Mastervolt Mass SINE 24/1000, Mass SINE 12/1200, Mass SINE 12/1000, Mass SINE 12/2000, Mass SINE 48/2500 User Manual

...
Page 1
MASTERVOLT Snijdersbergweg 93, 1105 AN Amsterdam The Netherlands Tel.: +31-20-3422100 Fax: +31-20-6971006
GEBRUIKERSHANDLEIDING/ USER’S MANUAL
BETRIEBSANLEITUNG / MODE D’EMPLOI
Mass SINE 12/1000 & 24/1000 - 117V / 60Hz
Mass SINE 12/1200 & 24/1500 - 230V / 50Hz
Mass SINE 12/2000, 24/2500 & 48/2500 - 230V / 50Hz
Mass SINE 12/2000 & 24/2500 - 117V / 60Hz
Page 2
22
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
CONTENTS
1 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
1.1 Use of this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
1.2 Guarantee specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
1.3 Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
1.4 Validity of this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
1.5 Liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
1.6 Changes to the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
2 SAFETY GUIDELINES AND MEASURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
2.1 Warnings and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
2.2 Use for intended purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
2.3 Organizational measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
2.4 Maintenance & repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
2.5 Warning for specific dangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
2.6 Warning regarding life support applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Page 3
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
23
3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.1 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.3 Mounting of the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.4 Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5 Connecting the remote control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.6 Commissioning after installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.7 Automatic switching between MASS inverter, the AC genset and/or shore power . . . . . . . . . . . . . .30
4 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
4.2 Switching on and off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
4.3 Indicator lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
4.4 Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
5 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
6 TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
7 TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
8 ENERGY SAVING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
8.1 Low energy mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
8.2 Stand by mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
9 EC DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
CONTENTS
Page 4
24
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
1 GENERAL INFORMATION
1.1 USE OF THIS MANUAL
This manual serves as a guideline for safe and effec­tive operation, maintenance and possible correction of minor malfunctions of the inverter. It is therefore obligatory that every person who works on or with the inverter must be completely familiar with the con­tents of this manual, and that he/she carefully follows the instruction contained herein. Installation of, and work on the inverter, may be car­ried out only by qualified, authorized and trained per­sonel, familiar with the locally applicable standards and taking into consideration the safety guidelines and measures (chapter 2 of this manual).
1.2 GUARANTEE SPECIFICATIONS
Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications. Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in this user's manual, then damage may occur and/or the unit may not fulfil its specifications. All of these matters may mean that the guarantee may become invalid.
1.3 QUALITY
During their production and prior to their delivery, all of our units are exhaustively tested and inspected.
The guarantee period is two years.
1.4 VALIDITY OF THIS MANUAL
All of the specifications, provisions and instructions contained in this manual apply solely to the Master­volt-delivered standard versions of the MASS inver­ter.
1.5 LIABILITY
Mastervolt can accept no liability for:
damage due to use of the inverter;
possible errors in the manuals and the results thereof.
CAREFUL ! Never remove the type number plate.
Important technical information required for service, maintenance & secondary delivery of parts can be derived from the type number plate.
1.6 CHANGES TO THE INVERTER
Modifications to the inverter may be carried out only after the written permission of Mastervolt.
GENERAL INFORMATION
Page 5
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
25
2.1 WARNINGS AND SYMBOLS
Safety instructions & warnings are marked in this
manual by the following symbols:
CAREFUL ! special data, restrictions and rules with regard to preventing damage.
WARNING refers to possible injury to the user or significant material damage to the charger if the user does not (carefully) follow the procedures.
2.2 USE FOR INTENDED PURPOSE
1 The inverter is constructed as per the applicable
safety-technical guidelines.
2 Use the inverter only:
in a technically correct condition;
in a closed, well-ventilated room, protected against rain, moisture, dust and non conden­sing circumstances;
observing the instructions in the user's ma­nual.
Never use the inverter in situations where there is danger of gas or dust explosion!
3 Use other than as mentioned above is not consi-
dered to be consistent with the intended purpo­se. Mastervolt is not liable for any damage resul­ting from failure to comply with the above.
2.3 ORGANIZATIONAL MEASURES
The user must always:
have access to the user's manual;
be familiar with the contents of this manual. This applies in particular to chapter 2, Safety Guidelines and Measures.
2.4 MAINTENANCE & REPAIR
1 If the inverter is switched off during maintenance
and/or repair activities, it should be secured against unexpected and unintentional switching on:
switch off the connection with the batteries or remove the inverter fuse;
be sure that third parties cannot reverse the measures taken.
2 If required, use only original spare parts. The in-
verter has no serviceable parts, except the fan and pcb.
2.5 WARNING FOR SPECIFIC DANGERS
1 Connect the earth of the inverter output to the
central ground and use a RCCB switch in the in­verter output.
2 Protect the DC wiring with a fuse, according to
the guidelines in this users manual.
3 Check the wiring at least once a year. Defects
such as loose connections, heat damaged cables etc. must be corrected immediately.
SAFETY GUIDELINES AND MEASURES
2 SAFETY GUIDELINES AND MEASURES
Page 6
26
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
4 Do not work on the inverter or the system if it is
still connected to a current source. Only allow changes in your electrical system to be carried out by qualified electricians.
5 Connection and protection must be done in ac-
cordance with local standards.
6 Before opening the cabinet of the inverter, switch
off the mains and remove the inverter fuse.
Setting the switch on the front of the inverter to ‘off’ is not sufficient !
2.6 WARNING REGARDING LIFE SUPPORT APPLICATIONS
Mastervolt products are not sold for applications in any medical equipment intended for use as a component of any life support system unless a spe­cific written agreement pertaining to such intended use is executed between the product manufacturer and Mastervolt. Such agreement will require the equipment manufacturer either to contract for addi­tional reliability testing of the Mastervolt parts and/or to commit to undertake such testing as a part of the manufacturing process. In addition such manufactu­rer must agree to indemnify Mastervolt from any claims arising from the use of Mastervolt parts in the life support equipment.
SAFETY GUIDELINES AND MEASURES
Page 7
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
27
3 INSTALLATION
During installation and commissioning of the MASS inverter, the Safety Guidelines and Measures are applicable at all times. See chapter 2 of this manual.
3.1 ENVIRONMENT
Install the MASS inverter in a dry, well ventilated, dust free situation. Locate the inverter as close as possible to the DC distribution in order to keep the battery cables short. Do not locate the inverter in the same compartment as the batteries. The heat of the inverter is discharged by a fan with a variable speed, from the top and side of the cabinet to the bottom of the cabinet.
When fitting the inverter be sure that:
the air flow is not obstructed;
the inverter is mounted vertically;
no water and/or dust can enter the cabinet.
Never use the inverter in locations where there is gas or explosion danger!
3.2 WIRING
The routing of the wires has influence on the EMC behaviour of the system in which the inverter is a component. This is caused by the fact that wires are excellent receivers and transmitters of radio frequen­cy electro magnetic interference. Most problems ori­ginate from mutual influencing between wires and cables.
Never remove the type number plate! Important technical data required for servi­ce, maintenance and later delivery of parts can be obtained from the type number plate (see fig. 1).
INSTALLATION
Fig. 1: Type number plate Mass Sine inverter.
Type: SINE 12/1200 inverter Part no: 012020500 Input: 12V DC (10 ... 16V) Output: 230V 50Hz sine wave Output power: 1200VA
Page 8
28
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
3.3 MOUNTING OF THE CABINET
To mount the MASS inverter follow the described instructions:
1 Determine the mounting points (see fig. 2 and 3).
2 Drill mounting holes for the cabinet.
3 Mount the MASS inverter with four screws or
bolts (M6) to the wall.
4 Fasten all screws or bolts securely.
INSTALLATION
Fig. 2: Mounting points Mass Sine 12/1200, 24/1500 230V / 50Hz and Mass Sine 12/1000, 24/1000 117V / 60Hz.
Fig. 3: Mounting points Mass Sine 12/2000, 24/2500, 48/2500 230V / 50Hz and Mass Sine 12/2000, 24/2500 117V / 60Hz.
Page 9
INSTALLATION
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
29
3.4 CONNECTING
The Mastervolt Service Centers have all accessories available, e.g. battery terminals and supply cables in all sizes.
Before beginning to connect the wiring, make the AC and DC distribution voltage­free.
Opening the front panel
Remove the two Philips screws from the front panel of the cabinet. Pull the grey front panel away from the cabinet (downwards). The terminals and cable glands are now accessible (see fig. 4).
3.4.1 Connecting AC wiring & earth wiring
General: The inverter is protected against overload and short circuit, so it is not necessary to install a fuse in the output of the inverter.
IMPORTANT!
For safe installation it is necessary to:
connect the earth (PE) and neutral (N) of the
inverter output to the central ground;
insert a RCCB (earth leakage) switch of 30mA
in the inverter output.
Check whether the voltage from the inver­ter is the same as the connected equip­ment.
The earth wire offers protection only if the inverter cabinet is connected to the earth. Connect the inverter's earth terminal (at the right hand side of the AC terminal block) to the hull or chassis.
To connect the MASS Sine inverters: Switch the on/off/remote switch to 'OFF'. The L1, N and PE terminals are situated on the left hand side inside the cabinet.
Connect the AC on-board system brown phase 1.5-
2.5 mm2wire to terminal L1, the blue 0-phase wire to terminal N and the green/yellow earth wire to terminal PE (see fig. 4).
3.4.2 DC wiring
Keep the cable length as short as possible, this will keep the system efficiency as high as possible. The recommended minimum size of the battery cables is:
12/2000 & 12/1200 &
24/2500 48/2500 24/1500
cable thickness 50 mm
2
35 mm
2
35 mm
2
The recommended length is a maximum of 6 meters. When longer cables are required, use thicker cables. When possible, use coloured (red and black) battery cables. If this is not possible, mark the cables with red and black isolation tape or heat shrink sleeve.
Battery cable connections
Pull the battery cables through the glands at the bottom side of the inverter. Keep the cable con­nection between batteries and inverter as short as possible (maximum 6 meters). Connect the black ne­gative battery cable to the negative connection bolt (right) and the red positive battery cable to the positive bolt (left) of the inverter. Cut the cables to the right length and fix, if necessary, connect cable clamps to both ends. Connect the negative cable to the negative battery pole and the positive cable via the inverter fuse to the positive red pole (see fig. 4).
Pull the battery cables through the glands before you install the cable clamps.
Page 10
INSTALLATION
30
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
CAREFUL ! Reversing positive and negative will cause major damage to the inverter. This damage is not covered by the guarantee.
CAREFUL ! Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore tighten all connections well, in order to limit tran­sistion resistance as much as possible. Use DC cables of the correct size.
3.5 CONNECTING THE REMOTE CONTROL PANEL
The remote control panel C4-RI for the MASS inver­ter comprises an off/on switch and two LEDs. The LED 'inverter on' indicates proper functioning of the inverter and the availability of 230/117V AC output voltage. The LED 'failure' indicates overload, over­temperature or too low voltage. Connect the remote control panel by means of a telephone cable (not supplied with the panel), see fig. 5.
3.6 COMMISSIONING AFTER INSTALLATION
Carefully check the polarity of the connections.
Careful ! Only insert the inverter fuse if the polarity is correct. Switching on with incorrect polarity will damage the inverter irreparably. The inverter fuse cannot prevent this.
If the connections are correct:
check whether the on/off switch is in the “OFF” position;
when inserting the inverter fuse, a spark will occur, caused by the capacitor used in the in­verter. This is normal.
The inverter is now ready for use.
3.7 AUTOMATIC SWITCHING BETWEEN MASS INVERTER, THE AC GENSET AND/OR SHORE POWER
Please contact your Mastervolt supplier if you intend to use the inverter with a genset or shore power connection. Handswitched or simple relay switching systems could damage your inverter, because of the lack off time delay. This kind of damage is not cover­ed by the warranty.
Page 11
INSTALLATION
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
31
on
failure
Inverter Control
Fig. 4: Connection of the Mass Sine.
Fig. 5: Connection cable for panel C4-RI (not delivered as a standard).
C4-RI, remote control panel.
Page 12
4 OPERATION
4.1 INTRODUCTION
The MASS SINE inverter is a fully automatic high ef­ficiency inverter, developed and produced by Mas­tervolt Amsterdam. The MASS SINE inverter is part of a series of advanced quality battery chargers and inverters supplied by Mastervolt all over the world. The MASS SINE inverter converts DC voltage to 230V AC, 50 Hz. The output voltage of 230V AC has a sinusoïdal waveform for reliable and trouble free operation of connected equipment. The inverter is protected against overload, short circuit and over temperature. In case of overload, the inverter will re­duce its output power. The MASS SINE inverter has a very high efficiency of 87%, due to the application of mosfets with high frequency switching technology.
4.2 SWITCHING ON AND OFF
Switching on:
Put the on/off/remote switch on the front of the inverter on " on". The green lamp “inverter on" lights up, and the inverter will start. If you use a remote control panel, put the on/off/remote switch to ‘re­mote’, and put the on/off switch on the remote control panel to ‘on’.
Switching off:
Put the on/off/remote switch on the front of the inverter on " off". The inverter stops and all the lights that are on, go off.
Careful ! Switching off the inverter with the switch on the front does not break the connection to the mains. The inverter remains connected to the mains.
4.3 INDICATOR LIGHTS
The functions of the indicator lights on the front are:
inverter on: inverter is switched on overload: inverter is overloaded overload + on slow: overload in ‘wait’ state overload + on fast: inverter is switched off low battery: battery voltage is too low temperature: inverter is overheated
Short description:
“inverter on”
The green light shows when the inverter is switched on.
“overload”
Glows if the inverter is overloaded. When the inverter is overloaded, the power limit reduces the output vol­tage. Depending on the load, the inverter will shut down after a short period.
“overload” + “on”
When the inverter is in a state of overload for a long period of time the inverter will switch off and the overload + on indicators will flash slowly. This takes approx. 20 seconds after which the inverter automa­tically will restart. This so called wait state gives the inverter time to recover from any heavy surge loads and the battery time to recover in case of an empty battery. When the inverter is switched of 10 times with intervals no more than 30 seconds apart the inverter will switch off permanently and the ‘overload’ and ‘on’ indicators will flash fast. To switch the inver­ter on again, you must manually switch the inverter off and on. When the output is short circuited, the inverter will go into overload. The ‘overload’ and ‘on’ indicators will flash slowly. The inverter will try to start up ten times. If the short circuit is not removed, the inverter will switch off permanently.
OPERATION
32
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
Page 13
OPERATION
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
33
Remove the short circuit and reset the inverter by switching it off and on.
“low battery”
The inverter is switched off if the battery voltage is too low (see table below). If the voltage rises above the values given below, the inverter restarts auto­matically.
model 12V 24V 48V switch off voltage 10V 19V 36V switch on voltage 11V 22V 44V
“temperature”
The inverter switches off in high ambient temperatu­res and /or sustained overload. After cooling down, the inverter restarts automatically.
4.4 ON THE REMOTE CONTROL
If you use a remote control panel, put the on/off switch to ‘remote’, and put the on/off switch on the re­mote control panel to ‘on’. The meaning of the illuminated LED’s is:
inverter on: inverter is switched on failure: inverter is overloaded, overheated
or battery voltage is too low
If the failure lamp is lit you can check the nature of the failure on the inverter front. See fig. 3 for a view of the panel.
Page 14
MAINTENANCE
34
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
5 MAINTENANCE
For a reliable and optimum function of the inverter, the following is required:
Check at least once a year if all cable and wire connections are still firmly connected.
Keep the inverter dry, clean and dust-free, in order to ensure good heat discharge.
Check the fan operation (has a lifetime of at least 10 years in normal use).
Page 15
6 TROUBLE SHOOTING
Malfunction Possible cause What to do
No output voltage High output voltage. Check battery voltage and switch and no indication lights charger off. (LED’s off).
DC fuse blown. Replace the fuse.
Switch set to remote, but no remote present. Put switch at on.
No output voltage, Flat battery. Charge the batteries, the inverter LED low batt is lit. will switch on if the battery voltage
is above 11/22/24V.
No output voltage and The inverter has been Reduce the load and let the LED temp is lit. overloaded. inverter cool down.
No output voltage and The inverter is in stand by Connect a load or change the LED on is lit. mode. jumper settings.
Low output voltage (208V). Low power mode = Connect a load > 30W or change
jumper setting. jumper settings.
Inverter goes on and off, Flat battery. Disconnect load and charge LED on and LED low bat batteries. are blinking in turn.
Cables too thin. Replace with cables of correct
diameter.
Connections are corroded Tighten the connections. If the or bad. cables are burned, replace them.
Inverter goes on and off, Inverter is overloaded. Reduce the load on the inverter. LED on and overload blink in turns one time per second, ventilator is running at full speed.
Inverter goes on and off, Inverter has been switched Reduce the load or the short. LED on and overload blink in off ten times as a result of circuit. Reset the inverter manually turns five times per second, an overload situation or by means of the on/off switch. ventilator is running at full speed. a short circuit.
If you cannot correct a problem with the aid of the malfunction table, contact your Mastervolt Service Center or Mastervolt Amsterdam for an extended service list, tel: INT+ 31-20-3422100.
TROUBLE SHOOTING
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
35
Page 16
36
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
TECHNICAL DATA
7 TECHNICAL DATA 230V INVERTERS
GENERAL
Function apparatus supplying of AC equipment Models Mass Sine 12/1200, 24/1500, 12/2000, 24/2500 and 48/2500 Manufacturer Mastervolt, Amsterdam
INPUT 12/1200 12/1200 24/1500 12/2000 24/2500 48/2500
Battery voltage nominal 12 Volt 24 Volt 12 Volt 24 Volt 48 Volt Switch off voltage low 10 Volt 19 Volt 10 Volt 19 Volt 36 Volt Switch on voltage low 11 Volt 22 Volt 11 Volt 22 Volt 44 Volt Switch off voltage high 16 Volt 32 Volt 16 Volt 32 Volt 62 Volt Switch on voltage high 14 Volt 30 Volt 14 Volt 30 Volt 59 Volt Maximal ripple 5% RMS Current (nominal load) 120A 80A 200A 120A 60A No load (stand by) 50 mA/0.6W 25 mA/0.6W 50 mA/0.6W 25 mA/0.6W 13 mA/0.7W No load power (low mode) 420mA/5W 210mA/5W 420mA/5W 225mA/5W 110mA/3W No load (full power) 450mA/6W 225mA/6W 480mA/6W 250mA/6W 140mA/6W Fuse 120A 80A 240A 160A 100A DC cables 25 mm
2
25 mm
2
50 mm
2
50 mm
2
35 mm
2
OUTPUT
Output voltage 230 Volt, ± 5% Output waveform true sine wave, < 5% thd Frequency 50 Hz, ± 0.1% Nomimal power Tamb=40°C 1000 Watt 1200 Watt 1800 Watt 2000 Watt 2000 Watt Half hour power Tamb=25°C 1200 Watt 1500 Watt 2000 Watt 2500 Watt 2500 Watt Peak power 2400 Watt 2900 Watt 4000 Watt 5000 Watt 5000 Watt Cos phi all power factors allowed Efficiency nominal 89% / 92%
CLIMATE
Nominal temperature -20 till 40°C Cooling partial conventional / forced with temperature regulated fan Humidity < 95% relative humidity, non condensing
ENCLOSURE
Dimensions (hxwxd) 340 x 261 x 130 mm 420 x 318 x 136 mm Weight 8 kg 8 kg 14,6 kg 14,6 kg 14,6 kg Protection degree IP 23
STANDARDS
Emmission EN 50081-1:1992 Immunity EN 50082-1:1997 Safety IEC 950
Page 17
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
37
TECHNICAL DATA
7 TECHNICAL DATA 117V INVERTERS
GENERAL
Function apparatus supplying of AC equipment Models Mass Sine 12/1000, 24/1000, 12/2000 and 24/2500 Manufacturer Mastervolt, Amsterdam
INPUT 12/1000 12/1000 24/1000 12/2000 24/2500
Battery voltage nominal 12 Volt 24 Volt 12 Volt 24 Volt Switch off voltage low 10 Volt 19 Volt 10 Volt 19 Volt Switch on voltage low 11 Volt 22 Volt 11 Volt 22 Volt Switch off voltage high 16 Volt 32 Volt 16 Volt 32 Volt Switch on voltage high 14 Volt 30 Volt 14 Volt 30 Volt Maximal ripple 5% RMS Current (nominal load) 120A 80A 200A 120A No load (stand by) 50 mA / 0.6W 25 mA / 0.6W 50 mA / 0.6W 25 mA / 0.6W No load power (low mode) 420mA/ 5W 225mA/ 5W 420mA/ 5W 225mA/ 5W No load (full power) 450mA / 6W 225mA / 6W 480mA/6W 250mA/6W Fuse 120A 80A 100A 63A DC cables 25 mm
2
25 mm
2
50 mm
2
50 mm
2
OUTPUT
Output voltage 117 Volt, ± 5% Output waveform true sine wave, < 5% thd Frequency 60 Hz, ± 0.1% Nomimal power Tamb=40°C 800 Watt 800 Watt 1800 Watt 2000 Watt Half hour power Tamb=25°C 1000 Watt 1000 Watt 2000 Watt 2500 Watt Peak power 2000 Watt 2000 Watt 4000 Watt 5000 Watt Cos phi all power factors allowed Efficiency nominal 88% / 91%
CLIMATE
Nominal temperature -20 till 40°C Cooling partial conventional / forced with temperature regulated fan Humidity < 95% relative humidity, non condensing
ENCLOSURE
Dimensions (hxwxd) 340 x 261 x 130 mm 420 x 318 x 136 mm Weight 8 kg 8 kg 14,6 kg 14,6 kg Protection degree IP 23
STANDARDS
Emmission EN 50081-1:1992 Immunity EN 50082-1:1997 Safety IEC 950
Page 18
38
November 2000 / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500/ EN
ENERGY SAVING MODES
8 ENERGY SAVING MODES
8.1 LOW ENERGY MODE
For applications that require a very low energy mo­de, it is possible to set the inverter into “low energy mode”. The “low energy mode” can be selected by placing a jumper (black) on the two metal pins on the bottom left of the unit (see fig. 4). When the jumper is in place, the unit will drop the output voltage from 230V to 208V at no load cond­itions. In case the inverter supplies 30W or more, the unit will supply 230V nominal output voltage.
8.2 STAND BY MODE
For applications that require an extremely low energy mode, it is possible to set the inverter to ‘stand by mode’. The stand by mode can be selected by placing a jumper (black) onto the metal pins on the bottom left hand side of the unit (see fig. 4). When the jumper is in place, the inverter will have no output voltage but will check the connected output load once every two seconds. The inverter will switch on when a load is detected. The stand by power and stand by hysteresis can be adjusted with the poten­tiometers on the bottom left of the unit (see fig. 4).
Stand by mode settings:
• energy mode low /high energy mode
• stand by mode on/off
• stand by power 0..40 Watt
• stand by hysteresis 0..100%
Page 19
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
39
EC DECLARATION OF CONFORMITY
9 EC DECLARATION OF CONFORMITY
Manufacturer Mastervolt
Address: Snijdersbergweg 93
1105 AN Amsterdam The Netherlands
Herewith declares that:
Product: MASS sine wave inverters
Models: Mass Sine 12/1200-230V Mass Sine 12/1000-117V
Mass Sine 24/1500-230V Mass Sine 24/1000-117V Mass Sine 12/2000-230V Mass Sine 12/2000-117V Mass Sine 24/2500-230V Mass Sine 24/2500-117V Mass Sine 48/2500-230V
Conform with the provision of the EC: EMC directive 89/336/EEC and amendments 92/31/EEC, 93/68/EEC.
The following harmonized standards have been applied:
Generic emission standard EN 50081-1:1992 Generic immunity standard EN 50082-1:1992 Safety according 73/23/EEG Low voltage directive EN60950/A4: 1996
Amsterdam,
Dr. F.J. ter Heide, Managing director Mastervolt
Page 20
MASTERVOLT
Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands
Tel.: INT+ 31-20-3422100
Fax: INT+ 31-20-6971006
Loading...