Masibus Automation And Instrumentation 8204 User Manual

4 - CHANNEL SCANNER
USER MANUAL
8204
Masibus Automation And Instrumentation Pvt. Ltd.
B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India
Email: support@masibus.com
Web: www.masibus.com
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
Contents
(1) Introduction……………………………………………………………………… (03)
(2) Installation……………………………………………………………………….. (05)
(3) Hardware Specification Detail……………………………………………… (08)
(4) Front and Back Panel Description…………………………………………. (11)
(5) Key Function Description…………………………………………………….. (13)
(6) Menu Layout………………………………………………………………………. (14)
(7) Parameter Flow Chart…………………………………………………………...(22)
(8) Relay Outputs…………………………………………………………………….. (25)
(9) Calibration Procedure…………………………………………………………… (32)
(10) Modbus Communication Detail……………………………………………… (34)
(11) Miscellaneous……………………………………………………………………… (40)
User‟s Manual - 2 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
1. INTRODUCTION:
Fo r ew o rd
Th a nk y o u for pu rc h asi ng 8 204 un iv e rsa l Sca n ne r . Th i s ma n ual de s cr i be s t h e b as i c fu n ct i o n s a nd op er a ti on me t ho d s of 8204 .P lea se rea d through this u se r‟s man ual ca ref ull y b efo re u sin g t he p ro d uc t .
No t ic e
Th e c o nt e nt s of th i s m an u al ar e su bje ct to cha ng e wi tho u t n oti ce as a
res ult of c ontinu ing i mprovem ent s to the instr ument‟ s perform ance and
fu n cti on s .
Every effort has been made to ensure accuracy in the preparation of this manual. Should any errors or omissions come to your attention, however, please inform MASIBUS Sales office or sales representative. Under no circumstances may the contents of this manual, in part or in whole, be transcribed or copied without our permission.
Trademarks
Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Masibus Automation and Instrumentation (P) Ltd. (herein after referred to as MASIBUS). Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. All other product names mentioned in this user's manual are trademarks or registered trademarks of their respective companies.
Re v is i on 8th Edition: SEPT 2014.
User‟s Manual - 3 -
4-CHANNEL SCANNER-8204
Model
Suffix code
Optional code
Remarks
No
Item name
Part number
Qty
Remarks
REF NO: m82/om/101
Issue NO: 09
Ch e ck i ng the Co nt ent s o f t h e P ac k ag e
Un p ack th e bo x an d ch eck th e con te n ts b ef o re u si n g t h e pr o du c t. If th e p ro d uct i s d i ff e re n t f ro m t h at wh ich y o u h av e o rde red , if a n y pa rts o r ac c es s ori es a r e mi s si n g, o r if th e pr odu c t ap p ea r s to b e da m ag e d, con tac t y ou r sa les r e pr e se n ta t iv e .
Product Ordering Code:
The 8204 Scanner unit has a nameplate affixed to the one side of the enclosure. Check the model and suffix codes inscribed on the nameplate to confirm that the product received is that which was ordered.
List of Accessories
The product is provided with the following accessories according to the model and suffix codes (see the table below). Check that none of them are missing or damaged.
User‟s Manual - 4 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
2. INSTALLATION:
How to Install:
Mounting method: Panel mounting
To install the controller select a location where:
o no one may accidentally touch the terminals o mechanical vibrations are minimal o corrosive gas is minimal o temperature can be maintained at about 25˚C to 35˚C and the
fluctuation is minimal
o no direct radiant heat is present o no magnetic disturbances are caused o no wind blows against the terminal board o no water splashed o no flammable materials are around
Turn off the power to the controller before installing it on the
panel because there is a possibility of electric shock
User‟s Manual - 5 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
External Dimensions and Panel Cutout Dimensions:
FRONT BEZEL: 48 x 96 mm PANEL CUTOUT: 45+0.8(H) x 92+0.8(W) mm DEPTH BEHIND THE PENAL: 130 mm
User‟s Manual - 6 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
How to connect wires:
Before carrying out wiring, turn off the power to the
controller and check that the cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
NOTE:
o All wiring must confirm to appropriate standards of good practice and
local codes and regulations. Wiring must be suitable for Voltage,
Current and temperature rating of the system.
o Provide power from a single-phase instrument power supply. If there
is a lot of noise in the power line, insert an insulating transformer into
the primary side of the line and use a line filter on the secondary side.
Do not place the primary and secondary power cables close to each
other.
o For thermocouple input, use shielded compensating lead wires for
wiring. For RTD input, use shielded wires that have low conductor
resistance and cause no significant differences in resistance between
the three wires. Do not connect Terminal Number – 3, 6,9,12 when
thermocouple or linear input is selected.
o Use repeater after each set of 32 instruments connected in RS-485
Communication.
o Unused terminals should not be used as jumper points as they may be
internally connected, which may cause damage to the unit.
CAUTION:
High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves. Through the internal contacts, these transients may introduce disturbances which could affect the performance of the instrument. For this type of load it is highly recommended that a “snubber” is connected across the normally open contact of the relay switching though load. The snubber recommended consists of a series connected resistor/capacitor (typically 15nF/100 Ohms). A snubber will also prolong the life of the relay contacts. A snubber should also be connected across the output of a trip output to prevent false triggering under line transient conditions.
User‟s Manual - 7 -
4-CHANNEL SCANNER-8204
Ty p e
Ra n ge
Ac c ur a cy
Re s ol u ti o n
E
-2 0 0 t o 1 000 C
+0.1% of instrument range + 1 digit for temperature equal to or higher than 0º C + 0.25% of instrument range + 1 digit for temperature below 0º C
+0.25% of instrument range + 1 digit(B,R,S TYPE TC)
0.1 C
(1 C B ,R , S TY P E T C)
J
-2 0 0 t o 1 200 C
K
-2 0 0 t o 1 370 C
T
-2 0 0 t o 4 00 C
B
45 0 t o 18 00 C
R
0 t o 1 750 C
S
0 t o 1 750 C
N
-2 0 0 t o 1 300 °C
RT D
-1 9 9.9 t o 85 0 .0 C
+ 0 .1 % o f in str u m e nt ran ge + 1 d i gi t
0 t o 7 5mV
-1 9 99 to 999 9
+ 0 .1 % o f in str u m e nt ran ge + 1 d i gi t
1 C ou n t
0 t o 1 00m v
0.4 t o 2V
0 t o 2 V
0- 2 0 m A*
4- 2 0 m A*
0 t o 5 V
1 t o 5 V
0 t o 1 0V
-1 0 t o 20mV
REF NO: m82/om/101
Issue NO: 09
3. Hardware Specification Detail:
Input type: Universal input type
Thermocouple, RTD, Millivolt, Voltage, Current INPUT types are software selectable.
Applicable Standards: DIN (ITS-90) for Thermocouple and RTD
*For DC current input, 100 Ohms (0.1%, 25 ppm) shunt resistor must be connected externally. For DC current and Voltage input, Scaling is possible and decimal point is selectable.
Sampling Period: 100mSec for TC and Linear Input, 200mSec for RTD Input.
Resolution: 17-bit
Burnout detection: Functions for TC, RTD, linear input signal. (It detects whether
sensor is connected or not) ALL Relay output can be selected for Burnout Condition. i.e. Open sensor Up scale or Down Scale
Measurement current (RTD): 1milli Ampere
User‟s Manual - 8 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
Input Impedance: >1 Mohm for thermocouple/ mV/RTD/Volts inputs
Noise Rejection Ratio:
NMRR (Normal mode rejection ratio) > 40 dB (50/60 Hz) or more CMRR (Common mode rejection ratio) > 120 dB (50/60 Hz) or more
Allowable wiring resistance for RTD: Maximum 15 ohms/wire (Conductor resistance between three wires should be equal).
Retransmission Output: (Optional)
Number of outputs: 1 Output signal: 0-20 mA, 4-20 mA, 0-5 V, 1-5 V or 0-10 V DC. Voltage or current output can be selected through software and internal jumper settings. Load resistance: 500 ohms Max. Or less for current output. 3k or higher for voltage output Output accuracy: ±0.25% of span
Relay Contact Outputs:
Number of outputs: 4 Output signal: Two terminals (NC/NO and C) (NC/NO is selectable by jumper setting) Relay Contact rating: 250 V AC or 30 V DC, 2A (resistive load)
Communication:
Communication Type: Half duplex/Asynchronous (RS-485) Communication Protocol: MODBUS RTU Baud rate, Parity and Stop bit are selectable form the key board. All parameters are Configurable through MODBUS.
Connectable number of unit: 32 Communication error Detection: CRC Check
Display Specifications:
PV display: 4-digits, 7-segment, Red LEDs, character height of 0.56‟‟ Channel No. Display: 1-digit, 7-segment, Green LEDs, character height of 0.56 St a tu s in di c ati ng l am p s: 4-Red LEDs for Relay status ,1-Red LED Manual mode status, 2-Red LEDS for Communication.
Power Supply Specifications:
Power supply: Rated voltage of 85 to 260V AC at 50/60 Hz, Rated Dc voltage 100 to 300VDC / Rated Voltage of 18V to 36V DC(Optional)
Power consumption: Max. <10 VA
Data backup: Non-volatile memory (can be written up to 100000 times) Withstanding Voltage:
Between primary terminals* and secondary terminals** at
least 1500VAC for 1 minute
Between secondary terminals at least 500V AC for 1 minute
User‟s Manual - 9 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
Insulation resistance: 20Mohms or more at 500V DC *P r im a ry te r min als in di c ate po w er te r mi n al s an d r ela y o u tp ut t er m in a ls ** S ec o nda ry te r min als in di cat e an al o g I /O sig nal s, Co m mu n ic a ti o n Si g na l s.
Signal Isolations Specifications:
PV input terminals (4 Channel input): Not isolated input terminals and from the internal circuit. But isolated from other input/output terminals. Retransmission output terminals (voltage/current): Not isolated from current or voltage outputs Isolated from other input/output terminals and internal circuit. Relay contact control output terminals: Isolated between contact output terminals and from other Input/output terminals and internal circuit. RS-485 Communication terminals: Isolated from other input/output terminals and internal circuit Power terminals: Isolated from other input/output terminals and internal circuit.
Construction, Installation, and Wiring:
Construction: Only the front panel is dust-proof Material: ABS resin and Polycarbonate Case color: Black
Weight: 0.4 kg or less
Dimensions: 48 (W) x 96 (H) x 130 (depth from panel face) mm. Installation: Panel-mounting type. With Top and Bottom mounting hardware (1 each) Panel cutout dimensions: 46 x 92 mm FRONT BEZEL: 48 x 96 mm
Environmental Conditions:
TEMPCO: FOR DATA (4-channel input) less than 100ppm. FOR Retransmission(Optional) less than 150ppm. Humidity: 30% to 95% RH (Non-Condensing) Instrument Warm-up Time: 30 minutes or more after power on Ambient temperature: 0 to 55°C
User‟s Manual - 10 -
4-CHANNEL SCANNER-8204
Name of Part
Function
Process Value Display(DATA window)
Displays Process Value. Display Parameter Name When You Set Parameter. Displays Error Message When An Error Occurs.
Channel No. Display
(CHANNEL window)
Displays Channel Number in run mode. Also it will display relay number (01 – 04) in set mode (i.e.R.1,R.2,R.3,R.4) It will also display Group no(GP 1,GP 2/GP 1,GP 2,GP 3,GP 4) in set mode
Relay Indicator LED
(RL1, RL2, RL3, & RL4)
OR
Open Sensor Indicator LED
When Respective Relay LED Lits (In Red). OR When Channel is OPEN(Channel no. is corresponding to Relay no.)
Auto/Manual Indicator LED (A/M)
If LED is on, it indicates Manual mode and if LED is off Auto Mode.
Communication Indicator LEDs(Rx,Tx)
When Communication on, two LEDs (In Red) blink.
REF NO: m82/om/101
Issue NO: 09
4. Front and Back Panel Description:
FRONT PANEL
User‟s Manual - 11 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
BACK PLATE CONNECTION DETAIL:
User‟s Manual - 12 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
5. Key Function Description:
MENU/ENTER KEY:
It is used to enter in the sub menu (various levels) and save the parameters to nonvolatile memory, when user setting a proper data by Increment and shift key for parameter configuration.
ESCAPE KEY:
It is used to come out from any sub menu (various levels) to the run mode. It is used for come out of the manual mode to auto mode too.
INCREMENT KEY:
It is used to increment the parameter for selection. Value of parameter can be incremented by pressing this key. When first time increment key is pressed, DP (decimal point) in PV display blink, so user can modify the value with increment key. It is used to increment the value in particular digit. Value can be incremented from 0- 9 and from „9‟ again it rollovers to „0‟. The function Auto/Manual is integrated with this key. This key is used to enter into manual mode while the unit is in run mode.
SHIFT KEY/DECREMENT KEY:
It is used to Shift the digit to set the parameter as describe in increment key when DP (decimal point) started to blink. Menu key is used to go forward to show next parameter and Shift key is used to go backward to show previous parameter.
User‟s Manual - 13 -
4-CHANNEL SCANNER-8204
LE V EL 1
Parameter (DATA window)
Set ti n g n am e an d de s cr i pt i on
De f au l t val ue
Sh o ws onl y i f
Symbol
Name
pwd
(PWD)
Le v el-1 P a ss w or d
0 t o 9 999
0000
-
Sp.1
(SP.1)
Ta r get S e t p oin t- 1
Set Poi nt - 1 f or Ch a nn e l 1 t o 4 .
0100 ( for al l 4 cha nn e ls )
-
SP.2
(SP.2)
Ta r get S e t p oin t- 2
Set Poi nt - 2 f or Ch a nn e l 1 t o 4 .
01 50 ( fo r al l 4 cha nn e ls )
Rel ay gr o up 2 is se l ect ed
SP.3
(SP.3)
Ta r get S e t p oin t- 3
Set Poi nt - 3 f or Ch a nn e l 1 t o 4 .
02 00( fo r al l 4 cha nn e ls)
Rel ay gr o up 1 is se l ect ed
SP.4
(SP.4)
Ta r get S e t p oin t- 4
Set Poi nt - 4 f or Ch a nn e l 1 t o 4 .
02 50( fo r al l 4 cha nn e ls)
Rel ay gr o up 1 is se l ect ed
Hys
(HYS)
Hy s tr e si s
Hy s tr e si s f o r C han ne l 1 to 4.
00 02 ( fo r al l 4 cha nn e ls )
-
REF NO: m82/om/101
Issue NO: 09
6. Menu Layout:
RUN TIME INDICATION:
Following parameters can view or change during run time.
Immediately after powering, unit will run in Auto Mode. In auto
mode channel will scan automatically according to scan time selection (1-250 second).
By pressing INCREMENT Key in run mode, Channel number
scanning on display is stopped. By pressing increment key again, we can change channel number manually.
By pressing SHIFT/DECREMENT Key in run mode, relay
acknowledgement can be done.
By pressing ESCAPE Key after going into the Manual Mode unit
comes back to run mode.
Le v el – 1:-
Pressing MENU key DATA window shows LVL1 (LvL1) message. Press MENU key again DATA window shows pWd (PWD) message, press increment key twice to select password and then press MENU key to enter into Level-1. DATA window shows SP.1 (SP.1) message and by pressing increment key, DATA window shows Set Point-1 Value. Use INC and SHIFT key to modify value. OR press MENU key again to change Set-point 1 for Channel 2. ESCAPE KEY is used to come out SP.1
User‟s Manual - 14 -
4-CHANNEL SCANNER-8204
LE V EL 2:
Pa r am e te r (D A TA Wi n do w )
Set ti n g n am e an d de s cr i pt i on
De f au l t val ue
Sh o ws onl y i f
Symbol
Name
pwd
(PWD)
Le v el - 2 Pa s sw o rd
0 t o 9 999
0000
-
inpt
(inP.t)
PV Inp ut Typ e (E , J, K , T Etc . )
Fol lo w T a bl e 3 ( In p ut typ e f or 1- 4 ch an n el )
K- TC(f o r al l 4 cha nn e l)
-
Pv.hi
(PV.HI)
Pr o ce s s v alu e ran ge hig h se t ti n g (P V hi gh > PV lo w )
Ra n ge of th e se n so r /- 1 99 9 t o 9 9 99 (f o r l in e ar inp ut typ es) (1-4 Ch a nn el)
1370(f or al l 4 cha nn e l)
-
Pv.lo
(PV.LO)
Proc ess va l ue ran ge lo w er se t ti n g
Ra n ge of th e se n so r /- 1 99 9 t o 9 9 99 (f o r l in e ar inp ut typ es) (1-4 Ch a nn el)
-200( for al l 4 cha nn e l)
-
dp
(dP)
De c ima l P oi n t Set ti n g O nl y ap p li c abl e f or Li n ea r i n put ty p e is sel ect ed
0 t o 3 (1 – 4 Ch a nn e l)
0( f or al l 4 cha nn e l)
-
Rl.lg
(rL.LG)
Rel ay Lo g ic ( Ap p li c abl e fo r 4 - RE L AY )
nl / fs (Normal / Fail Safe) 0: N ora ml 1:Fa i l S af e
No r mal (f o r al l 4 Rel ay )
-
Rl.oP
(rL.oP)
Rel ay Op e rat ion
Al / Co (Alarm / Control Output) 0: A la r m 1: Control Output
Al a rm
-
Rl.fn
(rL.Fn)
Rel ay Fu n cti on ( Ap p li c a bl e f o r 4 -R E LA Y )
AL / TR (Alarm / Trip ) 0: A LAR M 1: T RIP
Al a rm( fo r al l 4 Rel ay )
Rl.oP
is set to Al
Rl.dl
(rL.dL)
Rel ay De l ay ( Ap p li cabl e fo r 4 - RE L AY )
1 t o 9 9 s ec o nd s
1 se c on d (f o r al l 4 Rel ay )
-
Rl.o.s
(rL.o.S)
Rel ay Op e n se n so r (A p pl i cab le fo r 4 - RE L AY )
up / Dn (UP / Down) 0: D OW N 1: U P
Up Sca le ( fo r al l 4 Rel ay )
-
REF NO: m82/om/101
Issue NO: 09
LE V EL 2: -
Pressing MENU key DATA window shows LvL2 (LvL2) message. Press MENU key again DATA window shows pwd (PWD) message, press increment key twice to select password and then press MENU key to enter into Level-2. Following parameters can be configured in LEVEL – 2.
User‟s Manual - 15 -
4-CHANNEL SCANNER-8204
Rl.mp
(rl.mp)
Rel ay ma p pi n g (A p pl i cab le for 1
-4 Ch a nn e l)
Se e R e la y Co n fi g ura tio n
Re f er No t e: 3
Rl.oP
is set to Al
Rl.tp
(rl.tp)
Rel ay Gr o up Ty p e
Se e R e la y Co n fi g ura tio n
Re f er No t e:2
-
CHANNEL NO
NONE
G-1 1  2
3
4
Relay Group
Relay Type
G - 1
Low ON (L) or High ON (H)
CHANNEL NO
NONE
G-1
G-2 1  2
3
4
Relay Group
Relay Type
G – 1
High/ Very High (H-VH) or Very Low /Low (VL-L) or Low/High (L-H)
G – 2
High/ Very High (H-VH) or Very Low /Low (VL-L) or Low/High (L-H)
REF NO: m82/om/101
Issue NO: 09
Relay Configuration:
Relay configuration depends on selection of Relay group i.e. Relay
group 1 or Relay group 2 or Relay group 4 in Level-3.
Relay Group - 1:
If relay group – 1 is selected, there will be only one group of relay. That group has four relays. (G-1).
G-1 means RELAY 1 and RELAY 2 and RELAY 3 and RELAY 4
Example:
Note 1:
1) None means no group is selected for particular channel.
Relay Type can be selected as shown below:
Relay Group - 2:
If relay group – 2 is selected, there will be two group of relay. Each group has two relays. (G-1 and G-2).
G-1 means RELAY 1 and RELAY 3 G-2 means RELAY 2 and RELAY 4
Example:
Note 2:
2) All Groups can not be selected for single Channel .
3) None means no group is selected for particular channel.
Relay Type can be selected as shown below:
User‟s Manual - 16 -
4-CHANNEL SCANNER-8204
CHANNEL NO
NONE
G -1
G -2
G -3
G -4 1 
2
3
 4
CHANNEL NO
NONE
G -1
G -2
G -3
G -4
1
2
 3
4
Relay Group
Relay Type
G - 1
Low ON (L) or High ON (H)
G - 2
Low ON (L) or High ON (H)
G - 3
Low ON (L) or High ON (H)
G - 4
Low ON (L) or High ON (H)
Relay Group
Relay Type
G - 1
Low ON (L) or High ON (H)
G - 2
G - 3
G - 4
REF NO: m82/om/101
Issue NO: 09
Relay Group - 4:
If relay group – 4 is selected, there will be four group of all 4 relays. Each group has one relay. (G -1, G -2, G -3 and G -4).
G -1 means RELAY 1 G -2 means RELAY 2 G -3 means RELAY 3 G -4 means RELAY 4
Example:
Relay Type can be selected as shown below:
Note 3:
1) More than one Group can not be selected for single Channel .
2) None means no group is selected for particular Channel.
3) If rL.oP is set to Co then All relay will be assigned channelwise.
Whenever rL.oP is set to Co then All relay will be assigned channelwise and all assignments are remain fixed. And Relay type
Example:
Relay Type can be selected as shown below:
For relay functionality Refer Relay outputs (Chapter – 8).
User‟s Manual - 17 -
4-CHANNEL SCANNER-8204
LEVEL 3:
Parameter (DATA Window)
Set ti n g n am e an d de s cr i pt i on
De f au l t
val ue
Sh o ws onl y i f
Symbol
Name
pwd
(PWD)
Le v el - 3 Pa s sw o rd
0 t o 9 999
0000
-
Skip
(skip)
Ch a nn e l ski p/U ns k ip se l ect ion .
yes / no 0: N O 1: Y ES
0( f or al l 4 cha nn e l
-
Rl.lH
(rL.LH)
Rel ay Lat ch
on / off 0: O FF 1: O N
0
Rl.oP
is set to Al
Rl.Gp
(rL.GP)
Rel ay Gr o up
RGP.4 / rGP.2 0: R el a y G rou p- 4 1: R el a y G rou p- 2 2: R el a y G rou p- 1
1
Rl.oP
is set to Al
SCAn
(SCAn)
Sca n T ime
1 t o 2 50 se c ond s
1
-
A.CJC\
(A.CJC)
Au t o c ol d ju n cti on( Onl y ap p li c abl e f or TC in put ty p e
yes / no 0: N O 1: Y ES
1
-
F.CJC
(F.CJC)
Fi x c o ld ju n cti on( Onl y ap p li c abl e f or TC in put ty p e
0.0 t o 60 .0 Deg C
0.0 D e g C
-
Sr.no
(Sr.no)
Un i t I D
1 t o 2 47
1
-
BAUd
(baud)
Co m mun ic a ti o n Bau d r at e
9 6 00 / 1 9. 2 K 0:( 960 0) – 9 60 0 b p s
1: ( 19 . 2K ) –1 9. 2 Kb ps
19 . 2k bp s
Pr.St
(Pr.St)
Pa r it y /St op bi t se l ect ion
p.n.S.1 / P.nS.2 / P.o.s1 / P.ES.1 0: ( P. N .S. 1) - pa r it y non e- s top bi t- 1 1: ( P. N .S. 2) - pa r it y non e - st op bit -2 2: ( P. O .S. 1)-p a ri ty o dd
-st op bi t -1 3: ( P. E .S . 1)- pa r it y ev e n - st op bi t -1
No pa r it y /S t op bi t
- 2
T.ouT
(t.out)
Ti m eou t f or di s pl a y b ack to Ru n M o de
10 to 100 S e con ds
60
-
REF NO: m82/om/101
Issue NO: 09
LEVEL – 3:
Pressing MENU key DATA window shows LvL3 (LvL3) message. Press MENU key again DATA window shows pwd (PWD) message, press increment key twice to select password and then press MENU key to enter into Level-3.Following parameters can be configured in LEVEL – 3.
User‟s Manual - 18 -
4-CHANNEL SCANNER-8204
RT.o.S
(rt.o.s)
Ret ras mi s si o n Op e n s ens or
up / DoWn 0: D OW N 1: U P
1
-
Rt.tp
(rt.tp)
Ret ra n smi ss i on Out pu t T y pe
0-20/4-20/ 0-5v/1-5v/ 0-10v
0: ( 0-2 0) – 0 -2 0 mA 1: ( 4-2 0) – 4 -2 0 mA 2: ( 0 - 5 ) – 0 – 5 vo l t 3: ( 1 - 5 ) – 1 – 5 vo l t 4: ( 0 – 10 ) - 0 -1 0vo l t
1
-
Rt.dr
(rt.dr)
Ret ran smi ssi on di r ect ion
Dir / rev 0: (r e v) 1: ( di r )
1
-
Rt.CH
(rt.CH)
Ret ran sm i ss i on Ch a nn e l
1 t o 4 ch ann el
1
-
Rt.rd
(rt.rd)
Ret ran smi ssi on Ch a nn e l V al u e
MAx / Min / avg 0: (Mi n) 1: ( M ax ) 2: (Av g)
1
-
S.Pwd
(S.PWD)
Pa s sw o rd Set p a ss w ord t o lo c k s el e ct e d l ev e l
0 t o 9 999 0
-
Ca l ib r at i on :
Parameter (DATA Window)
Set ti n g n am e an d de s cr i pt i on
De f au l t val ue
Sh o ws onl y if
Symbol
Name
pwd
(PWD)
Pa s sw o rd
0 t o 9 999
0000
-
amb
(Amb)
Am b ien t
Am b ien t a dju stm ent
-
-
CAL.Z
(CAL.Z)
Th e rm o co u pl e , Rtd a n d L in e ar Ze r o Cal ib t ri a on
De p end in g on PV se n so r t y pe sel ect ed
-
-
CAL.S
(CAL.S)
Th e rm o co u pl e , Rtd an d L i ne a r Sp a n Cal ib t ri a on
De p end in g on PV se n so r t y pe sel ect ed
-
-
Rtr.Z
(rtr.Z)
Ret ran smi ssi on vo l ta g e a nd cu r ren t Z er o cal ib r ati on
De p end in g on Ret ras mi s si o n t yp e se l ect ed
-
-
REF NO: m82/om/101
Issue NO: 09
Ca l ib r at i on : -
Pressing MENU key, DATA window shows CAL (CAL) message. Press MENU key again, DATA window shows pwd (PWD) message, press increment key twice to select password and then press MENU key to enter into Calibration.
User‟s Manual - 19 -
4-CHANNEL SCANNER-8204
Rtr.S
(rtr.S)
Ret ran smi ssi on vo l ta g e a nd cu r ren t S pa n cal ib r ati on
De p end in g on Ret ras mi s si o n t yp e se l ect ed
-
-
Fa c to r y R es e t M od e :
Parameter (DATA window)
Set ti n g n am e an d de s cr i pt i on
De f au l t val ue
Sh o ws onl y if
Symbol
Name
Pwd
(Pwd)
Pa s sw o rd
0 t o 9 999
-
-
L.def
(L.dEF)
LO A D D ef a ul t
C A L\P A R A \ a l l (C A L) \ (P A RA ) \( A LL ) CA L - O nl y c a li bra t io n se t t o d e fau lt val ue PA R A- Al l p a ra m et e rs ex c lud in g ca li b rat i on wi l l s et to def a ul t val ue AL L -C a li brat ion an d pa r am e te r s w il l se t t o de f aul t v alu e
-
-
REF NO: m82/om/101
Issue NO: 09
Fa c to r y R es e t P ar a met er s :
Pressing MENU key, DATA window shows F.RST (F.rST) message. Press MENU key again, DATA window shows pwd (PWD) message, press Increment key twice to select password and then press MENU key to enter into Factory Reset.
Note: - Factory reset will load default parameters, as mention in MENU LAYOT (Default value). Once this function applies, user has to switch off the instrument and again switch on the instrument to work according to Default value.
User‟s Manual - 20 -
4-CHANNEL SCANNER-8204
Ty p e
I/ P
NO
Ty p e
Di s pl a y
Ra n ge
Re s ol u ti o n
E
1
E Tc
-2 0 0 t o 1000 C
0.1 °C
J
2
J tc
-2 0 0 t o 1200 C
K
3
K tc
-200 t o 1370 C
T
4
T tc
-2 0 0 t o 4 00 C
B
5
B tc
45 0 t o 18 00 C
R
6
R tc
0 t o 1 750 °C
S
7
S tc
0 t o 1 750 C
N
8
n tc
-200 t o
13 0 0°C
RT D
9
RTD
-1 9 9. 9 t o 85 0 .0 C
-1 0 t o 20mV
10
-10.20
-1 9 99 to
9999 C oun ts
1 C ou n t
0 t o 7 5mv
11
0-75
0 t o
10 0 mV
12
0-100
0.4 t o 2V
13
0.4-2
0 t o 2 V
14
0-2V
4 t o
20mAm p
15
4-20
0 t o
20mAmp
16
0-20
0 t o 5 V
17
0-5V
1 t o 5 V
18
1-5V
0 t o 1 0V
19
0-10V
REF NO: m82/om/101
Issue NO: 09
INPUT TYPE SELECTION TABLE:
Table 3:
User‟s Manual - 21 -
PV
Display
Run Mode
LVL1
pwd
00021
0000
0000
SP 1
SP 2
Hys
00021
00031
00031
00022 00023 00024
00031 00131
00131
Above setting is applicable to
ALL channels
01501 2 3 4
01001 01002 01003 01004
00021
Move to Next Page
How to set/change
different values to
different channels is
shown below . “see
Hys settings”
SP 3
SP 4 02501 2 3 4
02001 2 3 4
0150 0150 0150
0200 0200 0200
0250 0250 0250
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
7. Parameter FLOW CHART:
4 Channel Scanner-8204 has a number of software parameters which may or may not be required depending on your particular applications.
User‟s Manual - 22 -
LVL2
pwd
0000
0000
inPt
PvHi
PvLo
dP
rLFn
rLdL
rLoS
rLLG
rLmP
rLtP
LVL3
pwd
0000
0000
SkiP
rLLH
rLGP
SCAn
FCJC
Srno
bAud
ACJC
PrSt
tout
rtos
rttP
rtdr
rtCH
A
A
rtrd
SPwd
CAL
pwd
0000
0000
Amb
CALZ
CALS
rtrZ
rtrS
Procedure for changing/setting
different values to different channels
in all levels is shown in the level 1
Hysteresis setting. “see Hys settings”
Move to
Next Page.
rLoP
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
User‟s Manual - 23 -
4-CHANNEL SCANNER-8204
FrSt
pwd
0000
0000
LdEF
CLAL
CLAL
PArA
ALL
Procedure for changing/setting
different values to different channels
in all levels is shown in the level 1
Hysteresis setting. “see Hys settings”
REF NO: m82/om/101
Issue NO: 09
User‟s Manual - 24 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
8. Relay Outputs:
Following function can be set for Relay outputs.
Relay Logic (Direction):
Relay Logic means Relay contact can be changed from Open to Close OR Close to Open. If relay logic is selected Normal, when Fault occur Relay contact will change from Close to Open. If relay logic is selected Fail Safe, when Fault occur Relay contact will change from Open to Close.
Relay Function: Relay function can be selected as ALARM or TRIP. If relay is selected as ALARM, when abnormal condition occur Relay will ON, once normal condition after abnormal condition occur Relay will OFF. If relay is selected as TRIP, when abnormal condition occur Relay will ON, once normal condition after abnormal condition occur Relay will ON. Relay will be off through Acknowledge.
Relay Delay: A time delay can be provided for the actual output.
Relay Open Sensor:
Open sensor up scale or down scale can be selected for each relay output.
Relay Mapping:
Refer Menu layout LEVEL - 2
Relay Types: Various relay operations are shown in the reference figure. (High, Low, Very High- High, Low-Very Low, High- Low) For relay types selection Refer Menu layout LEVEL – 2.
User‟s Manual - 25 -
4-CHANNEL SCANNER-8204
ALARM 1 MOMEMTARY ALARM (when in abnormal condition ack not pressed)
CONDITION
NORMAL
ABNORMAL
UP (O/S)
DOWN (O/S)
ACK **
NORMAL *
ACK ***
HIGH
ALARM
LATCH YES
LAMP
OFF
STEADY
STEADY
OFF STEADY
OFF
RELAY
OFF
ON
ON
OFF OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
STEADY
OFF OFF
OFF
RELAY
OFF
ON
ON
OFF OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
OFF
LOW
ALARM
LATCH YES
LAMP
OFF
STEADY
OFF
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF
ON OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
OFF
STEADY
OFF
OFF
RELAY
OFF
ON
OFF
ON OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
OFF
VLOW
ALARM
LATCH YES
LAMP
OFF
STEADY
OFF
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF
ON OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
OFF
STEADY
OFF
OFF
RELAY
OFF
ON
OFF
ON OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
OFF
ALARM AL2 MOMEMTARY ALARM (when in abnormal condition ack not pressed)
CONDITION
NORMAL
ABNORMAL
UP (O/S)
DOWN (O/S)
ACK **
NORMAL *
ACK ***
VHIGH
ALARM
LATCH YES
LAMP
OFF
STEADY
STEADY
OFF STEADY
OFF
RELAY
OFF
ON
ON
OFF OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
STEADY
OFF OFF
OFF
RELAY
OFF
ON
ON
OFF OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
OFF
HIGH
ALARM
LATCH YES
LAMP
OFF
STEADY
STEADY
OFF STEADY
OFF
RELAY
OFF
ON
ON
OFF OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
STEADY
OFF OFF
OFF
RELAY
OFF
ON
ON
OFF OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
OFF
LOW
ALARM
LATCH YES
LAMP
OFF
STEADY
OFF
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF
ON OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
OFF
STEADY
OFF
OFF
RELAY
OFF
ON
OFF
ON OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
OFF
REF NO: m82/om/101
Issue NO: 09
Relay logic table:
User‟s Manual - 26 -
4-CHANNEL SCANNER-8204
ALARM AL1 MAINTAINED ALARM (when in abnormal condition ack is pressed)
CONDITION
NORMAL
ABNORMAL
UP (O/S)
DOWN (O/S)
ACK **
NORMAL *
ACK ***
HIGH
ALARM
LATCH YES
LAMP
OFF
STEADY
STEADY
OFF
STEADY
STEADY
OFF
RELAY
OFF
ON
ON
OFF
OFF
OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
STEADY
OFF
STEADY
OFF
OFF
RELAY
OFF
ON
ON
OFF
OFF
OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
ON
OFF
LOW
ALARM
LATCH YES
LAMP
OFF
STEADY
OFF
STEADY
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF
ON
OFF
OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
OFF
STEADY
STEADY
OFF
OFF
RELAY
OFF
ON
OFF
ON
OFF
OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
ON
OFF
VLOW
ALARM
LATCH YES
LAMP
OFF
STEADY
OFF
STEADY
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF
ON
OFF
OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
OFF
STEADY
STEADY
OFF
OFF
RELAY
OFF
ON
OFF
ON
OFF
OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
ON
OFF
ALARM AL2 MAINTAINED ALARM (when in abnormal condition ack is pressed)
CONDITION
NORMAL
ABNORMAL
UP (O/S)
DOWN (O/S)
ACK **
NORMAL *
ACK ***
VHIGH
ALARM
LATCH YES
LAMP
OFF
STEADY
STEADY
OFF
STEADY
STEADY
OFF
RELAY
OFF
ON
ON
OFF
OFF
OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
STEADY
OFF
STEADY
OFF
OFF
RELAY
OFF
ON
ON
OFF
OFF
OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
ON
OFF
HIGH
ALARM
LATCH YES
LAMP
OFF
STEADY
STEADY
OFF
STEADY
STEADY
OFF
RELAY
OFF
ON
ON
OFF
OFF
OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
STEADY
OFF
STEADY
OFF
OFF
RELAY
OFF
ON
ON
OFF
OFF
OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
ON
OFF
LOW
ALARM
LATCH YES
LAMP
OFF
STEADY
OFF
STEADY
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF
ON
OFF
OFF
OFF
ALARM
LATCH NO
LAMP
OFF
STEADY
OFF
STEADY
STEADY
OFF
OFF
RELAY
OFF
ON
OFF
ON
OFF
OFF
OFF
TRIP LAMP
OFF
STEADY
OFF****
OFF****
STEADY
STEADY
OFF
RELAY
OFF
ON
OFF****
OFF****
ON
ON
OFF
REF NO: m82/om/101
Issue NO: 09
User‟s Manual - 27 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
NOTE:
* means normal condition after abnormal has occurred ** means ack pressed in abnormal condition *** means ack pressed in normal condition after abnormal has already occurred. **** means it remains in the previous state. If previous state is ON then it will remain ON and the same case for OFF condition.
All Lamp status can only be viewed into PC software.
Pressing Shift/Decrement key for 3 seconds, acknowledgement will be given for alarm and trip relay in abnormal condition. Alarm Latch function applicable only for ALARM, there is no affect when TRIP Selected as a relay function LEVEL – 2.
Basic Relay Function:
RELAY GROUP - 4
User‟s Manual - 28 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
RELAY GROUP - 2
User‟s Manual - 29 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
RELAY GROUP - 1
User‟s Manual - 30 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
Control Output (ON/OFF Control ) :-
ON/OFF Controller is the simplest form of temperature control device. The output from the device is either on or off, with no middle state. An on-off controller will switch the output only when the temperature crosses the set point. For heating control, the output is on when the temperature is below the set point, and off above set point.Since the temperature crosses the set point to change the output stage, the process temperature will be cycling continually, going from below set point to above, and back below. In cases where this cycling occurs rapidly, and to prevent contactors and valves from getting damaged, an on-off differential, or “hysteresis,” is added to the controller operations. This hysteresis assures, if temperature exceed set point by a certain amount before then only output will turn off or on again. On-Off hysteresis prevents the output from “chattering” or making fast, continual switches if the cycling above and below the set point occurs very rapidly.
Relay type High (H-ON): For High type of set value, once process value reaches up to set point + Hysteresis value, relay will be ON after few seconds (as per relay delay) and it will be ON until process value goes down to Set point.
Relay type Low (L-ON): For Low type of set value, once process value reaches down to set point - Hysteresis value relay will be ON after nearly few seconds (as per relay delay) and it will be ON until process value goes up toward Set point.
NOTE:-
8204 has both Control Logic (ON-OFF) & Alarm Logic. If Control Logic (ON­OFF) is required, rloP in lvl2 must be selected as Co. Whenever Control Output(ON-OFF) logic is selected , all relays are mapped
as shown in chapter no.6. As well as, relay latch is off and relay group is assigned as relay per group 1. In this logic, user cannot change relay mapping, relay latch and relay group and user cannot acknowledge relays.
User‟s Manual - 31 -
4-CHANNEL SCANNER-8204 REF NO: m82/om/101
Issue NO: 09
9. Calibration Procedure:-
Calibration is provided for ambient temperature, PV sensor input, Retransmission output. First select the calibration function as described below and then follow the procedure depending on the parameter to be calibrated. The sequences of parameters that will be available for calibration are listed below:
Ambient temperature adjustment PV Sensor input Retransmission output (calibration for voltage or current)
Ambient temperature adjustment:-
DATA window shows Amb (Ambient temperature adjusts). If Increment Key is pressed, DATA window shows, temperature measured by the controller and by applying old calibration data. DP of last digit will blink to indicate that the value can be changed. Use Inc/Shift key to adjust it to desired value. Once the desired value set and press MENU key, the blinking DP will go off to indicate that the value has been registered. The controller will automatically save all the new calculations. Ambient temperature adjustment is over. Press MENU key to calibrate other parameters or press Escape key to come out to normal operation.
PV input sensor calibration:-
When user enters in calibration menu, DATA window shows CAL.Z (Calibration ZERO) for sensor input zero calibration for Thermocouple Linear input and RTD type. Press Increment Key, DATA window shows as per the Input feed. Feed sensor input using a calibrator, such that process value is close to lower range value.
Note: The controller allows the user to calibrate sensor‟s input anywhere in the range, but it is recommended that it should be calibrate the input at points close to lower and upper range values.
DP of last digit will blink to indicate that the value can be changed. Use Inc/Shift key to correct the displayed reading to the desired process value and press MENU key. The controller will display message wait (wait) in the DATA window to indicate that it is doing the necessary calculations. When the calculations are over, the new calibration values are stored automatically. So, Zero calibration is over. Press MENU key to calibrate other parameters or press Escape key to come out to normal operation.
DATA window shows the CAL.S (calibration SPAN) for sensor input span calibration for Thermocouple Linear input and RTD type. Press Increment Key, DATA window shows as per the Input feed. Feed sensor input using a calibrator, such that process value is close to sensor‟s upper range value. Use Inc/Shift key to arrive at the desired process value. Press MENU key to register the changes. The controller will display message wait (wait) in the DATA window to indicate that it is doing the necessary calculations. Depending on the situation, this process may take few seconds to calibrate. Zero and Span calibration is over.
User‟s Manual - 32 -
4-CHANNEL SCANNER-8204
Group
NO
Input type
Calibration for input
1
E,J,K,T,N,0-
75mv,0-100mv
Either of any input
2
Pt-100(RTD)
Specific input
3
B,R,S,-10 to 20mv
Either of any input
4
0-2V,0.4-2V,4-
20mAmp,0-
20mAmp
Either of any input
5
0-10V,0-5v,1-5V
Either of any input
REF NO: m82/om/101
Issue NO: 09
In case, the controller cannot complete the calibration due to any reason, it will hold previous calibration parameters. Calibration for input sensor is over.
Retransmission output calibration (Voltage/current output) (Optional):-
Press MENU key repeatedly, till DATA window shows message rtr.Z (retransmission output zero calibration). DATA window shows the value being outputted on Retransmission output terminals. Measure the value using a highly accurate digital multi meter. Use Inc/Shift key to change measured value observed in multi meter on DATA window. Press MENU key. The controller will store zero calibration value. Press MENU key to calibrate retransmission output span calibration menu. DATA window shows the message rtr.S (retransmission output span calibration). DATA window shows the value being outputted on retransmission output terminals. Measure the value using a highly accurate digital multi meter. Use Inc/Shift key to change measured value observed in multi meter on DATA window. Press MENU key. When the calculations are over, the new calibration values are stored automatically. Calibration for Retransmission output is over. Press Escape key to come out to normal operation.
Group Calibration Detail:-
NOTE:
If you calibrate any input from any group i.e. I/P E-TC from Group – 1 than calibration is not required for other input types from Group-1.
User‟s Manual - 33 -
4-CHANNEL SCANNER-8204
CODE
NAME
Function
01
Write Coil Status
Use to write output and input status
03
Read Holding registers
Use to read PV for 4-channels
04
Read input registers
Use to read programmable registers
05
Force Single Coil
Use to set or reset the coil
06
Preset Single register
Use to write programmable register
SR. NO.
Parameter
Value
1
Open sensor
32767
2
Over reading
32766
3
Under reading
32765
4
Skip Channel
32764
CODE
NAME
Function
01
ILLEGAL FUNCTION
The function code received in the query is not an allowable action for the slave. If a Poll Program Complete command was issued, this code indicates that no program function preceded it.
02
ILLEGAL DATA ADDRESS
The data address received in the query is not an allowable address for the slave
03
ILLEGAL DATA VALUE
A value contained in the query data field is not an allowable value for the slave
06
Slave Device Busy
When Master device write some parameters to Slave device If slave device busy it will send 06 code to indicate slave device is busy.
SR.NO.
Parameter
Absolute Address
Parameter Type
Min Value
Max Value
Access Type
1
PV Channel - 1
30001
INT - - R 2
PV Channel – 2
30002
INT - - R 3
PV Channel – 3
30003
INT - - R 4
PV Channel – 4
30004
INT - - R 5
Ambient
30005
INT - -
R
REF NO: m82/om/101
Issue NO: 09
10. Communication:
The MODBUS Communications protocol as RS-485 interface module is installed. Only RTU mode is supported. Data is transmitted as 8-bit binary bytes with 1 start bit, 1/2 stop bit and optional parity checking (None, Even, Odd). Baud rate may be set to 9600 and 19200.
Function code use for Modbus:
Exception responses for Modbus:
Modbus Parameter Details for Holding Register:
Modbus values for OPEN, OVER, UNDER and SKIP Conditions:
User‟s Manual - 34 -
4-CHANNEL SCANNER-8204
SR. NO.
Parameter
Absolute Address
Parameter Type
Min Value
Max Value
Acces s Type
Refer Table
1
SP.1 CH – 1
40001
INT - -
R/W
T-1 2 SP.1 CH – 2
40002
INT - -
R/W
T-1 3 SP.1 CH – 3
40003
INT - -
R/W
T-1 4 SP.1 CH – 4
40004
INT - -
R/W
T-1 5 SP.2 CH- 1
40005
INT - -
R/W
T-1 6 SP.2 CH- 2
40006
INT - -
R/W
T-1 7 SP.2 CH- 3
40007
INT - -
R/W
T-1 8 SP.2 CH- 4
40008
INT - -
R/W
T-1
9
SP.3 CH- 1
40009
INT - -
R/W
T-1
10
SP.3 CH- 2
40010
INT - -
R/W
T-1
11
SP.3 CH- 3
40011
INT - -
R/W
T-1
12
SP.3 CH- 4
40012
INT - -
R/W
T-1
13
SP.4 CH- 1
40013
INT - -
R/W
T-1
14
SP.4 CH- 2
40014
INT - -
R/W
T-1
15
SP.4 CH- 3
40015
INT - -
R/W
T-1
16
SP.4 CH- 4
40016
INT - -
R/W
T-1
17
HYS CH – 1
40017
INT 1 250
R/W
18
HYS CH – 2
40018
INT 1 250
R/W
19
HYS CH – 3
40019
INT 1 250
R/W
20
HYS CH – 4
40020
INT 1 250
R/W
21
INPUT TYPE CH - 1
40021
INT - -
R/W
T-1
22
INPUT TYPE CH - 2
40022
INT - -
R/W
T-1
23
INPUT TYPE CH - 3
40023
INT - -
R/W
T-1
24
INPUT TYPE CH - 4
40024
INT - -
R/W
T-1
25
Range High CH - 1
40025
INT - -
R/W
T-1
26
Range High CH - 2
40026
INT - -
R/W
T-1
27
Range High CH - 3
40027
INT - -
R/W
T-1
28
Range High CH - 4
40028
INT - -
R/W
T-1
29
Range Low CH - 1
40029
INT - -
R/W
T-1
30
Range Low CH - 2
40030
INT - -
R/W
T-1
31
Range Low CH - 3
40031
INT - -
R/W
T-1
32
Range Low CH - 4
40032
INT - -
R/W
T-1
33
Decimal Point CH - 1
40033
INT 0 3
R/W
34
Decimal Point CH - 2
40034
INT 0 3
R/W
35
Decimal Point CH - 3
40035
INT 0 3
R/W
36
Decimal Point CH - 4
40036
INT 0 3
R/W
37
RLY-Logic.1
40037
INT 0 1
R/W
T-2
38
RLY-Logic.2
40038
INT 0 1
R/W
T-2
39
RLY-Logic.3
40039
INT 0 1
R/W
T-2
40
RLY-Logic.4
40040
INT 0 1
R/W
T-2
41
RLY-Operation
40041
INT 0 1
R/W
T-3
42
RLY-Function.1
40042
INT 0 1
R/W
T-4
43
RLY-Function.2
40043
INT 0 1
R/W
T-4
44
RLY-Function.3
40044
INT 0 1
R/W
T-4
45
RLY-Function.4
40045
INT 0 1
R/W
T-4
46
RLY-Delay.1
40046
INT 1 99
R/W
47
RLY-Delay.2
40047
INT 1 99
R/W
48
RLY-Delay.3
40048
INT 1 99
R/W
49
RLY-Delay.4
40049
INT 1 99
R/W
50
RLY-OpenSensor.1
40050
INT 0 1
R/W
T-5
51
RLY-OpenSensor.2
40051
INT 0 1
R/W
T-5
REF NO: m82/om/101
Issue NO: 09
Modbus Parameter Details for Input Register:
User‟s Manual - 35 -
4-CHANNEL SCANNER-8204
52
RLY-OpenSensor.3
40052
INT 0 1
R/W
T-5
53
RLY-OpenSensor.4
40053
INT 0 1
R/W
T-5
54
RLY-Map CH - 1
40054
INT 0 2/4
R/W
T-6/7/8
55
RLY-Map CH - 2
40055
INT 0 2/4
R/W
T-6/7/8
56
RLY-Map CH - 3
40056
INT 0 2/4
R/W
T-6/7/8
57
RLY-Map CH - 4
40057
INT 0 2/4
R/W
T-6/7/8
58
RLY-Type.1
40058
INT 0 2/4
R/W
T-9/10
59
RLY-Type.2
40059
INT 0 2/4
R/W
T-9/10
60
RLY-Type.3
40060
INT 0 2/4
R/W
T-9/10
61
RLY-Type.4
40061
INT 0 2/4
R/W
T-9/10
62
SKIP-Channel CH - 1
40062
INT 0 1
R/W
63
SKIP-Channel CH - 2
40063
INT 0 1
R/W
64
SKIP-Channel CH - 3
40064
INT 0 1
R/W
65
SKIP-Channel CH - 4
40065
INT 0 1
R/W
66
RLY Latch
40066
INT 0 1
R/W
T – 11
67
RLY Group
40067
INT 0 1
R/W
T – 12
68
Scan Rate
40068
INT 1 250
R/W
69
Auto CJC
40069
INT 0 1
R/W
70
Fix CJC
40070
INT 0 60.0
R/W
71
Machine ID
40071
INT 1 247
R/W
72
Baud Rate
40072
INT 0 1
R/W
T- 13
73
Parity/Stop Bit
40073
INT 0 3
R/W
T -14
74
Timeout
40074
INT
10
60
R/W
75
PV Scale Retransmission
40075
INT 0 1
R/W
T -15 76
Retransmission Type
40076
INT 0 4
R/W
T-16
77
Retransmission Direction
40077
INT 0 1
R/W
T-17 78
Retransmission CH - 1
40078
INT 0 1
R/W
79
Retransmission CH - 2
40079
INT 0 1
R/W
80
Retransmission CH - 3
40080
INT 0 1
R/W
81
Retransmission CH - 4
40081
INT 0 1
R/W
82
Retransmission Value
40082
INT 0 2
R/W
T-18
83
Unused
40083
INT 1 4
R/W
84
Password
40084
INT 0 9999
R/W
Sr. No.
Parameter
Absolute Address
Parameter Type
Min Value
Max Value
Acces s Type
NOTE
1
Calibration Password
49001
INT 0 65000
W
2 Ambient Calibration
49002
INT - - W
3
Zero Calibration Channel-1
49003
INT - - W
4
Zero Calibration Channel-2
49004
INT - - W
5
Zero Calibration Channel-3
49005
INT - - W
6
Zero Calibration Channel-4
49006
INT - - W 7
Unused
49007
INT - - -
8
Unused
49008
INT - - -
9
Unused
49009
INT - - -
10
Unused
49010
INT - - -
11
Span Calibration Channel-1
49011
INT - - W
REF NO: m82/om/101
Issue NO: 09
User‟s Manual - 36 -
4-CHANNEL SCANNER-8204
12
Span Calibration Channel-2
49012
INT - - W
13
Span Calibration Channel-3
49013
INT - - W
14
Span Calibration Channel-4
49014
INT - - W 15
Unused
49015
INT - - -
16
Unused
49016
INT - - -
17
Unused
49017
INT - - -
18
Unused
49018
INT - - -
SR. NO.
Parameter
Absolute Address
Parameter Type
Access Type
1
Alarm.1 Channel-1
1
BIT R 2
Alarm.1 Channel-2
2
BIT
R
3
Alarm.1 Channel-3
3
BIT
R
4
Alarm.1 Channel-4
4
BIT R 5
Alarm.2 Channel-1
5
BIT
R
6
Alarm.2 Channel-2
6
BIT
R
7
Alarm.2 Channel-3
7
BIT R 8
Alarm.2 Channel-4
8
BIT
R
9
Alarm.3 Channel-1
9
BIT
R
10
Alarm.3 Channel-2
10
BIT R 11
Alarm.3 Channel-3
11
BIT R 12
Alarm.3 Channel-4
12
BIT R 13
Alarm.4 Channel-1
13
BIT R 14
Alarm.4 Channel-2
14
BIT R 15
Alarm.4 Channel-3
15
BIT R 16
Alarm.4 Channel-4
16
BIT R 17
RELAY STATUS-1
17
BIT R 18
RELAY STATUS-2
18
BIT R 19
RELAY STATUS-3
19
BIT R 20
RELAY STATUS-4
20
BIT R 21
Auto/Manual Mode
21
BIT
R/W
22
Acknowledge Status
22
BIT
W
23
Unused
- - -
24
Unused
- - -
REF NO: m82/om/101
Issue NO: 09
Modbus Parameter Details for Read Output Status Register:
NOTE: For Auto/Manual Mode, to set Manual mode bit value = 1 and to set Auto
mode bit value = 0.
User‟s Manual - 37 -
4-CHANNEL SCANNER-8204
Input Type
I/P no
Type Display
Zero
Span
Resolution
E
1
E tc
-200
1000
0.1°C
J
2
J tc
-200
1200
0.1°C
K
3
K tc
-200
1370
0.1°C
T
4
T tc
-200
400
0.1°C
B
5
B tc
450
1800
1°C
R
6
R tc
0
1750
1°C
S
7
S tc
0
1750
1°C
N
8
n tc
0
1300
0.1°C
RTD
9
RTD
-199.9
850.0
0.1°C
-10 to 20mv
10
-10.20
-1999
9999
1 Count
0-75mV
11
0-75
-1999
9999
0-100mV
12
0-100
-1999
9999
0 to 2V
13
0-2V
-1999
9999
0.4 to 2V
14
0.4-2V
-1999
9999
4 TO 20mAmp
15
4-20
-1999
9999
0 to 20 mAmp
16
0-20
-1999
9999 0-5V
17
0-5V
-1999
9999
1-5V
18
1-5V
-1999
9999
0-10V
19
0-10V
-1999
9999 Modbus Index
Parameter Value
0
Normal
1
Fail Safe
Modbus Index
Parameter Value
0
Alarm
1
Control Output
Modbus Index
Parameter Value
0
Alarm
1
Trip
Modbus Index
Parameter Value
0
None
1
G-1(RELAY – 1)
2
G-2(RELAY – 2)
3
G-3(RELAY – 3)
4
G-4(RELAY – 4)
Modbus Index
Parameter Value
0
Down
1
Up
Modbus Index
Parameter Value
0
None
1
G - 1(RELAY 1 & 3)
2
G – 2(RELAY 2 & 4)
Modbus Index
Parameter Value
0
None
1
G - 1(RELAY 1,2,3& 4)
REF NO: m82/om/101
Issue NO: 09
INPUT TYPE SELECTION TABLE :( T – 1)
Relay Logic (T – 2): Relay Operation (T – 3):
Relay Function (T – 4): Relay Group - 4 selections (T – 6):
Relay Open sensor (T – 5):
Relay Group 2 selections (T – 7):
Relay Group 1 selections(T-8):
User‟s Manual - 38 -
4-CHANNEL SCANNER-8204
Modbus Index
Parameter Value
0
Low ON
1
High ON
Modbus Index
Parameter Value
0
High/Very High
1
Low/Very Low
2
High/LOW
Modbus Index
Parameter Value
0
OFF
1
ON
Modbus Index
Parameter Value
0
Relay Per Group – 4
1
Relay Per Group – 2
Modbus Index
Parameter Value
0
Parity-None/Stop Bit - 1
1
Parity-None/Stop Bit - 2
2
Parity Odd/Stop Bit – 1
3
Parity Even/Stop Bit – 1
Modbus Index
Parameter Value
0
9600bps
1
19.2kpbs
Modbus Index
Parameter Value
0
Down
1
Up
Modbus Index
Parameter Value
0
0 – 20mAmp
1
4 – 20mAmp
2
0 – 5V
3
1 – 5V
4
0 – 10V
Modbus Index
Parameter Value
0
Reverse
1
Direct
Modbus Index
Parameter Value
0
Minimum
1
Maximum
2
Average
REF NO: m82/om/101
Issue NO: 09
Relay Type for Group – 4 and 1 (T - 9):
Relay Type for Group – 2(T – 10):
Relay Latch selection (T – 11): Relay Group Selection (T – 12):
Baud Rate for Communication (T – 13): Parity/Stop Bit Selection (T – 14):
Retransmission OPEN sensor (T – 15):
Retransmission Type (T – 16):
Retransmission Direction (T – 17):
Retransmission Value (T – 18):
User‟s Manual - 39 -
4-CHANNEL SCANNER-8204
Input type
Display Message
TC-E
OPEN(oPEn)
TC-J
OPEN
TC-K
OPEN
TC-T
OPEN
TC-N
OPEN
TC-B
OPEN
TC-R
OPEN
TC-S
OPEN
PT 100(RTD)
OPEN
0-10V DC
OPEN
0 to 5V DC
OPEN
1 to 5V DC
OPEN
0 to 2V DC
OPEN
0.4 to 2V DC
OPEN
0 to 20mAmp
PV LOW
4 to 20mAmp
PV LOW
-10 to 20mV DC
OPEN
0-100mV DC
OPEN
0-75mV DC
OPEN
REF NO: m82/om/101
Issue NO: 09
11. MISCELLANEOUS
PV INPUT STATUS DISPLAY DURING BURNOUT CONDITION:
Table 1
Note: If set PV_low/PV_high for input type is less then maximum value of zero and
span for then process value will display readings above 5% of display range, then after it will show oVER/UnDR (OVER/UNDER) message until value crosses maximum value of Sensor range. OVER/UNDER condition is applicable for TC and RTD input types only. Process value greater then maximum value of zero/span then display will show oPEn (OPEN) message. Retransmission o/p(Retransmission is optional) will follow 5% of display range and then it will give fixed o/p depending up on OPEN sensor selection. In case of linear inputs scaling is applied then during OPEN sensor condition it may not show oPEn (OPEN) message instead it will show either oVER/UnDR (OVER/UNDER).
User‟s Manual - 40 -
4-CHANNEL SCANNER-8204
RETRASMISSION
VARIABLE
SCALE
ACTION
OPEN
OVER
UNDER
ERROR
4-20mAmp
PV
UP
DIR
20.8
20.8
3.2
-
PV
DOWN
REV
20.8
3.2
20.8 -
PV
UP
REV
3.2
3.2
20.8
-
PV
DOWN
DIR
3.2
20.8
3.2
-
REF NO: m82/om/101
Issue NO: 09
RETRAMISSION OUTPUT TABLE FOR OPEN /OVER /UNDER CONDITION:
Table 2
NOTE: - 1) For Retransmission output type 0-20mAmp, 0-10v, 1-5v and 0-5v also
applicable according to above table.
2) Also, 0-20mAmp, 0-10v and 0-5v minimum output value will be 0mAmp and 0v respectively.
3) More than one channel can be selected for Retrasmission, but output depends on Maximum reading or Minimum reading or Average reading from the no of channel. Retrasmission output Maximum, Minimum and Average can be selected from Level-3.
User‟s Manual - 41 -