Mastervolt CS15TL, CS20TL Installation Manual

Page 1
USER’S AND INSTALLATION MANUAL / GEBRUIKERS- EN INSTALLATIEHANDLEIDING
BEDIENUNGS- UND INSTALLATIONSANLEITUNG / MANUEL UTILISATEURS ET D’INSTALLATION
MANUAL DEL USUARIO Y DE INSTALACIÓN / MANUALE DI USO E MANUTENZIONE
Sunmaster
High power grid connected solar inverter
MASTERVOLT Snijdersbergweg 93, 1105 AN Amsterdam The Netherlands Tel.: +31-20-3422100 Fax.: +31-20-6971006 www.mastervolt.com
Copyright © 2010 Mastervolt, v 1.4 August 2010
ENGLISH: PAGE 1
NEDERLANDS: PAGINA 37 DEUTSCH: SEITE 73 FRANÇAIS: PAGINA 109 CASTELLANO: PÁGINA 145 ITALIANO: PÁGINA 181
Page 2
OVERVIEW
2 August 2010 / SunMaster CS15TL/CS20TL / EN
OVERVIEW CS15TL / CS20TL
Figure 1: Inside view of the CS15TL/CS20TL
1. 3-phase 400V output plug
2. Fan module
3. Communication module
4. External grounding (PE) facility
5. Multi-language display
6. DC input 1
7. DC input 2
8. Foot stands
9. Air outlets
Page 3
CONTENTS
EN / SunMaster CS15TL/CS20TL / August 2010 3
CONTENTS: v 1.4 August 2010
1
GENERAL INFORMATION.............................................................................................................................................. 5
1.1 Product description............................................................................................................................................. 5
1.2 Use of this manual.............................................................................................................................................. 5
1.3 Validity of this manual ........................................................................................................................................ 5
1.4 Guarantee specifications.................................................................................................................................... 5
1.5 Liability ............................................................................................................................................................... 5
1.6 Changes to the CS15TL/CS20TL....................................................................................................................... 5
1.7 Identification label............................................................................................................................................... 5
2 SAFETY GUIDELINES AND WARNINGS....................................................................................................................... 6
2.1 Warnings and symbols....................................................................................................................................... 6
2.2 Use for intended purpose................................................................................................................................... 6
2.3 Organisational measures ................................................................................................................................... 6
2.4 Installation, maintenance, repair......................................................................................................................... 6
2.5 Warning of special dangers................................................................................................................................ 6
3 HOW IT WORKS.............................................................................................................................................................. 7
3.1 Working principle of the CS15TL/CS20TL.......................................................................................................... 7
3.2 Grid interface...................................................................................................................................................... 7
3.3 optima Cooling ................................................................................................................................................... 7
3.4 Monitoring........................................................................................................................................................... 7
4 BEFORE YOU START..................................................................................................................................................... 8
4.1 Transport, lifting and storage.............................................................................................................................. 8
4.2 Apparatus settings.............................................................................................................................................. 8
4.3 Installation environment ..................................................................................................................................... 8
4.4 Lightning protection............................................................................................................................................ 8
4.5 DC configuration................................................................................................................................................. 9
4.5.1 Separate or parallel inputs................................................................................................................. 9
4.5.2 Specifications of the PV installation................................................................................................... 9
4.6 DC Switch........................................................................................................................................................... 9
4.7 Three phase AC configuration............................................................................................................................ 9
4.8 Power Management ........................................................................................................................................... 9
5 COMMUNICATION MODULE........................................................................................................................................ 10
5.1 Alarm contacts.................................................................................................................................................. 10
5.2 RS485 connectors............................................................................................................................................ 10
5.3 MasterBus connectors...................................................................................................................................... 11
5.4 MasterBus network........................................................................................................................................... 11
5.5 How to set up a communication network .......................................................................................................... 11
6 INSTALLATION AND COMMISSIONING...................................................................................................................... 12
6.1 Things you need for installation........................................................................................................................ 12
6.2 Unpacking the CS15TL/CS20TL ...................................................................................................................... 12
6.3 Installation step by step.................................................................................................................................... 13
6.4 AC 3-phase connector...................................................................................................................................... 14
6.5 Isolation Transformer ....................................................................................................................................... 14
6.5.1 PV Array Grounding ........................................................................................................................ 14
6.5.2 High solar array capacity................................................................................................................. 14
6.5.3 MasterBus connections ................................................................................................................... 14
6.6 DC Distribution ................................................................................................................................................. 15
6.7 Commissioning after installation....................................................................................................................... 16
6.7.1 Switching on .................................................................................................................................... 16
Page 4
CONTENTS
4 August 2010 / SunMaster CS15TL/CS20TL / EN
6.8 De-commissioning............................................................................................................................................ 16
7 OPERATION .................................................................................................................................................................. 17
7.1 General ............................................................................................................................................................ 17
7.2 Remote monitoring ........................................................................................................................................... 17
7.3 Maintenance..................................................................................................................................................... 17
7.3.1 Air outlet .......................................................................................................................................... 17
7.3.2 Fan module ..................................................................................................................................... 17
7.3.3 Electrical connections...................................................................................................................... 17
8 DISPLAY........................................................................................................................................................................ 18
8.1 Home screen .................................................................................................................................................... 18
8.2 Buttons ............................................................................................................................................................. 18
8.3 Main menu........................................................................................................................................................ 18
8.4 Energy totals .................................................................................................................................................... 18
8.5 Plant totals* ...................................................................................................................................................... 19
8.6 Multimeter......................................................................................................................................................... 19
8.6.1 StringMaster*................................................................................................................................... 20
8.7 Datalogger........................................................................................................................................................ 21
8.8 Log book........................................................................................................................................................... 21
8.9 Configuration .................................................................................................................................................... 21
8.9.1 Date and time settings..................................................................................................................... 21
8.9.2 Grid Interface................................................................................................................................... 22
8.9.3 Display settings ............................................................................................................................... 22
8.9.4 Device Info ...................................................................................................................................... 22
8.9.5 Alarm contact settings ..................................................................................................................... 22
8.9.6 Entering installer code..................................................................................................................... 22
8.9.7 Reset to factory settings.................................................................................................................. 23
8.9.8 StringMaster settings* ..................................................................................................................... 23
9 TROUBLE SHOOTING.................................................................................................................................................. 24
9.1 LED indication and solution table ..................................................................................................................... 24
10 SPECIFICATIONS ......................................................................................................................................................... 25
10.1 Technical specifications ................................................................................................................................... 25
10.2 Outline drawings............................................................................................................................................... 27
11 ORDERING INFORMATION.......................................................................................................................................... 28
12 USE IN ITALY ................................................................................................................................................................ 29
12.1 Self test function............................................................................................................................................... 29
13 CERTIFICATES ............................................................................................................................................................. 31
13.1 EC declaration of conformity ............................................................................................................................ 31
13.2 VDE0126-1-1 Certificate of compliance ........................................................................................................... 32
13.3 RD 1663 Compliance ....................................................................................................................................... 33
13.4 Italy Certificate of compliance........................................................................................................................... 34
13.5 Certificate of compliance.................................................................................................................................. 35
Page 5
GENERAL INFORMATION
EN / SunMaster CS15TL/CS20TL / August 2010 5
1 GENERAL INFORMATION
1.1 PRODUCT DESCRIPTION
The Sunmaster CS15TL and CS20TL, further referred to as “CS15TL/CS20TL” or “inverter” are grid connected solar inverters. This inverter type is used to convert photovoltaic power and feed this into a three phase grid. The CS15TL/CS20TL is not suitable for stand-alone use (i.e. use without public grid).
1.2 USE OF THIS MANUAL
Copyright © 2010 Mastervolt. All rights reserved. Reproduction, transfer, distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited. This manual serves as a guideline for the safe and effective use and installation of the CS15TL/CS20TL:
For the electrician this manual gives directions for the installation, operation and commissioning.
For the end-user this manual gives directions for the operation, maintenance and possible correction of minor malfunctions of the CS15TL/CS20TL.
Every person who works with the apparatus should be familiar with the contents of this manual, and must carefully follow the instructions contained herein.
Store the manual in a user accessible place.
1.3 VALIDITY OF THIS MANUAL
This manual is valid for the following models:
Part no Model
131200150 Sunmaster CS15TL 131200200 Sunmaster CS20TL
All the specifications, provisions and instructions contained in this manual apply solely to the Mastervolt-delivered standard version of the CS15TL/CS20TL.
1.4 GUARANTEE SPECIFICATIONS
Mastervolt assures the product guarantee of the CS15TL/CS20TL during five years after your purchase, on the condition that all instructions and warnings given in this manual are taken into account during installation and operation. Among other things, this means that installation is carried out by a qualified electrician, that installation and maintenance are executed according to the stated
instructions and correct working sequence and that no changes or repairs may have been performed on the CS15TL/CS20TL other than by Mastervolt. The warranty is limited to the costs of repair and/or replacement of the product by Mastervolt only. Costs for installation labour or shipping of the defective parts are not covered by this warranty. For making an appeal on warranty you can contact your supplier directly, stating your complaint, application, date of purchase and part number / serial number.
1.5 LIABILITY
Mastervolt accepts no liability for:
consequential damage due to use of the CS15TL/CS20TL;
possible errors in the manuals and the results thereof.
1.6 CHANGES TO THE CS15TL/CS20TL
Changes on the CS15TL/CS20TL may be carried out only after the written permission of Mastervolt.
1.7 IDENTIFICATION LABEL
Figure 2
The identification label is positioned at the right side of the CS15TL/CS20TL, see figure 2.
CAUTION!
Never remove the identification label.
Part no : 131200200 Type : MasterSol CS20TL Input : 250-950Vdc, 1000Vdc Max
MPP 350-800Vdc, 2x30A
Output : 3 phase 400Vac, 50/60Hz, 20kWnom
VDE 0126-1-1
DK 5940
IP65
Serial no: X402-0007
Sunmaster CS20TL
Page 6
SAFETY GUIDELINES AND MEASURES
6 August 2010 / SunMaster CS15TL/CS20TL / EN
2 SAFETY GUIDELINES AND WARNINGS
2.1 WARNINGS AND SYMBOLS
Safety instructions and warnings are marked in this manual by the following pictograms:
A procedure, circumstance, etc which deserves extra attention.
CAUTION!
Special information, commands and prohibitions in order to prevent damage.
WARNING
A WARNING refers to possible injury to the user or installer or significant material damage to the CS15TL/CS20TL if the installer / user does not (carefully) follow the stated procedures.
2.2 USE FOR INTENDED PURPOSE
The CS15TL/CS20TL is constructed as per the applicable safety-technical guidelines. Use the CS15TL/CS20TL only in installations that meet the following qualifications:
in permanent installations;
connected to a separate, grounded three phase AC
group, to which no other electrical equipment is connected;
the electrical installation must meet the applicable regulations and standards, must be carried out correctly and must be in a good condition.
according to the technical specifications as stated in section 10.1.
WARNING
Never use the CS15TL/CS20TL in situations where there is danger of gas or dust explosion or potentially flammable products!
Use of the CS15TL/CS20TL other than as mentioned under § 2.2 and 4.3 is not considered to be consistent with the intended purpose. Mastervolt is not liable for any damage resulting from the above.
2.3 ORGANISATIONAL MEASURES
The installer / user must always:
have access to this manual;
be familiar with the contents of this manual. This
applies to Chapter 2, Safety Guidelines & Warning particularly.
2.4 INSTALLATION, MAINTENANCE, REPAIR
WARNING
As dangerous voltages exist, only allow installation, maintenance and repair of the CS15TL/CS20TL and changes in your electrical system to be carried out by qualified
electricians. Connections and safety features must be executed according to the locally applicable regulations. In case of decommissioning and/or demounting follow the instructions as stated in section 6.8. If such are required, only use original spare parts.
2.5 WARNING OF SPECIAL DANGERS
Two primary energy sources are present:
solar panels (DC) and grid (AC)! Switch off
both sources before starting any work on the
installation. Block the switching device against
unintentional switching. Verify de-energizing
of both DC and AC connections using a
suitable metering instrument.
The voltages (up to 1000V) present at the grid
and solar side of the CS15TL/CS20TL are not
safe to touch.
Make sure two persons are present when
working on an installation, at least until the
installation has been de-energized and
verified by a suitable metering instrument.
Page 7
HOW IT WORKS
EN / SunMaster CS15TL/CS20TL / August 2010 7
3 HOW IT WORKS
See figure 3. A string box combines multiple PV stings to two solar inputs. The CS15TL/CS20TL inverts the DC solar inputs to one 3-phase 3 x 400 V AC output. Both inputs and output are filtered from voltage ripples. For the operating voltage range refer to the specifications. The AC outputs are connected in a 400 V AC three-phase delta configuration. An isolation transformer between the
inverter and the grid is an option. Anti- islanding is provided according to national standards. If one of the phases of the AC grid fails in operation, the CS15TL/CS20TL will switch off immediately. Extended diagnostics via remote monitoring may be ordered as an option.
Figure 3: Schematic example of the CS15TL/CS20TL in a PV plant
3.1 WORKING PRINCIPLE OF THE CS15TL/CS20TL
See figure 3. The CS15TL/CS20TL converts the energy from a PV array and feeds this energy back to the electric grid. The electrical components in the CS15TL/CS20TL are housed in an IP65 compartment with IP44 cooling compartment.
3.2 GRID INTERFACE
The gird interface consists of a number of safety systems:
VFM (Voltage and Frequency Monitoring);
RCD (Residual Current Detection);
DCD (Direct Current Detection);
Controlling redundant AC relays for each grid phase.
3.3 OPTIMA COOLING
For an optimum internal temperature control the CS15TL/CS20TL is provided with four cooling fans. These fans start running slowly at inverter start up. Fan speed os controlled by internal temperature and output power. If internal temperature rises, the cooling fans will increase their speed. This is a normal effect which enhances the CS15TL/CS20TL efficiency and lifetime.
3.4 MONITORING
The CS15TL/CS20TL is equipped with a display for monitoring on location. However, remote monitoring is an option too, using the internet. See also chapter Operation. If you opt for remote monitoring, please contact your Mastervolt supplier.
Page 8
BEFORE YOU START
8 August 2010 / SunMaster CS15TL/CS20TL / EN
4 BEFORE YOU START
4.1 TRANSPORT, LIFTING AND STORAGE
Ensure adequate and secure packaging during transportation of the CS15TL/CS20TL. Always use suitable handling equipment for transportation.
When lifting the CS15TL/CS20TL avoid any risk of personal injuries, do not stand under the CS15TL/CS20TL.
4.2 APPARATUS SETTINGS
The CS15TL/CS20TL is equipped with an anti-islanding device that ensures instant disconnection in case of grid failure. European countries maintain different regulations with regard to anti-islanding devices and grid connection of distributed generation in general. The common islanding device switches off the inverter if the grid voltage or frequency is out of range. The CS15TL/CS20TL is set to local regulations by setting the country in the configurations menu. This setting is password protected. Contact your Mastervolt distributor in case the settings need to be changed.
CAUTION!
NEVER connect the CS15TL/CS20TL to a utility grid other than specified, refer to chapter 10.
4.3 INSTALLATION ENVIRONMENT
Obey the following stipulations during installation:
The CS15TL/CS20TL is designed for both indoor and
outdoor use, safety class is IP65.
Ambient temperature: -20 to 60°C; (power derating
above 40°C).
Keep at least 50 cm space around the
CS15TL/CS20TL, fig 4.
If the CS15TL/CS20TL is installed in the immediate
vicinity of living areas, take into account that it can produce a certain noise level when operating.
Mount the CS15TL/CS20TL vertically to a solid wall.
CAUTION!
Do not install in aggressive environments like ammonium, acids and salt air.
CAUTION!
Do not install in areas that are subject to the risk of gas- or dust explosions.
4.4 LIGHTNING PROTECTION
In a solar installation, precautions must be taken to avoid damage from induced surges caused by lightning. The CS 15/20 TL is equipped with class III (mcro) protection against over voltages on all DC, AC and communication in/ outputs. Additional (external) surge protection of these in/ outputs is strongly recommended. StringMaster string boxes featuring a class II surge protection are available from Mastervolt. Suitable surge arrestors (varistors) must be installed near the inverter (<10 m).
Figure 4: Mounting distance
50cm
[20 inch]
50cm
[20 inch]
50cm
[20 inch]
50cm
[20 inch]
Page 9
BEFORE YOU START
EN / SunMaster CS15TL/CS20TL / August 2010 9
4.5 DC CONFIGURATION
The solar or DC side of the system consists of several photovoltaic (solar) modules, further referred to as “PV modules”. The PV modules are connected in series to form a so called “string”. These strings have a plus (+) and a minus (–) connection which can be connected to the CS15TL/CS20TL via a string combiner box, eg. the Mastervolt StringMaster.
4.5.1 Separate or parallel inputs
The CS20TL has two separate inverters with an own input each, called Input 1 and Input 2. These inputs can be used as separate inputs (normal situation) or they can be configured in parallel. See figures and table for the applications.
Separate inputs Parallel operation
Per input different string lengths possible.
For uneven numbers of
strings. Per input max 13 kWp. MPP current above 30A. Per input different PV module positions possible.
For PV grounding. Refer to
section 6.5.1. Per input different module types possible.
Figure 5: Separate inputs and parallel operation
4.5.2 Specifications of the PV installation
The PV installation should meet next specifications:
The maximum open circuit string voltage for each power module at lowest possible temperature of the PV modules may not exceed 1000V.
Double isolated PV cabling, fitted with MultiContact 4mm type connectors must be used.
The maximum power connected to the CS15TL may not exceed 10 kWp per input or 19 kWp in total.
The maximum power connected to the CS20TL may not exceed 13 kWp per input or 25 kWp in total.
All connection devices (wiring, terminal blocks, fuse holders, fuses, switches etcetera) must be rated for the applicable voltage (up to 1000V DC) and current ratings (up to 30A DC) of the solar installation.
Do not install the CS15TL/CS20TL if the solar-system does not comply with the stipulations mentioned above!
4.6 DC SWITCH
For safety reasons, the use of a suitable DC siwtich is recommended. Depending on local applicable regulations the use of a DC switch between the PV modules and the power modules may be mandatory. The DC switch is included in the optional StringMaster CS 2-6 SW.
4.7 THREE PHASE AC CONFIGURATION
The CS15TL/CS20TL is intended for use in a permanent installation, connected to a separate three phase AC distribution group, to which no other electrical equipment is connected. All electrical connections must comply with local codes and regulations. The AC output is arranged in a 400 V AC three-phase delta configuration. Use a suitable cross section, so that the cable loss is well below 1%. The recommended cross section for a 10 m cable is 4,0 mm².
4.8 POWER MANAGEMENT
The CS15/20TL has a power management function built in. It enables a grid operator to send a request for delivering less power to the grid. For this purpose, an optional DataControl Premium or DataControl Pro II is connected to the inverter via RS485. The grid operator sends his request to the datalogger that triggers the Power Management function. In case such a request is done, the display shows the reduction value in the home screen. Example: ON, Pwr Mgmt 30 % means maximum 70% of the nominal output power should be delivered. For all power reduction values, see chapter 9. Contact your Mastervolt supplier for more information.
Page 10
COMMUNICATION MODULE
10 August 2010 / SunMaster CS15TL/CS20TL / EN
5 COMMUNICATION MODULE
The CS15TL/CS20TL is equipped with a detachable communication module for mounting the alarm wiring. It also facilitates inserting the MasterBus and RS485 plugs. The left gland is reserved for RS485 and alarm wiring, the right gland for the MasterBus wiring.
Install the communication wiring, see the steps below:
Loosen the Phillips screws at both sides of the front plate (see figure 6).
Pull out the module, taking care not to damage the connectors and components.
Release glands and remove plugs where applicable.
Insert the plugs and mount the alarm wiring. See the
label in figure 7 for more information.
MasterBus connectors are similar to RS485 connectors! Wrong installation causes communication failure.
5.1 ALARM CONTACTS
See figure 7, left part. The three alarm contacts (maximum load 30V/1A) are Common (Com), Normally Open (NO) and Normally Closed NC), see figure 8.
5.2 RS485 CONNECTORS
The two connectors in the middle are RS485 connectors. They can be used for connecting up to 20 CS15TL/CS20TL inverters. They also connect your inverter to an optional Datalogger or a PC for remote monitoring. We recommend not to make a ringnetwork or T-connections in your RS485 network. The maximum network length is 1000m. See chapter Specifications for more information.
Figure 9: RS485 connections
Figure 6 Communication module
Figure 7: communication label
NO NC
COM
COMMUNICATION
A
Max 30V/1A
ALARM
CONTACT
!
B
485
485
Figure 8: Alarm contacts
Page 11
COMMUNICATION MODULE
EN / SunMaster CS15TL/CS20TL / August 2010 11
5.3 MASTERBUS CONNECTORS
The CS15TL/CS20TL is equipped with 2 x 2 MasterBus connectors (A and B) to install two MasterBus networks. Network A is reserved for the string box connected to the CS15TL/CS20TL. The other network (B) is reserved for future upgrades.
Figure 10: RS485 and MasterBus connections
Proceed as follows to remount the communication module:
Close any unused holes in the glands, using the premounted caps.
Insert communication module, using the guidance rails.
Fix the Phillips screws at both sides of the front plate
(see figure 4).
For MasterBus connection of the CS-IT20 isolation transformer, refer to section 6.6.
The CS15TL/CS20TL is compatible with the Sunmaster XL and XS inverter series, so it can be combined with these inverters in the MasterBus network.
5.4 MASTERBUS NETWORK
All devices that are suitable for MasterBus are marked by the MasterBus symbol.
MasterBus is a fully decentralized data network for communication between the different Mastervolt system devices. The communication network is based on CAN­bus which has proven a reliable bus-system. New devices can be added to the existing network by just extending the network. This gives the MasterBus network a high degree of flexibility for extended system configuration. Mastervolt
also offers several interfaces, making even non-MasterBus devices suitable to operate in the MasterBus network.
CAUTION: Never connect a non-MasterBus device to the MasterBus network directly! This will void warranty of all MasterBus devices connected.
5.5 HOW TO SET UP A COMMUNICATION NETWORK
Every device that is suitable for the RS 485 and MasterBus network is equipped with two data ports. When two or more devices are connected using these ports, together they form a local data network.
Keep the following rules in mind:
Figure 11
Figure 12
MasterBus needs a terminating device on both ends of the network. This is not needed for RS485.
Terminating
device
Terminating
device
OK
Connections between the devices are made by standard straight UTP cables. Mastervolt can supply these cables. These cables are also commonly available at com
p
uter supply stores.
OK
1-8
1 2 B A A B 2 1
1 2 B A A B 2 1
1 2 B A A B 2 1
Page 12
INSTALLATION AND COMMISSIONING
12 August 2010 / SunMaster CS15TL/CS20TL / EN
6 INSTALLATION AND COMMISSIONING
CAUTION
Until all components have been verified to be de-energized, at least 2 persons are required during installation.
CAUTION!
Read chapters 2 and 4 prior to installation.
WARNING
Verify that all wiring is disconnected from any power source during the entire installation. Use suitable testing equipment.
CAUTION!
Short circuiting, miswiring or reverse polarity may lead to damage to the CS15TL/CS20TL, the cabling and/or the terminal connections. Follow all steps of the installation instructions in order of succession as described.
6.1 THINGS YOU NEED FOR INSTALLATION
Make sure you have all the parts you need to install the CS15TL/CS20TL:
1 CS15TL/CS20TL (included)
1 mounting bracket (included)
1 AC 3-phase output plug (included)
StringMaster CS 2-6 Pro when more than two string
inputs are needed
2 MasterBus terminating devices (included)
This user’s and installation manual (included)
M8 bolts and plugs to fix the CS15TL/CS20TL
enclosure to the wall. Use mounting materials that are suitable for the application.
Cabling
Tools to fix CS15TL/CS20TL wall mounting bracket
and enclosure to the wall
Tools to install the wiring
6.2 UNPACKING THE CS15TL/CS20TL
The CS15TL/CS20TL is packed in a plastic bag and delivered in a special transport box.
1. Unscrew the 6 box screws.
2. Lift the box cover and remove the plastic bag.
3. Lift the inverter from the bottom plate.
The inverter can be put on its four foot stands before hanging it to the wall. Take care not to bend the lips.
Figure 13: foot stands
After unpacking, check the contents for possible damage. Do not use a damaged product. If in doubt, contact your supplier.
Figure 14: Unpacking
+
+
+
+
+
+
1 2 3
6x
Page 13
INSTALLATION AND COMMISSIONING
EN / SunMaster CS15TL/CS20TL / August 2010 13
6.3 INSTALLATION STEP BY STEP
See also section 4.4.
1 Fix the CS15TL/CS20TL to the wall, starting with the
mounting bracket. See figure 15. Use suitable screws and plugs.
2 Open the communication module of the
CS15TL/CS20TL (section 4.5).
3 If applicable, connect alarm wiring and MasterBus
cables. 4 Connect the DC Solar wiring. 5 Connect the AC wiring. Refer to the manual of the AC
connectors (manual included with connector)
WARNINGS
High voltages (up to 1000 VDC) may exist on the PV strings! Switch off the solar voltage and verify that no dangerous voltage is present, before starting the cable work.
Figure 15: drilling template of bracket and housing
See figure 16. AC connector: refer to section 6.4 AC 3-phase connector, Communication module: refer to chapter 5, PV input: refer to section 6.6 DC Distribution.
Figure 16: Overview of the CS15TL/CS20TL connections
AC
Communication
module
PV input
272
(10,7)
323 (12,73)
592 (23,3)
188 (7,41) 270 (10,6)
80
(3,15)
Page 14
INSTALLATION AND COMMISSIONING
14 August 2010 / SunMaster CS15TL/CS20TL / EN
6.4 AC 3-PHASE CONNECTOR
The AC connector has five wire terminals, figure 16 shows the connector. Connect PE first (yellow-green).
Figure 17: AC 3-phase connector
Table: minimum cable diameters for power loss under 1%.
AC cable length Diameter
<10 m 4 mm2 10-30 m 6 mm2 >30 m > 6 mm2
The PE cable diameter must be at least as large as the largest AC cable used, with a minimum of 4 mm
2
. For more information on cable diameters, refer to the installation norms like NEN1010. If the cable diameter recommended exceeds the connector size, an adapter is necessary.
6.5 ISOLATION TRANSFORMER
An isolation transformer may be necessary for two purposes.
1. PV plant grounding (section 6.5.1);
2. Prevention of RCD tripping (section 6.5.2).
6.5.1 PV Array Grounding
Grounding of your CS20TL is necessary. This is possible at the AC side, see figure 18. Some PV panel suppliers prescribe connection of PE to the positive or minus DC input. In this case, follow next steps.
To avoid inverter damage, a high power isolation
transformer like the CS-IT20 must be installed at the AC side.
The DC inputs must be paralleled
Connect the Protective Earth (PE) to the positive or
negative DC input.
Switch off the Insulation Fault detection. See the CS-
IT20 manual for more information. Figure 18 shows the scheme for applying the isolation transformer in your PV plant.
Figure 18: PE at DC input isolation transformer
6.5.2 High solar array capacity
A high solar array capacitance may exist to the PV frame or support structure (PE). The CS20TL has been designed to withstand solar array capacities up to 4 µF. Capacities exceeding this value may cause the internal RCD to trip, installing an isolation transformer is necessary.
6.5.3 MasterBus connections
The CS-IT20 transformer is equipped with a MasterBus relay for MasterBus controlled switching. Network A is used for this purpose. Refer to figure 18 and chapter 5.
Figure 19: MasterBus network A: CS-IT20, CS20TL, StringMaster
DC
AC
DC
AC 3-P
+
_
+
_
PE CS 20 TL CS-IT20
Protective Earth
1. Line 1 (L1)
2. Line 2 (L2)
3. Line 3 (L3)
4. Not used
Page 15
INSTALLATION AND COMMISSIONING
EN / SunMaster CS15TL/CS20TL / August 2010 15
6.6 DC DISTRIBUTION
The CS15TL/CS20TL has two independent solar inputs. To accommodate more than two strings, a StringMaster string box is available especially for the CS15TL/CS20TL. Refer to the StingMaster manual for installation instructions. To release the MultiContact connectors, use of the special MultiContact tool is recommended. When more than three stings are paralleled, they must be fused. For fuse ratings refer to specifications of used fuse. All strings connected to the same Solar-input should consist of an equal number of identical PV modules. Measure the solar voltage for each input. The calculated string voltage equals the open circuit voltage (Uoc) per PV module (refer to the specifications of the PV module), multiplied by the number of PV modules in each string.
Depending on the solar irradiation and temperature, the measured string voltage amounts to 70-95% of the calculated value.
Note that the maximum power connected to each Solar­input shall not exceed 13 kWp for the CS20TL and 10 kWp for the CS15TL. The total input power must be distributed equally over the two Solar-inputs as much as possible.
Current MPP 15A MPP 20A MPP 30A Length
<10 m 2.5 mm2 4.0 mm2 6.0 mm2 10-20 m 4.0 mm2 6.0 mm2 10 mm
2 *
>20 m >4.0 mm2 >6.0 mm
2 *
>10 mm
2 *
* a cable adapter is necessary for cross sections >6.0 mm2
Figure 20:
Functional scheme StringMaster
Page 16
INSTALLATION AND COMMISSIONING
16 August 2010 / SunMaster CS15TL/CS20TL / EN
6.7 COMMISSIONING AFTER INSTALLATION
To check the correct operation of the CS15TL/CS20TL, commissioning should be carried out during daytime only.
6.7.1 Switching on
Follow these steps to switch On the CS15TL/CS20TL: 1 Check whether the DC switches (if applied) are in the
OFF position. 2 Check AC and DC cabling and connectors. 3 Move the DC switch (if applied) of the solar array to
the ON position.
As long as the CS15TL/CS20TL is not configured in accordance with the local regulations for grid connection, it will stay in Standby mode. This means that no power can be converted.
4 If applicable, switch on the AC grid. 5 Select language and country, using the display. See
chapter 8. 6 Set the day and time. 7 Check the PV input DC voltage and the AC voltage at
the grid side of the AC circuit breaker using the
display multimeter menu. The AC voltages should be
as follows:
L1 N 230V AC +/- 10% L2 N 230V AC +/- 10% L3 N 230V AC +/- 10% L1 L2 400V AC +/- 10% L2 L3 400V AC +/- 10% L3 L1 400V AC +/- 10%
If DC and AC voltages are within range and solar irradiation is sufficient, the CS15TL/CS20TL will switch on automatically. This may take a few minutes.
6.8 DE-COMMISSIONING
If it is necessary to put the CS15TL/CS20TL out of operation, follow the instructions in order of succession as described below:
CAUTION!
Follow below mentioned instructions in order of succession as described.
1 Cut off the grid voltage by switching off the AC circuit
breaker 2 Switch Off the DC switch 3 Release the AC connector 4 Release the CS15TL/CS20TL MultiContact
connectors, using the MultiContact tool
Now the CS15TL/CS20TL can be demounted in a safe way.
CAUTION!
Never release the MultiContact plugs during operation of the CS15TL/CS20TL. A spark or an electric arc may develop, in which case both plug and socket of the CS15TL/CS20TL must be replaced.
Page 17
OPERATION
EN / SunMaster CS15TL/CS20TL / August 2010 17
7 OPERATION
7.1 GENERAL
After installation and commissioning the CS15TL/CS20TL will switch on automatically if solar irradiation is sufficient. The CS15TL/CS20TL operates automatically: there is no need for operating it. If the irradiation of the PV modules is insufficient, for instance at night, the CS15TL/CS20TL switches off automatically. The LCD screen however still functions, as long as AC is available.
7.2 REMOTE MONITORING
Mastervolt provides several monitoring solutions like PC software, dataloggers, remote monitoring and so on. Consult www.mastervolt.com/Solar for a comprehensive overview of all possibilities.
7.3 MAINTENANCE
If necessary, use a soft clean cloth to clean the enclosure of the CS15TL/CS20TL. Never use any aggressive ofr abrasive cleaning agents.
7.3.1 Air outlet
The CS15TL/CS20TL is provided with wire mesh behind the air outlets (fig. 1 point 7).
Remove the two air outlets by unscrewing the two Phillips screws on top. Check the wire mesh at least every 12 months. Clean if necessary.
7.3.2 Fan module
The fan module (figure 21) also needs checking and cleaning every 12 months. Unscrew the 4 hand screws like indicated. Carefully move out the fan module, bottom first and unplug the four fans before removing the module completely. If necessary, clean the fans using compressed air.
Figure 22: Fan module with hand screws
7.3.3 Electrical connections
Examine your electrical installation on a regular base, at least once a year. Defects such as loose connections, burnt wiring etc. must be corrected immediately.
Figure 21: Removing the air outlets
Page 18
DISPLAY
18 August 2010 / SunMaster CS15TL/CS20TL / EN
8 DISPLAY
8.1 HOME SCREEN
If the CS15TL/CS20TL is operating normally and no button is touched, the home screen appears. It indicates the power that is fed into the grid, the energy produced and the status of the inverter. See figure 23.
Figure 23: Actual Power indication
In case an alarm occurs, this will appear on the screen.
8.2 BUTTONS
The CS15TL/CS20TL display has six buttons and one LED, refer to figure 24.
Figure 24: Display, buttons and LED
8.3 MAIN MENU
Figure 25: Main menu
1. Total energy generated since commissioning (kWh).
2. Actual measurements of all CS15TL/CS20TL connected to RS485 in the PV plant.
3. Actual measurements of this particular inverter.
4. Historical measurements of this particular inverter.
5. Log book for failures occurred.
6. Settings.
8.4 ENERGY TOTALS
This page (see figure 26) shows the inverted PV energy in kWh, per input and as total. It also shows the total CO2 equivalent in kg and the economic value in the unit of your country.
Figure 26: Energy totals
Back
To the left
Up
Power LED
To the right
Confirm
Down
OK
1
2
3
5
6
4
7
123
4
6
5
Page 19
DISPLAY
EN / SunMaster CS15TL/CS20TL / August 2010 19
8.5 PLANT TOTALS*
In figure 27 and 28 the four Plant Totals screens are shown. Use the display buttons left and right to scroll between the screens. Actual (figure 26, 1
st
) = actual total plant power kW,
2
nd
: P/Pwp = normalised power in %. The inverter Watt Peak value together with the inverter name (Ref.) are adjustable in Device Info (section 8.10.4). Adjust this value to let the inverter calculate the normalised power. 3
rd
: Day = total plant energy of the present day kWh.
4
th
: Inv = inverter number corresponding with inverter number in the other Plant Totals screens; Ref = Inverter reference to be entered by yourself; Serial = Inverter serial number; Info = Inverter information.
Figure 27: Plant totals screens 1&2
*
A software update may be necessary to activate this feature.
Contact Mastervolt for more information.
Figure 28: Plant totals screens 3&4
8.6 MULTIMETER
Use this screen to measure the actual DC and AC values. See figure 29. The power, voltage and current of Input 1 and 2 are shown. The output AC frequency is also indicated.
Figure 29: Multimeter inputs/output
Page 20
DISPLAY
20 August 2010 / SunMaster CS15TL/CS20TL / EN
8.6.1 StringMaster*
If a StringMaster Pro has been installed, the StringMaster home screen appears. Figure 30 is an example. This screen shows all string variables of StringMaster 1 (“---“ means not used). Up to three StringMasters Pro can be combined with a single inverter. This means the StringMasters have to be configured on the CS20TL display to indicate to what inverter they belong. Refer to section 8.10.8. The StringMaster compares all string currents. If one current stays behind in performance, it sends out an alarm and the display reads “LOW”. Refer to section 8.10.8.
*
A software update may be necessary to activate this feature.
Contact Mastervolt for more information.
Figure 30: Multimeter inputs per string
The next table describes the messages in figure 30.
Status Description
OK StringMaster x is ON. OFF StringMaster has been switched OFF. HW Error Refer to StringMaster manual. Not Connected StringMaster has no connection to MasterBus. StringMaster has not been configured. Warning OC: over current (>30A)
NEG: negative current (reverse polarisation) LOW: Performance (current) low. OVP1(2) Overvoltage protection of String Input 1 (2) GFD1(2) Ground Fault Detection and fuse TRIPPED of String Input 1 (2)** Switch Open: DC switch open (Off)**
** This function is reserved for future use
.
Page 21
DISPLAY
EN / SunMaster CS15TL/CS20TL / August 2010 21
8.7 DATALOGGER
The Datalogger shows the solar (total) variables in a 2 axis graphic. A day, month and year representation can be selected by pressing the buttons Up and Down (figure 23, button 3 and 7 respectively).
Figure 31: Datalogger, year representation.
The day (month, year) representation shows the energy inverted that day (month, year), the savings in your currency that day (month, year) and the best energy hour (day, month). The resolution for the day (month, year) representation is 15 minutes (1 day, 1 month).
8.8 LOG BOOK
The Log book shows all errors reported since installation of the inverter. Scrolling is done by pressing the buttons Up and Down (figure 23, button 3 and 7 respectively).
Figure 32: Log book use
8.9 CONFIGURATION
Figure 33: Configuration screen
See figure 33. The numbers 1 to 8 correspond with the section numbers 8.10.1 to 8.10.8.
8.9.1 Date and time settings
For settings the LCD buttons are used like below. Left and right are for scrolling, up and down for altering values. OK opens the setting mode and confirms the values after setting, Back exits the setting mode.
Figure 34: How to set values on the LCD screen
Figure 35: Date and time settings
1 2 3 4
5 6 7 8
OK
Set date
14 / / 201004
05
03
Page 22
DISPLAY
22 August 2010 / SunMaster CS15TL/CS20TL / EN
8.9.2 Grid Interface
The display features four menus with grid interface settings: Country setting, Grid settings, Selftest and Options. If changing these settings is necessary, please contact your Mastervolt supplier. An important setting in the Options menu is the Insulation Fault detection mode. It can be set to ON and OFF. If Fault detection mode is ON, the insulation impedance is measured and shown in K ohm. If applied, the CS-IT20 Isolation Transformer can be configured to shut down at night*, preventing no load energy loss. This function Night Shut down can be set to ON and OFF.
Figure 36: Insulation fault detection
8.9.3 Display settings
Brightness range = 1-5 Contrast range = 1-5 Display sleep mode switches off the backlight and lets the display return to the home screen when no button has been touched for 5 minutes. Language range: see specifications. Currency range = Euro, Dollar Set value / kWh = the money value of 1 kWh in the currency selected.
Figure 37: Display settings
8.9.4 Device Info
These screens show device type and firmware version, see figure 38. The Installation date appears automatically after inversion of 10 kWh or after 30 hours of operation. The General Info Device name and PV power can be adjusted in the screen**.
Figure 38: Device information
8.9.5 Alarm contact settings
In this screen the Alarm function can be switched On or Off. A MasterBus event to trigger the alarm can be selected. MasterBus event range:
On = Inverter ON;
ERROR = a system error has occurred;
Ground fault = current leaks to earth;
Solar OK = the PV voltage is within range;
Insulation or ground fault = the resistance to PE is out
of range or current leaks to earth.
8.9.6 Entering installer code
For enabling configuration like grid settings, an installer code must be entered. This way, unintentional changing of settings is prevented. Logging out happens automatically. Contact Mastervolt to obtain your installer code.
Figure 39: Installer code
Page 23
DISPLAY
EN / SunMaster CS15TL/CS20TL / August 2010 23
8.9.7 Reset to factory settings
By resetting to factory settings, all data will be removed, not only all settings but also the Datalogger history.
CAUTION!
Resetting removes all settings and all Datalogger history!
If you select this option, a warning screen appears (fig 40). If you select Continue, all custom settings are reset to factory default. A second screen confirms the reset.
8.9.8 StringMaster settings*
This section shows all settings to be made if you use a StringMaster. All string inputs 1 to 12 can be enabled if strings are connected. See figure 41.
Variable Description Default Range
Input 1, Str 1-6 Solar input 1, string 1 to 6 Not connected Not connected, connected Input 2, Str 7-12 Solar input 2, string 7 to 12 Not connected Not connected, connected OVP1 Over Voltage Protection of Solar Input 1 On Off, On OVP2 Over Voltage Protection of Solar Input 2 On Off, On GFD1 Ground Fault Detection of Solar Input 1
(not standard in String Master)
Off Off, On
GFD2 Ground Fault Detection of Solar Input 2
(not standard in String Master)
Off Off, On
Deviation Maximum allowed difference (percentage) with the
maximum string current measured. See also figure 41.
20% 10-100%
Theshold Offset Deviation below which no alarm is triggered. 0,5 A 0,5-30,0 A Alarm Option to disable the alarm function. On On, Off Alarm delay Time threshold to trigger an alarm. 60 min 0-1440 min Polarity Input polarity. In some countries it must be reversed.
Also useful when current measurement is negative.
Normal Normal/ Reverse
Performance Low warning
If the current of string (x) is LOW, a warning appears. The conditions for this warning are:
1. The current of string (x) is out of deviation. D (deviation) is the percentage to enter;
2. The current of string (x) is lower than the maximum current of all strings minus the Offset;
3. Conditions 1 and 2 are present for at least a period as long as the alarm delay. Refer to figure 42.
Figure 42: Performance Low warning graph
*
A software update may be necessary to activate this feature.
Contact Mastervolt for more information.
ContinueCancel
Figure 40
Figure 41
Page 24
24 August 2010 / SunMaster CS15TL/CS20TL / EN
9 TROUBLE SHOOTING
9.1 LED INDICATION AND SOLUTION TABLE
Fast blink= 2 blinks per second, slow blink = 1 blink per second
LED indication Display indication Description What to do
AC not connected and:
1. insufficient irradiation If no display appears during daytime, contact your installer.
2. DC switch in Off position Move DC switch to the ON position.
3. DC fuse blown Check string fuses.
No LED function No display function
4. No PV power (voltage out of range) The DC voltage should be 200-1000V.
Grid faults
Red AC freq high, low Grid frequency out of range If this happens often, contact installer. Red AC phase jump Disconnect: fast frequency fluctuations If often, contact your installer. Red AC quality Disconnect due to bad grid quality If often, contact your installer. Red No grid No grid available Check the fuses. Red AC volt low, high Grid voltage low, high If often, contact your installer. Red TR AC volt high Transient AC voltage high If often, contact your installer. Red SL AC volt high Grid voltage high for 10 minutes If often, contact your installer. Red AC Phase Balance Grid phase balance out of range If often, contact your installer.
Hardware faults
HW …\... Hardware problem Contact your installer. Red, fast blink HW insulation Insulation fault. Resistance between DC
and PE is too low.
Check the PE connections.
Red Temperature high Disconnect due to too high internal heat
sink temperature
The inverter will start up again as soon as It has cooled down.
Ambient faults
Red Sol 1,2 high Solar input 1 and/ or 2 over voltage (DC >
1000 V). Inverter may be damaged.
Check PV array open circuit voltage, check OVP in your Stringmaster Contact your installer.
Red Solar low Solar 1 and 2 voltage low due to low
irradiation. Inverter has shut down.
Check: string fuses, DC switch, DC cable. Wait till sunrise.
Normal operation
Red, slow blink Reclosure Time Reclosure time counting Nothing, reclosure may take 5 minutes. White ON, Derating Power Reduction due to: 1. internal
temperature, 2. fan failure (max. 75% load then), 3. DC voltage <350V or >800V,
4. Lower AC voltage.
Check the fan, MasterBus power setting and the voltages.
White ON, Pwr Mgmt xx%
xx ranges 100, 60, 30, 0
Power reduction by request of the grid operator (via DataControl Premium/ Pro II). Range 100% (no power), 60%, 30% and 0% (maximum power).
-
White ON, Sol1,2 Low Solar input voltage 1 and/ or 2 low.
The inverter is still operating.
Check the string fuses, DC switch if applicable, DC cable; wait till sunrise.
White ON Normal operation StringMaster faults HW Error Refer to StringMaster manual. Not Connected StringMaster has no connection to
MasterBus. StringMaster has not been configured.
Check MasterBus cabling and MasterBus configuration.
Warning. Refer to section 8.7 for warning decriptions. OC Over current: Installation error Check cabling and scheme. NEG Reverse polarisation Check string polarisation. LOW Performance (current) low Check fuse, cabling, irradiation of PV
modules (shadows spoil the performance).
OVP 1 (2) Over Voltage Protection of Input 1 or 2 Check Input 1 or 2 varistor.
Page 25
SPECIFICATIONS
EN / SunMaster CS15TL/CS20TL / August 2010 25
10 SPECIFICATIONS
10.1 TECHNICAL SPECIFICATIONS
CS15TL CS20TL GENERAL SPECIFICATIONS
Operating temp. Ambient temperature -20°C to 60°C Ambient temperature -20°C to 60°C Enclosure Powder coated aluminum Powder coated aluminum Protection degree IP65 (Inverter) IP44 (Cooling) for outdoor IP65 (Inverter) IP44 (Cooling) for outdoor Relative humidity 0 – 90% non condensing. Protective PCB 0 – 90% non condensing. Protective PCB Safety class Class I metal enclosure with protective earth Class I metal enclosure with protective earth Galvanic isolation No (optional transformer available) No (optional transformer available) Weight 65 kg (143 lbs) 65 kg (143 lbs) Dimensions See section 9.2 See section 9.2 Connectors Weather resistant connectors Weather resistant connectors SOLAR INPUT (DC) Recommended PV power range
14kWp – 19 kWp 18kWp – 25 kWp
Maximum input power 17 kW DC 22 kW DC Start up power 40 W 40 W Operating voltage 250 V DC – 950 V DC 250 V DC – 950 V DC Nominal voltage 650 V DC 650 V DC MPP voltage range @ nominal power
350-800 V DC 350-800 V DC
Absolute maximum voltage 1000 V DC 1000 V DC Number of inputs 2 MPP trackers / 2 inputs
(2 x 2 Multi Contact 4mm connectors)
2 MPP trackers / 2 inputs
(2 x 2 Multi Contact 4mm connectors) Rated current 2 x 23 A (can be paralleled) 2 x 30 A (can be paralleled) Typical string configurations 4 inch: 5 / 6 strings per input; 5 inch: 3 / 4
strings per input; 6 inch: 2 / 3 strings per input
4 inch: 5 / 6 strings per input; 5 inch: 3 / 4
strings per input;
6 inch: 2 / 3 strings per input String connections Optional 2x6 - string box with DC switch,
surge protection and string fuses
Optional 2x6 - string box with DC switch,
surge protection and string fuses PV array grounding Positive or negative grounding possible.
External transformer required
Positive or negative grounding possible.
External transformer required
GRID OUTPUT (AC)
Voltage 400V x 3Ph -20% / +20% (3phase, 3 wire) 400V x 3Ph -20% / +20% (3phase, 3 wire) Nominal power 15 kW @ 400 V +/- 10 % 20 kW @ 400 V +/- 10 % Maximum power 15.75 kW 21 kW Nominal current 3 x 26 A 3 x 32 A Frequency 50 Hz models: 47 - 53 Hz,
60 Hz models: 57 – 63 Hz
50 Hz models: 47 - 53 Hz,
60 Hz models: 57 – 63 Hz Power factor > 0,99 at full power > 0,99 at full power Harmonic distortion < 3 % < 3 % DC current injection Integrated Integrated Stand by power < 2 W < 2 W EU efficiency > 96.5 % > 97 % Maximum efficiency > 98 % > 98 % Connector 3 Ph + PE ; IP67 3-phase AC plug suitable
for 4 mm
2
and 6 mm2
3 Ph + PE ; IP67 3-phase AC plug suitable
for 4 mm2 and 6 mm2 Fuse Internal PCB fuses Internal PCB fuses
Page 26
SPECIFICATIONS
26 August 2010 / SunMaster CS15TL/CS20TL / EN
CS15TL CS20TL SAFETY DEVICES
Island protection Redundant voltage and frequency window
monitoring compatible with national standards
Redundant voltage and frequency window
monitoring compatible with national
standards Safety devices DC side • isolation resistance measurement
• polarity protection (diodes)
• surge protection class III (varistors)
• overload (temperature controlled power derating)
• isolation resistance measurement
• polarity protection (diodes)
• surge protection class III (varistors)
• overload (temperature controlled power
derating) Safety devices AC side • voltage / frequency window
• independent AC relays
• Integrated RCD (DC sensitive)
• DC current injection protection
• Ceramic fuse
• Class III surge protection
• voltage / frequency window
• independent AC relays
• Integrated RCD (DC sensitive)
• DC current injection protection
• Ceramic fuse
• Class III surge protection SYSTEM INFORMATION User interface Multi-language black-on-white graphical LCD
display. Languages: English, Nederlands, Deutsch, Français, Castellano, Italiano
Multi-language black-on-white graphical LCD display. Languages: English, Nederlands, Deutsch, Français, Castellano, Italiano
Diagnostics • 365 days datalogger and real time clock
• 10 years diagnostic memory
• 365 days Datalogger and real time clock
• 10 years diagnostic memory External communication A: MasterBus stringbox and transformer
interface with two connectors B: MasterBus field service interface with two connectors C: 2 RS485 connections for DataControl Professional, maximum 20 inverters, 1000 m maximum cable length
A: MasterBus stringbox interface with two connectors B: MasterBus field service interface with two connectors C: 2 RS485 connections for DataControl Professional, maximum 20 inverters, 1000 m
maximum cable length MasterBus powering Yes, when AC and/or DC is available Yes, when AC and/or DC is available MasterBus menu languages English, Nederlands, Deutsch, Français,
Castellano, Italiano, Norsk, Svenska, Suomi, Dansk *
English, Nederlands, Deutsch, Français,
Castellano, Italiano, Norsk, Svenska, Suomi,
Dansk *
MISCELLANEOUS
Cooling User replaceable fan bracket User replaceable fan bracket Enclosure Aluminium with powder coating.
Rubber foot stands are part of the enclosure. Mounting bracket.
Aluminium with powder coating.
Rubber foot stands are part of the enclosure.
Mounting bracket. String box option IP65 enclosure;
Integrated DC load switch 2x1000V DC /30A; Integrated string fuses; Integrated string current monitoring via Masterbus connection to inverter; 12 (2 x 6) string connections with MC 4 mm type connectors or glands.
IP65 enclosure;
Integrated DC load switch 2x1000V DC /30A;
Integrated string fuses;
Integrated string current monitoring via
Masterbus connection to inverter;
12 (2 x 6) string connections with MC 4 mm
type connectors or glands. Transformer option 20kW 3-phase transformer in IP54 enclosure
Cooling: natural convection Transformation losses : max 2% Weight 200 Kg.
20kW 3-phase transformer in IP54 enclosure
Cooling: natural convection
Transformation losses : max 2%
Weight 200 Kg.
* The number of menu languages may change without prior notice.
Page 27
SPECIFICATIONS
EN / SunMaster CS15TL/CS20TL / August 2010 27
10.2 OUTLINE DRAWINGS
Figure 43: Outline drawings of the CS15TL/CS20TL. All dimensions are in mm (inch).
1055 (41.5)
971 (38.2)
647 (25.4)
242 (9.53)
255 (10.0)
13,3 (0.52)
Page 28
ORDERING INFORMATION
28 August 2010 / SunMaster CS15TL/CS20TL / EN
11 ORDERING INFORMATION
Part number Description
131300200 StringMaster CS 2-6 SW Pro, string box for maximum 2x6 strings. 131300250 StringMaster CS 2-6 SW, string box for maximum 2x6 strings. 131300100 Isolation transformer CS-IT20
77040000 MasterBus terminating device 77040020* MasterBus connection cable (UTP patch cable), 0,2m / 0.6ft 77040050* MasterBus connection cable (UTP patch cable), 0,5m / 1.6ft 77040100* MasterBus connection cable (UTP patch cable), 1,0m / 3.3ft 77030100 MasterBus - USB interface (required as interface between your PC and the CS15TL/CS20TL ) 77010105 MasterView Easy MkII. (monitoring and control panel for configuration of the power modules with the local
regulations for grid connection).
130394000 QS Data Control 'Basic' – Free software package to monitor your photovoltaic (PV) system using your PC or
notebook. Use of QS PC Link is compulsory. 130391010 QS PC Link, RS485/232 converter (up to 3 CS15TL/CS20TL). 130391020 QS PC Link Industrial, RS485/RS232 converter for the connection of more than 3 CS15TL/CS20TL inverters or
for cable lengths of more than 100 meters. 130391040 QS PC-Link Industrial, RS485/USB converter for the connection of more than 3 CS15TL/CS20TL inverters or
for cable lengths of more than 100 meters. 130396000 QS Data Control 'Premium’ II local – Datalogger to monitor up to 6 CS15TL/CS20TL inverters locally . 130396100 QS Data Control 'Premium’ II remote – Datalogger to monitor up to 6 CS15TL/CS20TL inverters over the
Internet . 130396200 QS Data Control 'Pro’ Analogue – Datalogger to monitor up to 20 CS15TL/CS20TL inverters locally or over the
Internet . 130396210 QS Data Control 'Pro’ ISDN – Datalogger to monitor up to 20 CS15TL/CS20TL inverters locally or over the
Internet . 130396220 QS Data Control 'Pro’ GSM – Datalogger to monitor up to 20 CS15TL/CS20TL inverters locally or over the
Internet . 130396230 QS Data Control 'Pro’ Ethernet – Datalogger to monitor up to 20 CS15TL/CS20TL inverters locally or over the
Internet . 130010905 RS485 modular communication cable, cross wired, 8 pole, 1 meter / 3 ft 130010906 RS485 modular communication cable, cross wired, 8 pole, 5 meter / 16 ft 130010910 RS485 modular communication cable, cross wired, 8 pole, 10 meter / 33 ft 130010915 RS485 modular communication cable, cross wired, 8 pole, 15 meter / 49 ft 120107000 Complete set to assemble RS485 modular communication cables.
Delivery includes: 100 meter modular cable, 100 pcs. modular jacks and crimping tool.
*Other lengths of MasterBus connection cables upon request
See section 6.1 for an overview of parts that are standardly included with the delivery of the CS15TL/CS20TL Mastervolt offers a wide range of products for both grid connected and independent autonomous electrical installations. See www.mastervolt.com for an extensive overview of all our products.
Page 29
USE IN ITALY
EN / SunMaster CS15TL/CS20TL / August 2010 29
12 USE IN ITALY
12.1 SELF TEST FUNCTION
Uac Max-TEST (Uac Min-TEST)
The screen shows:
Measured value: Mval = the actual grid voltage;
Setting: Set = the set maximum / minimum
voltage limit of the inverter.
Time to shut down: Time = test time indication
Calculated setting: Cset = the calculated maximum / minimum
voltage limit of the inverter
During the test the high voltage limit is changed with rate -11.5V/sec (+11.5V/sec) until it reaches the actual grid voltage. The inverter will disconnect.
After the test, the result is shown.
Write down all values shown. After pressing Confirm, all values disappear from the display to start the next test.
Calculation Uac Max by hand: Cval = Mval + (TIME * 11.5). Calculation Uac Min by hand: Cval = Mval - (TIME * 11.5).
Figure I-1
Calculated setting
CONFIRM
GENERAL
The Self Test Function is meant to check the upper and lower limits of the AC voltage and AC frequency at which the inverter will disconnect from the grid.
To enter the Self Test, enter the country selection menu in the Grid Interface menu and choose Italy. In the Grid Interface, select the Self Test menu.
During the self test, next tests are possible:
Uac Max (high off limit AC voltage); Uac Min (low off limit AC voltage); Fac Max (high off limit AC frequency); Fac Min (low off limit AC frequency).
After each test you have to press Confirm before the inverter starts the reclosure count down and reconnects to the grid.
The test accuracy is better than 1V/ 0.1Hz if grid voltage and frequency are stable.
The standard reclosure time of 300 sec has been reduced to shorten the testing time. This is not an error.
Page 30
USE IN ITALY
30 August 2010 / SunMaster CS15TL/CS20TL / EN
The screen shows:
Measured value: Mval = the actual grid frequency;
Setting: Set = the set maximum (minimum)
frequency limit of the inverter.
Time to shut down: Time = test time indication
Calculated setting: Cset = the calculated maximum (minimum)
voltage limit of the inverter
During the test the high (low) frequency limit is changed with rate -
0.05Hz/sec (+0.0Hz/sec) until it reaches the actual grid frequency. The inverter will disconnect.
After the test, the result is shown.
Write down all values shown. After pressing Confirm, all values disappear from the display to start the next test.
Calculation Fac Max by hand: Cval = Mval + (TIME * 0.05). Calculation Fac Min by hand: Cval = Mval - (TIME * 0.05).
Figure I-2
Calculated setting
CONFIRM
Page 31
CERTIFICATES
EN / SunMaster CS15TL/CS20TL / August 2010 31
13 CERTIFICATES
13.1 EC DECLARATION OF CONFORMITY
The undersigned,
Mastervolt International B.V. Snijdersbergweg 93, 1105AN P.O box 22947 1100DK Amsterdam The Netherlands Tel: +31-(0)20-3422100 Fax: +31-(0)20-6971006
being the manufacturer, declares under his sole responsibility that the electronic equipment:
Product group: Solar Inverter Brand: MASTERVOLT Product type: Sunmaster CS15TL, Sunmaster CS20TL
to which this declaration relates, are in conformity with the essential requirements and other relevant provisions of the Electro Magnetic Compatibility Directive 2004/108/EG and the Low Voltage Directive 2006/95/EG and carries the CE mark accordingly. The following harmonized standards were applied:
Conducted and radiated emissions EN 55022: 2006, Class A Harmonic current emissions EN 61000-3-12: 2005 class A Voltage fluctuations and flicker EN 61000-3-11: 2001 Immunity EN 55024: 1998 + A1: 2001 + A2: 2003 Electrical safety EN 60950-1: 2006
This declaration will be void in case of unrightful use or unprofessional installation of the equipment.
Amsterdam, 22-4-2010 MASTERVOLT INTERNATIONAL B.V.
Ing. D.R. Bassie Product Manager Solar
Page 32
CERTIFICATES
32 August 2010 / SunMaster CS15TL/CS20TL / EN
13.2 VDE0126-1-1 CERTIFICATE OF COMPLIANCE
Page 33
CERTIFICATES
EN / SunMaster CS15TL/CS20TL / August 2010 33
13.3 RD 1663 COMPLIANCE
Page 34
CERTIFICATES
34 August 2010 / SunMaster CS15TL/CS20TL / EN
13.4 ITALY CERTIFICATE OF COMPLIANCE
Page 35
CERTIFICATES
EN / SunMaster CS15TL/CS20TL / August 2010 35
13.5 CERTIFICATE OF COMPLIANCE
Page 36
Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands
Tel : + 31-20-3422100
Fax : + 31-20-6971006
Email : info@mastervolt.com
Loading...