Mastervolt MASS 12/80-2, MASS 24/100-C, MASS 12/60-2, MASS 24/75-C, MASS 3-24/100 User Manual

...
Page 1
USERS MANUAL / GEBRUIKERSHANDLEIDING / BETRIEBSANLEITUNG
MANUEL UTILISATEUR / MANUAL DE UTILIZACION / INSTRUZIONI PER L’USO
Mass Charger
MASS 12/60-2; 12/80-2; 24/50-2; 24/75-C;
FULL AUTOMATIC BATTERY CHARGER
MASTERVOLT Snijdersbergweg 93, 1105 AN Amsterdam The Netherlands Tel.: +31-20-3422100 Fax.: +31-20-6971006 www.mastervolt.com
ENGLISH: PAGE 1
NEDERLANDS: PAGINA 29 DEUTSCH: SEITE 57 FRANÇAIS: PAGINA 85 CASTELLANO: PÁGINA 113 ITALIANO: PÁGINA 141
Copyright © 2010 Mastervolt, v 2.2 July 2010
Page 2
CONTENTS
CONTENTS: v 2.2 July 2010
GENERAL INFORMATION.............................................................................................................................................. 4
1
1.1 Use of this manual.............................................................................................................................................. 4
1.2 Validity of this manual ........................................................................................................................................ 4
1.3 Use of pictograms .............................................................................................................................................. 4
1.4 Identification label............................................................................................................................................... 4
1.5 Liability ............................................................................................................................................................... 4
2 IMPORTANT SAFETY INSTRUCTIONS ......................................................................................................................... 5
2.1 General .............................................................................................................................................................. 5
2.2 Explosive gases ................................................................................................................................................. 5
2.3 Warnings regarding the use of batteries............................................................................................................. 6
2.4 Warning regarding life support applications........................................................................................................ 6
2.5 Guarantee specifications.................................................................................................................................... 6
3 OPERATION .................................................................................................................................................................... 7
3.1 Introduction.........................................................................................................................................................7
3.1.1 Switching on ......................................................................................................................................7
3.1.2 Switching off:..................................................................................................................................... 7
3.2 Theory of operation ............................................................................................................................................ 7
3.3 Front panel ......................................................................................................................................................... 7
3.3.1 Bulk (LED 1 illuminates) .................................................................................................................... 8
3.3.2 (LED 1 and 2 illuminate).................................................................................................................... 8
3.3.3 Absorption (LED 1, 2 and 3 illuminate).............................................................................................. 8
3.3.4 (LED 1 to 4 illuminate)....................................................................................................................... 8
3.3.5 Float (LED 1 to 5 illuminate) .............................................................................................................. 8
3.4 Temperature compensated charging.................................................................................................................. 8
3.5 Compensation of the cable losses...................................................................................................................... 8
3.6 alarm function..................................................................................................................................................... 8
3.7 Charging a second battery ................................................................................................................................. 8
3.8 Equalize mode.................................................................................................................................................... 8
4 INSTALLATION ............................................................................................................................................................... 9
4.1 Mounting the Mass charger ................................................................................................................................ 9
4.2 Connections ....................................................................................................................................................... 9
4.3 Wiring ................................................................................................................................................................. 9
4.3.1 AC wiring........................................................................................................................................... 9
4.3.2 AC safety grounding........................................................................................................................ 10
4.3.3 DC wiring......................................................................................................................................... 10
4.4 Battery capacity................................................................................................................................................ 10
4.5 Battery isolator ................................................................................................................................................. 10
4.6 Connection of second battery (3A output) ..................................................................................................... 11
4.7 Temperature sensor ......................................................................................................................................... 11
4.8 Voltage sense................................................................................................................................................... 11
4.9 Alarm function .................................................................................................................................................. 11
4.9.1 Standard alarm mode ...................................................................................................................... 11
4.9.2 DC alarm mode ............................................................................................................................... 11
4.10 Connection of accessories ............................................................................................................................... 11
4.11 Overview connection compartment .................................................................................................................. 12
4.12 Things you need............................................................................................................................................... 12
4.13 Connection ....................................................................................................................................................... 13
4.14 Installation step-by-step ................................................................................................................................... 14
4.15 Commissioning after installation....................................................................................................................... 15
2 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 3
CONTENTS
4.15.1 General............................................................................................................................................ 15
4.15.2 MasterBus (optional) ....................................................................................................................... 15
4.16 Decommissioning ............................................................................................................................................. 15
4.17 Storage and transportation............................................................................................................................... 15
4.18 Re-installation................................................................................................................................................... 15
5 DIP SWITCH SETTINGS ............................................................................................................................................... 16
5.1 DIP Switch operation........................................................................................................................................ 16
5.2 DIP switch functions ......................................................................................................................................... 16
5.2.1 Force Float (DIP switch 1)............................................................................................................... 16
5.2.2 Traction setting (DIP switch 2)......................................................................................................... 16
5.2.3 Gel batteries (DIP switch 3)............................................................................................................. 16
5.2.4 Diode setting (DIP switch 4) ............................................................................................................ 16
6 MASTERBUS................................................................................................................................................................. 17
6.1 What is MasterBus? ......................................................................................................................................... 17
6.2 How to set up a MasterBus network................................................................................................................. 17
7 MASTERBUS SETTINGS.............................................................................................................................................. 18
7.1 Device .............................................................................................................................................................. 18
7.2 Presets ............................................................................................................................................................. 18
7.3 General ............................................................................................................................................................ 18
7.4 Bulk .................................................................................................................................................................. 18
7.5 Absorption ........................................................................................................................................................ 18
7.6 Float ................................................................................................................................................................. 19
7.7 Alarm setpoints................................................................................................................................................. 19
7.8 Traction settings ............................................................................................................................................... 19
7.9 Nicad settings................................................................................................................................................... 19
7.10 Li-ion settings ................................................................................................................................................... 19
7.11 Events .............................................................................................................................................................. 20
7.11.1 Mass Charger event source list (Mass Charger as event source)................................................... 20
7.11.2 Mass Charger event target list (Mass Charger as event target) ...................................................... 20
8 TROUBLE SHOOTING.................................................................................................................................................. 21
8.1 Fault finding table ............................................................................................................................................. 21
9 TECHNICAL DATA........................................................................................................................................................ 22
9.1 Specifications ................................................................................................................................................... 22
9.2 Dimensions....................................................................................................................................................... 24
9.3 Characteristics (230 V AC) ............................................................................................................................... 26
10 ORDERING INFORMATION.......................................................................................................................................... 27
11 EC DECLARATION OF CONFORMITY ........................................................................................................................ 28
EN / Mass Charger 12/60-2; 12/80-2; 12/150; 24/50-2; 24/75; 24/100; 48/25; 48/50; 3-24/100 / July 2010 3
Page 4
GENERAL INFORMATION
1 GENERAL INFORMATION
1.1 USE OF THIS MANUAL
Copyright © 2010 Mastervolt. All rights reserved. Reproduction, transfer, distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited.
This manual contains important safety and operating instructions for the safe and effective operation, maintenance and possible correction of minor malfunctions of the Mass Charger.
It is therefore obligatory that every person who works on or with the Mass Charger is completely familiar with the contents of this manual, and that he/she carefully follows the instructions and important safety instructions contained herein.
1.2 VALIDITY OF THIS MANUAL
All of the specifications, provisions and instructions contained in this manual apply solely to standard versions of the Mass Charger delivered by Mastervolt. This manual is valid for the following models:
Part no Model
40010606 Mass 12/60-2 (230 V) 40010806 Mass 12/80-2 (230 V) 40020506 Mass 24/50-2 (230V) 40020756 Mass 24/75-C (230V) 40021006 Mass 24/100-C (230V) 40031006 Mass 24/100 3-phase (3x400V) 40040256 Mass 48/25 (230 V) 40040506 Mass 48/50 (230 V)
These models are further mentioned as “Mass Charger” For other models see other manuals available on our website: www.mastervolt.com
1.3 USE OF PICTOGRAMS
Safety instructions and warnings are marked in this manual by the following pictograms:
WARNING
A WARNING refers to possible injury to the user or significant material damage to the Mass Charger if the user does not (carefully) follow the procedures.
CAUTION!
Special data, restrictions and rules with regard to preventing damage.
A procedure, circumstance, etc which deserves extra attention.
1.4 IDENTIFICATION LABEL
Part no : 44020800
40021006
Type : ChargeMaster 24/80-3
Mass Charger24/100-C
Input : 120/230V AC 50/60 Hz 26A/13A Output : 28.5VDC - 80A
Serial no: V822C0001
220-240V 16A 50-60Hz
28.50V 100A
XD10A0005
Serial number
XD10A
0005
Apparatus version “A”
Figure 1: Identification label
The identification label is located at the right-hand side of the Mass Charger (see figure 1). Important technical information required for service, maintenance & secondary delivery of parts can be derived from the identification label.
IP 23
Design by Mastervolt
Manufactured in China
Part number
CAUTION!
Never remove the identification label.
1.5 LIABILITY
Mastervolt can accept no liability for:
consequential damage due to use of the Mass Charger;
possible errors in the manuals and their results.
4 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 5
IMPORTANT SAFETY INSTRUCTIONS
2 IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
WARNING
This chapter describes important safety and operating instructions for use of a Mass Charger in residential, recreational vehicle (RV) and marine applications.
2.1 GENERAL
1 Before using the Mass Charger, read all instructions
and cautionary markings on the Mass Charger, the batteries, and all appropriate sections of the manual.
2 To reduce the risk of electric shock – Do not expose
Mass Charger to rain, snow, spray, moisture, excessive pollution and condensing circumstances. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the Mass Charger in a non-ventilated room, overheating may result.
3 Use of an attachment or spare part not recommended
or sold by Mastervolt may result in a risk of fire, electric shock, or injury to persons.
4 The Mass Charger is designed to be permanently
connected to an AC and DC electrical system. Installation of, and work on the Mass Charger, may be carried out only by a qualified, authorised and trained technician or electrician, consistent with the locally applicable standards and regulations.
5 Make sure that all wiring is properly installed and in
good electrical condition; and that wire size is large enough for AC ampere rating of the Mass Charger. Check the wiring on a regular base, at least once a year. Do not use the Mass Charger when the wiring is undersized or damaged.
6 Do not operate the Mass Charger if it has received a
sharp blow, been dropped, or otherwise damaged in any way; take it to a qualified serviceman.
7 Except for the connection compartment, see chapter
4, the Mass Charger may not be opened or disassembled. There are no serviceable parts inside the cabinet. Take it to a qualified, authorized and trained serviceman when service or repair is required. Incorrect reassembly may result in a risk of electric shock or fire. Only qualified, electrician installers are authorized to open the connection compartment.
8 To reduce risk of electric shock, disconnect the Mass
Charger from both AC and DC electrical system before attempting any maintenance or cleaning. Turning off controls will not reduce this risk.
9 The Mass Charger must be provided with an
equipment-grounding conductor to the AC-input ground terminal. Grounding and all other wiring must comply with local codes and ordinances.
10 Short circuiting or reversing polarity will lead to
serious damage to batteries, Mass Charger, wiring as well as accessories. Fuses can not prevent damage caused by reversed polarity and the warranty will be void.
11 In case of fire, you must use the fire extinguisher
which is appropriate for electrical equipment.
12 If applied in a marine application in the United States,
external connections to the Mass Charger shall comply with the United States Coast Guard Electrical Regulations (33CFR183, Sub part I).
2.2 EXPLOSIVE GASES
1 WARNING – RISK OF EXPLOSIVE GASES.
WORKING IN VICINITY OF A LEAD-ACID BATTERY IS DANGEROUS. BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION. FOR THIS REASON, IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE USING THE MASS CHARGER, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY.
2 To reduce risk of battery explosion, follow these
instructions and those published by battery manufacturer and manufacturer of any equipment you intend to use in vicinity of the battery. Review cautionary marking on these products.
3 DANGER: To reduce the risk of explosion – Never
use the Mass Charger in situations where there is danger of gas or dust explosion or an area in which ignition-protected equipment is required.
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 5
Page 6
IMPORTANT SAFETY INSTRUCTIONS
2.3 WARNINGS REGARDING THE USE OF BATTERIES
1 Someone should be within range of your voice or
close enough to come to your aid when you work near a lead-acid battery.
2 Have plenty of fresh water and soap nearby in case
battery acid contacts skin, clothing, or eyes.
3 Wear complete eye protection and clothing protection.
Avoid touching eyes while working near battery.
4 If battery acid contacts skin or clothing, wash
immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 10 minutes and get medical attention immediately.
5 NEVER smoke or allow a spark or flame in vicinity of
a battery or engine.
6 Do not short circuit batteries, as this may result in
explosion and fire hazard! Be extra cautious to reduce risk of dropping a metal tool onto a battery. It might spark or short-circuit battery or other electrical part and may cause explosion.
7 Remove personal metal items such as rings,
bracelets, necklaces, and watches when working with a battery. A battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn.
8 Only use the Mass Charger for charging Lead-acid,
NiCad and Li-ion batteries and the supply of users attached to these batteries, in permanent systems. Do not use the Mass Charger for charging dry-cell batteries that are commonly used with home appliances. These batteries may burst and cause
injury to persons and damage to property. 9 NEVER charge a frozen battery. 10 Excessive battery discharge and/or high charging
voltages can cause serious damage to batteries. Do
not exceed the recommended limits of discharge level
of your batteries. 11 If it is necessary to remove a battery, always remove
the grounded terminal from the battery first. Make
sure all accessories are off, so as not to cause an arc.
12 Be sure that the area around the battery is well
ventilated while the battery is being charged. Refer to the recommendations of the battery manufacturer.
13 Batteries are heavy! It may become a projectile if it is
involved in an accident! Ensure adequate and secure mounting and always use suitable handling equipment for transportation.
2.4 WARNING REGARDING LIFE SUPPORT APPLICATIONS
The Mass Charger is not sold for applications in any medical equipment intended for use as a component of any life support system unless a specific written agreement pertaining to such intended use is executed between the manufacturer and Mastervolt. Such agreement will require the equipment manufacturer either to contract additional reliability testing of the Mass Charger and/or to commit to undertake such testing as a part of the manufacturing process. In addition the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arising from the use of the Mass Charger in the life support equipment.
2.5 GUARANTEE SPECIFICATIONS
Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications. Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in this users manual, then damage may occur and/or the unit may not fulfil its specifications. All of these matters may mean that the guarantee becomes invalid. The guarantee is limited to the costs of repair and/or replacement of the product. Costs for installation labor or shipping of the defective parts are not covered by this guarantee.
6 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 7
OPERATION
3 OPERATION
3.1 INTRODUCTION
The MASS battery charger is a full-automatic high efficiency battery charger/rectifier, developed and produced by Mastervolt Amsterdam. The MASS series features a family of advanced quality battery chargers. The Mass Charger not only charges batteries rapidly and safely, it supplies the connected consumers at the same time. In addition, the Mass Charger is secured against short circuit, overload and high temperatures in an industrial environment.
3.1.1 Switching on
The battery charger will be switched on by the ON/OFF switch. One of the front LEDs will light up now and the charging starts immediately.
3.1.2 Switching off:
The battery charger will be switched off by the ON/OFF switch.
The connection between the mains and the battery charger will not be severed with the switch.
3.2 THEORY OF OPERATION
The battery charger is equipped with an intelligent 3-stage charge characteristic which takes care of an optimal charge of your batteries (see fig. 2). When switched on, the Mass Charger always starts in Bulk phase.
LEDs in charge
BULK ABSORPTION FLOAT
Fig. 2: Example: charge characteristic MASS 12/60-2. (For other models V/A according to specifications).
To prevent your batteries from overcharging a new cycle only starts when the battery voltage has been under the level of 12.8/25.6 or 51.2V for longer than 30 seconds or after a hard reset by switching the on/off switch back and forward.
stage, see fig. 3
charge voltage (V)
charge current (A)
charge time
3.3 FRONT PANEL
On the front of the Mass Charger a so called "capacity meter" (figure 3, LED 9 to 13) gives you information about the battery state like a fuel meter of a car. The more LEDs are illuminated the more power is in the battery.
Fig 3: Front panel of the battery charger
Illuminating LED’s Meaning
Normal operation, LED 6 illuminates green 1 Charger On 1+2 Uout> 13.8/27.6/55.2V 1+2+3 Uout = abs. (14.25/28.5/57.0V) 1+2+3+4 3 hrs after start max bulk timer,
or I < return amps
1+2+3+4+5 6 hrs after start max bulk timer,
or I < return amps for 15 min or longer 9 Charge current 0-5% of full current 9+10 Charge current 5-25% of full current 9+10+11 Charge current 25-50% of full current 9+10+11+12 Charge current 50-75% of full current 9+10+11+12+13 Charge current 75-100% of full current 6 Green: normal operation, Red: fault
condition, Off: standby or off 7 Green: MasterBus communication,
Off: no MasterBus communication
Fault condition, LED 6 illuminates red
6 red +1 Battery sense error 6 red +2 Charger temperature too high 6 red +3 Short circuit indication, charger will
reduce the charge current to 25% 6 red +4 DC error, DC voltage too low or too high 6 red +5 Temperature sense error
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 7
Page 8
OPERATION
3.3.1 Bulk (LED 1 illuminates)
The battery is empty when only the first LED Bulk/ON illuminates. In this stage the Mass Charger gives full current (see fig. 4 phase A) and the battery voltage will slowly increase. After reaching the level of 13.8V (12V charger), 27.6V (24V charger) or 55.2V (48V charger) the battery is charged for about 25% and the second LED will also illuminate.
3.3.2 (LED 1 and 2 illuminate)
The battery has been charged for 25%. The Mass Charger still gives the maximum output current and the voltage will increase till the absorption voltage level (see fig. 2 phase A). The time of phase A is 6 hours default.
3.3.3 Absorption (LED 1, 2 and 3 illuminate)
The battery has been charged for 50% (fig. 2 phase B). The Mass Charger limits the charge voltage to a safe level and the charge current shall slowly decrease.
3.3.4 (LED 1 to 4 illuminate)
The battery is charged for 75%. The charge voltage is limited at the absorption level, because the battery is almost full, the current consumption will further decrease.
3.3.5 Float (LED 1 to 5 illuminate)
When all LEDs are illuminated the battery is fully charged. The float/trickle charge program gives a lower output voltage, sufficient enough to maintain the batteries at 100% charge but low enough to prevent your batteries from unnecessary stress. In this stage the Mass Charger is able to supply full current to the connected users/loads.
The Mass Charger automatically resumes operation in Bulk phase after it was disconnected from an AC-source temporarily.
3.4 TEMPERATURE COMPENSATED CHARGING
By installing the battery temperature sensor the charge voltages are automatically adapted for deviating temperatures. This can increase the battery’s life time substantially and save you a lot of money.
Charge voltage (V)
Battery temperature (°C)
Figure 4: Temperature compensated charging
See figure 4. When the battery temperature is low, the charge voltage increases. On the other hand, when the battery temperature is high, the charge voltage is decreased. Over charge and gassing are prevented this way. This will extend the life of your batteries.
3.5 COMPENSATION OF THE CABLE LOSSES
The Mass Charger can compensate the voltage drop occurring over the DC cables. For this purpose the Mass Charger is provided with terminals for sense wires. The sense wires are connected closest possible to the batteries in order to charge them with the right voltage. When only the minus sense wire is connected only the losses of the minus DC cable will be compensated. Connecting both cables produces the best result, all losses will be compensated until a maximum of 3V in total.
3.6 ALARM FUNCTION
The battery charger is equipped with an integrated alarm function. External equipment can be controlled by the potential free contacts of this alarm. The maximum switch current of the relay is 1A. Exceeding the setpoints (refer to section 6.7) will activate the alarm.
3.7 CHARGING A SECOND BATTERY
Some installations have a main battery set and besides this a smaller (cranking) battery with the same voltage. It is possible to maintain this second battery with the 3A output of the battery charger. This function is standard available on the models 12/60-2, 12/80-2 and 24/50-2.
3.8 EQUALIZE MODE
An equalizing charge can be necessary after very deep discharges and/or inadequate charges. This has to be carried out according to the specifications of the battery manufacturer.
WARNING!
Equalization is ONLY applicable for wet type batteries and will damage gel/AGM/Spiral type batteries! Incorrect use of the equalize mode may lead to hazardous situations. Do not smoke or use any naked flame or other sources of ignition due to risk of explosion. Always ventilate the battery room during equalizing to clear the air.
During equalizing the batteries are brought into the gas state and permitted load voltages may be exceeded. Therefore appropriate measures must be taken, e.g. disconnect all loads from the battery and ventilate the room. For these reasons the equalizing mode should only be used by trained technical engineers. The equalizing mode can only be started when the Mass Charger is in operation. To start the equalize mode, select Equalize in the MasterBus device settings (section 7.2).
8 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 9
INSTALLATION
4 INSTALLATION
During installation and commissioning of the Mass Charger, the important safety instructions are applicable at all times. See chapter 2 of this manual. Please check the contents of the box before you start with the installation. The contents of the box need to be:
battery charger;
battery temperature sensor (incl. 6 mtr cable);
a MasterBus terminating device;
users manual;
If one of these items is missing, please contact your supplier.
Install the MASS battery charger in a dry, well ventilated area, closest possible to the batteries. Although the battery charger has a high efficiency, some heat will be produced. This heat will be discharged by a fan with variable speed. At installation of the battery charger be sure that:
the air flow is not obstructed;
no water and/or dust can enter the cabinet.
4.1 MOUNTING THE MASS CHARGER
Obey the following stipulations during installation:
The Mass Charger is designed for indoor use only.
Ambient temperature: 0 ... 60°C / 32°F … 140°F;
(power derating above 40°C / 104 °F to decrease the internal heat sink temperature).
Humidity: 0-95% non condensing.
Mount the Mass Charger vertically, with the connecting
cables downwards.
Make sure that the hot air that is developed during
operation can be discharged. The Mass Charger must be mounted in such a way that obstruction of the airflow through the ventilation openings will be prevented.
No objects must be located within a distance of 10 cm /
4 inch around the Mass Charger.
Do not locate the Mass Charger in the same
compartment as the batteries.
Do not install the Mass Charger straight above the
batteries because of possible corrosive sulphur fumes.
4.2 CONNECTIONS
Before making the connection between the battery charger and the system be sure that the AC and DC system are switched off. Remove the fuses in order to protect yourself against unexpected start up.
4.3 WIRING
WARNING!
The wire and fuse sizes stated in this manual are given as example only. Prescribed wire and fuse sizes may be different due to local applicable regulations and standards.
4.3.1
Check if the voltage of your mains source or generator corresponds with the AC input voltage of the battery charger as mentioned on the type number plate, see section 1.4. Cut the cable in accordance to fig. 5a. It is important that the green/ yellow earth wire is ± 1 cm (0.4 inch) longer than the other wires. By accidentally pulling at the cable, the earth wire stays connected to the Mass Charger longer which offers additional safety. Connect the green/yellow wire to PE, brown to L1 and the blue wire to the N terminal.
brown
Connect the 3-24/100 according to fig. 5b. The three black wires to L1, L2 and L3. Connect the green/yellow wire to the PE. For a safe installation the correct wire cross section must be applied. Don’t use a cross section that is smaller than indicated. See table below to select the appropriate cross section for the AC wiring (up to 6m / 20ft length):
AC Current Minimum cross section:
6-12 Amp 1.5 mm² AWG 14 12-20 Amp 2.5 mm² AWG 12 20-32 Amp 4.0 mm² AWG 10
Connection of AC-wiring and recommended wire colours.
230V/50Hz installations, see figure 5a:
Wire color Meaning
Brown or black Phase L1 Blue Neutral N Green/Yellow Earth PE / GND
400V/50Hz installations, see figure 5b:
Wire color Meaning
Black Phase L1, L2, L3 Green/Yellow Earth PE / GND
AC wiring
green/yellow
blue
Fig5a
minimal
black
black
minimal
1 cm
green/yellow
black
Fig5b
Must be connected to:
Must be connected to:
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 9
Page 10
INSTALLATION
4.3.2 AC safety grounding
WARNING!
The ground wire offers protection only if the cabinet of the Mass Charger is connected to the safety ground. Connect the ground terminal (PE / GND) to the hull or the chassis.
CAUTION!
For safe installation it is necessary to insert a Residual Current Device (earth leakage switch) in the AC input circuit of the Mass Charger.
4.3.3 DC wiring
Keep the cable connection between charger and batteries shortest possible. If available, use coloured battery cables. If this is not possible, mark the plus and the minus cables with coloured insulating tape, e.g. red for plus and blue/black for minus. Use the following diameters:
Model Mass Charger Length <3 m Length 3-6 m
Mass 12/60-2 (230 V) 25 mm² 35 mm² Mass 12/80-2 (230 V) 35 mm² 50 mm² Mass 24/50-2 (230V) 25 mm² 35 mm² Mass 24/75-C (230V) 35 mm² 50 mm² Mass 24/100-C (230V) 50 mm² 70 mm² Mass 24/100 3-phase (3x400V) Mass 48/25 (230 V) 10 mm² 16 mm² Mass 48/50 (230 V) 25 mm² 35 mm²
Connection of main batteries 1 Pull the cables through the cable glands of the Mass
Charger.
2 Crimp on the ring terminals to the cable:
ring M6 for 12/60-2, 12/80-2, 24/50-2 and 48/25;
ring M8 for 24/75, 24/100, 48/50 and 3-24/100.
3 Connect the cables to the terminals of the Mass
Charger. Pay attention to the polarity, positive on positive / negative on negative.
4 Integrate a suitable fuse (charger fuse) in the positive
cable. When using a DC distribution with fuses, no additional fuse is necessary.
5 Cut the cables at length and crimp on the ring
terminals. Connect the cable to the DC distribution or batteries.
Reversing the positive and negative battery poles will severely damage the Mass Charger.
Too thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals.
Lay the positive and negative cables next to each other to limit the electro magnetic field around the cables. The
50 mm² 70 mm²
negative cable should be connected directly to the negative post of the battery bank or the ground side of a current shunt. Do not use the chassis frame as the negative conductor.
4.4 BATTERY CAPACITY
The minimum required battery capacity is as follows:
Model Mass Charger Minimum required
battery capacity
Mass 12/60-2 (230 V) 140Ah Mass 12/80-2 (230 V) 200Ah Mass 24/50-2 (230V) 120 Ah Mass 24/75-C (230V) 160 Ah Mass 24/100-C (230V) 250 Ah Mass 24/100 3-phase (3x400V) 250 Ah Mass 48/25 (230 V) 60 Ah Mass 48/50 (230 V) 120 Ah
4.5 BATTERY ISOLATOR
If one or more batteries or battery sets must be charged at the same time via one output, a battery isolator should be used. It isolates the different battery sets from one another, in order to prevent one discharging the other. A consequence of the battery isolator is a voltage drop of 0.6 Volt. This voltage drop can be compensated in two ways:
1 By changing DIP-switch 4 to On (Diode enabled); 2 By MasterBus configuration (Diode compensate);
Warning! DIP-switch settings overrule MasterBus settings!
Mastervolt offers several Battery Isolators, refer to
www.mastervolt.com
For a proper installation, see also the connection diagram included with the battery isolator.
Steps: 1 Check if the Mass Charger, the main supply and the
DC distribution are switched off. 2 Check if the Dc fuses have been removed. 3 Connect the battery isolator(s) using cables with the
same diameter as the battery cables. 4 Compensate the voltage drop over the battery isolator
by changing the setting of dip switch 4 (see fig. 5). Not
suitable when using the voltage sense function. 5 Switch on the Mass Charger.
.
10 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 11
INSTALLATION
4.6 CONNECTION OF SECOND BATTERY (3A OUTPUT)
The battery chargers 12/60-2, 12/80-2 and 24/50-2 are standard equipped with a second charge output of 3A in order to give a small second battery set like a starter battery a maintenance charge. The maximum charge current of the second output is 3A, which comes from the main output.
Use 2.5 to 4 mm
2
cable for connection.
Connect the minus of the second battery to the minus
of the main battery.
Connect the plus of the second battery to the +3A
terminal of the Mass Charger (see fig. 2 and 3).
Integrate a 10A slow blow fuse in the plus cable.
4.7 TEMPERATURE SENSOR
The standard temperature sensor is provided with 6 m cable and a double-sided tape for easy installation. Determine the warmest place on the battery set and make it clean and grease free. Remove the piece of paper from the tape and stick the sensor on the battery. Plug the 6way cable into a terminal at the right of the Mass Charger (see fig. 7). For the C3 enclosure (refer to specifications) both "RS232" and "analog" are suitable. It is not necessary to shorten the cable. When you want to shorten it anyway please notice the polarity of the plug and use the old connector as an example.
4.8 VOLTAGE SENSE
To shorten the charge time substantially, the battery cable losses can be compensated by using the sense function. Use 0,75 mm
2
, preferably red and black wire and secure these with fuses of 2A slow blow. Connect the wires with the two upper terminals of the green connector at the right side of the cabinet (see fig. 7). Pay good attention to the polarity of the wires, red on +S and black on -S. Now connect the other side of the wires: black on the minus of the battery and red on the battery side of the Mass Charger fuse.
4.9 ALARM FUNCTION
The battery charger is equipped with a potential free contacts alarm relay, see figure 7. The alarm function has two modes: standard (factory setting) and DC alarm mode (continuous mode).
4.9.1 Standard alarm mode
In this mode the relay responds to all fault conditions that the Mass Charger can detect such as: no AC input voltage, too low DC voltage, voltage sense failure, temperature sense failure.
4.9.2 DC alarm mode
To enable this mode a DIP switch setting needs to be changed (switch 1 and 2 at ON). The alarm now works as a DC alarm and responds to the battery voltage only. Note: In the DC alarm mode the electronics stay active permanently and drain a very small current of ± 25mA, also when the Mass Charger is switched off.
4.10 CONNECTION OF ACCESSORIES
The battery charger is equipped with several terminals for accessories. Cable to connect the accessories is not delivered as a standard. Accessories can be plugged in at all times. For C3 enclosure (refer to specifications): when using a remote panel and the temperature sensor use the specified plug for the panel and the other (free) one for the temperature sensor.
Figure 6: Standard remote panel C3-RS, art. no 07-04-03040
The standard remote panel must be connected with an appropriate communication cable.
4.11 SPLITTER FOR ENCLOSURE C2
The RJ12 connector (QRS232 communication port) can be used to connect the battery temperature sensor or the remote panel (not included). Use a splitter to connect both at the same time (not included).
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 11
Page 12
INSTALLATION
4.12 OVERVIEW CONNECTION COMPARTMENT
C2 enclosure
1 Screw terminals AC input: L1, N, PE
(24/100-3ph: L1, L2, L3, PE)
2 Earth stud
C3 enclosure
3 MasterBus connector 4 MasterBus connector 5 Output (battery) positive connector
(maximum 3A) 6 RS232 / Temperature sensor connector 7 Analog connector 8 Output (battery) positive connector 9 Output (battery) negative connector 10 Voltage sense/ potential free alarm
contact
Figure 7: Overview connections Mass Charger
4.13 THINGS YOU NEED
Make sure you have all the parts you need to install the Mass Charger:
Product Quantity
Mass Charger (included) 1 Battery temperature sensor with cable and plug (included). 1 DC-cable to connect the positive DC connection (+) of the Mass Charger to the positive pole of the DC­distribution; for specifications see section 4.3.3. DC-cable to connect the negative DC connection (–) of the Mass Charger to the negative pole of the DC­distribution; for specifications see section 4.3.3. DC-fuse holder with a DC-fuse, to be integrated in the positive DC-cable. 1 Screws / bolts (Ø 6mm) (with plugs) to mount the cabinet to a surface. Use mounting materials which are suitable to carry the weight of the Mass Charger AC cable* to connect the AC input to an external power source (e.g. a shore connection or a generator set); 1 Batteries. See section 4.4 for recommended capacity X Appropriate and reliable cable terminals, cable lugs, battery terminals and cord end terminals X
* Double insulated three wire cable with wire colours according to the locally applicable regulations. The applicable length and wire diameter depend on the electrical installation (see section 4.3.1).
We recommend as a minimum tool kit:
Socket wrench 13mm to fix the DC-input (battery) cables
Flat blade screw driver 1.0 x 4.0 mm to fix the screw terminals
Tools to fix the screws / bolts (Ø 6mm) with plugs to mount the cabinets to a surface
Philips screw driver to open the connection area of the Mass Charger
2 mm flat blade screw driver for the sense terminal (figure 9 point 10).
1
1
4
12 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 13
g
INSTALLATION
4.14 CONNECTION
WARNING
Let installation work be done by a licensed electrician. Before beginning with the connection of the wiring, make the AC distribution as well as the DC distribution voltage free.
CAUTION!
Short circuiting or reversing polarity may lead to serious damage to the batteries, the Mass Charger, the cabling and/or the terminal connections. Fuses between the batteries and the Mass Charger can not prevent damage caused by reversed polarity. The damage as a result of reverse polarity is detectable by the service department and is not covered by the warranty.
CAUTION!
Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore tighten all connections well, in order to limit transition resistance as far as possible. Use cables of the correct size.
NOTE: If the battery temperature remains within 15­25°C, connection of the battery temperature sensor is optional.
NOTE: The Mass Charger is feasible for the connection of MasterBus and RS 232 compatible remote control panels.
This schematic is to illustrate the general placement of the Mass Charger in a circuit. It is not meant to provide detailed wiring instructions for any particular electrical installation.
Charger fuse
Fi
ure 8: Installation drawing of the Mass Charger
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 13
Page 14
p
INSTALLATION
4.15 INSTALLATION STEP-BY-STEP
Attach the battery temperature sensor to the
Mark the position of the mounting spots using
1
the drilling dimensions .
Place the four screws first and
2
hang the Mass Charger over them. Then fix the Mass to the wall by securing the screws.
Open the connection compartment by
3
loosening the two screws.
7
casing of battery bank 1. Plug the temperature sensor cable into the “temp.sensor” jack.
4
Feed the AC wiring through cable gland and connect the wiring to the screw terminals. Tighten the cable gland firmly.
Connect the DC-cabling of the house bank,
5
positive to +, negative to – .
+ -
+ -
Option: Connect the Mass Charger to the
7
MasterBus network.
The factory setting of the Mass Charger is
8
optimal for most installations. Sometimes however, it is desirable to change these settings. See ch. 5 DIP switch adjustment and cha
Check all wiring; see also figure 10 for wiring
9
details. If everything is all right, close the connection compartment by fixing the two screws.
ter 7 for MasterBus settings.
Option for models 12/60, 12/80 and 24/50:
6
Connect the DC-wiring of the second battery bank (max. 3A). This bank has a common negative with the main battery.
10
Continue with section 4.15 for commissioning of the Mass Charger.
14 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 15
INSTALLATION
4.16 COMMISSIONING AFTER INSTALLATION
When your Mass Charger is not new, you have to take into account that former users may have changed the settings. Reset the Mass Charger to factory settings when there is any doubt (see section 7.2).
4.16.1 General
The factory settings of the Mass Charger are optimal for most installations. With some applications however, it is desirable to change these settings. Therefore several adjustments can be made. See chapter 7.
NOTE: The DIP-switches must be adjusted prior to commissioning; all other settings can only be made after commissioning.
CAUTION!
Check the polarity of all wiring before commissioning: positive connected to positive (red cables), negative connected to negative (black cables).
If all wiring is OK, place the DC-fuse(s) of the DC­distribution to connect the batteries to the Mass Charger.
WARNING
When placing this fuse, a spark can occur, caused by the capacitors used in the Mass Charger. This is particularly dangerous in places with insufficient ventilation, due to the gassing of the batteries an explosion can occur. Avoid having flammable materials close by.
Now the Mass Charger is ready for operation. After switching on the AC power supply the Mass Charger will initiate the charging process.
4.16.2 MasterBus (optional)
During first commissioning the Mass Charger will be recognized by the MasterBus network automatically. The remote control panel of the MasterBus network will indicate that a new device was found.
Some settings can only be changed via the MasterBus interface. See chapter 7 for an overview of all available MasterBus settings. Refer to the user’s manual of the remote control panel to change these settings.
4.17 DECOMMISSIONING
If it is necessary to put the Mass Charger out of operation, follow the instructions in order of succession as described below:
1 Switch the Mass Charger to OFF (see section 3.1.2). 2 Remove the DC-fuse(s) of the DC-distribution and/or
disconnect the batteries.
3 Remove the AC-fuse(s) of the AC-input and/or
disconnect the AC-mains.
4 Open the connection compartment of the Mass
Charger.
5 Check with a suitable voltage meter whether the
inputs and the outputs of the Mass Charger are voltage free.
6 Disconnect all the wiring.
Now the Mass Charger can be demounted in a safe way.
4.18 STORAGE AND TRANSPORTATION
When not installed, store the Mass Charger in the original packing, in a dry and dust free environment.
Always use the original packing for transportation. Contact your local Mastervolt Service Centre for further details if you want to return the apparatus for repair.
4.19 RE-INSTALLATION
To reinstall the Mass Charger, follow the instructions as described in this chapter (chapter 4).
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 15
Page 16
DIP SWITCH SETTINGS
5 DIP SWITCH SETTINGS
The Mass Charger settings can be adjusted in two ways:
By means of DIP-switches;
Via the MasterBus network (by means of a remote
control panel or an interface connected to a PC with MasterAdjust software); see chapter 7.
Once a DIP switch has been set to On, MasterBus settings are disabled.
CAUTION!
Invalid settings of the Mass Charger can cause serious damage to your batteries and/or the connected load! Adjustments of settings may be undertaken by authorised personnel only.
5.1 DIP SWITCH OPERATION
The Mass Charger has six DIP switches, see figure 9. These switches are operated by flipping the levers to the other position, using a small screw driver.
5.2 DIP SWITCH FUNCTIONS
See the table below for the functional overview of the six DIP switches (Switch 5 and 6 are reserved for future use).
4 3 2 1 DIP switches/ Settings
0 0 0 0 Standard 1 0 0 0 Diode 0 1 0 0 Gel 1 1 0 0 Diode + Gel 0 0 1 0 Traction 1 0 1 0 Traction + Diode 0 1 1 0 ContMon + Traction 1 1 1 0 ContMon + Traction + Diode 0 0 0 1 ForceFloat 1 0 0 1 ForceFloat + Diode 0 1 0 1 ForceFloat + Gel 1 1 0 1 ForceFloat + Diode + Gel 0 0 1 1 ContMon 1 0 1 1 ContMon + Diode 0 1 1 1 ContMon + Gel 1 1 1 1 ContMon + Diode + Gel
5.2.1 Force Float (DIP switch 1)
For special applications a fixed charge voltage can be required. The battery charger allows you to change the three stage charge program to a single stage program by activating the function "Force Float", switching DIP switch 1 to "ON" (see fig. 2 & 3 for further information). The charge voltage will be fixed at 13.25V (12V charger),
26.5V (24V charger) or 53V for a 48V charger.
5.2.2 Traction setting (DIP switch 2)
Setting for traction charging: +0.7/1.4/2.8V during bulk and +0.4/0.8/1.6 V in absorption for 12/24/48V batteries.
Figure 9: DIP-switches C2 (above) and C3 enclosure
1 = ON; 0 = OFF
ContMon: Continuous monitor mode. MasterBus,
RS232 and DC-alarm stay functioning at mains failure. Remote stays functioning if it
has its own power source. Diode: Diode compensation on (+0.6V) Gel: Gel compensation on (+0,55V during float)
or 1.1V/24V or 2.2V/ 48V Traction Traction charging (+0.7V during bulk and
+0.4V in absorption). Force float: One step charge program with fixed float
voltage.
5.2.3 Gel batteries (DIP switch 3)
Some gel batteries need a higher float voltage for optimal charge. Changing the float voltage can by done by setting DIP switch 3 to "ON". The float voltage will increase to
13.8V (12V charger), 27.6V (24V charger) or 55.2V for a 48V charger.
5.2.4 Diode setting (DIP switch 4)
Setting for +0.6 V compensation in case a battery diode is used.
16 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 17
MASTERBUS
6 MASTERBUS
6.1 WHAT IS MASTERBUS?
All devices that are suitable for MasterBus are marked by the MasterBus symbol.
MasterBus is a fully decentralized data network for communication between the different Mastervolt system devices. It is CAN-bus based which has proven itself as a reliable bus-system in automotive applications. MasterBus is used as power management system for all connected devices, such as the inverter, battery charger, generator and many more. This enables communication between the connected devices, for instance to start the generator when the batteries are low. MasterBus reduces complexity of electrical systems by using UTP patch cables. All system components are simply chained together. Therefore each device is equipped with two MasterBus data ports. As only a few MasterBus cables are needed, installation and material costs are reduced importantly. New devices can be added to the existing network easily. Consequently the MasterBus network is highly flexible for extended system configuration. Mastervolt also offers several interfaces like the Modbus and NMEA interface, making even non­MasterBus devices suitable to operate in the MasterBus network. For central monitoring and control of the connected devices Mastervolt offers four different panels, from the small Mastervision compatible 120 x 65mm LCD screen up to the full colour MasterView System panel. All monitoring panels can be used for monitoring, control and configuration of all connected MasterBus equipment.
CAUTION: Never connect a non-MasterBus device to the MasterBus network directly! This will void warranty of all MasterBus devices connected.
6.2 HOW TO SET UP A MASTERBUS NETWORK
Every MasterBus device is equipped with two data ports. When two or more devices are connected via these ports, a local data network called the MasterBus is formed. Keep the following rules in mind:
Place a terminating device on both network ends.
Connections between the devices are made by standard straight UTP patch cables.
OK
At least one device in the network must be MasterBus powering (see specifications). As all powering devices are galvanic isolated, multiple powering devices are allowed.
OK
Do not make ring networks.
Do not make T-connections in the network.
OK
Terminating
device
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 17
Terminating
device
Page 18
MASTERBUS SETTINGS
7 MASTERBUS SETTINGS
Below parameters can be changed via the MasterBus network by means of a remote control panel or by means of an interface connected to a PC with MasterAdjust software. See applicable user’s manuals for details.
Value Meaning Factory setting Adjustable range
7.1 DEVICE
Language Language that is displayed on a monitoring
Name Name for the Mass Charger. CHG Mass Charger See specifications Device Device name recognized by MasterBus. Mass Charger ­Battery name Name for the main battery bank. House Bank Max 16 characters Factory settings Option to reset the Mass Charger to default
7.2 PRESETS
Diode compensate Option for charger diode +0.6 V voltage
Forced float Option for Forced Float or constant voltage
Continuous Option to keep MasterBus powered by the
Gel / AGM Gel/ AGM settings option. It includes fully
Traction Traction settings option. See section 7.8. Disabled Disabled, Enabled NiCad NiCad settings option See section 7.9. Disabled Disabled, Enabled Li-ion Li-ion settings option. See section 7.10. Disabled Disabled, Enabled Equalize Option to enable Equalizing. Shows only when
7.3 GENERAL
Max. current Maximum charge current, adjustable model
Temp. compensate Charge voltage compensation for temperature
7.4 BULK
Bulk voltage Bulk voltage 14.25/28.50/57.00 V 0.00-16.00/16.00-
Max. bulk time Maximum bulk timer 360 min 0-600 min Min bulk time Minimum bulk timer 4 min 0-600 min Start bulk time Voltage at which to start the bulk timer. 13.80/27.60/55.2 V 0.00-16.00/16.00-
Bulk ret. volt. Return to Bulk voltage 12.80/25.60/51.2 V 0.00-16.00/16.00-
Bulk ret. time Adjustable Return to Bulk time after the Return to
7.5 ABSORPTION
Abs. voltage Absorption voltage 14.25/28.50/ 57.00 V 0.00-16.00/16.00-
Max absorption Maximum absorption timer 360 min 0-600 min Min absorp. time Minimum absorption timer 15 min 0-180 min Return amps Return to Bulk current (in A) 6.0 %*I max 0-25% * I max
English EN, NL, DE, FR, ES,
device connected to the MasterBus.
IT
Not reset Not reset, reset
settings.
Disabled Disabled,
compensation. If it is enabled, the compensation
Enabled: 0-2.50 V
value is adjustable.
Disabled Disabled, Enabled charging. If it is enabled, Forced Float voltage is adjustable.
Disabled Disabled, Enabled battery when the Mass Charger is disabled.
Disabled Disabled, Enabled adjustable Bulk, Absorption and Float settings.
Disabled Disabled, Enabled no other battery type has been selected. Warning: Equalize is suitable for wet batteries only! Do not use Equalize for other battery types!
Model dependent 0-100% * Imax dependent.
-0.060 V/°C -1.000 .. 1.000 V/°C
(V/°C).
32.00/ 32.00-64.00 V
32.00/ 32.00-64.00 V
32.00/ 32.00-64.00 V
30 sec 0-255 sec Bulk voltage has been reached.
32.00/ 32.00-64.00 V
18 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 19
MASTERBUS SETTINGS
Value Meaning Factory setting Adjustable range
7.6 FLOAT
Float voltage Float voltage 13.25, 26.50,53.00 V 0.00-16.00/16.00-
32.00/ 32.00-64.00 V
Equalize voltage Equalize voltage 15.50/ 31.00/ 62.00 V 0.00-16.00/16.00-
32.00/ 32.00-64.00 V
Equalize time Equalize time 360 min 0-600 min
7.7 ALARM SETPOINTS
DC Alrm high on Alarm DC High on 16.00/32.00/ 64.00 V 0.00-16.00/16.00-
32.00/ 32.00-64.00 V
DC Alrm high off Alarm DC High off 15.00/30.00/60.00 V 0.00-16.00/16.00-
32.00/ 32.00-64.00 V
DC Alrm low on Alarm DC low on 10.00/20.00/40.00 V 0.00-16.00/16.00-
32.00/ 32.00-64.00 V
DC Alrm low off Alarm DC low off 11.00/22.00/44.00 V 0.00-16.00/16.00-
32.00/ 32.00-64.00 V
DC Alrm delay Alarm delay time 30 sec 0-255 sec
7.8 TRACTION SETTINGS
Bulk voltage Bulk voltage 14.60/29.20/58.40 V (read only) Max bulk time Maximum bulk time 360 min (read only) Min bulk time Minimum bulk time 4 min (read only) Start bulk time Start bulk time 13.80/27.60/55.20 V (read only) Bulk ret. volt. Bulk return voltage 12.80/25.60/51.20 V (read only) Bulk return time Bulk return time 30 sec (read only) Abs. voltage Absorption voltage 14.45/28.90/57.80 V (read only) Max absorp. time Maximum absorption time 480 min (read only) Min absorp. time Minimum absorption time 15 min (read only) Return amps Return to Bulk current (in A) 6.0 %*I max (read only) Float voltage Traction float voltage 13.25/26.50/53.00 V (read only)
7.9 NICAD SETTINGS
Bulk voltage Bulk voltage 14.5/29.00/58.00 V (read only) Max bulk time Maximum bulk time 480 min (read only) Min bulk time Minimum bulk time 2 min (read only) Start bulk time Start bulk time 13.25/26.50/53.00 V (read only) Bulk ret. volt. Bulk return voltage 10.00/20.00/40.00 V (read only) Bulk return time Bulk return time 30 sec (read only) Abs. voltage Absorption voltage 14.50/29.00/58.00 V (read only) Max absorp. time Maximum absorption time 480 min (read only) Min absorp. time Minimum absorption time 15 min (read only) Return amps Return to Bulk current (in A) 6.0 %*I max (read only) Float NiCad float voltage 13.00/26.00/52.00 V (read only)
7.10 LI-ION SETTINGS
Bulk voltage Bulk voltage 14.60/29.20/58.40 V (read only) Max bulk time Maximum bulk time 480 min (read only) Min bulk time Minimum bulk time 2 min (read only) Start bulk time Start bulk time 13.25/26.50/53.00 V (read only) Bulk ret. volt. Bulk return voltage 13.15/26.30/52.60 V (read only) Bulk return time Bulk return time 240 sec (read only) Abs. voltage Absorption voltage 14.50/29.00/58.00 V (read only) Max absorp. time Maximum absorption time 480 min (read only) Min absorp. time Minimum absorption time 15 min (read only) Return amps Return to Bulk current (in A) 6.0 %*I max (read only) Forced Float LI-ion forced float voltage 13.25/26.50/53.00 V (read only)
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 19
Page 20
MASTERBUS SETTINGS
7.11 EVENTS
Event x source See section 7.11.1 and 7.11.2 Disabled Event x target
Select a connected MasterBus device that should take action due to a Mass Charger event.
Select… Selectable targets are
system dependent.
Event x command Action to be taken by the target device. Select… See command list in
selected device manual
Event x data Data is linked to the command. See also figure 10. Off Off, On, Copy, Copy
Invert, Toggle.
Event x+1 The next event appears after enabling Event x. Disabled See Event x.
Figure 10 shows the meaning of the event data.
Input (pulses) The input is represented by an on/off switch.
Output (data) On changes the status to On at the first signal. Off changes the status to Off at the first signal. Copy lets the status follow the input. Copy Invert lets the status follow the opposite of the input. Copy is used for dimming too by holding the pulse switch
pressed for a longer time. Toggle changes the status at the first signal and back at the second signal. It is used in combination with a pulse switch.
Figure 10: Event data
7.11.1 Mass Charger event source list (Mass Charger as event source)
Charging Mass Charger state is On Bulk State of charge is Bulk Absorption State of charge is Absorption Float State of charge is Float Failure Charger failure MasterBus alarm CSI Charger Status Interface MasterBus alarm to sound a horn at charger failure Equalize Mass Charger is in Equalize mode TC Error Battery temperature sensor error Fan MasterBus signal for an external fan to start (at 50% load / 50°C) LED Bulk LED Bulk illuminates LED 20-40 LED 2 illuminates (see figure 3) LED Abs LED Abs illuminates LED 60-80 LED 4 illuminates (see figure 3) LED Float LED Float illuminates LED Failure LED Failure illuminates
7.11.2 Mass Charger event target list (Mass Charger as event target)
Mpc reduce Command to reduce AC current at a 5%/sec rate Mpc off Command to reduce AC current fast Bulk Command to start the Bulk state of charge Absorption Command to start the Absorption state of charge Float Command to start the Float state of charge On/ Standby Command to switch on the Mass Charger
20 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 21
TROUBLE SHOOTING
8 TROUBLE SHOOTING
In case of a failure, the Mass Charger display shows an error code to help you find its source. See section 3.3 for error codes. If you cannot solve a problem with the aid of the fault finding table, contact your local Mastervolt
8.1 FAULT FINDING TABLE
Malfunction Possible cause What to do
No output voltage and/or current
charger supplies maximum current
Charge current too low
Batteries not fully charged
Batteries are discharged too fast Batteries are too warm, gassing
No AC-input. Check AC wiring, check remote control panel. AC-input voltage too low (< 180VAC) . Check input voltage, check generator. AC input frequency out of range. Check input voltage, check generator. Load that is connected to the batteries is larger than charger can supply. Batteries not 100% charged. Measure battery voltage. After some time this will
Batteries almost fully charged. Nothing, this is normal when the battery is almost
High ambient temperature. Nothing; if ambient temperature is more than 40°C
Low AC input voltage. At lower AC-input voltages the charge current is reduced. See figure 14. Charge current too low. See “Charge current too low”. Current to load is too high. Reduce load taken from the batteries. Charge time too short. Use a battery charger with higher capacity. Battery temperature too low. Use the battery temperature sensor. Defective or old battery. Check battery and replace if necessary. Battery capacity reduced due to wastage or sulphation, stagnation. Defective battery (short circuit in cell). Check battery and replace if necessary. Battery temperature too high. Use the battery temperature sensor. Charge voltage too high. Check settings (see chapter 6).
Service Centre. See www.mastervolt.com. Make sure you have the article and serial number present if you have to contact your local Mastervolt Service Center to solve a problem (See section 1.4).
Reduce load taken from the batteries. Output voltage too low,
be higher.
fully charged.
the charge current is automatically reduced.
Check AC-input voltage.
Charge and recharge a few times, this might help.
Check battery and replace if necessary.
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 21
Page 22
TECHNICAL DATA
9 TECHNICAL DATA
9.1 SPECIFICATIONS
Model 12/60-2 12/80-2 24/50-2 24/75-C
Article no. 40010606 40010806 40020506 40020756
INPUT
Mains voltage 230V, -10% + 15% 230V, -10% + 15% 230V, -10% + 15% 230V, -10% + 15% Frequency 50 Hz ± 5 Hz 50 Hz ± 5 Hz 50 Hz ± 5 Hz 50 Hz ± 5 Hz Inrush current None, the battery charger is equipped with a soft start in accordance with IEC 1003-3 Current 4A 6A 7A 12A Power factor (Cos phi) 1 1 1 1 Efficiency 89% 89% 89% 89% Input power 900W 1400W 1600W 2700W
OUTPUT
Nominal voltage 12V DC 12V DC 24V DC 24V DC Charge current 60 A 80 A 50 A 75 A Outputs 1x60 A and 1x3 A 1x80 A and 1x3 A 1x50 A and 1x3 A 1 x 75 A Charge characteristic three-step plus, fully
automatic Kind of batteries Open and closed lead acid (gel or wet), NiCad, Li-ion (settings: section 7.10) Default charge voltages at 25°C absorption 14.25V 14.25V 28.5V 28.5V float 13.25V 13.25V 26.5V 26.5V Voltage ripple max. 100mV RMS with resistive load @ full power Short circuit current (1/4
15A 20A 12.5A 18.75A of max.) Cable size (within 3 m) 25 mm2 35 mm2 25 mm2 35 mm2 Charger fuse (external) 63A 100A 63A 80A ENVIRONMENTAL Ambient temperature -20 to 40°C @ 100% output power, derated with 2,5% / °C above 40°C Cooling Forced air, by means of a ventilator with variable speed Humidity Maximum 95%RV, non condensing MASTERBUS MasterBus powering
Yes Yes Yes Yes capability MasterBus menu
English, Dutch, German, French, Spanish, Italian languages
ENCLOSURE TYPE C2 C2 C2 C3
Dimensions (hxwxd) mm See figure 12 See figure 12 See figure 12 See figure 13 Protection degree IP23 IP23 IP23 IP23 Weight 5 kg 5 kg 5 kg 9 kg
* Adjustable, see chapter 5 for settings. Specifications are subject to change without prior notice.
three-step plus, fully automatic
three-step plus, fully automatic
three-step plus, fully automatic
22 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 23
TECHNICAL DATA
Model 24/100-C 3-24/100 48/25 48/50
Article no. 40021006 40031006 40040256 40040506
INPUT
Mains voltage 230V, -10% + 15% 3 x 400 V 230V, -10% + 15% 230V, -10% + 15% Frequency 50 Hz ± 5 Hz 50 Hz ± 5 Hz 50 Hz ± 5 Hz 50 Hz ± 5 Hz Inrush current None, the battery charger is equipped with a soft start in accordance with IEC 1003-3 Current 16 A 6.5 A 8 A 16 A Power factor (Cos phi) 1 0.8 1 1 Efficiency 89% 89% 89% 89% Input power 3600W 3500W 1800W 3600W
OUTPUT
Nominal voltage 24V DC 24V DC 48 V DC 48 V DC Charge current 100 A 100 A 25 A 50 A Outputs 1 x 100 A 1 x 100 A 1x25 A 1x50 A Charge characteristic three-step plus, fully
automatic
three-step plus, fully automatic
three-step plus, fully automatic
three-step plus, fully automatic
Kind of batteries open and closed lead acid (gel or wet),
Li-ion (settings: section 7.10) Default charge voltages at 25°C absorption 28.5 V 28.5 V 57 V 57 V float 26.5 V 26.5 V 53 V 53 V Voltage ripple max. 100mV RMS with resistive load @ full power Short circuit current (1/4 of
25 A 25 A 6 A 12.5 A max.) Cable size (within 3 m) 35 mm2 35 mm2 16 mm2 25 mm2 Charger fuse (external) 125 A 125 A 32 A 63 A ENVIRONMENTAL Ambient temperature -20 to 40°C @ 100% output power, derated with 2,5% / °C above 40°C Cooling Forced air, by means of a ventilator with variable speed Humidity Maximum 95%RV, non condensing MASTERBUS MasterBus powering
Yes Yes Yes Yes capability MasterBus menu
English, Dutch, German, French, Spanish, Italian languages
ENCLOSURE TYPE C3 C3 C2 C3
Dimensions (hxwxd) mm See figure 13 See figure 13 See figure 12 See figure 13 Protection degree IP23 IP23 IP23 IP23 Weight 9 kg 10 kg 5 kg 9 kg
* Adjustable, see chapter 5 for settings. Specifications are subject to change without prior notice.
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 23
Page 24
TECHNICAL DATA
9.2 DIMENSIONS
Figure 12: Dimensions of C2 enclosure in mm [inch]
24 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 25
TECHNICAL DATA
Figure 13: Dimensions of C3 enclosure in mm [inch]
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 25
Page 26
TECHNICAL DATA
9.3 CHARACTERISTICS (230 V AC)
Figure 14: Charge current versus input voltage
288
Float voltage + 2.25V
= 15.50VDC
Float voltage
= 13.25VDC
10% of Imax
= voltage
= current
Figure 15: Charge characteristic of the three-step Plus charging method (at 25°C / 77°F)
FLOAT EQUALIZE FLOAT
Max equalize time = 6hr
Start equalize cycle by jumper change (disabled when Gel)
Figure 16: Charge characteristic of the equalize charge cycle (at 25°C / 77°F)
26 July 2010 / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / EN
Page 27
TECHNICAL DATA / ORDERING INFORMATION
Figure 17: Temperature compensation characteristic (charge voltage versus temperature)
10 ORDERING INFORMATION
Part number Description
77040000 MasterBus terminating device 77040100 MasterBus connection cable (UTP patch cable), 1,0m / 3.3ft 77040300 MasterBus connection cable, 3.0m / 10ft 77040600 MasterBus connection cable, 6.0m / 20ft 77041000 MasterBus connection cable, 10m / 33ft 77041500 MasterBus connection cable, 15m / 49ft 77042500 MasterBus connection cable, 25m / 82ft 77050100 100m / 330ft MasterBus cable 6502001030 Modular communication cable, cross wired, 6 pole, 6 meter / 19 ft
6502100100 Modular communication cable, cross wired, 6 pole, 10 meter / 33 ft 6502100150 Modular communication cable, cross wired, 6 pole, 15 meter / 49 ft 77050200 50 pcs. modular jacks
77050000 Set to assemble MasterBus cables. Delivery: 100m / 330ft cable, 50 pcs. modular jacks and crimping tool 77030100 MasterBus USB interface, interface between your PC and the MasterBus 77010305 MasterView Easy MkII, Touch screen to control and monitor all MasterBus products 77010400 MasterView System, Full-colour touch screen to control and monitor all MasterBus products 77020100 MasterShunt 500, DC-distribution module for exact readout of battery voltage, charge / discharge current,
and state of charge on the display of the Mass Charger. continuous rating: 250A, peak current: 500A 77020200 DC Distribution 500, DC connection device with integrated fuses. 6384003200 Industrial DC fuse 32A DIN 00 6384006300 Industrial DC fuse 63A DIN 00 6384008000 Industrial DC fuse 80A DIN 00 6384010000 Industrial DC fuse 100A DIN 00 6384012500 Industrial DC fuse 125A DIN 00 6381001000 Fuse base DIN 00 (max. 160A) 79009006 Battery switch 250A with knob 79009005 Battery switch 250A with key 6387000600 Double pole automatic circuit breaker DPN 6A-B, 1P+N 6387001000 Double pole automatic circuit breaker DPN 10A-B, 1P+N 6387001600 Double pole automatic circuit breaker DPN 16A-B, 1P+N 6385401610 Double pole automatic circuit breaker and earth leakage switch DPN VIGI 16A / B / 16mA, 1P + N 41500500* Battery temperature sensor, incl. 6 meter / 19 ft cable 21730200 RJ12 splitter for C2 enclosure, refer to section 4.11
* standard included with the delivery of the Mass Charger Mastervolt can offer a wide range of products for your electrical installation. See our website www.mastervolt.com for an extensive overview of all our products.
EN / Mass Charger 12/60-2; 12/80-2; 24/50-2; 24/75; 24/100; 3-24/100; 48/25; 48/50 / July 2010 27
Page 28
EC DECLARATION OF CONFORMITY
11 EC DECLARATION OF CONFORMITY
We,
Manufacturer Mastervolt Address Snijdersbergweg 93 1105 AN Amsterdam The Netherlands
Declare under our sole responsibility that
Product: Mass battery charger Model: Mass 12/60, 12/80 Mass 24/50, 24/75, 24/100 & 24/100 3phase Mass 48/24 & 48/50
Is in conformity with the provisions of the following EC directives:
2006/95/EC (Safety directive); the following harmonized standards have been applied:
• EN 60950-1:2001+ A11:2004 (LVD)
• EN 60335-2-29: 2004
2004/108/EC (EMC directive); the following harmonized standards have been applied:
• EN 61000-6-3: 2007 Emission hold equipment
• EN 61000-6-2: 2007 Immunity industrial
• EN 55022: 2006, Class B EN 55024
• IEC 61000-3-3 voltage dip & flicker
• IEC 61000-4-11 voltage dip & flicker measurement techniques
• IEC 6100-4-2 ESD immunity
• IEC 6100-4-4 burst and surge
• IEC 6100-4-5 burst & surge measurement techniques
• IEC6100-4-3 EMC test and measurement techniques
• IEC 6100-4-6 conducted disturbance immunity
• IEC 6100-3-2 Limits for harmonic current emissions 16 A per phase
Amsterdam,
H.A. Poppelier product Manager marine & mobile
10
Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands
Tel : + 31-20-3422100
Fax : + 31-20-6971006
Email : info@mastervolt.com
Loading...