KEROSENE FORCED AIR
HEATER
User’s Manual &
Operating Instructions
Model Numbers
MH-45-KFA / MH-75T-KFA / MH-135T-KFA / MH-190T-KFA / MH-215T-KFA
CONSUMER: READ AND SAVE THESE INSTRUCTIONS
Safety Information
GENERAL HAZARD WARNING: READ AND UNDERSTAND ALL OF THE INSTRUCTIONS IN THIS MANUAL BEFORE
ASSEMBLING, STARTING, OR SERVICING THE HEATER.
Be sure to comply with the instructions and warnings provided with this heater. Failure to comply can result in fire or explosion that can cause property loss, bodily injury, or loss of life. Only persons who can follow and understand these instructions should operate or service this heater. If you need heater info; such as an operating manual, labels, etcetera, contact Pinnacle Climate Technologies at 800-779-3267.
NOT FOR USE IN RESIDENTIAL LIVING AREAS OR IN ENCLOSED SPACES WITHOUT ADEQUATE VENTILATION.
FOR OUTDOOR USE. INDOOR USE PERMITTED ONLY
FOR: THE TEMPORARY HEATING OF ADEQUATELY VENTILATED BUILDINGS OR STRUCTURES UNDER CONSTRUCTION, ALTERATION OR REPAIR. This is an
unvented portable heater that uses air (Oxygen) from within the area in which it is used. Failure to provide adequate combustion and ventilation air will result in asphyxiation, carbon monoxide poisoning, bodily injury or death. Refer to “Ventilation” on Page 5.
FIRE, BURN, INHALATION AND EXPLOSION HAZARD. Keep combustibles such as; building materials, paper or cardboard a
safe distance away from the heater as recommended by these instructions. Never use the heater in spaces which contain products such as; gasoline, solvents, paint thinners, dust particles, volatile or airborne combustibles or any unknown chemicals. This is an unvented portable heater. It uses air (Oxygen) from the area in which it is used. Adequate combustion and ventilation air must be provided. Refer to “Ventilation” on page 5. Bulk fuel storage should be a minimum of 25 feet (7.6 m) from heater.
DO NOT OPERATE THIS HEATER UNTIL
YOU HAVE READ AND THOROUGHLY
UNDERSTAND THESE SAFETY AND OPERATING INSTRUCTIONS.
Failure to comply with the precautions and instructions provided with this heater can result in death, serious bodily injury, property loss or damage from the hazards of fire, soot production, explosions, burns, asphyxiation or carbon monoxide poisoning. Only persons who can read and understand these instructions should use or service this heater.
FACTORY ID: 001
Fax: 320-251-2922 • Web: www.masterindustrialproducts.com • Email: info@pinnacleclimate.com
1 Industrial Blvd #101, Sauk Rapids, MN 56379 USA • Toll Free (800) 779-3267
© 2017 Pinnacle Climate Technologies, Inc. MAKB-400
Page 2
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
WARNING
WARNING
WARNING
WARNING
DANGER
OR WHILE CONNECTED TO A POWER SOURCE
DO NOT START THE HEATER WHEN EXCESS OIL HAS ACCUMULATED.
DO NOT START THE HEATER WHEN THE CHAMBER IS HOT.
CALIFORNIA RESIDENTS: This product contains chemicals,
including lead, known to the State of California to cause birth defects or other reproductive harm. Wash hands after handling.
MASSACHUSETTS RESIDENTS: Massachusetts state law prohibits the use of this heater in any building which is used in whole or in part for human habitation. Use of this heating device in Massachusetts requires local fire department permit (M.G.L.C. 148, Section 10A).
NEW YORK CITY RESIDENTS: The New York City Fire Code prohibits the storage, handling and use of kerosene fueled heaters for space heating. Any person violating that provision may be punished by a fine up to $10,000 and a term of imprisonment of up to 6 months.
THE INSTALLATION OF THIS HEATER SHALL COMPLY WITH THE REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION.
Look for this icon throughout the manual for helpful tips on how to assemble, use and clean your KFA Heater.
RISK OF INDOOR
AIR POLLUTION!
The products described in this manual are
kerosene direct-red, forced air heaters. Kerosene
forced air heaters are primarily intended for use for temporary heating of buildings under construction,
alteration or repair. Direct-red means that all of
the combustion products of the heater enter the heated space. This appliance is rated at 98%
combustion efciency, but does produce small
amounts of carbon monoxide.
CARBON MONOXIDE POISONING MAY
LEAD TO DEATH!
Carbon monoxide is toxic. Humans can tolerate only small amounts of carbon monoxide and so precautions should be taken to provide proper ventilation. Failure to provide proper ventilation in accordance with the instructions in this manual can result in death.
People with breathing problems should consult a physician before using this heater.
Early signs of carbon monoxide poisoning
resemble the u. Symptoms of improper ventilation
/ carbon monoxide poisoning are:
Headache • Dizziness • Nausea Dry Mouth
Sore Throat Burning of Nose and Eyes
If you experience any of these symptoms: GET FRESH AIR AT ONCE! Have your heater serviced and check for proper ventilation. Some people are more affected by carbon monoxide than others. These include: pregnant women, those with heart or lung problems, anemia or those under the influence of alcohol or at high altitudes.
FOR OUTDOOR USE. INDOOR USE PERMITTED ONLY FOR: The temporary heating of adequately ventilated buildings or structures under construction, alteration or repair! Provide at least a three square foot (2,800 sq cm) opening of outside air for every 100,000 Btu/Hr (29 kW) heater rating. Refer to “Ventilation” on page 5 for further instructions.
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
1
Page 3
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
WARNING
WARNING
WARNING
OR WHILE CONNECTED TO A POWER SOURCE
Safety Information
RISK OF
ELECTRIC
SHOCK!
ALWAYS use only the electrical power (voltage and frequency) specified on the model plate of the heater. ALWAYS use only three-prong, grounded outlet and extension cord.
ALWAYS use only 14 AWG or better extension cord.
ALWAYS unplug the heater when not in use.
ALWAYS install the heater so that it is not directly exposed to water spray, rain, dripping water, or wind.
NEVER move or handle heater while still hot.
NEVER transport heater with fuel in tank.
NEVER use with an external fuel tank. Keep all combustible materials away from this heater.
Minimum Clearance From Combustibles
45-190T-KFA 215T-KFA
Top
Sides
Front
ALWAYS locate heater on a stable and level surface.
4 ft. (125 cm) 4 ft. (125 cm)
4 ft. (125 cm) 4 ft. (125 cm)
8 ft. (250 cm) 10 ft. (305 cm)
NEVER use fuels such as gasoline, benzine, paint thinners or other oil compounds in this heater.
NEVER refill the heater’s fuel tank while the heater is operating or still hot. This heater is EXTREMELY HOT while in operation.
NEVER block air inlet (rear) or air outlet (front).
If your heater is equipped with a thermostat, once it is plugged in, it can start at anytime in accordance with the thermostat setting.
CAUTION!
NEVER use duct work in front or rear of heater.
HOT WHILE IN OPERATION.
RISK OF BURNS,
FIRE AND
EXPLOSION!
DO NOT TOUCH. KEEP CHILDREN, ANIMALS, CLOTHING AND COMBUSTIBLES AWAY FROM HEATER.
Specications
Model # 45-KFA 75T-KFA
Rating: Btu/Hr / kW 45,000 / 13.19 75,000 / 21.98 135,000 / 39.56 190,000 / 55.68 215,000 / 63.01 Fuel Consumption: Gal/Hr / L/Hr 0.35 / 1.32 0.56 / 2.12 1.00 / 3.79 1.42 / 5.38 1.63 / 6.17 Fuel Tank Capacity: Gallons / Liters Pump Pressure: psi / BAR 3.0 / 0.21 4.2 / 0.29 5.5 / 0.38 8.5 / 0.59 9.0 / 0.62
Volts: AC/Hz
Amps 1.4 1.5 2.3 2.7 2.8
Phase Single Single Single Single Single
5 / 19 5 / 19 10 / 38 13 / 49 13 / 49
120VAC / 60Hz 120VAC / 60Hz 120VAC / 60Hz 120VAC / 60Hz 120VAC / 60Hz
Specications subject to change without notice.
135T-KFA 190T-KFA 215T-KFA
Locating Your Serial Number:
Your serial number can be found on a white label on the right side cover of your heater. For Example:
150812779. Have your Serial Number ready before calling customer service at 800-779-3267.
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
2
Page 4
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
Wiring Diagrams
45-KFA
75T - 215T-
Assembly Instructions
- Remove the heater and all packaging materials from the shipping carton
What’s In The Box Models: 45-KFA / 75T-KFA
KFA
Note: Save the box and packaging materials for future storage.
Figure 3
Cord Wraps (Optional) Carry Handle (1)
Figure 4
10 mm Screws (2) 13 mm Screws (2)
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
3
Shown With Optional Cord Wraps
Page 5
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
What’s In The Box Models: 135T-KFA / 190T-KFA / 215T-KFA
Tip: Be sure to remove the axle from the side of the Styrofoam packaging.
Tip: Use a power screwdriver and locking wrench for easier assembly.
50 mm Screws (4)
Axle Nuts (2)
30 mm Screws (4)
Spacers (2)
8 mm Nuts (8)
Front Handle
Tools Needed:
- Phillips Head Screw Driver
- 8 mm open end wrench
- 19 mm open end wrench
Wheels (2)
Wheel Support Frame
Spare Drain Plug (1)
Rear Handle
Axle
Assembly Instructions
Models: 135T-KFA / 175T-KFA / 190T-KFA / 215T-KFA
1. Insert axle through holes in wheel support.
2. Slide spacer onto axle.
3. Slide wheel onto axle and hold in place with the axle nuts. (See Figure 1).
Wheel Support Frame
Tire
Axle
Axle Nut
Spacer
Figure 1
4. Place heater on wheel support and line up holes on the fuel tank lip.
5. Attach front handle with (2) long screws (50 mm) and (2) nuts through the second hole from the front on both sides of the tank lip and wheel support frame and tighten firmly.
6. Insert (2) short screws (30 mm) through the first hole from the front in the tank lip and tighten firmly. Make certain all (4) screws are secure.
7. Attach rear handle with (2) long screws (50 mm) and (2) nuts through the second hole from the rear
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
of the heater on either side. (See Figure 2)
8. Tilt the heater up gently so it is resting on the front handle.
NOTE: DO NOT do this if there is fuel in the tank.
9. Remove the wheels to secure the second set of screws through the rear handle.
10. Secure the rear handle with (2) short screws (30 mm) and (2) nuts and tighten firmly
11. Replace wheels and tighten with the wheel nuts.
12. Tilt heater back down onto wheels and check all screws and nuts to make sure they are secure.
Figure 2
4
Page 6
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
CAUTION
DANGER
WARNING
DANGER
OR WHILE CONNECTED TO A POWER SOURCE
Operation
Fueling The Heater:
Kerosene (K-1)
For optimal performance of this heater, it is strongly suggested that K-1 kerosene be used. K-1 kerosene
has been rened to virtually eliminate contaminants,
such as sulfur, which can cause a rotten egg odor during the operation of the heater. Using diesel fuel can cause excess soot production. Do not use Bio-Diesel as this
fuel will damage your heater’s seals and lter.
- CSA certified for use with K-1 kerosene, no. 1 & no. 2 diesel, JP8/Jet A Fuel, no. 1 and no. 2 fuel oil.
NEVER REFUEL THIS HEATER
WHILE IT IS HOT OR OPERATING. FIRE OR EXPLOSION COULD RESULT.
Ventilation:
- Risk of indoor air pollution and Carbon Monoxide Poisoning. Use heater only in well ventilated areas.
- Refer to Safety Information on page 1 for information about Carbon Monoxide Poisoning.
- ALWAYS provide a fresh air opening in the heated space
of at least three square feet (2,800 sq. cm) for each 100,00 Btu / Hr. (29 kW) of heater output. Provide a larger opening if more heaters are being used.
CARBON MONOXIDE POISONING MAY LEAD TO DEATH!
NEVER FILL THE FUEL TANK
INDOORS. ALWAYS FILL THE TANK OUTDOORS. BE SURE THAT THE HEATER IS ON LEVEL GROUND WHEN FUELING, AND NEVER OVERFILL THE TANK.
DO NOT USE GASOLINE OR CRANKCASE DRAININGS.
DO NOT use any fuel that is not approved above.
- NEVER use fuel such as, benzene, alcohol, white glass, camp stove fuel, paint thinners, or other oil compounds in this heater. THESE ARE VOLATILE FUELS THAT CAN CAUSE A FIRE OR EXPLOSION.
- NEVER store kerosene in the living space. Kerosene should be stored in a well ventilated area outside the living area.
- NEVER store kerosene in direct sunlight or near a source of heat.
- NEVER use kerosene that has been stored from one season to the next. Kerosene deteriorates over time. OLD KEROSENE WILL NOT BURN PROPERLY IN THIS HEATER.
NOTE: Kerosene should only be stored in a blue container that is clearly marked “Kerosene.” Never store kerosene in a red container. Red is associated with gasoline.
Minimum Ventilation Opening Needed
45-KFA 75T-KFA 135T-KFA
1.4 ft.² 2.3 ft.² 4.1 ft.²
1250 cm² 2090 cm² 3760 cm²
Minimum Ventilation Opening Needed
190T-KFA 215T-KFA
5.7 ft.² 6.5 ft.²
5290 cm² 5990 cm²
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
5
Page 7
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
Operation
Starting the Heater: (Ignition)
1. Fill the tank with kerosene or other approved fuel
until needle on fuel gauge points to “F”.
2. Replace fuel cap and tighten firmly.
3. Connect the heater to a three prong
(grounded) power source. You must use a three prong (grounded) extension cord that is at least 6 feet long and is a minimum of 14 AWG rating.
Model 45-KFA:
1. Complete steps 1-3 above.
2. Move power switch to “On” position. The power
indicator light will illuminate and the heater will ignite.
Stopping / Restarting Heater:
- To stop the heater, move the power switch to the “Off” position and unplug the power cord.
- To restart the heater; wait 10 seconds and follow ignition steps.
Stopping / Restarting Heater:
- To stop the heater, move the power switch to the “Off”
- To restart the heater; wait 10 seconds and follow
heater ignites. If the heater does not ignite; move switch to “Off” position, check steps 1-3 above and then move switch to “On” position.
Long Term Storage:
Models 45-KFA - 75T-KFA:
1. Use an approved siphon to drain fuel through the
Models 135T-KFA - 215T-KFA:
1. Drain fuel through the drain plug in the bottom
2. To remove the drain plug, pull the plug grip
TIP: If the heater does not ignite; move switch to “Off” position, check steps 1-3
above and then move switch to “On” position.
Models 75T-KFA - 215T-KFA:
1. Complete “starting heater ignition” steps 1-3
above
2. Turn thermostat control knob to desired
temperature setting. The thermostat set range is from 40 ºF to 110 ºF.
3. Move power switch to “On” position. The power
indicator light and room temperature display will illuminate and heater will ignite.
NOTE: 45-75T-KFA models do not have a room
temperature display feature.
The room temperature display will indicate the following:
- When the temperature is less than 0 ºF the
display says “LO”.
- When the temperature is more that 99 ºF the
display says “HI”.
- Between 0 °F and 99 °F the display shows
actual temperature.
3. Using a small amount of kerosene, rinse and
4. To replace the drain plug; push the drain head
IMPORTANT: Never store leftover kerosene between seasons, using old fuel can damage heater.
position and unplug the power cord.
ignition steps.
TIP: If the heater does not ignite, the thermostat may be set too low. Turn the control knob to a higher setting until the
fuel cap opening.
of the fuel tank.
downward and remove the seal head from the drain hole in the tank.
swirl the kerosene inside of the fuel tank, empty the tank fully.
fully into the drain hole and secure by pushing the seal cap fully into the head hole.
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
6
Page 8
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
WARNING
OR WHILE CONNECTED TO A POWER SOURCE
Maintenance
Service:
DO NOT TAMPER WITH THE UNIT. HAVE A COMPETENT SERVICEMAN MAKE ANY NECESSARY ADJUSTMENT OR REPAIRS.
Use only original equipment parts. The use of alternate or third party components can cause unsafe operating conditions and will void your warranty.
We suggest following a maintenance schedule as follows:
FUEL / FUEL TANK:
Flush tank every 200 hours of operation or as needed.
DO NOT ush with water; use fresh K-1 kerosene only.
AIR FILTERS:
The air intake lter should be replaced or washed with
soap and water and dried thoroughly every 500 hours of operation or less depending on conditions.
The output and lint lters should be replaced
every 500 hours of operation or less depending on conditions. (See Figure 4)
NOTE: Use of diesel fuel may require additional maintenance
FAN BLADES:
Blades should be cleaned at least once per heating season, depending on conditions. Remove all accumulated dust and dirt with a damp cloth, taking care not to bend any of the fan blades. Be sure the blades are dry before re-starting the heater.
ROTOR:
The rotor with carbon vanes should be evaluated every heating season. The rotor is behind the air filters. The vanes should be inspected for damage or wear. The rotor should be inspected for damage, chips, wear, cracks.
Check rotor gap: Remove the rear cover. Loosen the two pump ring screws. Lift the pump ring upwards. Insert a 0.1 mm feeler gauge and apply slight downward pressure, enough to offer resistance when attempting to remove gauge. Hand-tighten the two pump ring screws. Re-install the End Pump Cover and the plastic End Filter Cover. Start the heater and adjust to the proper pump pressure.
Never service heater while it is plugged in or hot!
Fuel Filter
Fuel Line
Side Cover
FUEL FILTER:
The fuel filter should be cleaned at least twice per heating season. Clean the filter by rinsing it in clean K-1 Kerosene. Contaminated fuel could make cleaning the fuel filter necessary immediately.
NOTE: To remove the filter from models 45 ­75T-KFA turn filter 90º clockwise. To remove the filter from models 125T - 215T-KFA turn filter 90º counter-clockwise. See Figure 3.
THERMISTER PLACEMENT:
Ensure the thermister wire is in the proper place. The wire should be lying on the bottom shell inside the heater with the plastic end placed under the motor support/motor and away from fan blade.
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
Figure 3
Air Output Filter
Intake Filter
Lint Filter End Filter
Figure 4
7
Page 9
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
X
X
OR WHILE CONNECTED TO A POWER SOURCE
Maintenance
Service (Continued):
SPARK PLUG:
Clean and re-gap every 600 hours of operation, or replace as needed. After removing the spark plug, clean the terminals with a wire brush. Re-gap the terminals to 0.140” (3.5mm) See Figure 5.
Spark Plug
Burner Head
PUMP PRESSURE:
While heater is operating, turn adjusting screw clockwise to increase, counter-clockwise to decrease pressure. Correct pump pressure is as follows:
Model Number Pump Pressure
45-KFA 3.0 PSI (0.21 BAR)
75T-KFA 4.2 PSI (0.29 BAR) 135T-KFA 5.5 PSI (0.38 BAR) 190T-KFA 8.5 PSI (0.59 BAR) 215T-KFA 9.0 PSI (0.62 BAR)
Tolerance ± 10%
Gap
Figure 5
Ignitor Wire
PHOTOCELL:
The photocell should be cleaned using a cotton swab dipped in alcohol or water at least once per heating season, or more depending on conditions. See Figure 6.
Photocell
Photocell Wire
Photocell lens
Pressure Valve
Adjusting Screw
Figure 8
NOZZLES:
Nozzles should be cleaned or replaced at least once per heating season. Contaminated fuel could make this necessary immediately. To clean dirt from nozzle, blow compressed air through nozzle front. It may be necessary to soak the nozzle in K-1 kerosene to loosen any dirt particles.
Nozzle Face
Nozzle
Burner Head
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
Figure 6
8
Figure 7
Page 10
Problem Possible Cause Solution
Heater Ignites, but main PCB shuts off after a short period of time.
Lamp ickers and LED display
shows “E1”.
Heater will not operate or motor runs for a short time.
Lamp ickers and LED display
shows “E1”.
Fan does not operate when heater is plugged in and power switch is in the “ON” position. The lamp is
ickering or and LED display shows
“E1” or “E2”.
Lamp is ickering and LED display
shows “E3”. Poor combustion and / or excess
soot production.
Heater does not turn on and the lamp is not lit.
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
Troubleshooting Guide
1. Incorrect pump pressure.
2. Dirty input, output or lint lter.
3. Dirty fuel lter.
4. Nozzle is dirty.
5. Photocell lens is dirty.
6. Photocell not installed properly.
7. Photocell is defective.
8. Improper electrical connection between main PCB and photocell.
9. Improper location of thermister sensor (does not apply to 45-KFA model)
10. Improper electrical connection within the temperature limit switch
1. No kerosene in the fuel tank.
2. Incorrect pump pressure.
3. Corroded spark plug or incorrect plug gap.
4. Dirty fuel lter.
5. Dirty nozzle.
6. Moisture in fuel tank.
7. Improper electrical connection between transformer and circuit board.
8. Ignitor wire not connected to spark plug.
9. Defective ignitor.
10. Improper spacing with rotor
1. Thermostat is set too low (does not apply to 45-KFA model).
2. Broken electrical connection between main PCB and motor.
1. Thermostat switch has failed. 1. Replace thermostat switch (see
1. Dirty input, output or lint lter.
2. Dirty fuel lter.
3. Poor quality of fuel.
4. PSI is too high or too low.
5. Dirty nozzle
1. Temperature limit sensor has overheated.
2. No electrical power.
3. Fuse is blown.
4. Improper electrical connection between temperature limit sensor and circuit board.
1. Adjust pump pressure.
2. Clean / replace air or lint lter.
3. Clean / replace fuel lter.
4. Clean / replace Nozzle.
5. Clean / replace photocell.
6. Adjust photocell position
7. Replace photocell
8. Check wiring connections (see wiring diagrams on page 3).
9. Check thermister placement
10. Replace temperature limit switch
1. Fill tank with fresh kerosene.
2. Adjust pump pressure.
3. Clean / replace spark plug.
4. Clean / replace fuel lter.
5. Clean / replace nozzle.
6. Rinse fuel tank with clean, fresh kerosene.
7. Inspect all electrical connections. (See wiring diagrams on page 3.)
8. Re-attach ignitor wire to spark plug.
9. Replace ignitor.
10. Adjust rotor
1. Rotate thermostat to a higher setting
2. Inspect all electrical connections (see wiring diagrams on page 3).
Wiring diagrams on page 3).
1. Clean / replace air or lint lter.
2. Clean / replace fuel lter.
3. Flush fuel tank and refuel heater.
4. Use proper pressure.
5. Clean / replace nozzle
1. Push power switch to “OFF and allow heater to cool for 10 minutes. Restart heater.
2. Check power cords for proper connection and test the power supply.
3. Check / replace the fuse.
4. Inspect all electrical connections (see wiring diagrams on page 3).
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
9
Page 11
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
Exploded View
34**
33*
15
22
25
31
32
5
28
7
1**
35**
41**
27
36
29
38**
10
14
12
11
13
8
9
30
16
3
26
2
4
6
24
17
20
42
18
19
21
30
37**
* 45-KFA - 75T-KFA Only ** 135T-KFA - 215T-KFA Only
39**
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
10
Page 12
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
Parts List
# Description 45-KFA 75T-KFA 135T-KFA 190T-KFA 215T-KFA
1
Drain Plug
2
Fuel Gauge
3
Fuel Filter
4
Fuel Cap - Large Plastic
5
Power Cord
6
Power Switch
7
Thermostat Control Knob
8
Air Line
9
Thermostat Limit Control
10
Combustion Chamber Assembly
11
Photocell Bracket
12
Fuel Line
13
Photocell
14
Burner Head Assembly
15
Nozzle Kit
16
Spark Plug Kit
17
Motor
18
Pump Body
19
Rotor Kit
20
End Pump Cover
21
Filter Kit
22
End Filter Cover
23
Pump Adjustment Kit
24
Capacitor
25
Fan
26
Ignitor
27
Fan Guard
28
Main PCB Assembly
29
Fuse
30
Clip Nut
31
Air Pressure Gauge
32
Cord Bushing
33
Handle
34
Front Handle
35
Rear Handle
36
Wheel Support Frame
37
Wheel Axle
38
Wheel
39
Wheel Nut
40
Hardware Kit (not pictured)
41
Cord Wrap
42
Motor Supporter
– 70-007-0110 70-007-0115 70-007-0210 70-007-0210 70-007-0215 70-003-0100 70-003-0100 70-003-0200 70-003-0200 70-003-0200 70-006-0140 70-006-0140 70-006-0140 70-006-0140 70-006-0140 70-034-0100 70-034-0100 70-034-0200 70-034-0200 70-034-0200 70-038-0100 70-038-0100 70-038-0100 70-038-0100 70-038-0100
70-031-0100 70-031-0100 70-031-0100 70-031-0100 70-035-0100 70-035-0200 70-035-0300 70-035-0400 70-035-0500 70-019-0100 70-019-0100 70-019-0100 70-019-0100 70-019-0200 70-011-0100 70-011-0200 70-011-0300 70-011-0400 70-011-0500 70-010-1010 70-010-1010 70-010-1010 70-010-1010 70-010-1010 70-036-0100 70-036-0200 70-036-0300 70-036-0400 70-036-0500 70-016-0100 70-016-0100 70-016-0100 70-016-0100 70-016-0100 70-014-0101 70-014-0101 70-014-0301 70-014-0401 70-014-0401 70-015-0100 70-015-0210 70-015-0310 70-015-0410 70-015-0500 70-052-0100 70-052-0100 70-052-0200 70-052-0200 70-052-0200 70-021-0500 70-021-0500 70-021-0510 70-021-0520 70-021-0520 70-020-0101 70-020-0101 70-020-0101 70-020-0401 70-020-0401 70-022-0100 70-022-0100 70-022-0100 70-022-0200 70-022-0200 70-020-0102 70-020-0102 70-020-0102 70-020-0102 70-020-0102 70-054-0100 70-054-0100 70-054-0100 70-054-0100 70-054-0100 70-020-0103 70-020-0103 70-020-0103 70-020-0103 70-020-0103 70-055-0100 70-055-0100 70-055-0100 70-055-0100 70-055-0100 70-020-0125 70-020-0125 70-020-0200 70-020-0201 70-020-0201 70-024-0100 70-024-0200 70-024-0300 70-024-0400 70-024-0400 70-037-0350 70-037-0350 70-037-0350 70-037-0350 70-037-0350 70-016-0700 70-016-0700 70-016-0200 70-016-0200 70-016-0220 70-027-0110 70-027-0200 70-027-0310 70-027-0310 70-027-0310 70-027-0101 70-027-0101 70-027-0101 70-027-0101 70-027-0101 70-001-0105 70-001-0105 70-001-0105 70-001-0105 70-001-0105
70-025-0100 70-025-0100 70-025-0100 70-025-0100 70-033-0100 70-033-0100 70-033-0200 70-033-0200 70-033-0200 70-001-0103 70-001-0103
70-042-0100 70-042-0200 70-042-0200
70-043-0105 70-043-0205 70-043-0205
70-041-0101 70-041-0201 70-041-0201
70-041-0115 70-041-0205 70-041-0205
70-041-1400 70-041-1400 70-041-1400
70-041-0550 70-041-0550 70-041-0550 70-056-0100 70-056-0100 70-056-0200 70-056-0200 70-056-0200 70-032-0100 70-032-0100 70-032-0200 70-032-0200 70-032-0200
0-020-0600 70-020-0600 70-020-0610 70-020-0610 70-020-0610
70-002-0105 70-002-0105 70-002-0105
TIP: To order parts call 800-779-3267.
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
11
Page 13
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
LIMITED WARRANTY
Pinnacle Climate Technologies, Inc. warrants this heater
to the original retail purchaser only, to be free from defects in material and workmanship for a period of one (1) year from the date of initial purchase. This product must be properly installed, maintained and operated in accordance with the instructions provided.
Pinnacle Climate Technologies, Inc. requires reasonable proof of your date of purchase from an authorized retailer or distributor. Therefore, you should keep your sales slip, invoice or cancelled check from the original purchase. This Limited Warranty shall be limited to the repair or replacement of parts, which prove defective under normal use and service within the warranty period, and which Pinnacle Climate Technologies , Inc. shall determine at its reasonable discretion.
This warranty does not apply to products purchased for rental use.
This Limited Warranty does not cover any failures or
operating difculties due to normal wear and tear, accident,
abuse, misuse, alteration, misapplication, improper installation or improper maintenance and service by you or any third party. Failure to perform normal and routine maintenance on the heater, shipping damage, damage related to insects, birds or animals of any kind, and damage due to weather conditions are also not covered. In addition, the Limited Warranty does not cover damage
to the nish, such as scratches, dents, discoloration, rust or
other weather damage, after purchase.
All transportation costs for the return of damaged product or parts will be the responsibility of the purchaser. Upon receipt of damaged item, Pinnacle Climate Technologies,
Inc. will examine the item and determine if defective. Pinnacle Climate Technologies, Inc. will repair or replace
and return the item, freight pre-paid.
If Pinnacle Climate Technologies, Inc. nds the item to be in normal operating condition, or not defective the item will be returned freight collect. This Limited Warranty is in lieu of all other express warranties. Pinnacle Climate Technologies, Inc. disclaims all warranties for products that are purchased from sellers other than authorized dealers or distributors.
AFTER THE PERIOD OF THE ONE (1) YEAR EXPRESS WARRANTY EXPIRES, Pinnacle Climate Technologies,
Inc. DISCLAIMS ANY AND ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR APPLICATION. FURTHER, Pinnacle Climate Technologies, Inc. SHALL HAVE NO LIABILITY WHATSOEVER TO PURCHASER OR ANY THIRD PARTY FOR ANY SPECIAL, INDIRECT, PUNITIVE INCIDENTAL, OR CONSEQUENTIAL DAMAGES. Pinnacle
Climate Technologies, Inc. assumes no responsibility for any defects caused by third parties. This Limited Warranty
gives the purchaser specic legal rights; a purchaser may
have other rights depending upon where he or she lives. Some states do not allow the exclusion or limitation of special, incidental or consequential damages, or limitations on how long a warranty lasts, so the above exclusion and limitations may not apply to you.
Pinnacle Climate Technologies, Inc. does not authorize any person or company to assume for it any other obligation or liability in connection with the sale, installation, use, removal, return or replacement of its equipment, and no such representations are binding on Pinnacle Climate
Technologies, Inc.
Always be sure to specify the model number and serial number when making any claim with Pinnacle Climate Technologies, Inc. For your convenience, use the space provided below to list this information.
Locating Your Serial Number:
Your serial number can be found on a white label on the right side cover of your heater. It will be a series of 9 digits. For Example: 131234956. Have your Serial Number ready before calling customer service at 800-779-3267.
XX-X-XXXXXX
Model #:________________________________
Serial #:________________________________
Date of Purchase: ________________________
© 2017, Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
12
Serial Number Label
Page 14
Fax: 320-251-2922 • Web: www.masterindustrialproducts.com • Email: info@pinnacleclimate.com
1 Industrial Blvd #101, Sauk Rapids, MN 56379 USA • Toll Free (800) 779-3267
© 2017 Pinnacle Climate Technologies, Inc.
Loading...