RESTRICTOR & EXPANSION DEVICES
* Restrictor change required - supplied loose in outdoor unit
** Heating expansion assembly - supplied loose in the indoor unit.
ELECTRICAL CONNECTIONS, CONTROLS and DATA
Mains, control and interconnecting cables must be supplied and fitted by the installer. Installer wiring must be carried out
in accordance with local and national codes. Cables must be size compatible with the recommended fuse for a given
system. An isolator switch should be positioned within easy reach of the unit.
If slave units are connected to a standard unit, isolation of any slave MUST
also isolate the standard unit.
The equipment MUST be earthed. Installers must supply a method of securing any solid sheathed cable.
DXD/H UNIT WIRING
Remove the electrics box cover (2 screws) and connect a suitably fused and isolated mains supply.
Site fitted controls should be connected as specified on the wiring diagram found on the inside face of the electric box
cover: typical wiring diagrams are shown on pages 5 and 6, but these are for reference only as many CWD units have a
unique configuration
ELECTRICAL DATA AND N.R.GUIDE
ELECTRICAL DATA
Input (watts) FLC (Amps) S.C. (Amps) Specific Fan Power
MODEL SPD
A’flow
(l/s)
AC EC/DC AC EC/DC AC EC/DC AC EC/DC
N.R.
GUIDE
1 160 93 53 0.57 0.46 1.71 1.38 0.58 0.33 35
2 170 98 62 0.59 0.53 1.77 1.59 0.58 0.36 37
DXD(H) 50
3 180 118 71 0.65 0.60 1.95 1.80 0.66 0.40 40
1 180 125 63 0.65 0.60 1.95 1.80 0.69 0.35 35
2 210 146 - 0.74 - 2.22 - 0.70 - 37
DXD(H) 60
3 225 177 - 0.80 - 2.40 - 0.79 - 40
1 310 196 83 1.18 0.80 3.54 2.40 0.63 0.27 35
2 360 236 112 1.30 1.13 3.90 3.39 0.66 0.31 37
DXD(H) 90
3 435 262 - 1.38 - 4.14 - 0.60 - 40
1 335 218 103 1.55 0.71 4.65 2.13 0.65 0.31 35
2 382 264 130 1.71 0.86 5.13 2.58 0.69 0.34 37
DXD(H) 130
3 462 294 184 1.77 1.21 5.31 3.63 0.64 0.40 40
1 425 290 140 2.08 0.91 6.24 2.73 0.68 0.33 35
2 477 330 179 2.20 1.06 6.60 3.18 0.69 0.38 37
DXD(H) 150
3 560 373 259 2.32 1.40 6.96 4.20 0.67 0.46 40
DXD DXDH MRC+ MHPUE
EXPANSION
ASSY
COOLING
RESTRICTOR
HEATING
RESTRICTOR
50 - 30 - 0.040 -
50 - 30 0.040 0.039
60 - 60 - 0.051 -
60 - 60
3/8”
0.055 0.053
90 - 90 0.063 -
- 90 - 90 0.067 0.058/
130 - 100 - 0.068 -
- 130 - 100 0.068 0.086**
130 - 130 - 0.071 -
- 130 - 130 0.076 0.086**
150 - 130 - 0.074* -
- 150 - 130
1/2”
0.080* 0.092**