ENGLISH
To obtain full benefit from these heaters and to ensure trouble free operation, please read the following instructions and information carefully.
INSTALLATION
3 Consult the local regulations. 3 Place the heater on a level concrete floor. 3 Install the distributor and steel wire on the 3 WA 29 A 3 Remove all tools and parts that are packed inside
the combustion chamber.
3 Level the heater. To check if the heater is level,
install the combustion dish (22) at the bottom of the combustion chamber and pour a very small amount of diesel into it. The fuel must be central in the combustion dish.
3 Always install a T-piece including draught
stabiliser on the flue-exit of the combustion chamber. This to ensure a stable draught on the combustion chamber during operation.
3 Mount a minimum of 5 meter heat resistent
vertical flue pipe to ensure efficient draught (never aluminium),
3 Horizontal sections of flue pipe are not
recommended and flue bends should be 45° minimum to ensure that the flue gases can still rise.
3 Flue stack must be higher then the apex of the
roof.
NOTE: Points at which the flue pipe passes through a ceiling , wall or roof should be insulated to avoid the possibility of creating a fire hazard. Use of a double skinned, insulated flue is recommended where people could touch it and for the flue outside the building in order to ensure continuous good draught and to avoid condensation.
3 Ensure that the flue pipe connections are tight. If
not, use flue tape.
3 Make sure that the combustion dish is centrally
positioned inside the combustion chamber.
3 Place the upper ring (21) inside the combustion
chamber with the cone upwards and install the after burner cylinder (75) on top of it (WA 29 A).
3 Check the voltage supply (220-240V/50Hz) and
connect the plug to the main supply. Both the fan and pump should not run as the heater is not switched on and no heat has been yet developed.
3 The heater has a pump control thermostat (PT
upper) and a limit thermostat (STB).
NOTE: Do not put unflammable materials close to the heater.
Make sure that the combustion air is continuously available.
+ “NEVER RELIGHT A HOT BURNER DISH” + “ALWAYS WAIT UNTIL THE BURNER
DISH HAS COOLED DOWN COMPLETELY”
+ “MAKE SURE THAT ADEQUATE AIR IS
AVAILABLE FOR COMBUSTION”
USE OF THE HEATER
3 The heater can operate on different waste oils up
to SAE 80, diesel oil or a combination of both.
3 The control panel includes a switch and a
indication light to show that the oil pump is running.
3 In position “0” the pump is stopped.
In position “1”, the pump starts immediately. In this
position the heater is not secured when the flame extinguishes; the pump shall not stop running and oil may run over. The overflow protection (60) will stop the pump (light will go out), but both fan’s (12,) not. LET THE HEATER COOL DOWN, clean the overflow protection and under the the burner dish (22).
RECOMMENDATION: use position “1” only in
very cold conditions with problems to start. Put the switch to position “2” after 20-30 minutes.
In position “2” the pump starts and the indication light
comes in when the combustion dish is sufficiently pre heated.
3 The pump motor (8) drives the pump that is
positioned in the tank and the oil is fed by a continuous flow through the drip feed pipe (69) into the burner dish. (22).
3 The pump speed control is positioned on the
cover of the control box and has a position “high”
and a position “low”. Position “high” : max. capacity 3 ltr/hr. Position “low” : min. capacity 2 ltr/hr.
3 After lighting the heater, it has to remain for
about 20 minutes at low capacity to build up
sufficient heat for operation at full capacity.
3 To stop the heater, the switch must be put in
position “0” and the flame will extinguish a while
later (all models). Еhe hot air blower will stop automatically.
3 NEVER REMOVE THE MAIN PLUG FROM
THE WALL SOCKET UNTIL THE HEATER
IS COMPLETELY COOLED DOWN.
LIGHTING AND RUNNING PROCEDURE
3 Put the switch into position “0”. 3 Check setting of the reset of the limit thermostat
on top of the fan box.
3 Set pump to low capacity.
3 Check voltage. It must correspond with the
voltage as indicated on the production label. Connect the plug to 220-240V supply.
3 Open the lid of the tank and fill the tank with
waste oil or a mix of diesel and waste oil.
3 Drain water and clean the filling filter if
necessary. The drain tap is positioned on the side of the tank (40).
3 Open the heat distributor (4 on WA 29 A) or top
plate
3 Remove the cover from the combustion chamber
as well as the rings inside the combustion chamber. Check if the burner dish is cold and clean, and pour one cup. (1/3 pint) of diesel, no more end no less, into the combustion dish (22).
3 Reposition the upper ring (21) and the after
burning cylinder (75) in WA 29 A.
3 Light a small crumbled ball of paper and drop it
into the burner dish to ignite the diesel.
NEVER RELIGHT A HOT COMBUSTION
CHAMBER OR DISH!
3 Replace the lid and close the heat distributor (4
on WA 29 A).
START:
3 Wait for 5 minutes for the combustion chamber
to be preheated.
3 Put 3-way switch in position “1”. The oil pump
and the pilot light come on. Remark: In position “1” the safety thermostat is not in circuit.
3 Leave set on low capacity for 20-30 minutes. 3 Switch to position “2” after 20-30 minutes, the
safety thermostat is now operational.
3 Oil and pilot stays on. 3 Set pump speed regulator to high capacity
maximum heat outlet is required.
NOTE:
WHEN HOT AIR BLOWER WILL START AUTOMATICALLY WHEN THE HEATER HAS REACHED THE CORRECT TEMPERATURE.
HOW TO STOP THE HEATER
+ For all three models: turn the switch (54) to
position “0”. The pump will stop and after the heater has cooled down sufficiently (10-30 minutes), the indication light will go out.
+ For the WA 29 A heater, the hot air blower stops
after the heater is sufficiently cooled down.
+ Never remove the main plug from the wall socket
until the heater is completely cooled down.
MAINTENANCE
+ If the drip feed pipe (69) is blocked, the oil will
return to the tank trough the overflow pipe that is connected with the transparant hose to the tank in front of the heater (70).
Clean the drip feed pipe if necessary. Replace the pipe
when it becomes burnt or damaged.
+ Clean the burner dish daily and at max. 10 hr.
intervals.
+ The tank can be removed at suitable intervals for
full cleaning.
+ In case the heater will not be used for a long
period, we recommend to clean it and wipe with a cloth, that contains some oil, over the combustion chamber to protect it against corrosion.
+ If parts or wiring are altered, any garantee claim
will be refused. Keep always the inner wall off the combustion chamber free from cokes.
LOCATIONS OF FAULTS
If faults occur in the burner, the list below can be used to locate the problem. Normally, faults are relatively easy to correct. The common faults are listed below. The numbers indicate the possible cause as listed under the heading “Correction of faults”. The sequence of these number relates to the likelihood of the cause of fault.
Check: a: The voltage b. Fuel supply in the burner c. Chimney draught (see “Flue installation”).
CORRECTIONS OF FAULTS
FAULTS CAUSE
Flame is extinguished immediately after ignition 1-2-3-4-5-6-7-8-9-10-11-12-13-14 Pump does not start and signal light does not come in, 6-3-14 in position “1” or position “2” when the heater is preheated. Flame extinguishes while the pump still works. 2-5-7-9-10-12 Burner makes humming noise. 10-11-12 Soot formation in burner and chimney. 8-9-10-11-12 Unburned oil in burner. 8-9-11-12 or too much diesel at start.
CAUSE SOLUTION
10 No electrical supply. + Check if the plug is in the socket and check fuses.
20 Water or sediment in the tank. + Clean tank and filter.
30 Pump motor not switched on. + Put the switch in position “1”.
40 Motor and pump do not work. + Fuel too thick or too cold. Dilute with diesel. + Check pump thermostat and replace if necessary. + Check motor and see if there is dirt inside the pump.
50 Inlet tube is blocked, oil flows back into the tank + Clean the drip feed pipe. replace if required. through the return line.
60 Pump thermostat has not yet reached full temperature. + Let heater cool down and re-start. + Let the burner operate longer in position “1” + Replace pump thermostat (74). Remember: before any investigation, remove
the plug from the socket.
90 Combustion air supply is not sufficient. + Clean the holes of the combustion chamber. + Check proper functioning of the fan.
100 Flue draught is not correct. + Ensure assembly follows pattern shown in “Flue Installation”.
+ Check if there is any air leak. + Clean the flue if necessary.
110 Chimney draught is too strong or fluctuates + Mount draught stabilizer and adjust at minimum too much. 2 mm W.C. (19,6 Pa).
120 Chimney draught is too low. + Check all connections. + Reduce quantity of bends. + Heighten chimney. + Insulate the flue pipes outside the building. + See flue details in this manual.
130 Limit thermostat is faulty or blocked. + Replace thermostat.
140 Overflow protection is full. + Clean overflow protection.
+ Reset thermostat.
POLISH
Dla optymalnego wykorzystania możliwości urządzenia oraz zapewnienia jego bezawaryjnego funkcjonowania prosimy o dokładne zapoznanie się z poniższą instrukcją obsługi.
MONTAŹ
3 Zapoznać się z lokalnymi przepisami. 3 Ustawić piec na płaskim betonowym podłożu.
3 Zamontować dystrybutor ciepła z przewodem na
górze pieca WA 29 A.
3 Wyjąć z komory spalania wszystkie części pieca
w nią spakowane.
3 Wypoziomować piec. Aby sprawdzić czy piec
jest wypoziomowany, umieścić płytę spalania (22) w dolnej części komory spalania i wylać na nią niewielką ilość oleju napędowego. Olej powinien rozlać się dokładnie na środku płyty.
3 Zamontować trójnik oraz stabilizator ciągu na
rurze wychodzącej z komory spalania, by zapewnić w jej wnętrzu stabilny ciąg w czasie użytkowania pieca. Dla zapewnienia optymalnego ciągu zainstalować
3
co najmniej 5-metrową odporną na wysoką temperaturę pionową rurę kominową (nie aluminiową).
3 Montując system odprowadzenia spalin zaleca się
unikanie poziomych odcinków rury kominowej. W celu zapewnienia swobodnego odpływu gazów kąt ewentualnego zgięcia rury nie powinien być większy niż maks. 45º.
3 Wylot komina musi być wyżej niż wierzchołek
dachu.
UWAGA: Miejsca, w których rura kominowa przechodzi przez sufit, ściany lub dach, muszą być izolowane w celu uniknięcia zagrożenia pożarowego. Zalecane jest używanie dwuwarstwowej izolowanej rury kominowej wszędzie tam, gdzie istnieje możliwość kontaktu dotykowego oraz na zewnątrz budynku, by zapewnić stały dobry ciąg i zapobiec kondensacji.
3 Sprawdzić szczelność wszystkich połączeń, w
razie potrzeby uszczelnić taśmą izolacyjną.
3 Upewnić się, że płyta spalania jest umieszczona
centralnie w komorze spalania.
3 Umieścić górny pierścień (21) we wnętrzu
komory spalania wypustką po środku pierścienia w górę i zamontować na nim cylinder dopalacza (75).
3 Sprawdzić napięcie sieciowe (220-240V/50Hz) i
podłączyć piec do zasilania. Ani wentylator, ani
pompa nie powinny się uruchomić, ponieważ piec nie jest jeszcze włączony i żadne ciepło nie zostało wyprodukowane.
3 Urządzenie posiada termostat kontroli pracy
pompy (PT) i termostat przegrzania (STB).
->UWAGA: Nie umieszczać żadnych materiałów w pobliżu pieca, nawet niepalnych. Zapewnić stały dostęp powietrza niezbędnego dla prawidłowego procesu spalania.
->NIGDY NIE ROZPALAĆ PONOWNIE GORĄCEJ PŁYTY PALNIKA.
->ZAWSZE ODCZEKAĆ DO CAŁKOWITEGO SCHŁODZENIA PŁYTY PALNIKA.
->DLA PRAWIDŁOWEGO PROCESU SPALANIA ZAPEWNIĆ DOSTĘP ODPOWIEDNIEJ ILOŚCI POWIETRZA
EKSPLOATACJA PIECA
¾ Piec może pracować na różnego rodzaju olejach
(napędowym, opałowym, biodiesel, silnikowym
czystym i przepracowanym, przekładniowym,
hydraulicznym, roślinnym itp.) Nie wolno
stosować olejów transformatorowych oraz
substancji nitro.
¾ Ze względu na lokalne przepisy zaleca się aby w
Polsce stosować olej napędowy, olej opałowy lub
biodiesel.
¾ Panel kontrolny zawiera włącznik oraz lampkę
kontrolną informującą o pracy pompy..
¾ Jeżeli włącznik jest w pozycji "0", pompa nie
pracuje. Pompa uruchamia się natychmiastowo po ustawieniu włącznika na "1". Piec nie posiada zabezpieczenia przed zgaśnięciem płomienia w tym momencie; pompa nie przestanie działać, a olej może się przelać. Zabezpieczenie przed przelewem (60) wyłączy pompę (kontrolka zgaśnie), ale wentylatory (12) będą działać dalej. PIEC MUSI OSTYGNĄĆ, następnie należy wyczyścić zabezpieczenie przed przelewem oraz miejsce pod płytą palnika. ZALECENIE: Używać pozycji przełącznika"1" wyłącznie w bardzo niskich temperaturach przy problemach z odpaleniem pieca. Po 20-30 minutach przełączyć na pozycję "2". W pozycji "2" pompa startuje i kontrolka zapala się dopiero
¾ Silnik pompy (8) napędza pompę, która znajduje
¾ Prędkość pracy pompy jest kontrolowana
"high"- maksymalny pobór oleju 3 l/godz. "low" - minimalny pobór oleju 2 l/godz. ¾ -Po odpaleniu, piec powinien pracować na
,gdy płyta spalania jest wstępnie rozgrzana.
się w zbiorniku, i przelewa olej w sposób ciągły przez rurę wtryskową (69) na płytę spalania (22).
przełącznikiem na pokrywie panelu kontrolnego (2 ustawienia: "high" i "low")
minimalnym poborze oleju („low”) przez około 20
minut w celu stworzenia odpowiedniej temperatury do pracy z wysoką wydajnością ("high").
¾ Aby wyłączyć piec, przełącznik ustawić należy w
pozycji "0" i poczekać, aż płomień zgaśnie chwilę źniej.
Wentylator wyłączy się automatycznie.
3 NIE WYJMOWAĆ WTYCZKI Z GNIAZDKA
ELEKTRYCZNEGO, ZANIM PIEC NIE SCHŁODZI SIĘ CAŁKOWICIE.
ODPALANIE I PRACA PIECA
¾ Ustawić przełącznik w pozycji "0". ¾ Sprawdzić ustawienie przycisku ‘reset’ termostatu
przegrzania na górze obudowy wentylatora.
¾ Ustawić pompę na niski pobór paliwa ("low"). ¾ Sprawdzić napięcie. Musi odpowiadać napięciu na
tabliczce znamionowej. Włożyć wtyczkę do gniazdka o napięciu 220-240V.
¾ Otworzyć pokrywę zbiornika paliwa i napełnić go
olejem lub mieszanką olejów.
¾ W razie potrzeby odprowadzić wodę ze zbiornika
paliwa i wyczyścić filtr wlewu. Korek spustowy znajduje się z boku zbiornika (40).
¾ Otworzyć dystrybutor ciepła (4) lub płytę górną. ¾ Zdjąć pokrywę komory spalania oraz wyjąć z niej
pierścienie. Sprawdzić czy p chłodna i czysta, następnie wlać ok. 180 ml (jeden mały kubek) oleju napędowego na płytę spalania (22).
¾ W celu zapalenia oleju, zgnieść papier w małą
kulkę, podpalić ją i wrzucić ją na płytę spalania. NIGDY NIE ROZPALAĆ PONOWNIE PIECA, GDY KOMORA LUB PŁYTA SPALANIA SĄ WCIĄŻ GORĄCE! ¾ Włożyć z powrotem pierścień i cylinder, założyć
pokrywę komory spalania i zamknąć dystrybutor
ciepła (4).
łyta palnika jest
ODPALANIE PIECA:
3 Odczekać 5 minut, by komora spalania wstępnie
się rozgrzała
3 Ustawić 3-pozycyjny wyłącznik w pozycji “1”.
Pompa olejowa zacznie działać i zapali się lampka kontrolna pracy pompy. Uwaga: W pozycji “1” termostat bezpieczeństwa jest odłączony.
3 Ustawić pompę na niski pobór paliwa (“low”) na
20-30 minut.
3 Po 20-30 minutach przestawić wyłącznik na
pozycję “2”, termostat bezpieczeństwa zacznie działać.
3 Palą się płomień i lampka kontrolna. 3 Ustawić pompę na maksymalny pobór paliwa,
zaleca się maksymalny wydmuch ciepłego powietrza.
UWAGA:
WENTYLATOR URUCHOMI SIĘ AUTOMATYCZNIE, GDY PIEC OSIĄGNIE ODPOWIEDNIĄ TEMPERATURĘ.
WYŁĄCZENIE PIECA
+ Ustawić wyłącznik (54) tw pozycji “0”. Zatrzyma
się pompa paliwa, a po schłodzeniu pieca (10-30 minut) zgaśnie lampka kontrolna..
+ Po dostatecznym schłodzeniu pieca wentylator
wyłączy się automatycznie.
+ Nigdy nie wyjmować wtyczki z gniazdka przed
całkowitym schłodzeniem się pieca.
KONSERWACJA
+ Jeśli przewód paliwa (69) będzie zanieczyszczony,
olej powróci do zbiornika z przodu urządzenia przewodem powrotnym (70). Przewód paliwa należy wyczyścić lub wymienić, jeśli jest spalony lub uszkodzony.
+ Płytę spalania czyścić codziennie co maks. 10
godzin pracy urządzenia.
+ W celu wyczyszczenia można wyjąć zbiornik. + Każdorazowo przed zmagazynowaniem na dłuższy
czas zaleca się dokładne wyczyszczenie pieca i przetarcie komory spalania szmatką nasączoną olejem, by zapobiec rdzewieniu.
+ W przypadku stwierdzenia samowolnej wymiany
części lub dokonania jakichkolwiek zmian w instalacji elektrycznej gwarancja na urządzenie zostanie cofnięta.
+ Wewnętrzne ściany komory spalania chronić przed
zabrudzeniem sadzą.
NAPRAWA USTEREK
W przypadku awarii urządzenia poniższa lista może pomóc w zlokalizowaniu usterki. Na ogół jej usunięcie jest proste. Najczęstsze problemy wymienione są poniżej. Cyfry oznaczają możliwe przyczyny wymienione dalej w rozdziale “Naprawa usterek”. Kolejność cyfr wyraża prawdopodobieństwo wystąpienia usterki.
Zawsze sprawdzić: a: Napięcie b. Dopływ paliwa do płyty spalania c. Ciąg kominowy (patrz “Montaż przewodu kominowego”).
Loading...
+ 11 hidden pages