Master DHA 250 Instruction Manual

Page 1
Page 2
Contents
General safety information..........................................................................................................................4
Applications..................................................................................................................................................5
Method of operation.....................................................................................................................................5
Product description......................................................................................................................................6
Casing........................................................................................................................................................................6
Filter..........................................................................................................................................................................6
Fan for process- and reactivation air.........................................................................................................................6
Heater for reactivation air.........................................................................................................................................6
Electrical panel..........................................................................................................................................................6
Operation options......................................................................................................................................................6
Installation....................................................................................................................................................7
Installation and service access..................................................................................................................................7
Duct connection for permanent installation..............................................................................................................7
Wet air duct out from dehumidifier.......................................................................................................................7
Reactivation air into the dehumidifier..................................................................................................................7
Process and dry air with the dehumidifier installed in the dehumidified room...................................................7
Process and dry air with the dehumidifier installed outside the dehumidified room...........................................7
Duct connection for basement installation................................................................................................................7
T
emporary installation..............................................................................................................................................8
Electrical installation.................................................................................................................................................8
3
Commissioning.............................................................................................................................................9
Maintenance................................................................................................................................................10
Filter........................................................................................................................................................................10
Electrical motors.....................................................................................................................................................10
Heater......................................................................................................................................................................10
Rotor drive belt.......................................................................................................................................................10
General summary of maintenance intervals............................................................................................................11
Transportation............................................................................................................................................11
Fault finding...............................................................................................................................................12
Technical data.............................................................................................................................................13
Performance chart...................................................................................................................................................13
Dimensions..............................................................................................................................................................14
Technical data.........................................................................................................................................................14
Noise data...........................................................................................................................................................15
Symbols...............................................................................................................................................................15
Noise path...........................................................................................................................................................15
Noise data................................................................................................................................................................15
Spare parts list............................................................................................................................................16
Electrical wiring.........................................................................................................................................17
Electrical components................................................................................................................................18
Miscellaneous / Notes.................................................................................................................................19
Subject to change without notice DHA 250
Page 3
General safety information
4
Anyone operating the DHA 250 should
have access to this manual, and should be aware of the safety information.
Only personnel with adequate knowledge of
the dehumidifier should be allowed to oper­ate and service it.
Only personnel with authorisation for elec-
trical installations are allowed to make repair of electrical components.
Repair of electrical components should be
carried out by suitable qualified personnel.
The dehumidifier must not be installed in
areas where explosion proof equipment is required.
Disconnect the dehumidifier from the mains
prior to opening any service panel.
Prior to servicing the dehumidifier must be
left to cool down for at least 15 minutes after operation.
The service panels should remain closed
except when serviceing is carried out.
The dehumidifier can only be used for dehu-
midification of air at atmospheric pressure.
Never use the dehumidifier without the
filters as the desiccant rotor can become contaminated and lose capacity
Signs and instructions on the dehumidifier
should not be removed or altered.
This manual should always be accessible and
kept close to the dehumidifier
All maintenance and control of the dehumid
ifier should be as per the specified schedule.
Use only genuine spare parts.
.
.
-
Subject to change without notice DHA 250
Page 4
5
Applications
Dehumidifier DHA 250 is of the solid des­iccant wheel type designed to dry air of atmos­pheric pressure. The dehumidifier can be used for drying air of up to 100 % relative humidity (RH) with temperatures from -30 ºC to +40 ºC.
The applications are numerous and wide spread. Below are some examples:
Controlling humidity levels in production
processes.
Drying of temperature sensitive products.
Maintaining correct humidity in storage
areas.
Protection of equipment sensitive to corro-
sion.
Controlling humidity levels in museums and
archives.
Drying after water damage and drying of
buildings during construction.
Climatic improvements in damp areas.
Method of operation
The dehumidifier operates with two air streams. A larger air stream to be dehumidified, and a smaller air stream to exhaust the moisture out of the desiccant rotor.
Both airstreams are created by one common fan which pressurises a compartment of the dehu­midifier creating two separate airstreams.
The larger air volume, the process air, passes through the slowly rotating silica gel rotor. Silica gel is a hygroscopic material adsorbing water vapour direct from the air. When pass­ing through the rotor the humidity of the air is reduced, whilst the moisture content of the rotor material increases. On exiting the rotor the dried air is introduced into the area, or the process to be dehumidified. The adsorption process works in temperatures from -30 ºC to +40 ºC.
The smaller air volume, the reactivation air, adsorbs the moisture from the silica gel rotor. This reactivation air first enters a purge sector of the rotor, thus cooling down the rotor material, and simultaneously increasing the reactivation air temperature. The temperature of this pre­heated air is further increased by an electrical heater to a temperature of approximately +100 ºC. As the reactivation air passes through the rotor, in an opposite direction to the dry air, it will decrease the moisture content of the rotor material. The reactivation air will leave the dehumidifier as warm, wet air, which is then exhausted out from the building.
Subject to change without notice DHA 250
Page 5
Product description
6
The dehumidifier is designed to meet the requirements of IEC protective class IP 44:
Casing
The casing is fabricated from stainless steel
2333. The top of the dehumidifier has a top panel that can be removed for service access to electrical and mechanical components. All duct connections to the dehumidifier are designed for connections to standard size spiral ducts.
Rotor
The dehumidifier has a drying rotor fabricated from a desiccant material. The rotor has a matrix of corrugated and flat heat resistant sheets which houses the Silica Gel desiccant agent. This matrix creates a large number of axial flutes through the rotor, which together builds up an immense surface area for moisture adsorption in a small volume. The rotor is manufactured and processed to be able to withstand mois­ture saturated air without being damaged. This means that the rotor can be used in conjunction with a pre-cooling coil. Furthermore the rotor will not be damaged even if the fan or the heater for reactivation should fail during operation. The
rotor is incombustible and non flammable.
The slow rotation of the rotor is achieved by an electrical gear motor and a belt drive. The belt sits on the outer rim of the rotor and is driven by a pulley on the drive motor. An adjustable belt tension device keeps the belt in place and main­tains tension to prevent belt slip. Correct opera-
of the drive system, and direction of rotation
tion can be checked by opening the top panel.
Fan for process- and reactivation air
The fan is a direct drive radial fan with a single phase standard motor class IP 54, ISO F. The fan is accessible for service after removing the top panel of the dehumidifier.
Heater for reactivation air
The reactivation heater is of the PTC-type (Positive Temperature Control), which can not be overheated, and gives the possibility of a stepless control for 30 - 100 % of the dehumidi­fication capacity. This is achieved by controlling the wet air volume.
Electrical panel
The electrical panel is located inside the dehu­midifier and is accessible through the top panel. Switches and indications for operation are mounted at the front of the electrical panel.
Operation options
Using the operation switch on the front side of the dehumidifier, different running options can be selected:
0 Dehumidifier not in operation.
1 Dehumidifier in operation mode.
MAN Dehumidifier in continuous operation.
AUTO Automatic operation by remote humidistat, or other external on/off signal.
The centre hub of the rotor is equipped with ball bearings. The rotor shaft is made from stain­less steel. The complete rotor part can easily be removed and lifted as one piece out from the casing.
Filter
The dehumidifier has one common filter for process- and reactivation air.
Subject to change without notice DHA 250
Page 6
Installation
7
Installation and service access
Dehumidifier DHA 250 is designed for indoor installation. The dehumidifier should be installed horizontally.
All components in the dehumidifier are acces­sible from the top of the unit. For inspection and service, a space of 400 mm must be left free above the dehumidifier to accommodate for servicing of filter, fan and rotor.
When using a mounting plate, the dehumidifier must be put so that the rotorshaft still is horizon­tal and the wet air outlet is placed low.
Duct connection for permanent installation
The dehumidifier can be installed in the room that should be dehumidified or in a separate plant room.
To obtain the best performance the outlets from the fans should be equipped with diffusors.
Reactivation air into the dehumidifier
For reactivation of the dehumidifier an addi­tional air volume is needed. This air enters the unit along side the process air. As an option the dehumidifier can be equipped with duct connec­tions for entering air (2 x Ø80). One of them can be used for intake of ambient air The duct should be as short as possible, requires no insulation, and can slope up or down. In some installations, as an alternative, the reactivation air can be taken from the installation plant room, for this alternative no duct connection is needed.
for reactivation.
Process and dry air with the dehumidifier installed in the dehumidified room
When the dehumidifier is installed in the dehumidified room it would normally take the process air directly from the room without any duct system. If the process air inlet needs to be connected to a duct system, the dehumidifier is prepared for using a plate with duct connections. The dry air outlet would normally have a duct system designed for distribution of the dry air in the building.
Wet air duct out from dehumidifier
The wet air from the dehumidifier should be exhausted to the outside. The duct should be as short as possible to minimise the chance of con­densation of the wet air. This duct should slope down slightly to stop any condensed water from flowing back into the dehumidifier.
If the wet air duct is extremely long, or must be installed sloping upwards from the dehumidifier, it should be insulated and have a drainage point (2 mm) drilled at its lowest position.
A damper should be installed in the wet air duct to enable correct setting of the reactivation air volume during commissioning.
The exhaust opening should have a coarse wire net.
Process and dry air with the dehumidifier installed outside the dehumidified room
When the dehumidifier is installed in a separate plant room all inlet and outlet openings are usu­ally ducted.
The dehumidifier takes the process air as ambi­ent air, or as pre-treated air (cooled/heated), or alternatively as return air from the dehumidified room. The dry air from the dehumidifier can be connected for post treatment or ducted back to the dehumidified room.
Dampers should be installed in the dry and wet air ducts, enabling correct commissioning of the air volumes.
Subject to change without notice DHA 250
Page 7
Duct connection for basement installation
If the dehumidifier should be installed in the basement it is sometimes desirable to achieve a slight negative pressure in the basement to prevent odours from penetrating up into the building. In these circumstances the reactivation air is taken directly from the basement and the wet air is exhausted out from the basement. This method of installation will create a small nega­tive pressure. The other ducts should be installed according to ”Duct connection for permanent installation”.
Temporary installation
8
With temporary installations for water damage or building drying, flexible plastic ducts would normally be used instead of the spiral duct type. The drying method differs depending on situa­tion and construction to be dried. The complete room could be dehumidified, or just the dam­aged part. For the later option plastic sheet is used to cover the damaged area, and the dry air is supplied under the sheet. For both options the wet air must be exhausted out from the building via flexible duct, or alternatively connected to the general exhaust ventilation system for the building.
Electrical installation
See the electrical wiring diagram on page 17.
Subject to change without notice DHA 250
Page 8
Commissioning
9
On initial start up, the following steps should be taken in this order:
1. Ensure that the external isolation switch is isolating the unit from the mains, or that the power plug is disconnected.
2. Select the OFF position on the main switch (orange) at the front of the dehumidifier.
3. Open the service panel on the top of the dehu­midifier and ensure no foreign objects are left inside the unit or in the electrical compart ment
Make sure the air filter is installed.
4.
5. Rotate the fan impeller by hand and make sure it can move freely.
6. Ensure that the dry and wet air dampers are open, and that ducts are clean and free of blockages.
Ensure that the mains supply fuse is suitably
7. rated (10A), and that the fuse is of a slow kind.
9.
Connect the dehumidifier to the main electri­cal supply by turning the isolation switch to ON, or alternatively connect the power plug to the socket.
-
10. Select the MAN position on the operation switch (black) of the dehumidifier the main switch (orange) to the ON posi­tion for 3-4 seconds. Check that the rotor is slowly rotating, the fans are starting, and that the orange lamp in the main switch lights up. Turn OFF the dehumidifier.
1
1. Mount the service panel and ensure it seals properly to the casing.
12. The dehumidifier is now ready for operation.
13. Start the dehumidifier and check that the unit is operating at the correct air volumes. indication of correct operation is if the ampere meter on the front of the dehumidifier indi­cates approximately 6 A.
14. From the factory the dehumidifier is electri­cally wired in such a way that when operat ing in AUTO mode, the controls operate the complete unit to start or stop. By shifting one terminal connection in the electrical panel the operation mode can be altered to operate the fan continuously. The control will then only operate the heater on /of signal from the humidistat or other external signal.
See the electrical wiring diagram on page 17.
f, depending on the
. Switch
An
-
Subject to change without notice DHA 250
Page 9
Maintenance
NOTE ! With all maintenance and service of the dehumidifier:
Switch off the dehumidifier approximately
15 minutes prior to opening the service panel, allowing the heater to cool down.
Disconnect the dehumidifier from main
electrical supply by turning the external switch to the of the power plug.
f position or by pulling out
10
The maintenance intervals for the dehumidifier depend on the surrounding environment and installation site. Recommended maintenance intervals could therefore differ from one instal­lation to another. Incorrect maintenance and service may result in reduced dehumidification capacity.
Filter
The dehumidifier is equipped with one common filter for the process air and reactivation air. The filter is positioned at the inlet and will clean the air prior to entering the dehumidifier.
Intervals for cleaning or replacement of the filters will be determined by the amount of dust and particles in the air at the installation site.
We recommend that the filter is checked at least once a month, at least for the first year of a new installation.
Never operate the dehumidifier without the
, as the rotor can be damaged by dust.
filter
Electrical motors
The electrical motors are equipped with ball bearings. The bearings are designed to last the life of the motor and therefore no maintenance is required.
Check the motors once a year for any abnormal sound.
Heater
The reactivation electric heater does not need maintenance, but should be checked twice a year for any dust or mechanical damage to the heat­ing rods. Clean with a soft brush, or vacuum clean with dust. Gentle use of compressed air is another alternative.
Rotor drive belt
Check the belt tensioning at regular intervals. Adjust when needed by moving the tensioning support wheel closer to the desiccant rotor.
Rotor
The rotor is maintenance free. However should it be necessary to clean the rotor careful use of compressed air should be the first choice. With severe contamination the rotor can be washed with water.
Cleaning with water is no routine matter, please contact distributor prior to this procedure.
Check the rotor bearing and the rotor surface once a year
Subject to change without notice DHA 250
.
Page 10
General summary of maintenance intervals
Filter Rotor Bearing Motors Rotor drive Heater Sealings
On demand
11
Every 6
Every 12th month
th
month
Transportation
Observe the following for transport or handling of the dehumidifier:
Check the dehumidifier on delivery for any
transport damage.
The dehumidifier should be protected from
rain and snow
The dehumidifier should always stand upright
on its feet.
ransport and lift the dehumidifier by the
T
two handles on each side of the transportation box.
.
Subject to change without notice DHA 250
Page 11
Fault finding
Malfunction Possible cause of trouble Corrective action
12
None, or reduced dehumidification capacity
Main fuse faulty Fan faulty
Dehumidifier does not start No control circuit
Filter clogged
Electrical heater faulty
Airflow reduced
No rotation of rotor
Internal leakage in unit
Altered air volumes
Altered reactivation temperature
Air leakage
T
oo large air volume
Rotor does not rotate
Reactivation heater faulty
Faulty control signal
Fuse for controls faulty
Clean or replace filters
Check fuses
Check openings and dampers
Check belt tensioning
Check springs
Measure and check air volumes
Check reactivation heater
Check panel and casing
Check fan and motors
Check air volumes and dampers
Check drive motor and drive belt
Check reactivation heater
Check control fuses
Check external start/stop signal
Check electrical components
Rotor does not rotate Drive belt is slipping
Drive belt broken or worn
Rotor jammed
Drive motor faulty
No dry- or wet air volume Filter clogged
Fan faulty
Ducts blocked
Check belt tensioning
Replace drive belt
Check centre shaft, rim of rotor
Replace complete gear motor
Clean or replace filters
Check fan, motor and impeller
Check dampers and ducts
Subject to change without notice DHA 250
Page 12
Technical data
Performance chart
CAPACITY DIAGRAM
13
(g/kg) X
20
T
15
10
20
C)
o
15
tp=30°C
=20°C
t
p
5
t
10°C
p
Temperature rise (
10
5
0
0 5 10 15 20
X
P
(g/kg)
EXAMPLE: Process air: x
Dry air: x
T
= 9,0 g/kg, tp = +20°C giving
p
= 6,1 g/kg, tT = 20+8,5 = 28,5°C
0
Subject to change without notice DHA 250
Page 13
Dimensions
14
Technical data
Dehumidification capacity 1,1 kg/h (at +20 ºC and 60 % RH. See performance chart for other data)
Dry air flow 290 m (freeblowing)
Wet air flow 80 m (freeblowing)
Power supply 1,4 kW (1 x 230 V, 50 Hz)
Current 6,1 A (connection fuse: 10 A)
Weight 18 kg
Noise level
61 dB(A)
3
3
/h
/h
Subject to change without notice DHA 250
Page 14
Noise data
Noise path
15
A Open intake for process air.
D Only dry air and wet air outlet ducted.
Noise data
B Open intake for process air. Dry air outlet ducted and air discharged at 2-3 m above floor.
Ducted outlet for dry air. Wet air outlet ducted with short 90 degree angle duct.
C
E
All outlets completely ducted.
Correction of K dB at ISO-band No/Centre frequency (Hz)
Noise path LWA 1/64 2/125 3/250 4/500 5/1000 6/2000 7/4000 8/8000
A 65 -26 -14 -10 -10 -9 -3 -9 -15
B 66 -22 -11 -6 -10 -10
C 67 -27 -12 -7 -7 -10 -3 -8 -14
D 67 -27 -13 -7 -10 -10 -3 -8 -14
E 59 -24 -10 -11 -6 -4 -5
-3 -9 -15
-14 -20
Symbols
L
= Total noise level in dB(A) (rel. 10
WA
L
= Noise power level in octave band dB(A) (rel. 10
WAO
K = Correction for calculation of LWAO (L
-12
W)
= LWA + K)
WAO
-12
W)
dB(A) = Noise power level at room condition R = 102 Sab
Subject to change without notice DHA 250
Page 15
Spare parts list
16
Part Technical specification No installed No of recom-
mended spare
parts
Drive motor Gearmotor 230-240 V 50 Hz 3 rpm
low temp grease
Belt pulley HTD 5M, Z=20 1
Drive belt 1050-5M-9 1
Fan G2E 160-AS52-132 1
Capacitor 4 µF 400 V 1
Heater PTC HR-AB PH2PA24014711 230 V 1 1
Wet air duct Heat resistant flexcord Ø80 1
Rotor PPS 250 1
Belt tensioning 1
Filter AAF R29 EN779:G3 220 x 330 mm 1 3
Toggle switch 2x1 pol. electric switch 1
Ampere meter RQ48E 10A
Cord H07RNF/3 x 1,5 1
IP 54 1
1 1
Comment
Process air duct con­nection
2 x Ø80 0 Option
Subject to change without notice DHA 250
Page 16
Electrical wiring
17
M2
P2
Black
2
Brown
Blue
ellow / Green Y
C
Name Component
S1/S2 On-Off / Man-Auto switch
h Runtime meter *
HS Humidistat *
A Amperemeter
P1 Terminal block 7-pin
E React. heater
M1 Drive motor, rotor
C Capacitor
P2 Terminal block 4-pin
P3 Terminal for humidistat
M2 Fan
6 4
*) Optional
M1
E
4
5
P1
S2S1
P3
1 1
8
1 4
1
9
6 2
2 2
2
3 3
3
3 6
4 4
A
4
5 5
h
6
6
Optional operation method when controlled
by humidistat
If continuous operation of the fan is requested,
and the humidistat HS should control only the
reactivation heater, shift wire 2-2 from terminal
230 V
50 Hz
P1:2 to terminal P1:1
1,4 kW
Humidistat
Connect humidistat to terminal P3:8-9
Subject to change without notice DHA 250
Page 17
Electrical components
No
Part Mark Type Quantity Manufacturer
1 Gear motor 230 V, 50 Hz, 3 rpm M1 823055BJ 1 Crouzet AB
2 Radial fan, G2E 160-AS52-132 M2 EK259 1 ZIEHL-ebm AB
3 Capacitor, 4 µF 400 V C KO218 1 ZIEHL-ebm AB
4 Toggle switch 2x1-pol. bl/or S1/S2 255036 1 Orbitus Ind.komp.
5 Amperemeter A RQ48E 10A IP54 1 Tälje mätinstrum.
18
6 Heater, 230 V E PH2P
7
Terminal male 7-pin P1 sls 5.08/7B sn or 1 Weidmüller AB
8 Terminal, female 7-pin P1 blz 5.08/7 sn or 1 Weidmüller AB
9 Terminal male 4-pin P2 sls 5.08/4B sn or 1 Weidmüller AB
10 Terminal female 4-pin P2 sls 5.08/4 sn or 1 Weidmüller AB
11 Blind panel, 48 x 48 - 1
12 Blind plug, 22,0-25,5 mm - P208/4 1
13 Cord, H07RNF/3G1.5/3,5m - 2440032 1 OEM Component
14 Runtime meter h *
15 Humidistat plug connection HS *
*) Option
A24014711 1 Victon Ltd.
1110 1 Tälje mätinstrum.
OEM Component
Subject to change without notice DHA 250
Loading...