Mastervolt Mass Sine Ultra 24/4000 Installation Manual

Page 1
Mass Sine Ultra
24/4000
SINE WAVE INVERTER
USER’S AND INSTALLATION MANUAL
NL
Zie www.mastervolt.com/products/inverters-sine-wave/
Siehe www.mastervolt.com/products/inverters-sine-wave/
FR
Voir www.mastervolt.com/products/inverters-sine-wave/
ES
Vea www.mastervolt.com/products/inverters-sine-wave/
IT
Vedere www.mastervolt.com/products/inverters-sine-wave/
10000010358/01
Page 2
EN / Mass Sine Ultra
2
OVERVIEW MASS SINE ULTRA
Figure 0-1: Overview of the Mass Sine Ultra
1. Display with front switch
6. Fan (3x)
2. Battery negative
7. Ground stud
3. Battery posit ive
8. Sync connector (2x)
4. AC output
9. MasterBus connector (2x)
5. DIP switch unit (1x8)
Page 3
EN / Mass Sine Ultra
3
TABLE OF CONTENTS:
OVERVIEW MASS SINE ULTRA ................................................................................................................................................ 2
1 GENERAL INFORMATION .............................................................................................................................................. 5
1.1 Product description ............................................................................................................................................. 5
1.2 Use of this manual .............................................................................................................................................. 5
1.3 Validity of this manual......................................................................................................................................... 5
1.4 Scope of warranty .............................................................................................................................................. 5
1.5 Liability ............................................................................................................................................................... 5
1.6 Changes to the Mas s Sine Ultra ......................................................................................................................... 5
1.7 Identification label ............................................................................................................................................... 5
2 SAFETY GUIDELINES AND WARNINGS ....................................................................................................................... 6
2.1 Warnings and symbols ....................................................................................................................................... 6
2.2 Use for intended purpose ................................................................................................................................... 6
2.3 Organizational measures .................................................................................................................................... 6
2.4 Warning of special dangers ................................................................................................................................ 6
2.5 General safety and instal lat i on precauti ons ........................................................................................................ 6
2.6 Warning regarding life support applications ........................................................................................................ 7
2.7 Warning regarding the use of batteries............................................................................................................... 7
2.8 Correct disposal of this produ c t (w aste electrical & electronic equipment). ........................................................ 7
3 OPERATION .................................................................................................................................................................... 8
3.1 General ............................................................................................................................................................... 8
3.2 Energy saving mode (selectable) ....................................................................................................................... 8
3.3 Front panel ......................................................................................................................................................... 8
3.4 Protections ......................................................................................................................................................... 8
3.5 Maintenance ....................................................................................................................................................... 9
3.6 Daily use, MasterBus monitoring ...................................................................................................................... 10
4 INSTALLATION ............................................................................................................................................................. 11
4.1 Unpacking ........................................................................................................................................................ 11
4.2 Environment ..................................................................................................................................................... 11
4.3 Wiring ............................................................................................................................................................... 11
4.4 Things you need ............................................................................................................................................... 12
4.5 Removal of the front lid ..................................................................................................................................... 12
4.6 Mounting the cabinet to a surface .................................................................................................................... 13
4.7 Wiring instructions ............................................................................................................................................ 13
4.8 Installation overview ......................................................................................................................................... 14
4.9 Setting up a MasterBus network ....................................................................................................................... 15
4.10 How to set up a MasterBus network ................................................................................................................. 15
5 INSTALLATION OF MULTIPLE CLUSTERED MASS SINE ULTRA’S ........................................................................ 16
5.1 Purpose of a multiple configuration .................................................................................................................. 16
5.2 General installation guidelines .......................................................................................................................... 16
5.3 Parallel configura tio n diagr a m .......................................................................................................................... 17
5.4 Three phase configuration diagram .................................................................................................................. 17
5.5 Multi Mass Sine Ultra communication............................................................................................................... 17
5.6 Synchronization ................................................................................................................................................ 17
5.7 Configuration for multiple Mass Sine Ultra systems ......................................................................................... 18
5.8 MasterBus configuration for clusters ................................................................................................................ 18
5.9 MasterBus monitoring for a three phase cluster ............................................................................................... 18
5.10 MasterBus specific alarms for multi Mass Sine Ultra systems .......................................................................... 19
5.11 DIP switch settings for two Mass Sine Ultra’s in parallel .................................................................................. 19
5.12 Operation of multiple Mass Sine Ultra systems ................................................................................................ 19
Page 4
EN / Mass Sine Ultra
4
6 CONFIGURATION ......................................................................................................................................................... 20
6.1 Configurati on via dip-switches .......................................................................................................................... 20
6.2 MasterBus configuration ................................................................................................................................... 21
7 COMMISSIONING, DECOMMISSIONING ..................................................................................................................... 23
7.1 Commissioning ................................................................................................................................................. 23
7.2 Decommissioning ............................................................................................................................................. 23
7.3 Trouble shooting ............................................................................................................................................... 23
8 TECHNICAL DATA ........................................................................................................................................................ 25
8.1 Specifications ................................................................................................................................................... 25
8.2 Dimensions ....................................................................................................................................................... 26
9 ORDERING INFORMATION .......................................................................................................................................... 27
Page 5
EN / Mass Sine Ultra
5
1 GENERAL INFORMATION
1.1 Product description
The Mass Sine Ultra is a si n e wave inverter. It converts DC energy from the battery into AC output power.
1.2 Use of this manual
Copyright © 2015 Mastervolt. All rights reserved. Reproduction, transfer, distri bution or storage of par t or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited.
This manual serves as a guideline for the safe and effective use and installation of the Mass Sine Ultra:
For the installer this manual gives directions for the installation, operation and com missio nin g.
For the end user, this manual gives directions for the operation, maintenance and possible corr ection of minor malfunctions.
Every person who works with the device should be familiar with the contents of this manual, and must carefully follow the instructions contained herein.
Store the manual in an accessible place.
1.3 Validity of this manual
This manual is valid for the following model:
Part no
Model
26024000
Mass Sine Ultra 24/4000
All the specifications, provisions and instructions contained in this manual apply solely to the Mastervolt-delivered standard version of a single Mass Sine Ultra.
1.4 Scope of warranty
Mastervolt assures the product warranty of the Mass Sine Ultra during two years after purchase, on the condition that all instructions and warnings given in this manual are taken into account during installation and operation. Among other things, this means that installation is carried out by a qualified electrician, that installation and maintenance are executed according to the stated instructions and correct working sequence, and that no changes or repairs may have been performed on the Mass Sine Ultra other than by Mastervolt. The warranty is limited to the costs of repair and/or replacement of the product by Mastervolt only. Costs for installation labour, shipping of the defective parts and indirect damage are not covered by this warranty. For making an appeal on warranty you can cont act your sup plier directly, stating your co mplaint, applicat ion, date of purch ase and part number / serial number.
1.5 Liability
Mastervolt accepts no liability for:
consequential damage due to use of the Mass Sine Ultra;
possible errors in the manuals and the results thereof.
1.6 Changes to the Mass Sine Ultra
Changes to the Mass Sine Ultra may be carried out only after obtaining the written permission of Mastervolt. This is not applicable for DIP-switche s which are used for u ser settings.
1.7 Identification label
Figure 1-1: Example of an identification label
The identification label is positioned at the right side of the Mass Sine Ultra, see figure 1-1.
CAUTION!
Never remove the identification label.
Page 6
EN / Mass Sine Ultra
6
2 SAFETY GUIDELINES AND
WARNINGS
2.1 Warnings and symbols
Safety instructions and warnings are marked in this manual and on the product by the following pictograms:
A procedure, circumstance, etc. whi ch deserves extra attention.
CAUTION!
Special information, commands and prohibitions in order to prevent damage.
WARNING
A WARNING refers to possible injury to the user or installer or significant material damage to the Mass Sine Ultra if the installer / user does not (carefully) follow the stated procedures.
Read this manual before installation and use.
This product has been declared conform the EC directives and standards.
Degree of protection: IP23. The product is protected against touch by fingers and water spray < 60 degrees from vertical.
Safety class 1. This product must be provided with an equipment grounding conductor to the AC-output ground terminal.
2.2 Use for intended purpose
1 The Mass Sine Ultra is constructed as per the
applicable safety-technical gui deli nes.
2 Use the Mass Sine Ultra only:
for the conversion of battery DC voltage to AC voltage;
with a fuse, protecting the wiring between Mass Sine Ultra and battery;
in a technically correct condition;
in a closed, well-ventilated ro o m, protected against
rain, moist, dust and condensation;
observing the instructions in the user’s manual.
WARNING
Never use the Mass Sine Ultra in situations where there is danger of gas or dust explosion or potentially flammable products!
3 Use of the Mass Sine Ultra other than mentioned in
point 2 is considered to be inconsistent with the intended purpose. Mastervolt does not hold itself liable for any damage resulting from the above.
2.3 Organizational measures
The user must always:
have access to the user’s manual;
be familiar with the contents of this manual. This applies
in particular to chapter 2, Safety Guidelines and Warnings.
2.4 Warning of special dangers
1 If the Mass Sine Ultra is switched off during
maintenance and/or repair activities, it should be secured against unexpected and unintentional switching on:
remove the connection to the batteries
be sure that others cannot reverse the measures
taken.
2 If maintenance and repairs are required, use only
original spare parts.
2.5 General safety and installation precautions
Do not expose the Mass Sine Ultra to rain, snow, spray, moisture, excessive pollution and condensing circumstances. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the Mass Sine Ultra in a non-ventilated area, ov erheating results.
The Mass Sine Ultra must be provided with an equipment grounding condu ctor to t he AC-output ground terminal. Grounding and all other wiring must comply with local rules and regulations.
In case of fire, you must use a fire extinguisher which is appropriate for electrical equipment.
Short circuiting or reversing polarity will lead to serious damage to batteries, Mass Sine Ultra and wiring. Fuses between batteries and Mass Sine Ultra cannot prevent damage caused by reversed polarity and warranty will be void.
Protect the D C wiring w ith a proper fuse, accordi ng to the guidelines in this manual.
Connection and protection must be done in accordance with local standards.
Do not work on the Mass Sine Ultra or s ystem if it is still connected to a power source. Only allow changes in your electrical system to be carried out by qualified electricians.
Page 7
EN / Mass Sine Ultra
7
Check the wiring and connections at least once a year. Defects such as loose connections, burnt cables etc. must be corrected immediately.
Do not touch the equipment when wet or with clammy hands.
Not only the batteries, but the Mass Sine Ult ra as well can become a projectile if your transport is involved in an accident! Ensure adequate and secure mounting and always use suitable transportation handling equipment.
Except for the connectio n com partment, see secti on 4.5, the cabinet of the Mass Sine Ultra must not be opened. There are no serviceable parts inside the cabinet. Only qualified, authorized and trained electricians are authorized to open the connection compartment.
2.6 Warning regarding life support applications
The Mass Sine Ultra products are not sold for applications in any medical equipment intended for use as a component of any life support system unless a specific written agreement pertaining to such intended use is executed between the manufacturer and Mastervolt. Such agreement will require the equipment manufacturer either to contract additional reliability testing of the Mass Sine Ultra parts and/or to commit to undertake such testing as a part of the manufacturing process. In addition the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arising from using Mass Sine Ultra parts f or life support equipment.
2.7 Warning regarding the use of batteries
Excessive battery discharge and/or high charging voltages can cause serious damage to batteries. Do not exc eed the recommended limits of your batteries. Avoid short circuiting batteries, as this may result in explosion and fire hazard. Installation of the batteries and adjustments of the Mass Sine Ultra should only be undertaken by authorised personnel!
2.8 Correct disposal of this product (waste electrical & electronic equipment).
This product is designed an d manu factured w ith high q uality materials and components, which can be recycled and reused. When this crossed-out wheeled bin symbol is attached to a produc t, it me ans the pr oduct is covered by th e European Directive 2012/19/EU . Please be informed about the local separate collection system for electrical and electronic products. Please act according to your local rules and do not dispose of your old products with y our norma l ho use hol d waste. The correct disposal of your old product will help prevent potential negative consequences to the environment and human health.
Page 8
EN / Mass Sine Ultra
8
3 OPERATION
The Mass Sine Ultra is a fully automatic inverter. It converts a DC voltage to a pure AC s in e wave voltage. Under normal circumstances there is no need for adjustment or operation besides switching on and off.
3.1 General
The inverter provides voltage and frequency regulated AC power from a battery ba nk. Fast acting ele ctronic circuits and fuses protect the inverter against extreme overloads, low and high battery voltage and overheating of the inverter. A large momentary surge power is available for starting up electric motors. High efficiency ensures long battery usage between recharges. A built in energy saving feature can reduce battery power consumption when no loads are connected to the inverter.
3.2 Energy saving mode (selectable)
The Mass Sine Ultra has a built-in automatic energy saving feature that reduces battery power consumption when no load is present on the output s. Response from idle is in stant. In most cases the operation is not noticeable. The energy saving mode can be set by means of MasterBus or dipswitch, refer to chapter 6, Configuration.
The Mass Sine Ultra scans the A C output w ith pul ses of 2 30 V every 2½ seconds. When it detects a load that is larger than 50 W (adjustable), it switches On the inverter automatically. Smal l loads such as clocks in VCR’ s or micro waves are most likely not to work in this mode.
Figure 3-3: Front panel
3.3 Front panel
See figure 3-3. The operation of the Mass Sine Ultra is controlled by the main On/Off switch and displayed by means of LED indicators at the front side of the housing. If the Mass Sine Ult ra is ac ti vated and as lo ng as none of th e red indicators are illuminated, no failure is detected and the unit is operating normally.
3.3.1 AC Output LED
See figure 3-3 item 1. The illuminated arrow indicates that AC Output is powered.
3.3.2 Power bar LED’s
See figure 3-3 item 2. Every LED indicates 20% of nominal inverter power. If the upper LED illuminates red, the inv erter is in overload. On: inverting, Off: not inverting.
3.3.3 Switching On and Off
See figure 3-3 item 3. The only control on the Mass Sine Ultra itself is the main switch on the front of the unit. This switch controls inverter On and Off. Switching the main switch or an optional remote control panel to the “ON” position activates the Mass Sine Ultra. After switching On, expect a three till five second delay before the unit is activated. With the m ain switch in position “On“, the Mass Sine Ultra inverter can also be switched Off and On via Mas terBus. Move the main switch or t he optiona l remote co ntrol panel t o the “Off” position to swi tch off the Mass Sine Ultra.
3.3.4 Battery LED
See figure 3-3 item 4. This LED illuminates red when the voltage of the connected battery is too high or low.
3.4 Protections
The Mass Sine Ultra is protected against overload, short circuit, overheating and under and over voltage. You can detect failures from the front panel by means of the indicators or from one of the (optional) remote control panels.
CAUTION!
The Mass Sine Ultra is not protected against reversing polarity of the DC-input, AC voltage on the DC-input and extreme over voltage (>300 VAC ) on the AC-output.
1 AC Output LED,
section 3.3.1
2 Power bar LED’s,
section 3.3.2
3 Main switch On/Off,
section 3.3.3
4 Battery LED, section
3.3.4
Page 9
EN / Mass Sine Ultra
9
3.4.1 Output overload or short circuit
In case of overload or short circuit, the Power bar top LED illuminates red and the output voltage of the Mass Sine Ultra is limited. The Mass Sine Ultra shuts dow n if this overloa d or short circuit lasts over 5 seconds. The Mass Sine Ultra will automatically restart after shutdown. After 5 failed start attempts the Mass Sine Ultra shuts down permanently, the Power bar top LED stays blinking red. You can restart the Mass Sine Ultra only by switching the unit manually off and on with the main switch on the Mass Sine Ultra after the overload or short circuit is removed. Restart is also possible via MasterBus and when DC supply was interrupted.
3.4.2 Overheating
The Mass Sine Ultra shuts down in t he event of ov erheating. Overheating is most likely caused by:
heavy or non-resistive loads operating for a longer period,
high ambient temperature,
disrupted air flow (dust or too little space).
The Mass Sine Ultra i s pow ered up autom atically as soon as the temperature drops below the factory default threshold.
3.4.3 Under and over voltage
The DC-input of the Mass Sine Ultra is protected against over and under voltage. See specifications. The Mass Sine Ultra switches off if the DC-input voltage is out of range.
3.4.4 Dynamic DC input window
Figure 3-4: Dynamic DC input window
The Mass Sine Ultra was designed to switch off depending on both the battery voltage and current. The reason for this is that low current l oad s cau se a s mal l volt a ge drop but they are responsible for sev ere bat tery damage. By switchin g the Mass Sine Ultra off at higher voltages with lower currents, your batteries are saved. Shown in figure 3 .4 is the graph for a 24 V lead acid batt er y . The horizontal axis shows the battery current. The graph shows three lines:
(1) Low voltage switch on. Above this voltage the Mass
Sine Ultra switches On.
(2) Low voltage switch off with delay. Under this line the
Mass Sine Ultra sw itches O ff a fter a d elay. N ote th e 2% point at which the line drops 1 Volt. From 2% till 100% of nominal battery current it declines 2 Volts.
(3) Low v oltage switch off without delay. Under this line t h e
Mass Sine Ultra switches off without delay.
3.5 Maintenance
Checking all connections every 6 months is required. Further, no specific maintenance is required. If necessary, use a soft clean cloth to clean the Mass Sine Ultra. Do not use any liquids or corrosive substances, such as solvents, alcohol, petrol or abrasive components.
2
4V
22V
17V
0
2%
10
0
% 200%
21V 19V
1
2
3
U
% I
nom
Page 10
EN / Mass Sine Ultra
10
3.6 Daily use, MasterBus monitoring
The MasterBus Monitoring page off ers th e opt ion to do your daily settings and it shows your setti ngs fr om the Configuration page. The table below shows the Mass Sine Ultra monitoring values. The values with a default value are adjustable.
Value
Meaning
Default
Range
Group-item
Index
General
Device state The state of your Mass Sine Ultra Standby; Inverting; Alarm;
Overload; Low battery
1-1 16
Inverter Option to switch Off the inverter to
prevent depleting of your batteries
On On, Off 1-3 20
Mode
User mode
Disabled; On; Error; Shutdown
1-4
60
Battery (DC)
Main battery
Battery voltage
0..32 V
2-2
6
Main battery Approximate battery current (minus
is discharging)
-500..0 A 2-3 7
AC output
AC output
AC output voltage
0..300 V
5-1
10
AC output
AC output current
0..70 A
5-2
11
AC output
AC output power
0..20000 W
5-3
98
Page 11
EN / Mass Sine Ultra
11
4 INSTALLATION
During installation and commissioning of the Mass Sine Ultra, the Safety Guidelines and Warnings are applicable at all times. See chapter 2 of this manual.
4.1 Unpacking
In addition to the Mass Sine Ultra the delivery includes:
this user’s manual;
MasterBus terminating device.
After unpacking, check the contents for possible damage. Do not use the product if it is damaged. If in doubt, contact your supplier. Check from the identification l abel ( see se ction 1.7) w hether your Main battery voltage is the same as the DC-input voltage of the Mass Sine Ultra (e.g. 24 V main battery set f or a 24 V input voltage). Also check that the AC output voltage and output power of the Mass Sine Ultra complies with your system and loads.
4.2 Environment
Obey the following stipulations during installation:
The Mass Sine Ultra is designed for indoor use only.
Ambient temperature: -25˚C to 60˚C, (power derating
above 40˚C).
Maximum usage/installation height: 2000 m.
Humidity: 0-95% non-condensing.
Mount the Mass Sine Ultra on a solid surface, with the
connecting cables downwards.
Make sure that the hot air produced d uring o peration c an be discharged. The Mass Sine Ultra must be mounted in such a way that obstruction of the airflow through the ventilation openings will be prevented.
No objects must be located within a distance of 10 cm / 4 inch around the Mass Sine Ultra. Keep at least 15 cm / 6 inch free space below the Mass Sine Ultra.
Do not locate the Mass Sine Ultra in the same compartment as the batteries.
Do not install the Mass Sine Ultra straight above the batteries because of possible corrosive fumes.
4.3 Wiring
The wiring is connected inside the connec tion compart ment. If necessary, the w iring can be f ed from th e top to the bottom side of the cabinet along the back of the cabinet. Always feed the wiring through the strain reliefs of the cabinet, and then connect the wiring to the terminals. Connect the phase line w ire to termi nal L, th e neut ral wir e to terminal N and the ground wire to terminal PE, see figure 4-
3.
Figure 4-3: AC terminal connection
4.3.1 AC-wiring
For a safe installation the corr e ct wir e cross sectio n must be applied. Don’t use a cross section that is smaller than indicated. See table below to select the appropriate cross section for the AC wiring:
AC-Current
Minimum cross section:
0-20 Amp
2.5 mm²
AWG 13
20-32 Amp
4 mm²
AWG 11
32-48 Amp
6 mm²
AWG 9
48-80 Amp
10 mm²
AWG 7
Recommended wire colours (refer to local rules and fig 5-1)
Wire colour
Meaning
Connected to:
Brown or black
Phase
L1
Blue
Neutral
N
Green/Yellow
Earth
PE / GND
Page 12
EN / Mass Sine Ultra
12
4.3.2 DC wirin g
Keep in mind that high current will pass through the DC wiring. Keep the cable length as short as possible, this will keep the system efficiency as high as possible. The table shows recommended DC wire size:
Model
Minimum cross section:
24/4000
70 mm²
2/0 AWG
Use M8 cable lugs termina ls on the ends of t he wires. T hese lugs should be crimped with a proper crimping tool. Use the following wire colours for DC wiring (refer to local rules):
Wire colour
Meaning
Must be connected to:
Red
Positive
+ (POS)
Black
Negative
– (NEG)
Position the positive and negative cables next to each other to limit the electromagnetic field around the cables. The negative cable should be connected directly to the negative post of the battery bank or the ground side of a current shunt. Do not use the chassis frame or hull of the ship as the negative conductor. Tighten the Mass Sine Ultra connections securely (15 - 20 Nm / 130 - 175 In-Lbs.). The positive battery cable must be fused and connected to the positive post of the battery bank. Fuse rating d epends on the applied cable cross section. The fuse with fuse holder is available from your local Mastervolt distributor or Customer Service Representative.
4.3.3 AC safety grounding
WARNING
The ground wire offers protection only if the cabinet of the M ass Sine Ultra i s connect ed to the safety ground.
The ground stud is positioned at the left foot of the cabinet, see the overview on page 2, position 7. Connect the earth terminal (PE / GND) t o the hull or the chassis w ith a minimum 10 mm².
CAUTION!
For safe installation it is necessary to:
connect the neutral conductor (N) of the AC output to the earth (PE / GND);
insert a Residual Current Device (earth leakage switch) of 30 mA in the AC output of the Mass Sine Ultra.
Refer to local regulations on these issues!
4.4 Things you need
Make sure you have all the p arts you need to install the Mass Sine Ultra:
Mass Sine Ultra (included);
AC wiring. Double insulated three wire cable with wire
colours according to the locally applicable standards. The applicable length and wire diameter depend on the electrical installation. See section 4.3.1;
DC-wiring to connect the DC connections of the Mass Sine Ultra to the DC-distribution. See section 4.3.2;
DC-fuse holder with a DC-fuse, to be integrated in the positive DC-cable. For specific ation s see section 4.3.2;
Screws / bolts (Ø 6 mm) (with plugs) to mount the ca binet to a surface. Use mounting materials which are suitable to carry the weight of the Mass Sine Ultra;
Batteries. Refer to chapter 8 for specifications;
Appropriate and reliable cable terminals, cable lugs,
battery terminals and cord end terminals.
We recommend as a minimum tool kit:
Socket wrench 13 mm to fix the DC-input (battery) cables;
Flat blade screw driver 1.0 x 4.0 mm to fix the screw terminals;
Tools to fix the screws / bolts (Ø 6 mm) (with plugs) to mount the cabinets to a surface;
Philips screw driver to open the connection area of the Mass Sine Ultra.
4.5 Removal of the front lid
Figure 4-5.1: Removal of the front lid
Steps: 1 Loosen the two screws that secure th e front cover plat e; 2 Lift the front cover plate from the cabinet. See figure
4-5.2.
Page 13
EN / Mass Sine Ultra
13
Figure 4-5.2: Front lid removed
WARNING
The front panel is never to be removed while the Mass Sine Ultra is still connected to a power source!
4.6 Mounting the cabinet to a surface
M6 bolts can be used for the mounting of the cabinet vertically to a surface, like shown on the front page of this manual and figure 4-6. Take the following steps to mount the cabinet: 1 Determine the four mounting spots on basis of the
outline drawings. 150 mm of free space is required below the Mass Sine Ultra for installation and DIP
switch operation; 2 Screw the topmost bolts somewhat into the wall; 3 Hang the cabinet with its key holes over the two bolts
and screw these bolts finger tight, so shifting is still
possible; 4 Place the two lowermost bolts; 5 Fasten all bolts securely; 6 Fix cabinet to the surface with remaining two bolts.
4.7 Wiring instructions
WARNING
Have installation work done by a licensed electrician only. Before connecting the wiring, make the AC distribution as well as the DC distribution voltage free. Move the main switch to the “Off”-position.
CAUTION!
Short circuiting or reversing polarity may lead to serious damage to the batteries, the Mass Sine Ultra, the wiring and/or the terminal connections. Fuses between the batteries and the Mass Sine Ultra cannot prevent damage caused by reversed polarity. The damage as a result of reverse polarity is not covered by the warranty.
CAUTION!
Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore tighten all connections well. Only use cables of the correct size.
Figure 4-6: Mount the Mass Sine Ultra upright to a solid surface that is part of the construction
Page 14
EN / Mass Sine Ultra
14
4.8 Installation overview
Figure 4-8: Installation overview for one Mass Sine Ultra
CAUTION!
Ensure correct polarities, cross sections and fuses for all wiring. An RCD according to local regulations must be connected to the output.
Page 15
EN / Mass Sine Ultra
15
4.9 Setting up a MasterBus network
All devices that are suitable for MasterBus are marked by the MasterBus symbol.
MasterBus is a fully decentralized data network for communication between the different Mastervolt system devices. It is CAN-bus based which has proven itself as a reliable bus-system in automotive applications. MasterBus is used as power management system for all connected devices, such as the inverter, battery charger, generator and many more. This enables communication between the connected devices, for instance to start the generator when the batteries are low. MasterBus reduces complexity of electrical systems by using UTP patch cables. All system components are simply chained together. Therefore each device is equipped wit h two MasterBus data ports. As only a few MasterBus cables are needed, installation and material costs are reduced importantly. New devices can be added to the existing network easily. Consequently the MasterBus network is highly flexible for extended system configuration. Mastervolt also offers several interfaces like the Modbus interface, making even non-MasterBus devices s uitable to oper ate in the M asterBus network. For central m onitoring and contro l of the c onnected devices Mastervolt offers different panels, lik e the full colour MasterView System panel. All monitoring panels can be used for monitoring, control and configuration of all connected MasterBus equipment.
CAUTION!
Never connect a non-MasterBus device to the MasterBus network directly! This will void warranty of all MasterBus devices connected.
4.10 How to set up a MasterBus network
Every MasterBus device is equipped with two data ports. When two or more devices are connected via these ports, a local data network ca lled t he M asterB us is for med. Ke ep t he following rules in mind:
Place a terminating device on both network ends.
OK
Connections between the devices are made by standard straight UTP patch cables.
OK
At least one device in the network must be MasterBus powering (see specifications). As all powering devices are galvanic isolated, multiple powering devices are
allowed.
OK
Do not make ring networks.
Do not make T-connections in the network.
Page 16
EN / Mass Sine Ultra
16
5 INSTALLATION OF MULTIPLE CLUSTERE D MASS SINE ULTRA’S
This installation instruction serves as a guideline for the safe and effective installation of the Mass Sine Ultra in a multiple configuration, i.e.
a parallel configuration, or
a split phase configuratio n, or
a three phase configuration, or
a combination of a split ph ase or three phase in a parallel
configuration.
5.1 Purpose of a multiple configuration
There are several reasons for a multiple configuratio n of t he Mass Sine Ultra:
If more output p ower is neede d than one M ass Sine Ultra
can supply, two up to ten Mass Sine Ultra’s can be connected in parallel;
If redundancy is required, Mass Sine Ultra’s can be
connected in parallel to maintain reliable power supply if one of the Mass Sine Ultra’s fails in operation;
Three Mass Sine Ultra’s can be connected in a 3-phase
configuration to supply three phase AC power. By connecting more Mass Sine Ultra’s in parallel as well, virtually unlimited three phase power can be made available.
5.2 General installation guidelines
When using Mass Sine Ultra’s in a multiple configuration, the following requirements are:
Only identical Mass Sine Ultra’s with the same article numbers may be used in a multipl e configuration;
Maximum number of Mass Sine Ultra’s in parallel: 10;
Maximum number of Mass Sine Ultra’s in a three phase
-parallel configuration: 3 x 3;
Installation and commissioning of multiple Mass Sine Ultra’s requires configuration of MasterBus settings and programming of MasterBus events by means of a MasterBus control panel or a PC (in combination with a MasterBus USB-interface) with MasterAdjust software installed. The installer must be familiar with MasterBus configuration tools and the programming of such events ;
Allow sufficient ventilation to prevent build-up of hot air. When installing multiple Mass Sine Ultra’s either side by side or vertically abov e each ot her, at lea st 10 cm / 4 inch free space must be kept in between the units. If necessary, adequate measures must be taken to avoid one Mass Sine Ultra heating up the other.
Figure 5-3: Two Mass Sine Ultra’s connected in parallel
Page 17
EN / Mass Sine Ultra
17
5.3 Parallel configuration diagram
Figure 5-3 shows a basic installation diagram of two Mass Sine Ultra’s in parallel. B oth M ass S ine Ultra’s are supplying AC to output-1 and the outputs are connected in parallel. All corresponding cables must be the same length. The connection compartment of two Mass Sine Ultra’s is displayed, together with the communication module (figure 0-1, item 8 and 9).
5.4 Three phase configuration diagram
See figure 5-4. Three Mass Sin e Ultra’s are show n in a three phase configuration. Each Mass Sine Ultra is connected to a phase, and so is delivering power to that phase. All corresponding cables must be the same length. The connection compartment of three Mass Sine Ultra’s is displayed, together with the communication module. As you see, the MasterBus network has a terminator on both ends.
Figure 5-4: Three Mass Sine Ultra’s connected in 3-phase
5.5 Multi Mass Sine Ultra communication
Within the MasterBus databus communication protocol, Mass Sine Ultra’s connected in a parallel, split phase or a three phase configuration shall be configured as a so called “cluster”. After establishing such cluster, it can be operated through MasterBus as one single single power conversion unit.
Always connect the sync cables in cluster connections!
5.6 Synchronization
Synchronization between the Mass Sine U ltra’s is necessary for parallel, split phase and 3-phase configurations. For a 3­phase configuration, three Mass Sine Ultra (groups) are connected to the phase cables with a 120 degree phase angle between them. To accomplish this, the Mass Sine Ultra’s must be able to communicate. This is done via the sync cables. Each Mass Sine Ultra has two sync ports for this.
Page 18
EN / Mass Sine Ultra
18
5.7 Configuration for multiple Mass Sine Ultra systems
The MasterBus name for a multi Mass Sine Ultra system is “Cluster“. A cluster can be a
single phase,
split phase or
3-phase
configuration, with one or more Mass Sine Ultra’s in parallel connection per phase.
5.8 MasterBus configuration for clusters
The table below shows the MasterBus configuration variables and their meaning.
Value
Meaning
Default
Range
Cluster
Phase System
Configuration of your energy system.
Single phase
Single phase,
Split phase,
Three phase
Dev. per phase
Number of Mass Sine Ultra’s in parallel connection per phase.
1
1…10
Select devices
Button to enable selection of the other Mass Sine Ultra’s in the
cluster. It opens the Phase groups to select the Mass Sine Ultra connected via MasterBus. If you wish to return to less Mass Sine Ultra’s per phase, change the Dev. per phase value and press
Select devices again.
Mass Sine
Ultra’s connected
Maximum 27
Mass Sine Ultra’s
Cluster topology
State of the topology proposed. If not enough Mas s Sine Ultra’s are available for the cluster, the topology “needs approval“.
Needs approval
Needs approval, approved
Phase L1, L2, L3
(shows in 3-ph
cluster only)
Phase groups with scrollbars for selecting multiple Mass Sine
Ultra’s per phase. After cluster activat ion the pha se mas ter and
slaves are shown.
Activate cluser
Button to set the cluster to active.
Cluster state
Indicates the cluster configurat ion state .
Inactive
Inactive, double devices, active
5.9 MasterBus monitoring for a three phase cluster
In the monitoring tab, first the data for the single Mass Sine Ultra itself is shown in the gro ups G eneral and B attery (DC ). Next are the Cluster groups (Cluster L1, etc.). Per phase they show the following data respectively.
Value
Variable
Meaning
Cluster L1 out
AC output 1
V
A
W
AC output 1 voltage
AC output 1 current
AC output 1 power
For a three phase system the monitoring page tabs shows the following;. Cluster L1 out shows the values for the first phase output. If more Mass Sin e Ultra’s are clustered per phase, their values are combined. Cluster L2 and L3 are displayed the same way as Cluster L1. The tab with AC outputs shows the values for the Mass Sine Ultra you are looking at.
Page 19
EN / Mass Sine Ultra
19
5.10 MasterBus specific alarms for multi Mass Sine Ultra systems
Value
Meaning
Sync error
Synchronization error. The Mass Sine Ultra switched to standby, there is no output.
Config error
Configuration error. This alarm is triggered
when more Mass Sine Ultr a’s are needed for
a cluster than available in the system.
Install error
Error in the system installation, for instance an expected slave is not in the Sync network.
If one Mass Sine Ultra is in alarm, it switches Off together with the other Mass Sine Ultra’s in the same c luster. This applies for parallel, split phase and 3-phase configur at i ons.
5.11 DIP switch settings for two Mass Sine Ultra’s in parallel
The DIP switches have a combined function for parallel settings of two Mass Sine Ultra’s. See table below and section 6.1. MasterBus configuration is necess ary for more Mass Sine Ultra’s in a parallel connection.
By operating the DIP switches you will lose all previous cluster configuration!
DIP switch #
Meaning
1 2 Parallel connection
0 0 Mass Sine Ultra as stand-alone device
1 0 Mass Sine Ultra as Master device
0 1 Mass Sine Ultra as Slave devi ce
5.12 Operation of multiple Mass Sine Ultra systems
If connected in a more phase or parallel configuration, it is important which Mass Sine Ul t ra you se lected a s the ma ster and which as the slave(s). Operation is done via the main switch on the master. The slave Mass Sine Ultra’s must be switched On already but they follow the master. If the master is switched On or Off, the sl aves fol low. I f there is m ore th an one master, for instance in a three phase by two parallel configuration (3X2), operation is done on the L1 master.
Page 20
EN / Mass Sine Ultra
20
6 CONFIGURATION
The Mass Sine Ultra is provided with a group of DIP­switches to adjust the Mass Sine Ultra according to the specifications of the electrical installation, see figure 6-1. DIP-switch settings are 0 for default values. The Mass Sine Ultra also features the more sophisticated MasterBus configuration. Previously done MasterBus settings are overruled by the DIP-switch settings and they are greyed out in the menu. When a DIP-switch is set to 0, the corresp onding M asterBus setting becomes default too, regardless the previo us setting.
6.1 Configuration via dip-switches
The DIP-switches are located in the connection compartment. Figure 6-1 shows the location of the DIP­switches and the print on the inside of the front cover plate.
Figure 6-1: DIP-switches and cover print
DIP switch
Function
A1-A2
Parallel mode
0-0: Stand alone
1-0: Master 0
0-1: Slave
1-1: NA
A3
Output frequency inverter
0: 50 Hz
1: 60 Hz
A4
Energy saving mode
0: off
1: on (scan mode)
A5-A6
N.A.
A7-A8 Main battery type 0-0: Flooded 1-0: Gel 0-1: AGM 1-1: Flooded
traction
Page 21
EN / Mass Sine Ultra
21
6.2 MasterBus configuration
Parameters below can be changed via the MasterBus network. See applicable user’s manuals for details. DIP switch settings overrule MasterBus settings. If DIP switches are not set to default, the corresponding MasterBus configuration is greyed out.
Value
Meaning
Default
Adjustable range
Device
Language Language that is displayed on a
monitoring device connected to the
MasterBus.
English English, Nederlands, Deutsch,
Français, Castellano, Italiano,
Norsk, Svenska, Suomi, Dansk
Name Name of this particular device in
MasterBus. This name will be recognized by all devices that are connected to the
MasterBus network.
MSU [Serial number]
All names with a maximum of 12 characters.
Lock config Option to lock the configuration (installer
login).
Not checked Not checked, Checked
Factory settings Option to reset the configuration to
default (installer login).
Not selected Not checked, Selected
System
MasterBus power Checkbox to have the Mass Sine Ultra
power MasterBus or not.
Checked Checked, Not checked
Inverter
Voltage
AC voltage.
230 V
180-260 V
Frequency
AC frequency.
50 Hz
50 Hz, 60 Hz
Energy save mode
Option to enable Energy save mode.
Not checked
Not checked, checked
Scanning below The Mass Sine Ultra starts scanning
below this inverted power level in Energy
save mode.
10 W 10-250 W
Battery type Select the battery type. Flooded (Lead acid
wet cell)
User defined, Flooded, Gel, AGM, Spiral, MLi, Flooded traction, Nickel
Cadmium
The below dynamic DC window is configurable when Battery type is User defined. Refer to section 3.4.4.
DC high off
High battery voltage for inverter switch off
32.00 V
26.00-32.00 V
DC high on High battery voltage for inverter switch on
after DC High Off alarm.
29.00 V 26.00-32.00 V
DC low off I=0% Low battery voltage at which the inverter
switches off when the battery current is
0-2% of nominal.
22.00 V 19.00-26.00 V
DC low off I=2% Low battery voltage at which the inverter
switches off when the battery current is
2% of nominal.
21.00 V 19.00-26.00 V
DC low off 100% Low battery inverter swit ch off voltage,
batt. current 100%.
19.00 V 19.00-26.00 V
DC low on Low battery inverter switch on voltage at
DC Low off alarm.
24.00 V 20.00-26.00 V
DC low off delay Delay time before inverter swit che s off on
a low battery voltage.
30 s 0-30 s
Page 22
EN / Mass Sine Ultra
22
6.2.1 MasterBus alarms
This is the Mass Sine Ultra list of MasterBus alarms with their meaning.
Alarm
Description
Overload
Mass Sine Ultra in overload. The loads exceed the nominal inverter power.
Over temperature
Internal temperature of the Mass Sine Ultra is too high.
Battery low
Battery voltage is too low.
Battery high
Battery voltage is too high.
Sync. error
Two or more Mass Sine Ultra’s in a multiple configuration do not synchronize well.
Config error
Configuration error, most often in multi inverter installations. Check M asterBus and DIP sw it ch sett ing s.
Install error
Installation error around the Mass Sine Ultra, not inside the unit. Check all connections.
System error
Internal Mass Sine Ultra er ror . Contac t your M asterv olt supp li er.
6.2.2 List of event sources
This is the Mass Sine Ultra list of event sources. These can initiate an event at another MasterBus connected device.
Event source
Description
Disabled
(no event programmed)
Inverting
The Mass Sine Ultra is in Inverter mode
Overload
The inverter current is too large
Low bat
The main battery voltage has dropped below the Low bat value
Alarm
A Mass Sine Ultra alarm has been triggered
External fan
Trigger point to activate an external cooling fan
6.2.3 List of event commands
This is the Mass Sine Ultra event commands list. Other MasterBus connected devices can be configured to initiate these commands.
Event command
Description
Inverter On/Off
Change the Mass Sine Ultra inverter state to On/Off
Page 23
EN / Mass Sine Ultra
23
7 COMMISSIONING, DECOMMIS SI O NING
7.1 Commissioning
CAUTION!
Check the polarity of all wiring before commissioning: plus connected to plus (red cables), minus connected to minus (black cables). The DIP-switches must be adjusted prior to commissioning; see chapter 6.
Follow the steps descr ibed below to switch on t he Mass Sine Ultra. 1 Tighten all strain reliefs; 2 Check all wiring and connections; 3 Close the front cover plate of the connection
compartment;
4 Pla ce the DC-fuse(s) of the DC-distribution to connect
the batteries to the Mass Sine Ultra.
WARNING
When placing this fuse, a spark can occur, caused by the capacitors used in the Mass Sine Ultra. This is particularly dan gerous in pla ces with insufficient ventilation, due to the gassing of the batteries an explosion can occur and avoid having flammable materials close by.
Now the Mass Sine Ultra is ready for operation.
7.2 Decommissioning
If it is necessary to put the Mass Sine Ultra out of operation, follow the instructions in order of succession as described below: 1 Move the Main-switch of the Mass Sine Ultra to “Off”; 2 Remove DC-distribution fuses and/or disconnect the
batteries;
3 Open the connection compartment of the Mass Sine
Ultra;
4 Check with a suitable voltage meter whether the input
and the output of the Mass Sine Ultra are voltage free;
5 Disconnect all the wiring.
Now the Mass Sine Ultra can be demounted in a safe way.
7.3 Trouble shooting
If a failure occurs, the origin of the failure is displayed by means of the LED’s at the front of the Mass Sine, see figure 7-3.
Figure 7-3: Error LED’s
The table at section 7.3.1 shows the meaning of the error indications and their solutions, togeth er with other directions. If you cannot solve a problem using this table, contact your local Mastervolt Service Centre. See www.mastervolt.com. Make sure you have the following information present if you have to contact your local Masterv olt Service Centre to solve a problem:
Article and serial number (see section 1.7).
Software version (see summary page in MasterA dj ust or
the Configuration page in MasterView control panel).
Page 24
EN / Mass Sine Ultra
24
7.3.1 Trouble shooting table
Illuminating LED’s
MasterBus alarm
Explanation / Possible cause
What to do
Normal operation and warnings
None The Mass Sine Ultra is switched
off manually.
Switch on the Mass Sine Ultra by
means of the main switch.
(1) red MB monitoring:
Overload
Inverter in overload, inverter
exceeds max continuous power.
Check the load connected. Check the
connections.
(3) red
Battery low/high
Battery voltage low/high.
Stop inverting
Errors (Mass Sine Ultra shuts down)
(1) and (3) red,
(2) yellow
Over temperature Mass Sine Ultra too hot. Restart
when alarm is over.
Check ventilation. Reduce load.
(1) and (3) red System error,
Sync error,
Config error
Communication disturbed. Configuration wrong.
Check communication cables and connectors
Permanent errors (manual reset required)
(1) and (3) blinking fast red
Overload Number of inverter overload
restart attempts exceeded.
Reduce the output loads, shut the
Mass Sine Ultra Off and On.
System error
Hardware issue.
Shut the Mass Sine Ultra Off and On.
(4) blinking fast Install error Installation error. Correct installation, shut the Mass
Sine Ultra Off and On.
Page 25
EN / Mass Sine Ultra
25
8 TECHNICAL DATA
8.1 Specifications
Mass Sine Ultra
24/4000
Article number
26024000
Inverter specifications
Nominal battery voltage
24 V
Inverter output voltage
230 V (±2%)
Frequency
50/60 Hz (±0.005%) selectable
Continuous power@Tamb=25˚C, cos phi = 1
4000 W
Continuous power@Tamb=40˚C, cos phi = 1
4000 W
Max. peak load
7000 W
Output waveform
True sine wave, Thd < 1 % under standard conditions
Max. efficiency
≥ 92%
DC input voltage range
19 – 32 V programmable
Dynamic input window battery Current dependent switch-off levels, vary with set battery type (Gel /
AGM settings below)
Switch off voltage low battery@ load ≤ 2%
22.0 V(±2%)
Switch off voltage low battery@ load 2-100%
21.0 V - 19.0 V (±2%)
Switch on voltage low battery
24.0 V(±2%)
Switch off voltage high battery
32.0 V(±2%)
Switch on voltage high battery
29.0 V(±2%)
Max. ripple on DC @ full load
10% RMS
Nominal DC current at full load
200 A
Recommended batteries
200 – 600 Ah
No load, DC drain
Off mode (hard switched)
0 W
Inverter off mode (remote)
4 W
Normal operation mode
16 W
Parallelling/3-phase
Parallel stacking
Yes, up to 10 standard
3-phase configuration
Yes, up to 3 x 3
General specifications
Dimensions (H x W x D mm)
472 x 318 x 178
Weight
15 kg
Protection degree
IP23 (vertical wall mounting)
Safety class
IEC protection class I
Grounding
Ground stud (ABYC compliant)
Operating temperature
-25˚C to 60˚C, above 40˚C derating
Overvoltage category
Mains: OVIII
Pollution degree
PDII
Relative humidity Protected against humidity and condensing air by conformal coating,
max 95% relative humidity, none condensing
Standards, approvals & listings
CE, ABYC
Options & features
Front panel display
Yes, shows inverter power, input/output state and includes on/off switch
MasterBus functionality
MasterBus powering
Standard on, selectable
Overload protection
AC Output:
Short circuit protection
Yes
Battery input:
Short circuit protection
Yes
Reversed polarity protection
No
Page 26
EN / Mass Sine Ultra
26
8.2 Dimensions
Figure 8-1: Dimensions in mm
Page 27
EN / Mass Sine Ultra
27
9 ORDERING INFORMATION
Part number
Description
77049200
ANL Fuse 200 A
607006
ANL Fuse base
701
Battery switch 275 A
6502000010
Sync cable for parallel and three phase operation, 1 meter / 3 ft
6502000030
Sync cable for parallel and three phase operation, 3 meter / 9 ft
6502001030
Sync cable for parallel and three phase operation, 6 meter / 19 ft
6502100100
Sync cable for parallel and three phase operation, 10 meter / 33 ft
6502100150
Sync cable for parallel and three phase operation, 15 meter / 49 ft
77040000*
MasterBus terminating device
77040020
MasterBus connection cable (UTP patch cable), 0,2 m / 0.6 ft
77040050
MasterBus connection cable (UTP patch cable), 0,5 m / 1.6 ft
77040100
MasterBus connection cable (UTP patch cable), 1,0 m / 3.3 ft
77040300
MasterBus connection cable (UTP patch cable), 3,0 m / 10 ft
77040600
MasterBus connection cable (UTP patch cable), 6,0 m / 20 ft
77041000
MasterBus connection cable (UTP patch cable), 10 m / 33 ft
77041500
MasterBus connection cable (UTP patch cable), 15 m / 49 ft
77042500
MasterBus connection cable (UTP patch cable), 25 m / 82 ft
77045000
100 m / 330 ft MasterBus cable (UTP cable)
77040010
MasterBus RJ45 conn 8-pol e 25 pcs
77040015
Cover for RJ45 conn. -set a 25 st
77050000 Complete set to assemble UTP patch cables: 100 m / 330 ft UTP cable, 50 pcs. modular jacks and
crimping tool
77030100
MasterBus – USB interface, required when using MasterAdjust or MasterView System software.
77010305
MasterView Easy, Touch screen to control and monitor all MasterBus products
77010400
MasterView System, Full-colour touch screen to control and monitor all Mas terBus products
77020100 MasterShunt 500, DC-distribution module for exact readout of battery voltage, charge / discharge current,
and state of charge. Continuous rating: 250 A, peak current: 500 A
77020200 DC-Distribution 500.
The Mastervolt DC Distribution offers fused DC connections to install up to four different devices
* Standardly included with the delivery of the Mass Sine Ultra
Mastervolt can offer a wide range of products for your electrical installation, including automatic AC transfer switches, remote control panels and DC distribution kits. See our website www.mastervolt.com for an extensive overview of all our products.
Loading...