDITY OF THIS MANUAL

All the specifications, provisions and instructions contained in this manual apply solely to the MASTERVOLT-delivered standard versions of the Mass Systemswitch.

1.5 LIABILITY

MASTERVOLT can accept no liability for:
Consequential damage due to use of the Mass
Systemswitch.
Possible errors in the manuals and the results thereof.
CAUTION!
Never remove the identification label.
Important technical information required for service, maintenance & secondary delivery of parts can be derived from the identification label.

1.6 DISCLAIMER

Our products are subject to continual development and improvement. Therefore, additions or modifications to the products may cause changes to the technical data and functional specifications. No rights can be derived from this document. Please consult our most current Terms & Conditions of Sale.
Page 4
4
Mass Systemswitch 16 kW (230V) – User and Installation Manual

2 SAFETY GUIDELINES AND MEASURES

2.1 USE FOR INTENDED PURPOSE

1. The Mass Systemswitch is constructed as per the applicable low voltage directive.
2. Use the Mass Systemswitch only:
in a technically correct condition in a closed room, protected against rain, moisture,
dust and non-condensing circumstances
observing the instructions and specifications in the
manual
as a stand-alone unit or in combination with a
Mastervolt remote control systems.
WARNING
Never use the Mass Systemswitch at locations where there is danger of gas or dust explosion!
3. Use other than as mentioned under 2 is not considered to be consistent with the intended purpose. MASTERVOLT is not liable for any damage resulting from the above.

2.2 ORGANISATIONAL MEASURES

The user must always:
have access to the user manual  be familiar with the contents of this manual. This

2.3 WARNING OF SPECIAL DANGERS

1. Check the wiring at least once a year. Defects such
2. Do not work on the Mass Systemswitch or the
3. Installation must be done in accordance with local
4. Voltages above 34 V can be dangerous. Use caution
applies particularly to Chapter 2, Safety Guidelines & Measures.
as loose connections, burnt wiring etc. must be corrected immediately.
electrical system if it is still connected to a power source. Only allow changes in your electrical system to be carried out by qualified electricians.
standards.
and pay careful attention when installing the Mass Systemswitch. Avoid short circuiting.
4 May 2007 / Mass Systemswitch / EN
Page 5
Mass Systemswitch 16 kW (230V) – User and Installation Manual
5

3 HOW IT WORKS

3.1 SOURCE PRIORITY

The Mass Systemswitch switches the right AC power source to the output(s). Therefore the Mass Systemswitch is equipped with a source priority. If more than one AC power source is available, the source with the highest priority is switched to the output(s).
See figure 1. The generator input has the highest priority: when generator power is available, all outputs (except the inverter only output) are supplied by the generator. Power on the shore input and/or the inverter input will be denied even when they are available.
The shore input has the second priority. If there is no generator power available, shore power will be transferred to the power output and the short break output. Power on the inverter input will be denied.
The lowest priority is assigned to the inverter. AC power on the inverter input is transferred to the short break output only when no other power source is available.

3.2 AC INPUTS

Three AC-sources can be connected to the Mass Systemswitch:
Inverter power (IN3)  Shore power (IN2)  Generator power (IN1)

3.2.1 Only inverter power available

When there is no AC power available on the generator input or the shore input, power from the inverter input is transferred to the short break output only. The power output and the generator only output are unavailable now.
The Mass Systemswitch is in a neutral state and consumes no energy itself.

3.2.2 Shore power available

When there is no generator power available but AC power is available on the shore input, the Mass Systemswitch will supply both the power output and the Short break output with AC power from the shore input. The generator only
output is unavailable now.
Figure 1: principle schematics of the Mass Systemswitch

3.2.3 Generator power available

When the generator is started, a control circuit samples its output voltage and frequency. Only when both are within allowed limits for approximately 10 seconds, the Mass Systemswitch transfers the power from the generator input to all outputs (except for the inverter only output).
Too low generator frequency and voltage may cause damage to both the generator and the connected load. Therefore AC power on the generator input is continuously checked by a control circuit. If the generator frequency or voltage is too low, generator power is immediately cut off from the load.
The 10 seconds time delay provides an ‘easy start up’ for
the generator. This increases the generator’s lifetime.

3.3 AC OUTPUTS

The Mass Systemswitch has the following AC-outputs:
Inverter only output Short break output Power output Generator only output
Page 6
6
Mass Systemswitch 16 kW (230V) – User and Installation Manual
Incoming AC power is available on
Incoming shore power is available
Incoming AC power from the inverter
Load on inverter illuminates if the AC power is available on the
AC power is available on the Power
AC power is available on the
AC power is available on the

3.3.1 Inverter only output (no break)

The Inverter only output is directly powered by the inverter. This means that this output will never be transferred to one of the other AC sources. Critical loads, like a computer or navigations equipment which are sensitive for voltage drops, should be connected to this output.

3.3.2 Short break output

The Short break output is transferred between the generator input, shore input and inverter input, depending
on the availability. In principle, AC-power is always available on this output.
CAUTION!
During transfer between the AC inputs, users are not supplied with power for a short time. Because of this, computers etc. connected to this output might lose data.
Due to the source priority, this output is supplied by shore power if available. And also, if generator power is available, this output will be supplied by the generator
input. This means that the generator input has a higher priority than shore input and the shore input has a higher priority than inverter input. This preferent behaviour is not always wanted. For instance if the external shore power breaker is only 4A, it is not possible to power the whole electrical system at the same time. It is however possible to override this preference manually by means of the load on inverter mode. See section 3.5 for additional information.

3.3.3 Power output

Depending on its availability, the power output is powered by the generator input or the shore input. The generator is the highest in priority and therefore overrules the shore power. Medium power loads like the battery charger must be connected to this output.

3.3.4 Generator only output

Finally the generator only output is powered by the generator only. Larger loads like a water maker or an electric cooking appliance should be connected to this output.
the generator input.
on the Shore input.
is available on the Inverter input.
load on inverter mode is activated. See section 3.5.
Figure 2: Indicator lights on front of the Mass Systemswitch

3.4 MONITORING AND CONTROL

The LED indicators on the front of the cabinet indicate the status your AC installation. The meaning of the LEDs is explained in figure 2.
Generator only output
output
Shortbreak output
Inverter output

3.4.1 Remote control panel (optional)

For remote operation Mastervolt offers a wide range of intelligent remote control panels that can be connected to the Mass Systemswitch, giving you a status overview of the available AC-power sources. Besides when a remote control panel is applied, a very useful feature of the Mass Systemswitch can be used: the load on inverter mode.
Page 7
Mass Systemswitch 16 kW (230V) – User and Installation Manual
7
Generator
Generator Inverter
Short break
Generator
Generator Inverter
Short break

3.4.2 MasterBus (optional)

The Mass Systemswitch is compatible with the MasterBus network: a fully decentralized data network for communication between Mastervolt devices such as the inverter, battery charger, generator, batteries and many more. See section 5 for details.

3.5 LOAD ON INVERTER MODE

The Short break output is transferred between the generator input, shore input and inverter input, depending
on its availability. However, to prevent the generator from an overload situation or to prevent the shore fuse from tripping, the load that is connected to the Short break output can be switched either manually or automatically from the generator or shore power to the output of the inverter. We call this the “load on inverter mode” or the “force to inverter mode”.
or shore
Figure 4: Load on inverter mode is ON, while power from the generator or the shore is available
or Power

3.6 AUTOMATIC LOAD ON INVERTER MODE

It is also possible to toggle the load on inverter mode automatically. Then the load on inverter mode will be switched ON when the current on the shore input or the generator input exceeds a predefined set point. Then we call it the automatic load on inverter mode” or the automatic force to inverter mode”.
When the load on inverter mode is switched OFF (figure
3), the Mass Systemswitch is in normal state. This means
that the Short break output is transferred between the generator input, shore input and inverter input, depending on the availability.
When the load on inverter mode is switched ON (figure 4), power from the generator or the shore can no longer be used to supply the Short break output. The Short break output will only be supplied by the inverter. See the manual of the remote operation panel to toggle the load on inverter mode manually.
or shore
Figure 3: Load on inverter mode is OFF, while power from the generator or the shore is available
or Power

3.6.1 Traditional remote control panel

If a traditional remote control panel is applied, the “automatic load on inverter mode” can be triggered by:
- The generator current (delayed)
- The shore current (not delayed) To adjust the settings of the automatic load on inverter
mode refer to ADVANCED A-menu of the manual of the remote operation panel.

3.6.2 MasterBus

If the Mass Systemswitch is controlled by MasterBus, operation of the “automatic load on inverter mode” can be programmed by means of an event-based command. See section 6.3 for details. Refer to the manual of the MasterBus remote panel for details about programming of event-based commands.

3.6.3 Example

See figure 5. A coffee machine is switched on, causing an extra load on the shore/generator. When the total load that is connected to the shore or the generator exceeds its maximum current level, first a time delay is triggered. After this delay time the automatic load on inverter mode will be activated: a part of the total load is switched from the generator/ shore to the AC output of the inverter. When the automatic load on inverter mode is activated, it is switched off again when the adjusted time has elapsed.
Page 8
8
Mass Systemswitch 16 kW (230V) – User and Installation Manual
Load on inverter mode active
Actual shore or generator load
Inverter load
Load
Time
Switching on delay time Maximum available shore or
Switching on level of the load
Run time of the load on
(shore load only)
on inverter mode
generator power
inverter mode
Figure 5: Settings of the “Automatic load on inverter”- mode
Page 9
Mass Systemswitch 16 kW (230V) – User and Installation Manual
9
AC-Current
Minimum cross section:
in mm²
AWG
0-16 A
2.5 mm²
AWG 13
16-32 A
4 mm²
AWG 11
32-48 A
6 mm²
AWG 9
48-80 A
10 mm²
AWG 7

4 INSTALLATION

WARNING
Be sure that all AC power sources are switched off or disconnected during installation.
WARNING
External fuses and earth leakage switches must be integrated in the wiring of all inputs and outputs of the Mass Systemswitch.

4.1 GENERAL

During installation and commissioning of the Mass Systemswitch the Safety Guidelines and Measurements
are applicable at all times. See section 2 of this manual. After unpacking, check the Mass Systemswitch for
possible damage. Do not use the Mass Systemswitch if the cabinet is damaged.

4.2 ENVIRONMENT

Obey the following stipulations during installation: The Mass Systemswitch is designed for indoor use
only.
Humidity: 0-95% non-condensing.  Mount the Mass Systemswitch on a solid surface, with
the connecting cables downwards.
Figure 6: mounting of the cabinet

4.5 OPENING THE CONNECTION COMPARTMENT

See figure 7. Steps:
1. Loosen the two Phillips screws A and B that secure the front cover plate two turns.
2. Slide the front cover plate from the cabinet (C) (downwards).
3. The terminals and cable glands are now accessible.
Note: If necessary you can also remove the gland plate
by loosening screws D, E and F. Read section 4.13 carefully to close the connection compartment again.

4.3 TOOLS REQUIRED FOR INSTALLATION

We recommend as a minimum tool kit: Flat blade screw driver 1.0 x 4.0 mm to fix the screw
terminals of the AC wiring.
Flat blade screw driver 0.6 x 3.5 mm for connection of
the remote panel.
Tools to fix the screws / bolts (Ø 6mm) with plugs to
mount the cabinets to a surface.
Phillips screw driver number 2 to open the connection
area of the Mass Systemswitch.

4.4 MOUNTING OF THE CABINET

Take the following steps to mount the cabinet:
1. Determine for the four mounting spots on the basis of the outline drawings (section 6.2 Dimensions).
2. Fix the screws (Ø 6mm) into the surface but do not tighten them entirely.
3. Place the housing over the screws.
4. Fix the housing by fastening the screws securely.
Always close the connection compartment prior to commissioning of the Mass Systemswitch.

4.6 WIRE CROSS SECTION

For a safe installation the correct wire cross section must be applied. Don’t use a cross section that is smaller than indicated. See table below to select the appropriate cross section for the AC wiring:
WARNING
Use cables with the right wire cross section!
Under-sized wires and/or loose connections can cause dangerous overheating of the wires and/or terminals. Therefore use the proper size and tighten all connections well, in order to limit transition resistance as far as possible.
Page 10
10
Mass Systemswitch 16 kW (230V) – User and Installation Manual
A
B
C
D E F
Front cover plate
Gland plate
Figure 7: opening of the connection compartment

4.7 GROUND CONNECTIONS

The ground wire offers protection only if the cabinet of the Mass Systemswitch is connected to the system ground.
Connect the inverter’s earth terminal (PE) to the hull or the
chassis. For safety reasons it is very important that all ground
connections of the power sources and power consumers are connected to the central ground connection of the ship/vehicle. Improper ground connections might lead to life threatening situations. A reliable ground connection is made by connecting the sources and the consumers to the ground terminal (ref. 10) of the Mass Systemswitch. This ground terminal must be connected to the central ground connection of the ship, which is connected to the hull of the ship.
When the ship lies in sea water (salt) while using shore power, corrosion can occur. This corrosion is caused by potential differences between shore ground and ships ground. Using an isolation transformer will solve this problem. Mastervolt can provide a suitable transformer.

4.8 WIRING

The wiring is connected inside the connection compartment. If necessary, the cabling can be fed from the top to the bottom side of the cabinet along the back of the cabinet. Always feed the wiring through the cable glands of the cabinet, and then connect the wiring to the terminals.
Fix the phase line wire to the L terminal, the neutral wires to the N terminal. Fix the ground wires (PE) to the ground terminal bus bar (ref. 10).
Page 11
Mass Systemswitch 16 kW (230V) – User and Installation Manual
11
Terminals
AC source
Generator
Shore power connection
Inverter
Terminals
AC output
Inverter only
Short break
Power
Generator only
Figure 8

4.9 INPUTS

See figure 8 and the table below to connect the AC power sources. Refer to section 3.2 for additional information about the AC inputs.
Figure 9: Connections to the AC sources This Mass Systemswitch is provided with a ground
bonding terminal (ref 8) which is indicated by “N-INV”. It allows you to connect the Safety Ground (PE) of the inverter to the neutral conductor (N) of electrical installation. Refer to local regulations on this issue.

4.10 OUTPUTS

The output terminals are situated on the right hand side. Connect the load to the terminals as indicated in figure 8 and figure 10.
Figure 10: Connections to the AC output groups Refer to section 3.3 for additional information about the
use of the above mentioned AC output groups.
Page 12
12
Mass Systemswitch 16 kW (230V) – User and Installation Manual
Pin
Function
1
- load on inverter
2
+ load on inverter
3
GND
4
U Generator
5
U shore
6
U inverter
7
System voltage
8
+ 12V power
9
GND
10
AC current

4.11 REMOTE PANEL (OPTIONAL)

See figure 8. If a Mastervolt remote control panel is applied, you can fix the wires of the 10x0.5 mm² cable from the remote panel to the remote control connector (ref 9 in figure 11) See also section INSTALLATION of the manual of the remote control panel. These signals are galvanically isolated from the mains grid.
Note: for an easy installation you can pull the screw connector from the holder on the printed circuit board.
Figure 11: Pin configuration of the 10-pole connector to the remote control panel

4.12 MASTERBUS (OPTIONAL)

See figure 8. The Mass Systemswitch can be connected to the MasterBus network by means of the two data ports (figure 8, reference 11). See also section 5.3 for details.
Note: For remote operation of the Mass Systemswitch
you have to choose between either the MasterBus network or a remote panel as described in section
4.11. You cannot use both.

4.13 COMMISSIONING AFTER INSTALLATION

Follow the steps described below to switch on the Mass Systemswitch.
1. Tighten all cable glands to ensure the pull relief.
2. Check all wiring and connections.
3. Close the front cover plate of the connection compartment.
Note: If the gland plate was removed during installation,
be sure to slide back the cover plate before you fix screws D and E (see figure 7).
4. Switch on the AC power sources.

4.13.1 MasterBus (optional)

During first commissioning the Mass Systemswitch will be recognized by the MasterBus network automatically. The remote control panel of the MasterBus network will indicate that a new device was found.
The factory settings of the Mass Systemswitch are optimal for most installations. In some applications however, it is desirable to change settings. See section 6.3 for an overview of all available settings. Refer to the user manual of the remote control panel to change these settings.
Note: Some settings can only be changed via the
MasterBus interface. If changes were made to the factory settings, all LEDs will flash three times during powering of the Mass Systemswitch, i.e. when either generator or shore input comes available or when the MasterBus is powered.

4.14 DECOMMISSIONING

If it is necessary to put the Mass Systemswitch out of operation, follow the instructions in order of succession as described below:
1. Switch off all loads.
2. Switch off the AC power sources. These power sources should be secured against unexpected and unintended switching on.
3. Open the connection compartment of the Mass Systemswitch (see paragraph 4.5).
4. Check with a suitable voltage meter whether the inputs and the outputs of the Mass Systemswitch are voltage free.
5. Disconnect all wiring.
Now the Mass Systemswitch can be demounted in a safe way.

4.15 STORAGE AND TRANSPORTATION

When not installed, store the Mass Systemswitch in the original packing, in a dry and dust free environment.
Always use the original packing for transportation. Contact your local Mastervolt Service Centre for further details if you want to return the apparatus for repair.

4.16 RE-INSTALLATION

To reinstall the Mass Systemswitch, follow the instructions as described in section 4.
Now the Mass Systemswitch is ready for operation.
Page 13
Mass Systemswitch 16 kW (230V) – User and Installation Manual
13
Event source:
Shore pre overload
Select from list of events
sources (see Mass Systemswitch manual)
Event target:
Generator
Select from the device list (devices connected to MasterBus)
Event command:
Status
Select event command from the list of event commands of the target (see Generator manual)
Event data:
On
Select event data from the list of event commands of the target (see Generator manual)

5 MASTERBUS

5.1 WHAT IS MASTERBUS?

All devices that are suitable for MasterBus are marked by the MasterBus symbol.
MasterBus is a fully decentralized data network for communication between the different Mastervolt system devices. It is a CAN-bus based communication network which has proven itself as a reliable bus-system in automotive applications. MasterBus is used as power management system for all connected devices, such as the inverter, battery charger, generator and many more. This gives the possibility for communication between the connected devices, for instance to start the generator when the batteries are low.
MasterBus reduces complexity of electrical systems by using UTP patch cables. All system components are simply chained together. Therefore each device is equipped with two MasterBus data ports. When two or more devices are connected to each other through these data ports, they form a local data network, called the MasterBus. The results are a reduction of material costs as only a few electrical cables are needed and less installation time.

5.2 EVENT BASED COMMANDS

With MasterBus each device can be programmed to initiate an action at another connected device. This is done by means of event based commands.
Example: if the shore power is almost in overload, the generator must be started. As the shore power is measured by the Mass Systemswitch, this device is considered as the command source. The generator is the device that should initiate an action (start the generator), and is therefore considered to be the target. This means that the Mass Systemswitch must be programmed as follows:
For central monitoring and control of the connected devices Mastervolt offers a wide range of panels which show full status information of your electrical system at a glance and a push of a button.
New devices can be added to the existing network in a very easy way by just extending the network. This gives the MasterBus network a high degree of flexibility for extended system configuration, not only today, but in the future as well! Mastervolt also offers several interfaces, making even non-MasterBus devices suitable to operate in the MasterBus network.
See section 6.3.4 for the list of events sources and section
6.3.5 for the list of event commands of the Mass System-
switch.
Page 14
14
Mass Systemswitch 16 kW (230V) – User and Installation Manual
Connections between the devices are made by
OK
As with all high speed data networks, MasterBus
OK
The electric power for the network comes from the
OK
Do not make ring networks.
Do not make T-connections in the network.

5.3 HOW TO SET UP A MASTERBUS NETWORK

Each device that is suitable for the MasterBus network is equipped with two data ports. When two or more devices are connected to each other through these ports, they form a local data network, called the MasterBus.
Keep the following rules in mind:
standard straight UTP patch cables. Mastervolt can supply these cables.
connected devices. At least one device in the network should have
powering capabilities (see specifications). One powering device can power up to three non-
powering devices. As all powering devices are galvanically isolated,
multiple powering devices are allowed.
needs a terminating device on both ends of the network.
Page 15
Mass Systemswitch 16 kW (230V) – User and Installation Manual
15
Model
Mass Systemswitch 16
Part number:
55008205
Function of the product:
Automatic transfer switch system between single phase 230V power sources and output groups. Additional external circuit breakers must be applied (installation dependent)
Manufacturer:
Mastervolt, Amsterdam, the Netherlands
System voltage:
Single phase 200 – 250 VAC / 50-60Hz
Nominal input current
- Generator input:
63A
- Shore input:
40A
- Inverter input:
25A
Earth leakage breaker (RCCB):
N/A, must be applied externally (installation dependent)
Nominal output current
- Inverter only output:
25A
- Short break output:
25A
- Power output:
40A
- Generator only output:
63A
Automatic circuit breakers:
N/A, must be applied externally (installation dependent)
General
Power consumption: (AC available on all inputs)
33VA ± 10%
Power consumption: (only inverter power available)
< 1VA
Connection for optional Mastervolt remote panel:
Yes, see www.mastervolt.com for an overview of available models
Compatible with MasterBus
Yes, see section 6.3 for settings
LED indications:
AC source present for each input, AC output present for each output and Load on inverter
Switching time:
On: 12…22ms / Off: 4…19ms
Standard settings threshold values Generator input pass through (adjustable via MasterBus, see section 6.3)
- Voltage:
On: > 205V ± 5% / Off: < 150V
- Frequency:
On: > 48Hz ± 5% / Off: < 43 Hz
- Delay time:
Approximately 10 sec.
Environment
Specified operation temperature
-5…+60 °C (will meet specified tolerances)
Allowed operating temperature:
-40…+70 °C (may not meet all specified tolerances)
None operating temperature:
-60…+80 °C (storage temperature)
Relative humidity:
95% max., non-condensing
Enclosure
Dimensions, H x W x D:
340x261x144 mm / 13.4x10.3x5.7 inch. See also section 6.2.
Approximate weight:
5.0 kg / 11.1 Lbs ± 5%
Protection degree:
IP23
Terminals
Wire size:
Recommended torque:
AC inputs and outputs:
0.5 - 10mm² / AWG 20 - 7
1.2 – 1.5 Nm / 11 – 13 In Lbs
Recommended strip length: 12mm / 0.5 inch
Remote control panel:
0.14 – 2.5mm² / AWG 26 - 13
0.5 – 0.6 Nm / 4.4 – 5.3 In Lbs

6 SPECIFICATIONS

6.1 TECHNICAL DATA

All specifications are subject to change without prior notice.
Page 16
16
Mass Systemswitch 16 kW (230V) – User and Installation Manual
All dimensions are in millimeters.

6.2 DIMENSIONS

Figure 12: dimensions of the Mass Systemswitch
Page 17
Mass Systemswitch 16 kW (230V) – User and Installation Manual
17
Value
Meaning
Default
Adjustable range
Load on inverter
See section 3.6
Auto
Auto/On/Off
Short break src
Shows name of the input that supplies electric power to the short break output of the Mass Systemswitch at this moment.
Generator/ Shore/ Inverter
(read only)
Power source
Shows name of the input that supplies electric power to the power output of the Mass Systemswitch at this moment.
Generator/ Shore
(read only)
Gen. voltage
Actual voltage of the generator (V)
(read only)
Gen. Frequency
Actual frequency of the generator (Hz)
(read only)
Generator load
Actual power of the generator (kVA)
(read only)
Shore voltage
Actual voltage of the shore power (V)
(read only)
Shore fuse
Setting of the shore fuse. This setting is used as threshold for the “automatic load on inverter mode” function
40A (25A)
0-40A (0-25A)
Pwr src current
Actual input current (Amps) of the AC-source that feeds the Power output of the Mass Systemswitch. The actual AC-source is either the generator or shore, depending on its availability (see “Power source” above).
(read only)
Pwr src limit
Maximum allowed input current (Amps) of the AC-source that feeds the Power output of the Mass Systemswitch. The actual AC-source is either the generator or shore, depending on its availability (see “Power source” above).
Shore: see Shore fuse;
section 6.3.1.
Generator: see Generator Power; section
6.3.3
(read only)
Value
Meaning
Factory setting
Adjustable. range
Generator
Gen power max
Maximum recorded power supplied at the generator input.
--
(read only)
Gen freq. min
Lowest frequency recorded at the generator input.
--
(read only)
Gen freq. max
Highest frequency recorded at the generator input.
--
(read only)
Gen voltage min
Lowest voltage recorded at the generator input. This value is always above Gen. U low off (see section 6.3.3).
--
(read only)
Gen voltage max
Highest voltage recorded at the generator input.
--
(read only)
Shore
Shore power max
Maximum recorded power supplied at the shore input
--
(read only)
Shore freq. min
Lowest frequency recorded at the shore input.
--
(read only)
Shore freq. max
Highest frequency recorded at the shore input.
--
(read only)
Shore volt. min
Lowest voltage recorded at the shore input.
--
(read only)
Shore volt. max
Highest voltage recorded at the shore input.
--
(read only)
Inverter
Inv freq. min
Lowest frequency recorded at the inverter input.
--
(read only)
Inv freq. max
Highest frequency recorded at the inverter input.
--
(read only)
Inv. volt. min
Lowest voltage recorded at the inverter input.
--
(read only)
Inv. volt. max
Highest voltage recorded at the inverter input.
--
(read only)

6.3 MASTERBUS

6.3.1 Menu level 2: Monitoring

6.3.2 Menu level 3: History

This menu shows the absolute maximum readings
Page 18
18
Mass Systemswitch 16 kW (230V) – User and Installation Manual
Value
Meaning
Factory setting
Adjustable. range
General
Language
Language that is displayed on a monitoring device connected to the MasterBus
English
English/ Nederlands/ Deutsch/ Français
Device name
Name of this device. This name will be recognized by all connected devices
Systemswitch
0-12 chars
Generator
Gen. U low on
Lower acceptance voltage for pass through of AC power at the generator input
205V
191-223V
Gen. U low off
Lower rejection voltage for pass through of AC power at the generator input
150V
124-177V
Gen. F low on
Lower acceptance frequency for pass through of AC power at the generator input
48Hz
41-60Hz
Gen. F low off
Lower rejection frequency for pass through of AC power at the generator input
43Hz
35-55Hz
Ignore gen freq.
If set to On, the generator input ignores the frequency of AC power at the generator input
Off
Off/On
Generator Power
Maximum power of the AC-source that is connected to the Generator input. In general, this is the nominal output power of the generator set.
16kVA
0-16.0kVA
Names
Shore name
Name of the AC input Shore
Shore
0-16 characters
Generator name
Name of the AC input Generator
Generator
0-16 characters
Auto load on inv.
LOI gen load
The automatic load on inverter mode (see sections 3.6) will be triggered when the generator load exceeds this percentage (percentage of the Generator Power setting).
100%
0-100%
LOI gen delay
Time delay for the automatic load on inverter mode (see sections 3.6) caused by a generator overload. It prevents the automatic load on inverter mode being activated due to a short­time peakcurrent.
5s
0-30s
LOI generator
To enable the automatic load on inverter mode triggered by the generator load, this parameter must be set to “On”
Off
Off/On
LOI shore load
The automatic load on inverter mode (see sections 3.6) will be triggered when the shore load exceeds this percentage (percentage of the Shore fuse setting; see section 6.3.1)
100%
0-100%
LOI shore
To enable the automatic load on inverter mode triggered by the shore load, this parameter must be set to “On”
Off
Off/On
LOI runtime
When the automatic load on inverter mode is activated, it is switched off again when the adjusted time has elapsed.
120min
5-540min
Events
Event x source
Event-based command (see section 5.2) Event by the Mass Systemswitch that should result in an action by one of the other devices on the MasterBus network
(See List of events, section 6.3.4)
Event x target
Event-based command (see section 5.2) Selection of device on the MasterBus network that should take
action due to an event. by the Mass Systemswitch
(See Device list on the remote control panel)
Event x command
Event-based command (see section 5.2) Action to be taken by the selected device.
(See List of event commands in the manual of the selected device,)
Event x data
Event-based command (see section 5.2) Value of the action to be taken by the selected device.
(See List of event commands in the manual of the selected device,)
Art. nr Serial
Shows the article number and the serial number of the Mass Systemswitch
(read only)

6.3.3 Menu level 3: Configuration

Page 19
Mass Systemswitch 16 kW (230V) – User and Installation Manual
19
Event source
Description
Gen pre overload
Actual power at the Generator input is more than 80% of the Generator power setting (see section
6.3.3). This event is cancelled again when the power at the Generator input is less than 75% of the Generator power setting.
Gen. overload
Actual power at the Generator input is more than the Generator power setting (see section 6.3.3). This event is cancelled again when the power at the Generator input is less than 95% of the Generator power setting
Generator OK
AC power is available on the generator input and within specifications
Shore pre overld
Actual power at the Shore input is more than 80% of the Shore fuse setting (see section 6.3.1). This event is cancelled again when the power at the Shore input is less than 75% of the Shore fuse setting.
Shore Overload
Power at the Shore input is more than the Shore fuse setting (see section 6.3.1). This event is cancelled again when the power at the Shore input is less than 95% of the Shore fuse setting
Shore OK
AC power is available on the Shore input and within specifications
Pwr pre overload
Actual power connected to the Power output is more than 80% of the maximum allowed output current (see section 6.3.1, “Pwr src limit”)
This event is cancelled when the actual power is less than 75% again.
Power overload
Actual power connected to the Power output is more than the maximum allowed output current (see section 6.3.1, “Pwr src limit”)
This event is cancelled when the actual power is less than 95% again.
Power OK
AC power is available on the Power output and within specifications
Value
Default
Personal setting
Load on Inv
Auto
Device name
Systemswitch
Gen. U low on
205V
Gen. U low off
150V
Gen. F low on
48Hz
Gen. F low off
43Hz
Ignore gen freq.
Off Generator Power
16kVA
Shore name
Shore
Generator name
Generator
LOI gen load
100%
LOI gen delay
5s
LOI generator
Off LOI shore load
100%
LOI shore
Off LOI runtime
120min

6.3.4 List of event sources

Below the list of event sources of the Mass Systemswitch is shown. These event sources can be used to initiate an event command at another device that is connected to the MasterBus.

6.3.5 List of event commands

With this version of the Mass Systemswitch programming of event commands at the Mass Systemswitch is not possible.

6.3.6 Personal settings and notes

Use the table below to fill in your personal settings and notes.
Page 20
EMEA
Snijdersbergweg 93 1105 AN AMSTERDAM The Netherlands
+31 (0)20 34 22 100 info@mastervolt.com
NORTH AMERICA
N86 W12500 Westbrook Crossing Menomonee Falls, WISCONSIN 53051 USA
+1 800 307 6702, Option 1 technical@marinco.com
ASIA/PACIFIC
42 Apollo Drive, Rosedale AUCKLAND 0632 New Zealand
+ 64 9 415 7261 enquiries@bepmarine.com
Copyright © 2019 Mastervolt. All rights reserved.
document in any form without the prior written permission of Mastervolt is prohibited.
Reproduction, transfer, distribution or storage of part or all of the contents in this
Loading...