Master MGH8500IE Owner's Manual

R
PORTABLE GASOLINE
GENERATORS
OWNER’S OPERATION AND INSTALLATION MANUAL
F
UEL
E
F
K
C
120V ISTLO
TW
120V
120V
CI
GF
T
E
S E R
T
S
E T
ER
ET
M
R
OU
H
M
N E
5 0
0
0
0
0
0
1
/
0
1
0
S R U
O
H
LE D I
TO-
AU
ON
FF
O
ET
RES
CK
TLO
IS
TW
CK
ISTLO
TW
ET
RES
ESET
R
T
RESE
Generator Model: MGH8500IE
IMPORTANT: Read and understand this manual before operating or servicing generator. Improper use of generator can cause serious injury. Keep this manual for future reference.
R
PORTABLE GASOLINE GENERATORS
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual and the engine owner’s manual carefully. Become famil­iar with this generator before try­ing to operate or service it. Know its uses, limitations, and any haz­ards involved. Improper use of generator can cause severe in­jury or death from explosion, fire, burns, electrical shock, or car­bon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Engine exhaust contains poisonous carbon monoxide gas. Overexposure will cause loss of consciousness and will lead to death. Use only in well-vented areas. Make sure area has plenty of free-moving, fresh, outside air. Never run generator in an enclosed or confined area. Never run generator inside occupied building.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning re­semble the flu, with headaches, dizziness, and nausea. If you have these signs, get fresh air at once! Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this generator.
Safety information appears throughout these instructions. Pay close attention to them. Below are definitions for the safety infor­mation listed throughout this manual.
DANGER: indicates a hazard which will cause severe personal injury, death, or substan­tial property damage if you ignore warning
WARNING: indicates a hazard which can cause severe personal injury, death, or substan­tial property damage if you ignore warning.
CAUTION: indicates a hazard which will or can cause minor personal injury or prop­erty damage if you ignore warning.
.
1. Gasoline presents a hazard of fire or ex­plosion. Gasoline is flammable. Its va­por is explosive.
•Keep fuel out of children’s reach.
• Refuel generator in a well-vented
area. Do not fill fuel tank in the dark. Do not refuel while engine is run­ning. Unhook all electrical loads and shut off engine before refueling.
• Do not overfill fuel tank. Always al-
low room for fuel to expand. If you overfill tank, fuel can overflow onto hot generator. This can cause fire or explosion. After refueling, tightly close fuel tank cap.
• Do not spill fuel. Fuel or fuel vapor
may ignite. If fuel spills, make sure area is dry before starting engine.
•Never smoke in refueling area. Never
allow open flames or sparks in area.
• Store fuel in approved container.
Store fuel in a well-vented area free of open flames or sparks.
2. Guard against fire hazard. Keep opera­tion area well-vented. Keep generator at least three feet away from any ob­ject. Do not place flammable objects near generator.
• Do not use generator where flam-
mable vapors are present. Some va­pors are heavier than air. These va­pors settle in low-lying places.
• Do not use generator in enclosed
spaces. This includes motor home or RV generator compartments.
3.
Guard against electric shock. Generator produces high voltage. This high voltage can cause severe electric shock. Only re­sponsible adults should use generator.
•Properly ground generator before
starting.
•Never let anyone operate or service
generator without proper instructions.
•Avoid contact with live terminals or
bare wires.
• Do not use generator outdoors in rain
or snow.
• Do not use generator near standing
water or snow.
• Do not use if generator is wet or
damp.
• Do not use generator in highly con-
ductive areas. These areas include metal decking and steelwork.
• Only use grounded extension cords.
• Do not use any worn or damaged electric cords. Electric shock or dam­age to generator may result.
• Do not wear damp clothing or wet shoes when using generator.
4. Guard against burns. Hot engine parts can cause severe injury. Use caution and remain alert when using generator.
•Keep children and animals away from
generator while it is running or hot.
•Keep all covers and shields in place.
Keep them tightly secured.
•The muffler becomes very hot dur-
ing operation. The muffler remains hot for a while after shutdown. Do not touch muffler while it is hot. Do not let muffler touch anything flam­mable. Let engine cool before trans­porting or storing.
5. Have standby installation to home or building performed by a licensed elec­trician. Do not let anyone else wire into a utility circuit. Personal injury, equip­ment damage, or damage to home could occur.
6. Never connect generator to any existing electrical circuits. The generator output will back-feed into the utility power line. This may electrocute a power company line repair person. Also, if generator is powering electrical circuits, the chance of an electrical fire exists.
7. Battery gives off explosive gases. Keep sparks, flames, and cigarettes away. Do not remove or install battery cables when engine is cranking or running. Only service or use battery in a well­vented area.
8. Battery contains sulfuric acid. Battery acid is poisonous if swallowed. Con­tact with skin or eyes may cause severe burns. Do not tilt generator with bat­tery installed. Tilting could cause bat­tery acid to spill. Wear protective cloth­ing and face shield when servicing. Keep out of children’s reach.
2
115407
OWNER’S MANUAL
SAFETY INFORMATION
Continued
9.
Only a qualified electrical service per­son should service and repair generator.
• Generator produces high voltage. Use extreme caution when working on electrical parts.
•Always remove spark plug wire from spark plug before servicing. This will prevent accidental starting.
When working on generator, avoid hot muffler, exhaust manifold, and engine parts. Severe burns may occur.
• Do not work on generator when tired.
• Use only factory approved replace­ment parts.
10. Store generator in a well-vented area. Make sure fuel tank is empty. Never store with fuel in tank. Vapors may reach an open flame or spark. Fire or explosion may result.
11. Never operate generator
• if engine speed changes greatly
• if engine misfires often
• if powered items overheat
• if electrical output drops
• if it is sparking
• if it produces smoke or flames
• if it vibrates at high levels
• if it has a damaged receptacle
12. Keep generator and nearby areas clean.
•Keep generator free of oil, mud, and
other foreign matter.
• Remove anything that creates slip-
pery areas around generator.
• Remove oily rags and other items
that create fire hazards.
•Keep a fire extinguisher nearby.
Make sure it is rated ABC by the NFPA. They are good for all uses. Consult your local fire department.
•Keep fire extinguisher well main-
tained. Be familiar with its use.
13. Know how to stop engine quickly. Know how to use all controls.
14. Prolonged exposure to loud noise can cause hearing loss.
•When working around generator,
wear approved hearing protection.
• Remember neighbors when using
generator.
PRODUCT IDENTIFICATION
Gas Tank
Gas Cap/Fuel Gauge
E
Ground Bolt
Alternator
120 Volt Receptacle (GFCI)
Hour Meter
Auto-Idle Switch
Control Panel
Figure 1 - Portable Generator
F
UEL
F
Choke Lever
Oil Filter
120V
TWISTLOCK
120V
120V
CI
GF
T
E S E
R
T S E T
120/240V
TWISTLOCK
120/240V
TWISTLOCK ER T
OUR ME
H
M
N E
5 0 0 0
0
0
0
1
/
0
1
0
S R
U O H
LE D I
TO-
AU
ET
RES
ON
RESET
FF
O
T
RESE
ET
RES
120 Volt Receptacle
120/240 Volt Receptacle
120 Volt Receptacle (Duplex)
Circuit Breaker
Roll Cage
115407
3
R
PORTABLE GASOLINE GENERATORS
GENERAL INFORMATION
Master portable generators are rugged and compact. These generators use brushless al­ternators for dependable, trouble-free service. Honda gasoline engines provide long life un­der heavy use. Honda engines have overhead valves (OHV). This provides high perfor­mance with lower fuel consumption. These engines are governed to maintain engine speed of 3600 RPM under load. 3600 RPM engine speed provides 120/240V, 60 Hz power.
Additional Features
• Circuit breaker protection
• Large fuel tank
• Oil alert system
• 15-Amp ground fault circuit interrupter (GFCI) receptacle
• Electric starter
UNPACKING
1. Remove generator from carton.
2. Remove any protective packaging ap-
plied to generator for shipment.
3. Check for loose or missing parts. Check
for shipping damage. If any parts are missing or damaged, please contact our Technical Service Department at 1-800­858-8501 (English Only).
4. Battery cables are supplied and in-
stalled on engine.
VENTILATION
DANGER: Use only in well­vented areas. Make sure area has plenty of free-moving, fresh, out­side air. Never run generator in an enclosed or confined area. Never run generator inside occu­pied building. Engine exhaust contains poisonous carbon mon­oxide gas. Overexposure will cause loss of consciousness and will lead to death.
This generator needs cooling air to run prop­erly. Never block free-flowing, cooling air to generator. Overheating will occur with­out cooling air. This will damage the gen­erator. Keep generator at least three feet away from any object.
DUST, DIRT, RAIN, AND SNOW
WARNING: Do not use gen­erator outdoors in rain or snow. Do not use generator near stand­ing water or snow. Do not use if generator is wet or damp. Oper­ating generator in these condi­tions increases the risk of elec­trocution. Severe injury or death can occur.
Do not use generator in extremely dusty or dirty conditions. This will severely affect its life. Keep generator clean. Do not allow dust, dirt, rain, or snow to collect on it. Protect generator from outdoor elements.
HIGH AND LOW TEMPERATURE OPERATION
Air temperature affects generator output. Output drops 1% for each 10° temperature rise above 60° F. Very low temperatures may make the engine hard to start. See engine owner’s manual for more information.
SPECIFICATIONS
Note:
Ratings apply to SAE standard conditions. Reduce ratings 3 1/2% for each 1000 feet above sea level and 1% for each 10° Fahrenheit rise above 60°F.
MGH8500IE
Electrical
Rated Wattage ................................. 8500
Rated Amperage
120 V ........................................... 70.8
240 V ........................................... 35.4
Receptacle
120-V, 20-A Duplex ........................... Yes
120-V, 15-A GFCI .............................. Yes
120-V Twist-Lock, 30 Amp ................ Yes
120/240-V Twist-Lock, 20 Amp ......... Yes
120/240-V Twist-Lock, 30 Amp ......... Yes
General
Honda Engine H.P. ...............................18
Honda Model ............................... EX-610
Fuel Type ................................... Gasoline
Fuel Tank Capacity .......................... 8 gal.
Oil Alert System ................................. Yes
Start Method ................................. Electric
Weight (pounds) ................................. 325
* Single-phase, 1.0 power factor
4
115407
OWNER’S MANUAL
GENERATOR FEATURES
OIL ALERT SYSTEM
The oil alert system protects the engine from low oil damage. This system automatically shuts down the engine and prevents engine restarting if the oil level falls too low.
Note:
When this happens, the engine switch remains in the ON position. The oil alert system is wired into the ON/OFF Switch.
If this system shuts down the engine, the engine will not start until you add oil. Add oil to engine (see Engine Oil, page 6).
Note:
Operate generator on a level surface. If not level, the oil may flow away from the oil level sensing device. This will cause the oil alert system to shut down engine.
See engine owner’s manual for more information.
HONDA
AUTO-IDLE SYSTEM
The Auto-Idle System allows the engine to idle down or run at a slower speed when the generator is not being used to supply power. The Auto-idle system can be turned ON or OFF by a rocker switch on the control panel. When the switch is in the OFF position, the engine runs at full speed all of the time. When the switch is in the ON position, the engine slows down to idle speed until an electrical load is applied. When a load is applied to the generator (an electrical item is plugged in and turned on) the engine speeds up to the preset speed required to produce the correct voltage.
IMPORTANT:
A minimum current load of 1 Amp is required to disengage the auto idle solenoid and cause the engine to come up to speed for correct voltage. Powering items at reduced engine speed will damage genera­tor and powered items.
ELECTRIC START
A battery is not supplied with generator. You must provide a 12-volt, 32-amp-hour battery. For more battery information, see Battery, page 7.
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE
The GFCI receptacle is on the control panel. The GFCI protects you against hazardous electrical shock caused when your body becomes a path through which electricity travels to reach ground. This could happen when you touch an appliance or cord that is ‘live’ through faulty mechanism, damp or worn insulation, etc.
When protected by the GFCI, you may still feel a shock, but the GFCI should cut it off quickly. A person in normal health should not receive serious injury. very small children may still be affected.
Test Procedure
Check the GFCI receptacle every month. This insures it is working right.
1. Push TEST button. RESET button should pop out. This should trip GFCI, resulting in no electrical power at re­ceptacle. Verify this by plugging test lamp with good bulb into receptacle. If lamp does not work, GFCI receptacle is good.
Note:
Infants and
OFFONSTART
Engine Switch
Figure 2 - Engine Switch Location
ENGINE SW
CIRCUIT BREAKER
ON/push OFF
WARNING: If RESET button does not pop out, do not use the GFCI receptacle. Contact a quali­fied electrician for repairs.
2. If the GFCI receptacle tests okay, re­store power by pushing the RESET button back in. The test lamp should work at this time
. IMPORTANT:
Yo u must press the RESET button firmly and fully. It should lock into place. If the GFCI does not lock into place, do not use receptacle. Contact a qualified electrician for repairs.
RESET
TEST
Figure 3 - GFCI Receptacle
115407
5
R
PORTABLE GASOLINE GENERATORS
GENERATOR FEATURES
Continued
RECEPTACLE CIRCUIT BREAKER
The circuit breakers protect the receptacles and alternator. Overloading generator will trip circuit breaker. A short circuit in item being powered will also trip breaker. If this occurs, unplug electrical load from recep­tacle. Let circuit breaker cool down. Push circuit breaker button to reset.
Electric motors need higher starting current. They require up to three-times their rated wattage to start. The starting current needed may be too high. This can cause nuisance circuit breaker tripping. To help prevent this, start electric motors first. Connect ad­ditional items to generator after starting motors. If this continues to happen, reduce the total generator load.
Note:
High ambient temperature will cause
nuisance tripping.
20
Figure 4 - Receptacle Circuit Breaker Button
ENGINE CIRCUIT BREAKER
This circuit breaker, or fuse, protects the battery charging circuit. A short circuit will trip the circuit breaker. The circuit breaker will also trip if you install the battery wrong. Push circuit breaker button to reset. The fuse is located inside of the Keyswitch box.
TrippedNormal
20
OIL ALERT
ENGINE OIL
We ship the generator without oil in the engine crankcase. You must add oil before starting engine. See engine owner’s manual for specific oil type.
CHECKING OIL LEVEL AND ADDING OIL
Follow steps below to check oil level. Make sure engine is level and stopped.
1. Remove dipstick (see Figure 6). Wipe dipstick clean.
2. Insert dipstick into oil filler neck. Oil level should be at top of filler neck the upper limit mark on dipstick.
3. If level is low, fill to top of oil filler neck (see Figure 6). Only use oil recom­mended in engine owner’s manual.
Note:
If oil level is too low, oil alert system will shutdown engine and prevent engine from restarting.
Oil Fill Cap
Upper Limit
Lower Limit
Dip Stick
Figure 6 - Checking Oil Level
FUEL
WARNING: Gasoline presents a hazard of fire or explosion. Gasoline is flammable. Its vapor is explosive.
• Keep fuel out of children’s
reach.
Refuel generator in a well­vented area. Do not fill fuel tank in the dark. Do not refuel while engine is running. Unhook all electrical loads and shut off engine before refueling.
• Do not overfill fuel tank. Al-
ways allow room for fuel to expand. If you overfill tank, fuel can overflow onto hot engine. This can cause fire or explo­sion. After refueling, tightly close fuel tank cap.
• Do not spill fuel. Fuel or fuel
vapor may ignite. If fuel spills, make sure area is dry before starting engine.
• Never smoke in refueling area.
Never allow open flames or sparks in area.
•Store fuel in approved con-
tainer. Store fuel in a well­vented area free of open flames or sparks.
Use clean, fresh, unleaded gasoline. Use gasoline with octane rating of 86 or higher. Service station gasoline pumps should dis­play the octane rating. Using gasoline with lower octane level could damage engine. Avoid getting dirt, dust, or water in fuel tank. Do not mix oil with gasoline.
See engine owner’s manual for more information.
OFFONSTART
Engine Circuit Breaker Button
Figure 5 - Engine Circuit Breaker
ENGINE SW
CIRCUIT BREAKER
ON/push OFF
BATTERY
WARNING: Battery gives off explosive gases. Keep sparks, flames, and cigarettes away. Do not remove or install battery cables when engine is cranking or running. Only service or use battery in a well-vented area.
6
115407
OWNER’S MANUAL
S
BATTERY
Continued
WARNING: Battery contains sulfuric acid. Contact with skin or eyes may cause severe burns. Do not tilt generator with battery installed. Tilting could cause bat­tery acid to spill. Wear protective clothing and face shield when servicing. Keep out of children’s reach.
• If battery acid gets on your
skin, wash with water.
• If battery acid gets in your eyes,
flush with water at least 15 min­utes. Call a doctor at once. Battery acid is poisonous.
• If swallowed, drink large
amounts of water or milk. Fol­low with milk of magnesia or vegetable oil. Call a doctor at once.
CAUTION: If you remove bat­tery, insulate the red, positive (+) battery cable terminal. Insulate with electrical tape. Exposed terminal may spark when generator runs.
IMPORTANT:
tions are the correct polarity. Electric start generators use negative ground, 12-volt DC starting system.
A battery is not supplied with generator. You must provide a 12-volt, 32-amp-hour battery. The positive and negative battery cables are supplied with generator. You must install these cables before mounting battery.
Always wear safety glasses when working with battery. Make sure battery terminals are clean. Make sure cable connections are tight.
Always shut down engine before removing or attaching battery cables. Always remove the negative (–) cable first. Always attach negative (–) cable last.
INSTALLING BATTERY CABLES TO ENGINE
1. Attach the red, positive (+) battery cable to the starter solenoid on engine (see Figure 7). The starter solenoid is located directly above the starter.
Make sure battery connec-
CAUTION: Do not over tighten positive terminal on starter sole­noid. Positive terminal could ro­tate and cut into negative termi­nal, causing a short.
2. Attach the black, negative (–) battery cable to the engine block. Use the bolt, nut, and two washers provided with the battery cables. Use long mounting hole on oppo­site side of engine from starter solenoid. Attach cable as shown in Figure 8.
Starter Solenoid
Red, Positive (+) Battery Cable
Figure 7 - Connecting Red, Positive (+) Battery Cable to Engine Starter Solenoid
Black, Negative (–) Battery Cable
Figure 8 - Connecting Black, Negative (-) Battery Cable to Engine Block
MOUNTING BATTERY TO GENERATOR
1. Secure battery to generator by battery hold-down system. This system con­sists of the battery mounting bracket, hook bolts, and nut (see Figure 9).
Nut
Battery Mounting Bracket
V
0 2 1
I
C F
Battery
Hook Bolt
Figure 9 - Battery Hold-Down System (Alternator Removed for Clarity)
G
ET
S
E
R
T
S
E T
R E
T
E
M
R
OU
H
M
N
E
5 0
0 0 0
0
0 0
0
1/1
RS
HOU
LE D I
­O T
AU
ON
F
F
O
E
R
ET
S E R
2. Locate the red, positive (+) battery cable from starter solenoid. Connect it to the positive (+) battery terminal (see Figure 10).
3. Locate the black, negative (–) battery cable attached to engine block. Connect it to the negative (–) battery terminal (see Figure 10).
4. Check battery before starting engine. Make sure fluid levels are full. Make sure battery is charged.
See engine owner’s manual for more information.
To Engine Block (–)
V
0 2 1
I C F
G
T RESE TEST
R
E
T E
M
R
OU
H
NM
E
00005
0
To Starter Solenoid (+)
Figure 10 - Connecting Positive and Negative Cables to Battery (Alternator Removed for Clarity)
EXTENSION CORDS
Only use grounded extension cords. Be sure to use extension cord with proper wire gauge size. See chart below.
Recommended Minimum Wire Gauges (AWG) for Extension Cords
Ampere AWG for Length of
Load Cord in Feet
50' 100' 150'
2181818 3181818 4161616 5161616 6161614
8161412 10 16 14 12 12 14 14 12 14 14 12 10 16 12 12 10 20 10 10 8
115407
7
R
H
O
PORTABLE GASOLINE GENERATORS
GENERATOR GROUNDING
WARNING: You must prop­erly earth-ground generator be­fore starting. This will help guard against deadly electric shock. Only use grounded plugs with generator. Only use grounded ex­tension cords. Only use three-wire or double-insulated power tools.
Grounding generator helps prevent electric shock from a ground fault condition. Follow these steps to ground your generator:
1. Locate ground bolt on generator hous­ing (see Figure 11).
2. Loosen SEM nut on ground bolt. Do not remove SEM nut from bolt.
3. Attach a spade connector to the end of a #10-8 stranded-copper ground wire.
4. Attach spade connector to ground bolt between flat washer and SEM nut (see Detail A in Figure 11).
5. Drive grounding point into ground.
Note:
Grounding point can be a stake, grounding rod, or pipe. Grounding point should be copper or brass.
6. Attach ground wire to grounding point.
Note:
You must supply the ground wire and ground­ing point. These do not come with generator. Follow the National Electrical Code and all state and local codes. Consult your power company or a licensed electrician.
WARNING: For a grounding point, do not use metal pipe be­ing used to carry combustible materials or gases.
Flat Washer
SEMS Nut
Ground Bolt
Spade Connector
Detail A
FUEL
E
F
2 1
V
0 2 1
I
FC
Ground Wire
Copper or Brass Grounding Point
Alternator
G
T E S
E
R
T S
E T
/2
0 2 1
T IS
W
R
T
TE
E
M
R
HOU
M N
E
5 0 0
0
0 0 0
0
1/10
S UR
O
H
LE
ID
-
O T
AU
ON
F
OF
T SE E
R
ET
S E R
STANDBY INSTALLATION TO HOME OR BUILDING
WARNING: Have standby in­stallation performed by a skilled, licensed electrician. Do not let anyone else wire into a utility circuit. Personal injury, equip­ment damage, or damage to home could occur.
IMPORTANT:
power your entire home. Most home utility electric service is more than 60 amps. This will exceed generator output. Only power needed items during a power outage. Make sure total wattage of electrical load does not exceed rated wattage of generator.
You may need to use this generator as a standby power source. During a power out­age, the generator will power selected items in a building. Have generator and additional wiring installed by a skilled, licensed elec­trician. This is not a do-it-yourself job. Fol­low all local codes.
WARNING: The electrician
V 0
must install a double-throw trans­fer switch. This isolates existing
V 0 4
K
C O L
R
electrical circuits from the utility power line. If not isolated, gen­erator output will back-feed into
T SE E
utility power line. This may elec­trocute a power company line repair person.
This generator will not
Figure 11 - Grounding Generator
8
115407
Loading...
+ 16 hidden pages