This manual details technical, installation and operating information for the CD3 range (929 series)
DX indoor units for use in conjunction with 550 series CKC condensing units or 542 series DCU
ducted condensing units. Remove the expansion device from the outdoor condensing unit if the
CD3 unit has capillaries or expansion valves fitted.
INDEXL
GENERAL General description and part numbers 3
- DX upflow package units 3
- DX configured units 4
- Condensing units 4
- DX configurable accessories 5
Dimensions and weights 6
SELECTION Unit combinations 7
Performance data DX 7
Airflows 8
INSTALLATION Airflow options 9
APPLICATION Pipe sizing and application 16
Fuses 19
Fan speed controller 20
WIRING CD3 21
DIAGRAMS CKC 24
DCU 25
ACCESSORIES Condensate pump 27Humidifier 27
Auto change over 28
OPERATION pCONet Parameters 29
and Microprocessor control 33
COMMISSIONING
COMPONENT Exploded views of units with 42
IDENTIFICATION component identification
Condensate pump, including high
water level indication.
(hot or cold, 5m lift)
ALL
92919077
Floor stand plinth 75mm high
008
92911032
010, 015
92911033
020
92911034
Fresh air spigot 100mm dia.
ALL
92911062
Double deflection grille
008
92911094
Fresh air spigot 160mm dia.
ALL
92911063
010, 015
92911095
Fresh air fan and filter 93m
3
/h
ALL
92911003
020
92911096
Fresh air fan and filter 186m
3
/h
ALL
92911004
Disposable filter
(replaces washable filter)
008
92911038
Top ducted discharge spigot
008
92911059
010, 015
92911039
010, 015
92911060
020
92911040
020
92911061
Sound attenuation section
008
92911075
Master/slave, run/standby, duty assist and unit sequencing
are available using a pLAN network
010, 015
92911076
020
92911077
Changeover on alarm
ALL
92900820
3 phase to 1phase conversion
kit
008/2 + 50
92911125
Changeover on set time and/or alarm
ALL
92900821
008/2 + 30
92911126
Two circuit to single circuit pipe work
conversion kit
008
92911102
010/2 + 50
92911127
010
92911103
010/2 + 60
92911128
015
92911104
015/2 + 80
92911129
020
92911105
020/2 + 90
92911130
BACnet Controls
pCONET BMS BACnet
Control
ALL
92919134
USB to RS485 Connector
ALL
92919136
GENERALL
INTRODUCTION
The CD3 range of direct expansion units is designed to provide the close control of temperature and humidity demanded
by computer rooms, laboratories, banks, offices etc.. All units are fitted with programmable microprocessor controls.
CD3 indoor units are available in upflow or downflow configurations, matching with the Marsatair range of CKC and DCU
outdoor/ducted condensing units using R407C refrigerant. There is a range of 4 capacities in 3 cabinet sizes for both
upflow and downflow units. Packaged units are available in upflow versions only.
CD3-RANGE - GENERAL DESCRIPTION
DX UPFLOW PACKAGE UNITS
Twin circuit, packaged upflow units are normally supplied ex-stock. A field fit kit is available for converting from twin
circuit to single circuit if required.
PACKAGE UNITS INCLUDE:
* Electronically controlled fan speeds * Four pole mains isolator
* Class 'O' thermal and acoustic insulation * Microprocessor controls
* Washable filters * Display giving access to set points and alarms
* Discharge plenum and grille * Alarms: humidity/temperature out of limits
* Twin circuit coils * Switches: Off/standby, unit run
* Electric heating (2 stage) * De-ice thermostat
* Humidifier with modulating control * Dehumidification
KITS AVAILABLE FOR FIELD FITTING TO PACKAGE UNITS:
* Electronically controlled fan speeds * Microprocessor controls
* Class 'O' thermal and acoustic insulation * Display giving access to set points and alarms
* Washable filters * Alarms: humidity/temperature out of limits
* Discharge plenum and grille * Switches: Off/standby, unit run
* Single and twin circuit coils * Upflow and downflow units available
CKC CONDENSING UNITS (For use with R407C refrigerant)
CKC 30 and 40 units are fitted with reciprocating compressors. All other CKC units are fitted with scroll compressors.DCU DUCTED CONDENSING UNITS (for use with R407C)
All DCU units are fitted with reciprocating compressors.
STANDARD FEATURES AND OPTIONS, CKC, DCU
CKC = standard condensing unit + head pressure control + HP and LP switch and timers
DCU = electronic controlled ducted condensing unit + head pressure control + HP and LP switches and timers
4
92908135-17
Description
Model
Factory
Fitted
Part No.
Description
Model
Factory
Fitted
Part No.
THERMOSTATIC EXPANSION
VALVE
008/1
92900468
ALARMS
010/1
92900469
High water level
ALL
92919064
015/1
92900470
Water spillage indication (no pump)
ALL
92919067
020/1
92900471
Water spillage indication (with
pump)
ALL
92919066
008/2
92900472
Fan failure
ALL
92919069
010/2
Dirty filter indication
ALL
92919071
015/2
92900473
Condensing unit 1 trip
ALL
92919073
020/2
92900474
Condensing unit 2 trip
ALL
92919075
2kW
92919001
Common alarm (volt free relay)
ALL
92919056
ELECTRIC HEATERS - Upflow
4kW
92919002
008
92900456
Single stage
6kW
92919003
ISOLATOR 63A
010, 015
92900457
8kW
92919004
020
92900458
10kW
92919005
FRESH AIR SPIGOT 100mm
dia.
ALL
92900462
2kW
92919011
160mm
dia.
ALL
92900463
ELECTRIC HEATERS - Upflow
4kW
92919012
FRESH AIR FAN + FILTER
93m³/h
ALL
92900403
Second stage
6kW
92919013
186m³/h
ALL
92900404
8kW
92919014
TOP DUCTED DISCHARGE
SPIGOT (If used for return air on
downflow units add plenum for
disposable filter access)
008
92900459
10kW
92919015
010, 015
92900460
HEATER RAIL - Upflow
008
92919021
020
92900461
Required for all heater kits
010, 015
92919024
008U
92900475
020
92919026
SOUND ATTENUATOR SECTION
010/015U
92900476
2kW
92919006
020U
92900477
ELECTRIC HEATERS - Downflow
4kW
92919007
008U
92900432
Single stage
6kW
92919008
FLOOR STAND PLINTH
010015U
92900433
8kW
92919009
75mm high
020U
92900434
10kW
92919010
(Recommended for all floor
standing
008D
92900435
2kW
92919016
Units and for side entry of services)
010/015D
92900436
ELECTRIC HEATERS – Downflow
4kW
92919017
020D
92900437
Second stage
6kW
92919018
DOWNFLOW PLINTH
008
92900481
8kW
92919019
300mm high Font
discharge
010/015
92900482
10kW
92919020
020
92900483
HEATER RAIL - Downflow
008
92919022
008
92900484
Required for all heater kits
010, 015
92919025
300mm high Rear
discharge
010/015
92900485
020
92919027
020
92900486
LPHW HEATING 7.52kW
008
92900423
DOUBLE DEFLECTION GRILLE
008
92900494
(Add de-ice stat 10.50kW
010
92900424
(Upflow only)
010, 015
92900495
For all units) 14.94kW
015
92900424
020
92900496
18.40kW
020
92900425
008U
92900438
LPHW VALVE Motorised 2 port
ALL
92919048
010/015U
92900439
3 port
ALL
92919049
DISPOSABLE FILTER 50mm
020U
92900440
Modulating
ALL
92919050
(Replaces standard washable filter)
008D
92900441
DE-ICE THERMOSTAT(1 per circuit)
ALL
92900410
010/015D
92900442
008U
92919028
020D
92900443
010/015U
92919029
008
92900478
HUMIDIFIER 03kg/h
020U
92919030
HIGH EFFICIENCY FILTER
100mm
010,015
92900479
008D
92919031
020
92900480
010/015D
92919032
REMOTE CONTROL PANEL
008
92919078
020D
92919033
Supplied separately
010, 015
92919079
CONDENSATE PUMP
(With alarm interface)
ALL
92919054
(Includes 6m ribbon cable)
020
92919080
BACnet Controls
pCONET BMS BACnet Control
ALL
92919133
CD3 DX UNIT CONFIGURABLE ACCESSORIES
(All options are factory fitted or supplied loose for site fitting during installation)
5
92908135-17
DIMENSIONS AND WEIGHTS
UPFLOW UNITS (With plenum fitted)
UNPACKED
PACKED
Model
008
010
015
020
008
010
015
020
HEIGHT mm
1595
1595
1595
1595
1755
1755
1755
1755
WIDTH mm
1230
1380
1380
1580
1250
1400
1400
1600
DEPTH mm
430
430
430
430
455
455
455
455
WEIGHT kg
142
162
171
182
163
185
194
211
DOWNFLOW UNITS
UNPACKED
PACKED
Model
008
010
015
020
008
010
015
020
HEIGHT mm
1165
1165
1165
1165
1300
1300
1300
1300
WIDTH mm
1230
1380
1380
1580
1250
1400
1400
1600
DEPTH mm
430
430
430
430
455
455
455
455
WEIGHT kg
124
142
151
160
141
160
169
184
UNPACKED
Model
CKC
30
CKC
40
CKC
50
CKC
60
CKC
80
CKC
90
CKC
100
CKC
130
CKC
165
CKC
180
CKC
200
HEIGHT mm
620
620
720
720
720
820
820
1080
1080
1275
1275
WIDTH mm
904
904
1004
1004
1004
1004
1004
1004
1004
1104
1104
DEPTH mm
304
304
304
304
304
354
354
429
429
429
429
1 Ph kg
48
53
64
65
66
76----
-
3 Ph kg
48
53
62
63
64
73
81
101
103
118
173
PACKED
Model
CKC
30
CKC
40
CKC
50
CKC
60
CKC
80
CKC
90
CKC
100
CKC
130
CKC
165
CKC
180
CKC
200
HEIGHT mm
620
620
720
720
720
820
820
1080
1080
1280
1280
WIDTH mm
980
980
1080
1080
1080
1090
1090
1090
1090
1215
1215
DEPTH mm
340
340
340
340
340
390
390
465
465
465
465
1 Ph kg
50
55
66
67
68
78-----3 Ph kg
50
55
64
65
66
75
83
105
107
123
178
UNPACKED
PACKED
Model
DCU
30
DCU
50
DCU
60
DCU
80
DCU
30
DCU
50
DCU
60
DCU
80
HEIGHT mm
560
625
625
625
580
650
650
650
WIDTH mm
1075
1245
1245
1245
1090
1270
1270
1270
DEPTH mm
565
565
565
565565
610
610
610
610
WEIGHT kg
66
70
81
8184
76
86
86
90
CD3 INDOOR UNITS
CKC CONDENSING UNITS
DCU DUCTED CONDENSING UNITS
6
92908135-17
SELECTION L
CD3 MODEL
008
010
015
020
AIRFLOW (maximum) ³/s
0.78
1.04
1.23
1.51
HIGH SENSIBLE COOLING SYSTEMS
CKC/DCU
1 x 80
2 x 30
1 x 100
2 x 50
1 x 165
2 x 80
1 x 180
2 x 90
Return air
EXTERNAL AMBIENT 30°C
22°C 50%RH
Total
7.20
7.36
10.63
11.08
13.56
13.86
16.76
18.05
Sensible
7.20
7.36
10.58
10.77
13.44
13.57
16.56
17.11
24°C 50%RH
Total
7.46
7.74
11.23
11.62
14.23
14.44
17.60
19.05
Sensible
7.46
7.74
10.86
11.01
13.76
13.84
16.96
17.54
26°C 50%RH
Total
7.75
8.09
11.89
12.13
14.87
14.98
18.40
20.04
Sensible
7.75
8.09
11.13
11.22
14.03
14.07
17.29
17.91
Return air
EXTERNAL AMBIENT 35°C
22°C 50%RH
Total
6.86
7.17
10.11
10.56
12.97
13.19
16.03
17.20
Sensible
6.86
7.17
10.11
10.55
12.97
13.19
16.03
16.75
24°C 50%RH
Total
7.11
7.39
10.60
11.15
13.62
13.72
16.78
18.05
Sensible
7.11
7.39
10.60
10.83
13.52
13.56
16.63
17.14
26°C 50%RH
Total
---
---
11.22
11.64
14.22
14.22
17.79
19.00
Sensible
---
---
10.88
11.04
13.79
13.79
17.07
17.52
Return air
EXTERNAL AMBIENT 40°C
22°C 50%RH
Total
6.57
6.63
9.43
10.15
12.28
12.62
15.22
15.83
Sensible
6.57
6.63
9.43
10.15
12.28
12.62
15.22
24°C 50%RH
Total
6.79
6.98
9.93
10.60
12.85
13.08
16.00
16.78
Sensible
6.79
6.98
9.93
10.60
12.85
13.08
16.00
16.63
26°C 50%RH
Total
---
---
10.42
11.05
13.43
13.49
16.79
17.54
Sensible
---
---
10.42
10.82
13.43
13.49
16.70
16.98
Return air
EXTERNAL AMBIENT 45°C
22°C 50%RH
Total
---
6.21
8.79
9.75
11.52
---
14.33
14.88
Sensible
---
6.21
8.79
9.75
11.52
---
14.33
14.88
24°C 50%RH
Total
---
6.46
9.24
10.20
12.09
---
15.11
15.59
Sensible
---
6.46
9.24
10.20
12.09
---
15.11
15.59
26°C 50%RH
Total
---
---
9.73
10.65
12.73
---
15.83
16.31
Sensible
---
---
9.73
10.65
12.73
---
15.83
16.31
STANDARD COOLING SYSTEMS
CKC/DCU
1 x 100
2 x 50
1 x 130
2 x 60
1 x 180
2 x 100
1 x 200
2 x 130
Return air
EXTERNAL AMBIENT 30°C
22°C 50%RH
Total
9.84
10.26
11.67
11.81
15.98
18.78
18.88
21.90
Sensible
8.80
8.98
11.02
11.08
14.48
15.72
17.49
18.80
24°C 50%RH
Total
10.40
10.79
12.30
12.53
16.84
19.98
19.91
23.13
Sensible
9.01
9.17
11.29
11.38
14.82
16.13
17.89
19.22
26°C 50%RH
Total
10.96
11.32
12.92
13.08
17.69
21.20
21.04
24.36
Sensible
9.20
9.34
11.52
11.58
15.11
16.49
18.30
19.59
Return air
EXTERNAL AMBIENT 35°C
22°C 50%RH
Total
9.31
9.84
11.08
11.30
15.17
17.91
17.95
20.91
Sensible
8.57
8.80
10.77
10.86
14.13
15.33
17.07
18.36
24°C 50%RH
Total
9.90
10.35
11.77
11.85
16.10
19.01
19.05
22.11
Sensible
8.81
9.00
11.08
11.11
14.51
15.72
17.54
18.80
26°C 50%RH
Total
10.45
10.88
12.37
12.45
16.92
20.12
19.92
23.41
Sensible
9.00
9.17
11.31
11.34
14.81
16.06
17.87
19.22
Return air
EXTERNAL AMBIENT 40°C
22°C 50%RH
Total
8.67
9.44
10.46
10.78
14.33
16.76
16.65
19.77
Sensible
8.29
8.63
10.46
10.64
13.77
14.82
16.52
17.86
24°C 50%RH
Total
9.19
9.94
11.07
11.31
15.13
17.65
17.71
20.93
Sensible
8.52
8.83
10.80
10.89
14.12
15.15
17.00
18.31
26°C 50%RH
Total
9.76
10.45
11.64
11.89
16.02
18.81
18.76
22.10
Sensible
8.74
9.00
11.04
11.13
14.46
15.54
17.43
18.71
Return air
EXTERNAL AMBIENT 45°C
22°C 50%RH
Total
8.02
9.06
9.84
---
13.47
15.35
15.63
18.47
Sensible
8.02
8.46
9.84
---
13.40
14.21
15.63
17.29
24°C 50%RH
Total
8.57
9.55
10.38
---
14.23
16.56
16.47
19.70
Sensible
8.27
8.67
10.38
---
13.76
14.70
16.47
17.80
26°C 50%RH
Total
9.08
10.04
10.88
---
15.08
17.50
17.54
20.82
Sensible
8.48
8.85
10.75
---
14.11
15.03
16.98
18.21
PRODUCT SELECTION
Systems can be selected to provide either comfort cooling or cooling with higher sensible heat ratios
CD3 COMBINATIONS AND DX PERFORMANCE DATA (nominal cooling capacities in kW)
7
92908135-17
Model
008
010
015
020
Fan speed
Min
Max
Min
Max
Min
Max
Min
Max
Airflow
0.42
0.78
0.67
1.04
0.72
1.23
0.92
1.51
Model
30
50
60
80
90
100
130
165
180
200
Airflow m³/s
0.81
0.78
0.78
0.78
1.14
1.14
1.74
1.74
1.74
1.74
Model
30
50
60
80
Fan speed
Min
Max
Min
Max
Min
Max
Min
Max
Airflow m³/s
0.32
0.42
0.42
0.53
0.42
0.53
0.34
0.48
UNIT
008
010
015
020
UPFLOW
Fan speed
Min
Max
Min
Max
Min
Max
Min
Max
Top discharge and front return
air
NC
43
59
46
60
47
58
48
61
dBA
52
66.5
55
67
56
65
57
68
Front discharge with standard
plenum and front return air
NC
43
60
44
58
47
58
48
60
dBA
52
67
52.5
65
56
65
58.5
67
Front discharge with additional
attenuator and front return air
NC
38
49
41
49
41
48
43
50
dBA
47
58.5
50
58.5
50
57
52
58
DOWNFLOW
Top return and bottom
discharge air (supplied as
NC
31
44
37
45
37
45
39
48
dBA
41
53
46
54
46
54
48
56
CKC
SOUND POWER LEVELS
SOUND PRESSURE
LEVELS
Frequency Hz
dBA
125
250
500
1k
2k
4k dBA
NC
30
77.4
67.5
68.5
64.8
60.2
53.8
69.8 50.0
44
50
73.6
68.2
67.1
65.5
61.1
54.3
69.7 49.2
44
60
72.9
67.7
67.8
66.4
61.9
54.1
70.3 49.8
45
80
70.9
68.6
68.1
65.3
59.5
53.8
69.7 49.2
43
90
81.8
71.8
69.2
68.6
63.1
57.4
72.8 52.3
47
100
79.4
73.7
71.5
68.5
63.8
58.1
73.4 52.9
47
130
73
70.3
70.0
68.8
65.0
56.7
72.6 52.1
47
165
73.1
70.3
70.1
68.9
65.5
57.5
73.1 57.2
51
180
72.5
71.9
71.7
68.9
66.0
58.2
75.5 59.2
53
200
73.0
71.8
71.5
70.1
66.1
58.3
75.7 61.8
55
Measurement point
Unit
Fan speed
dBA
NC
3m from
unit in void
DCU 30
Max
52
46
Min
35
28
DCU 50, 60, 80
Max
54
48
Min
44
31
Office
area
DCU 30
Max
37
26
Min
30
15
DCU 50, 60, 80
Max
42
28
Min
32
17
3m from
discharge grille
DCU 30
Max
52
46
Min
34
27
DCU 50, 60, 80
Max
52
44
Min
40
28
AIRFLOWS (m³/s)
CD3
Note: Maximum external resistance at the maximum speed = 150Pa
CKC (Maximum fan speed)
Note: All CKC units are fitted with fan speed control that will allow the fan to stop during normal operation.
DCU
Note: All DCU units are fitted with fan speed control, modulating the airflow according to system conditions.
SOUND PRESSURE LEVELS – CD3 UNITS
Note: CD3 Sound Pressure Levels were calculated from measurements taken at 3m from the front of the unit in an office
installation and should be used for guidance only.
SOUND POWER AND SOUND PRESSURE LEVELS – 550 SERIES CKC UNITS (Maximum fan speed)
Sound Power Levels were obtained in full accordance with the direct method of ISO 3741: 1988. Quantities are shown in dB
with a standard reference of 1 pW.
Sound Pressure Levels are dB relative to 2 x 10-5N/m2 , calculated from the results under anechoic conditions and quoted as
an average of all points on a sphere of a radius of 3m away from the centre of the unit (in cooling mode); (add 3dBA or 3NC for
units at an intersection of a wall, add 1dBA or 1NC for high level wall mounted units).
DUCTED CONDENSING UNITS
Sound Pressure Levels are dB relative to 2x10-5N/m2. All readings taken from a typical application of a unit suspended in a ceiling void
complete with 5m of insulated ducting, conditioning an office directly below.
8
92908135-17
INSTALLATION L
CD3 AIRFLOW OPTIONS
9
92908135-17
MODEL
WEIGHT
(kg)
Upflow units with plenum
fitted
CD3
142
CD3
162
CD3
171
CD3
182
Downflow units
CD3
124
CD3
142
CD3
151
CD3
160
CD3 SERIES CLOSE CONTROL UNIT INSTALLATION
An envelope containing important user information is supplied with the indoor unit. Please pass to the end user.
1. The Packaged units are supplied for Upflow operation with front return air and top discharge.
Configured units are supplied for Upflow or Downflow operation. Standard upflow units are supplied with front return
air and top discharge; Downflow units with top return air and front discharge.
Units may be ordered with other airflow configurations or altered on site. Other configurations include:
Upflow: (wall mounted) with bottom return air.
with front or top discharge, wall or floor mounted.
Downflow: with top return air and under floor discharge.
See page 9 for all available configurations.
Note:- The required airflow arrangement must be configured prior to installation.
2. The chassis is made up of removable panels. The central panel, with control panel inset, MUST be removed first
using the two keys provided.
UNIT ACCESS AND CABINET STRIP DOWN
1 If a door interlock isolator is fitted, ensure that the switch is turned to the OFF position.
2 Using the keys provided, unlock the electrics access panel. Remove the panel by easing outwards and down.
3 The side panels can be removed by releasing the two swell latches located through the side bulkheads within the
electrics compartment and carefully pulling outwards until they are clear of the upper and lower grabber catches.
4 Access to the fan section, (and coil section in the downflow mode), can be gained by releasing the appropriate swell
latches located through the cut outs to the front of the side bulkheads and removing the panel.
5 The return air grille is removed by turning the 4 retaining screws anticlockwise, until a click is heard, and pulling the
grille outwards.
MOUNTING
1 It is recommended that ALL field fit kits are installed prior to mounting the unit and brazing the pipe work.
2 Ensure that the wall or floor will accept the operating weight of the unit; weights shown below include the plenum.
NOTE:-When wall mounting, the unit should be lifted into position using the pallet provided.
3 Mark off the mounting holes as shown and drill holes to suit M6 Rawlbolt shields or equivalent fasteners.
4 If a fresh air facility is required, the appropriate apertures must be prepared to match up with the positions of the
unit fresh air inlets as shown in the diagrams following. Any opening in the external wall must be suitably lined and
screened to prevent brick dust entering the unit during installation and operation.
5 Mount the unit as required and secure all fixing bolts
6 Check that the unit is square and level. Failure to do so will result in misalignment of the cabinet access panels and
possible operational problems.
10
92908135-17
UNIT SIZE
DIMENSION 'A'
DIMENSION 'B'
008 1230 -
010 / 015
1380 690 020 1580 790
COILSECTION
Note: Plenum (not
shown) is 430mm high
UPFLOW SERVICE AND FIXING HOLE CENTRES (excluding discharge plenum)
11
92908135-17
DOWNFLOW SERVICE AND FIXING HOLE CENTRES
UNIT
DIMENSION 'A'
DIMENSION 'B'
008 1230 -- 010/015
1380
690
020 1580
790
12
92908135-17
INSTALLATION of 550 Series CKC CONDENSING UNITS
Model
CKC 30 - 80
CKC 90 - 200
Mounting Bracket Kit
55021100
55021101
MODEL
A B C D E F G
H
Weight (kg)
1 Ph
3 Ph
CKC 30
900
300
560
525
185
60
333
308
48
48
CKC 50
1000
300
660
570
213
60
333
308
64
62
CKC 60
1000
300
660
570
213
60
333
308
65
63
CKC 80
1000
300
660
570
213
60
333
308
66
64
CKC 90
1000
350
760
495
250
70
383
358
76
73
CKC 100
1000
350
760
495
250
70
383
358 - 81
CKC 130
1000
425
1020
495
251
100
458
433
-
101
CKC 165
1000
425
1020
495
251
100
458
433
-
103
CKC 180
1100
425
1215
675
211
95
458
433
-
118
CKC 200
1100
425
1215
675
211
95
458
433
-
173
CKC units include fan speed control, high & low pressure switches with low ambient and compressor delay start timers.
Note: It is easier to fit any kits prior to mounting the unit.
The units are designed to stand on a flat surface. If they are to be wall mounted the following kits are available.
(TEV Ltd cannot accept liability for installers own mounting arrangements).
Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit weight. Leave
space around the unit for air circulation and access for installation and maintenance.
MOUNTING: CKC 15 – 100 CKC 130 - 200
Dimensions in mm.
13
92908135-17
INSTALLING 542 SERIES DUCTED CONDENSING UNITS
A
D
B
PLAN VIEW
E
C
G
F
J
K
H
SPIGOT DIAMETERS:-
DCUE 30 - 40 = 354
DCUE 50 - 80 = 404
Model A B C D E F G H J K
Spigot dia.
Weight (kg)
DCU 30
930
510
495
1004
490
65
65
210
317
717
354
70
DCU 50
1100
510
560
1174
490
65
65
240
392
865
404
81
DCU 60
1100
510
560
1174
490
65
65
240
392
865
404
81
DCU 80
1100
510
560
1174
490
65
65
240
392
865
404
84
DCU A B
30
930
510
50-80
1100
510
B
A
PLAN VIEW
MOUNTING
Units are supplied with a polystyrene packing piece supporting the blower assembly, this MUST be removed prior to
commissioning.
Ducted Units are designed to be hung on a wall (kit available), suspended from a ceiling (installer supplied fittings), or to
stand on a flat surface. Whichever method is used it is essential that the mounting surface is capable of supporting the
units weight.
DIMENSIONS
FLOOR MOUNTING
Using the appropriate side of the packing carton as a template, (centres marked A), mark out and drill 4 holes to suit
maximum M8 bolts (also see opposite). Secure the unit to the floor. Discard the stabilizing brackets.
Dimensions in mm
Dimensions in mm
14
92908135-17
Dimensions
mm.
Model
30
50-80
A
400
450B300
350
C
100
100
SUSPENSION MOUNTING
The installer must supply 4 x M8 threaded rods with 16 nuts and washers to suit.
IMPORTANT: The stabilizing brackets provided MUST be used when suspending a unit.
Fit the stabilizing brackets to the top corners of the back panel and front face using the No. 10 screws
provided, (2 per bracket).
If these brackets are omitted the unit will be subject to unacceptable movement on compressor start.
Where long drops of M8 rod are used, it is advisable to incorporate flexible pipes in the suction and expansion lines to
absorb any movement of the unit.
Using the template printed on the side of the packing
carton, (centres marked A), mark out the ceiling and
drill 4 holes to suit M8 screwed rod. Raise the unit to
the required height and pass the screwed rods
through the mounting holes in the units feet and
stabilizing brackets. Secure the unit with a nut and
washer on either side of each stabilizing bracket and
two nuts and washers underneath each foot mounting
hole, (as shown).
WALL MOUNTING
Brackets to enable ducted units to be wall mounted are available as an optional kit (53200407).
DUCTWORK
Each unit is supplied with air inlet and discharge spigots, models 30 to 40 - 354mm (14") dia., models 50 to 80 - 404mm
(16") dia. These may be used for connecting installers ducting or used with the optional Duct, Plenum and Grille kits.
Please refer to the kit instruction for installation methods. The front face of the units are also fitted with M6 rivnuts to
accept installer supplied square ducting, see dimensions below. Maximum flange width is 25mm and fixing holes should
be central within them.
NOTE: It is essential that ducting is adequately insulated to prevent sweating. An insulation thickness of at least 45mm
is recommended.
15
92908135-17
APPLICATIONL
UNIT
SIZE
MAXIMUM LENGTH OF EQUIVALENT
SUCTION LINE PIPE SIZES (m)
LIQUID LINE
⅜ ½ ⅝ ¾ ⅞
1⅛
1⅜ ⅜ ½
⅝
20
7.5
20
30
15
45
45
40
10
36
45 7.5
45
50
7.5
18
45 7.5
45 60
14
36
45
7.5
45
80
11
30
45 45
90
10
25
45 20
45
100
7.5
22
45 15
45
130
15
30
45
12
45
150
12
27
45 8 45
165
8 18
45
7.5
45
180
7.5
16
45
7.5
45
200
15
45
7.5
45
Fitting
Pipe Size (outside diameter in inches)
3/8
1/2
5/8
3/4
7/8
1-1/8
45° Bend
0.12
0.15
0.18
0.21
0.24
0.3
90° Bend R/d = 1
0.37
0.43
0.49
0.55
0.61
0.79
90° Bend R/d = 2
0.24
0.27
0.30
0.37
0.43
0.52
180° Bend C/d = 1
0.73
0.91
1.10
1.28
1.46
1.83
180° Bend C/d = 2
0.46
0.55
0.64
0.76
0.85
1.07
90° Elbow
0.67
0.85
1.04
1.25
1.46
1.89
R = Radius of bend
d = Diameter of tube
C = Centres of bend
APPLICATION
1 To maximise performance, pipe runs should be kept as short as possible, avoiding sharp bends. Individual pipe
runs to a maximum of 45m are allowed for air conditioners, providing pipe work is sized and installed correctly.
Performance ratings are based on 6m pipe runs but there will be no significant loss of capacity on extended pipe runs
for correctly sized pipes.
a) Pipe sizes are based on: Minimum of 3.8 m/s (750fpm) suction gas velocity for horizontal or down flow.
Minimum of 7.6 m/s (1500 fpm) suction gas velocity for up flow.
Maximum of 15.2 m/s (3000 fpm) suction gas.
b) Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil returns to the
compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.
2 Add 25 grams of refrigerant oil for every 350 grams of charge added to systems with pipe runs exceeding 25m, up to
a maximum of 300 grams; preferably by slowly pumping into the suction side with the unit running, after charging the
system.
R407C : Use polyolester oil - L’Unite 181-023, ICI Emkarate RL32S,RL32CF,Mobil Artic EAL22 or EAL22CC
3 For systems with capillary control at the indoor unit; the table shows the suggested pipe sizes (in inches).
4 In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into account. Information
5 Use the shortest possible route, avoiding sharp bends.
6 Fully insulate the suction line, (or suction and liquid line if run together).
relating to the equivalent lengths of line fittings and bends etc. is generally available to the design engineer. The table
below covers the fittings most likely to be encountered in this type of installation. The equivalent lengths of all the
fittings in a particular pipe run must be added together and the total added to the actual length of pipe in the run, in
order to calculate its total equivalent length.
FITTING LOSSES, in equivalent straight lengths of pipe (metres).
16
92908135-17
Model
008S
008T
010S
010T
015S
015T
020S
020T
Liquid
3/8
3/8
3/8
3/8
1/2
3/8
1/2
3/8
Suction
3/4
1/2
3/4
1/2
7/8
5/8
7/8
5/8
Single circuit
systems
CD3
Outdoor unit
CKC charge (g)
Twin circuit
systems
CD3
Outdoor units
CKC charge (g)
R407C
R407C
S 08 S
008
CKC 90
1422
S 08 T
008
2 x CKC 50
1167*
S 10 S
010
CKC 130
3075
S 10 T
010
2 x CKC 60
1477*
S 15 S
015
CKC 180
3389
S 15 T
015
2 x CKC 100
1882*
S 20 S
020
CKC 200
4229
S 20 T
020
2 x CKC 130
3075*
HS 08 S
008
CKC 80
1357
HS 08 T
008
2 x CKC 30
761*
HS 10 S
010
CKC 100
1882
HS 10 T
010
2 x CKC 40
807*
HS 15 S
015
CKC 165
3445
HS 15 T
015
2 x CKC 80
1357*
HS 20 S
020
CKC 180
3389
HS 20 T
020
2 x CKC 90
1422*
REFRIGERATION INSTALLATION
1 Units are supplied with the following pipe connections (in inches):-
S = Single Circuit T = Twin Circuit
NOTE: On twin circuit units, the lower half of the coil is the first circuit.
2 Using a tube cutter, remove sealed ends of suction and liquid pipes. This will release a small holding charge of
dry nitrogen. Discard the expansion device on the condensing unit.
3 Pipe exit positions are shown on pages 3 and 4. It is recommended that the liquid and suction lines be kept at the
supplied size until exit, when the full pipe size can be run.
4 Connect pipe work between units noting the following:-
a) Use only refrigeration quality copper tube/pipe, supported every 2 metres.
b) Use tube cutters to avoid forming swarf.
c) If brazing, use copper phosphorus alloy with 5% silver, and purge the system with dry nitrogen to avoid
oxidation and build up of scale.
d) Do not leave pipe ends, valves, driers etc. open to the atmosphere longer than necessary.
e) Fully insulate the suction line, or suction and liquid if run together.
5. A strainer is fitted in the liquid line just prior to the capillary on the air handler. It is recommended that a liquid line
filter drier is fitted.
6. If a sight glass is fitted to assist charging, position this in the liquid line as near to the air handler as practicable, and
downstream of the liquid line filter/drier.
EVACUATING AND CHARGING
When the compressor is first started in the field, the bearing surfaces are susceptible to damage if not properly
lubricated. Care should be taken when the bearings are being run in to ensure that: a) The compressor is not started the first time with excessive refrigerant charge.
b) The system is not overcharged, which could result in liquid return to the compressor.
Evacuate the air handler and interconnecting pipe work by connecting a vacuum pump to the Schrader connections on
both suction and discharge service valves on the condensing unit (DO NOT OPEN THE VALVES) and evacuate to 1000
microns (1 Torr) or better and hold for a minimum of 15 minutes.
REFRIGERANT CHARGE
* = per circuit
The table above shows the base charge for R407C
The base charge will generally be sufficient for 3m pipe runs at room 22°C 50% RH, ambient 27°C 50% RH.
Typical charge to be added for longer liquid lines:-
3/8" OD add 50 g/m; 1/2" OD add 80 g/m; 5/8" OD add 110 g/m.
The preferred method of adding refrigerant is:-
1. Start the unit (on highest fan setting ) and allow the compressor to run for a few seconds.
2. Additional charge should be introduced through the Schrader valve on the suction side of the compressor.
3. The correct unit charge may be determined by examining the condition of the evaporator coil during the charging
process (with the system running in cooling). Refrigerant enters the coil at the bottom left hand side and leaves
at the top left hand side. A properly charged unit should show signs of 'sweating' all the way up the coil. 'Sweating'
should be reduced at the coil outlet as it enters the suction line, which should be completely dry a few inches before
it enters the compressor.
4. If a sight glass is fitted, position this in the liquid line as near to the air handler as possible. Charge should be
added to the unit, (with the system running), until the sight glass is just clear of bubbles (flooded).
17
92908135-17
Undercharged Unit - the top few tubes of the evaporator are dry and there are, (possibly), slight signs of frosting
Single Phase Supply 230 Volts - 50 Hz
Three Phase Supply 400 Volts - 50 Hz
System
Model
Combination
Full Load Amps
System
max.
starting
current
Full Load Amps
System
max.
starting
current
Cool
Only
Cool &
Heat
Cool/Heat/
Hum/Dehum
If DCU
fitted
Cool
Only
Cool &
Heat
Cool/Heat/
Hum/Dehum
If DCU
fitted
Amps
Amps
Amps
Amps
Amps
A/PH*
A/PH*
A/PH*
A/PH
A/PH
S 08 S
CD008 + CKC 100
- - - - -
12.5
16.7
32.7
-
69.0
S 10 S
CD010 + CKC 130
- - - - -
15.75
16.7
32.7
-
89.3
S 15 S
CD015 + CKC 180
- - - - -
22.1
33.0
47.1
-
139.6
S 20 S
CD020 + CKC 200
- - - - -
23.91
33.4
49.3
-
138.0
HS 08 S
CD008 + CKC 80 / DCU 80
19.9
**38.7
-
+1.0
82.5
10.3
16.7
32.7
+2.0
57.8
HS 10 S
CD010 + CKC 100
- - - - -
14.5
23.1
32.7
-
75.4
HS 15 S
CD015 + CKC 165
- - - - -
19.4
33.0
44.6
-
109.2
HS 20 S
CD020 + CKC 180
- - - - -
22.5
33.4
49.3
-
140.0
S 08 T
CD008 +2x CKC 50 / DCU 50
26.8
**38.7
-
+1.0
75.2
13.7
16.7
32.7
+4.0
43.8
S 10 T
CD010 +2x CKC 60 / DCU 60
35.5
**40.7
-
+1.0
83.0
16.3
23.1
32.7
+5.0
56.2
S 15 T
CD015 +2x CKC 100
- - - - -
25.1
33.0
41.0
-
85.3
S 20 T
CD020 +2x CKC 130
- - - - -
27.1
33.4
49.3
-
99.6
HS 08 T
CD008 +2x CKC 30 / DCU 30
21.9
**38.7
-
+4.0
51.0
11.8
16.7
32.7
+4.0
36.1
HS 10 T
CD010 +2x CKC 50 / DCU 50
28.8
**40.7
-
+1.0
77.2
15.9
23.1
32.7
+4.0
50.2
HS 15 T
CD015 +2x CKC 80 / DCU 80
38.5
**42.3
-
+1.0
100.9
19.7
33.0
41.0
+4.0
74.1
HS 20 T
CD020 +2x CKC 90
44.7
**44.7 - -
129.4
22.5
33.4
49.3
-
81.7
at the inlet to the evaporator coil.
Overcharged Unit - the suction line 'sweats' all the way back to the compressor.
ELECTRICAL CONNECTIONS
The installation wiring should be carried out in accordance with I.E.E. regulations and/or local codes.
A mains isolator should be used and the system suitably fused, (see page 7). Supply cables and inter-connecting cables
are to be provided by the installer.
INDOOR UNIT WIRING
Connections for internal wiring are made within the electrics enclosure accessed by removing the centre front cover.
Disconnect the connecting cable from the display panel before moving the cover away from the unit.
Mains cables should be connected via a fused switch and routed through knockouts in the bottom left hand corner of the
unit, then through an access hole in the bottom left hand side of the electrics compartment to the mains terminal block.
System Interconnecting Wiring
On single or three phase systems, connect the incoming mains supply to the indoor unit and then link to the condensing
unit via a three pole circuit breaker.
The earth wire is connected to an earth stud at the right hand side of the mains terminal block. All mains and interconnecting
cable must be sized to suit the electrical rating of the unit and the length of cable run.
Make sure that all connections are secure and all wires are clear of any rotating parts.
Data Plates
Because indoor and outdoor units can be mix-matched, the data plates only give information relevant to the indoor unit
with maximum possible running currents. To determine the full system details please refer to the Technical Manual for
more specific information.
ELECTRICAL DATA
* Max. Phase
**Single phase models are available for twin circuit dx systems where electric heating requirement is 8kW or less.
The electric heating loads shown are based on maximum amounts of heating which are:-
CD 008 = 8kW (4+4) CD 010 = 10kW (4+6) CD 015 = 16kW (8+8) CD 020 = 20kW (10+10)
18
92908135-17
Typical control panel and terminal layout
System
S 08 S
S 10 S
S 15 S
S 20 S
S 08 T
S 10 T
S 15 T
S 20 T
1 Phase Cool Only
----40
40--
1 Phase Cool and Heat
----50
50--
3 Phase Cool Only
20
25
35
40
16
20
32
35
3 Phase Cool and Heat
20
32
40
40
20
32
40
40
3 Phase Cool/Heat/Hum/Dehum
40
40
63
63
40
40
50
63
System
HS 08 S
HS 10 S
HS 15 S
HS 20 S
HS 08 T
HS 10 T
HS 15 T
HS 20 T
1 Phase Cool Only
32---32
40
50
63
1 Phase Cool and Heat
50---50
50
50
63
3 Phase Cool Only
16
20
32
40
16
20
25
32
3 Phase Cool and Heat
20
32
40
40
20
32
40
40
3 Phase Cool/Heat/Hum/Dehum
40
40
63
63
40
40
50
63
RECOMMENDED FUSE SIZES
The system and its supply/interconnecting wiring must be protected by fuses, preferably H.R.C. motor rated types to
BS60269 or miniature circuit breakers to BS60898 or local codes having similar time lag characteristics that allow
starting of the compressor yet still afford close over current protection under running conditions. The ratings below are for
H.R.C. motor rated or semi-enclosed wire fuses.
Standard Cooling
High Sensible Cooling
19
92908135-17
Pico Controller *
Setting
High/Boost Switch
Potentiometer
Unit Fan Speed
High
No Adjustment
Possible
No Adjustment
Possible
Unit Fan Speed
Low
Select High or
Boost
Adjust for
De-Hum Low SP
50% to 100%
* See Page 4 of 92908131 Operator Instructions if the Pico
Controller is set at high. Low speed will automatically be
selected during de-hum
CONDENSATE DRAIN
The condensate drain connection is at the left hand end of the condensate drain tray.
A 15mm O.D. copper drain pipe is provided in the drain sump for connection with non-kink plastic tubing secured with
a suitable clip.
Should it be necessary for the drain pipe to go through the back or base of the unit, a knockout is provided in the back
panel or base plate.
The drain line must have a constant fall to open drain using a 'U' trap if required. Check that the water will run freely
and that there are no leaks.
IMPORTANT: If a humidifier is fitted the drain pipe must be capable of carrying water at 60°C.
FAN SPEED CONTROLLER
One control is used on each CD3 unit, and has a switch for selecting high or boost speed (see diagram below).
These can only be selected if the Pico Controller is set at low.
SETTING
The boost speed should be selected for:-
The High speed should be selected for standard 'Free Blow' Upflow units.
Units are despatched with the low speed set on 50%. The fan speed may be adjusted between 50% and 100% of
the selected top speed by turning the low speed potentiometer clockwise.
ALL DOWNFLOW units
Upflow units requiring ductwork on the supply or return air
When high efficiency filters are fitted.
WHEN INSTALLATION HAS BEEN COMPLETED - CHECK:-
1. All pipe work and joints for leakage.
2. All pipe work and fittings for insulation.
3. All bolts are secure and that fan rotates freely.
20
92908135-17
WIRING DIAGRAMSL
POWER WIRING DIAGRAM – Sheet 1
21
92908135-17
POWER WIRING DIAGRAM – Sheet 2
22
92908135-17
CONTROL WIRING DIAGRAM
For HUMIDIFIER wiring diagram see page 27.
23
92908135-17
To
indoor
unit
To
indoor
unit
To
indoor
unit
To
indoor
unit
CKC WIRING DIAGRAMS
1 PHASE CKC 30 to 90 3 PHASE CKC 30 to100
3 PHASE CKC 130 to 180 3 PHASE CKC 200
24
92908135-17
DCU WIRING DIAGRAMS
DCU 30 to 80 1 phase
DCU 15 to 80 3 phase
INTERCONNECTING WIRING DIAGRAMS
25
92908135-17
1 phase units
Ø
( mm )
3.5
4
5.5
6
(mm²)
2.5
4
6
10
3 phase units
WAGO terminals
26
92908135-17
ACCESSORIESL
CONDENSATE PUMP (OPTIONAL)
An optional condensate pump is available, providing a 5m lift where gravity drain is not an option. The full
assembly comprises a condensate pump (suitable for hot and cold water removal), a control board, a float
switch to activate the pump and a second float switch to provide a high water level alarm. The high level
alarm disables cooling until the condensate in the tray has fallen to a safe level.
WATER SPILL SENSOR (OPTION)
Can be connected to the condensate pump board providing an alarm in the event of
CD3 SYSTEM HUMIDIFIER (OPTIONAL)
Plumbing connections
HUMIDIFIER WIRING DIAGRAM
condensate spillage.
DESCRIPTION
The humidifier is an electrode steam boiler, electronically controlled. The steam bottle will require replacing
periodically. The humidifier is fitted with bottle change indication and the frequency of change is dependent upon
the condition of the water feeding the humidifier.
INSTALLATION
Water supply
The humidifier operates with a range of water qualities; pre-treated water is preferable, extending the bottle life
(fully de-mineralised water is not suitable). The humidifier system incorporates an air break in the water feed to meet
local regulations. Connect directly to a water supply operating at pressures between 0.1 and 1 MPa (14 to 145 psig).
For supplies at higher pressures fit a pressure regulator set at 0.4 to 0.6 MPa (60 to 90 psig).
The inlet connection is a 15mm pipe. A stop valve and strainer should be fitted ahead of the control solenoid valve
that is fitted to the inlet of the humidifier.
Waste water is drained into the unit condensate tray. The drainpipe should be suitable for use with water at 60C .
Drain pipes should be correctly sized with a minimum slope of 5% (1 in 20) and an air break at the entry.
27
92908135-17
Setting the capacity limitation “Sx%”
Jumper Positions
POS
With Jumper
Without Jumper
Fi
Connection to a mains supply with ground fault
circuit interrupter
Connection to a mains supply without ground fault
circuit interrupter *
DRN
Increased drain operation factor
Regular drain operation factor *
CDY
Low water conductivity (<125 µS/cm)
Normal water conductivity (≤125 µS/cm) *
DSP
Exchangeable steam cylinder *
Cleanable steam cylinder
K
Fault No.4 “steam cylinder maintenance due”: the
unit triggers a warning only *
Fault No.4 “steam cylinder maintenance due”: 72
hours after the warning an error is triggered and the
unit is switched off
L
Fault No.3 “Fill time”: a warning is triggered after
20 minutes filling time exceeded. After 220
minutes filling time exceedance an error is
triggered and the unit is switched off *
Fault No.3 “Fill time”: the unit directly triggers an error
after 20 minutes filling time exceedance. However,
the unit is switched off after 220 minutes filling time
exceedance.
Z, M, N
No function (spare)
Use the potentiometer “Sx%” to set the capacity limitation in % of the minimum capacity (setting range: 25…100%,
factory setting: 100%).
Setting the humidity setpoint value “%rH”
Use the potentiometer “%rH” to set the humidity setpoint value for the internal controller in % relative humidity (setting
range: 0…100%, factory setting: 100%).
General Settings
With the jumpers on the jumper blocs “JP1” and “JP2” you can set different unit parameters.
* Factory settings
COMMISSIONING
Pre-start check
Ensure the drain line is connected and that water flows away freely. Do this by filling and draining the bottle using the
manual drain switch.
HUMIDIFIER START UP
On initial start up the feed valve will open to fill the bottle and the drain valve will remain closed.
The initial current draw will be below the normal operating level as the bottle is filled with fresh water. This will
increase as the humidifier continues to operate until reaching it’s full value (this may take several operations
depending upon the condition of the water and the length of time it is operating). The bottle will continue to fill and
drain automatically on demand.
During the start up period, whenever the current is less than 70% of the set operating level, the 'bottle change’
indication will be active. This is normal and the indication will go off once the current has risen above 70% of the set
output. The 'bottle change' indication will not appear again until the bottle requires changing.
NOTE: The start up process described above occurs only when a new bottle has been fitted.
Adding a teaspoon of table salt into the new bottle before connecting up may reduce the start-up time after a bottle
change.
NORMAL OPERATION
After the start up period, the unit will operate automatically, at a constant output until the bottle requires changing.
The frequency of the drain and fill sequence will depend upon the quality of the water.
There will be a short delay from the unit receiving a humidifier on signal and the steam being generated as the water
is brought up to temperature.
HUMIDIFIER MAINTENANCE
Prior to carrying out maintenance on the humidifier, the cylinder should be drained by operating the manual switch.
The system should also be isolated from the electrical supply.
STEAM BOTTLE REPLACEMENT
Access to the bottle and solenoid valves is from the front and left hand side of the unit.
1. Before switching off the power to the humidifier, isolate the water supply and drain the bottle using the manual
drain switch.
28
92908135-17
SETTINGS
CONFIGURATION
pCONET BMS CONTROL KIT 92919134
OPERATION AND COMMISSIONING
2. Remove the discharge hose from the top of the bottle.
3. Remove the electrical connectors pulling upwards.
4. Lift the bottle support bracket clear of the outlet spigot.
5. Remove and replace the bottle.
6. Replace the hose and electrical connectors.
7. When replacing the bottle clean the feed/drain manifold and check the "O" ring seal, replacing if necessary.
Check and clean the strainer protecting the outlet solenoid valve
8. Reconnect the water supply and switch on the electrical supply.
After replacing the bottle check that the operating current is correct (see start up).
ENSURE THE ELECTRICAL SUPPLY IS DISCONNECTED
1. If a door interlock isolator is fitted, ensure that the switch is turned to the OFF position.
2. Using the keys provided, unlock the electrics access panel. Remove the panel by easing outwards and down,
before fully removing the panel, release the cable from the keypad.
3. Remove the “Serial card” cover from the pCO3, insert pCO net into the plug in connector and make sure it is
fully inserted.
4. Insert the required Jumper (see Carel pCO net instruction supplied for more information)
5. Fit the cover supplied with pCO net
The pCO3 has been configured for the BACnet MS/TP network as from January 2016
Comm. Speed 19200 bps (RS485)
NOTE: For CD3 systems supplied before January 2016 contact Marstair for further assistance.
Procedure for configuring the pCOnet parameters for correct communication over an MS/TP network
Connect pCOnet via RS485 to a computer: during configuration, the CAREL RS485 converter (CVSTDMOR0)
for USB ports can be used, Marstair part number 92919136. USB converters should not be used in the
installation due to the large volume of data transmitted across a complex BACnet network.
Install the CAREL ”BACset” configuration tool, available free of charge at ksa.carel.com. You need to create a
free of charge account to access the software download sections. Navigate through the following menu’s:-
Software and support
pCONet
BacSet.
29
92908135-17
DATABASE OF THE SUPERVISOR
Address
Description
Type
Communication type
1
Compressor 1 general alarm digital input
Digital
Reading
2
Compressor 2 general alarm digital input
Digital
Reading
8
ON/OFF remote
Digital
Reading
11
fire / smoke alarm digital input
Digital
Reading
12
Dehumidification
Digital
Reading
13
ON /OFF unit
Digital
Reading
18
3p cold valve opening contact (CW) / Cooling 1 DX
Digital
Reading
19
3p cold valve closing contact (CW) / Cooling 2 DX
Digital
Reading
20
3p warm valve opening contact (CW) / Electric Heating
Digital
Reading
21
3p warm valve closing contact (CW)
Digital
Reading
22
General alarm
Digital
Reading
23
Compressor 1 general alarm
Digital
Reading
24
Compressor 2 general alarm
Digital
Reading
31
Fire / smoke alarm
Digital
Reading
32
Air filter alarm / Filter Clog
Digital
Reading
33
Ambient high temperature alarm
Digital
Reading
34
Ambient temperature alarm
Digital
Reading
35
Ambient high humidity alarm
Digital
Reading
36
Ambient low humidity alarm
Digital
Reading
55
Humidity probe enabling
Digital
Writing / Reading
58
Inlet water probe enabling
Digital
Writing / Reading
61
Cold modulating valve 0/10V enabling
Digital
Writing / Reading
63
Enabling of simultaneous operation of compressors with
Digital
Writing / Reading
64
Warm 0/10V modulating valve enabling
Digital
Writing / Reading
66
Compressor rotation enabling
Digital
Writing / Reading
67
Compressor 1dehumidification enabling
Digital
Reading
68
Compressor 2 dehumidification enabling
Digital
Reading
73
ON/OFF from supervisor enabling
Digital
Writing / Reading
74
3p cold valve enabling
Digital
Reading
75
3p warm valve enabling
Digital
Reading
The variables reported below will be transmitted between pCO and supervisor only if all the following conditions will be
met:
- the serial card is inserted into the proper connector that is found on the interface
- the supervisory function is enabled in the M_MANUF_CONF1.window protected by manufacturer’s password
- the address of the unit is properly selected with reference to the supervisory network in the
M_PARAM_USER12 window protected by user password.
- the equipments have been correctly connected to the network (supervisor and pCO)
Digital Variables
30
92908135-17
Whole Variables
Address
Description
Type
Communication type
01
Delay common alarm relay
Whole
Writing / Reading
10
Cold 0/10V valve ramp start
Whole
Writing / Reading
11
Cold 0/10V valve ramp end
Whole
Writing / Reading
12
Warm 0/10V valve ramp start
Whole
Writing / Reading
13
Warm 0/10V valve ramp end
Whole
Writing / Reading
16
Compressor 1 step without energy saving
Whole
Writing / Reading
17
Compressor 1 hysteresis without energy saving
Whole
Writing / Reading
18
Compressor 2 step without energy saving
Whole
Writing / Reading
19
Compressor 2 hysteresis without energy saving
Whole
Writing / Reading
26
Time interval between same compressor switching on
Whole
Writing / Reading
28
Low pressure delay alarm
Whole
Writing / Reading
29
Stop minimum time compressors
Whole
Writing / Reading
30
Time interval between different compressor switching on
Whole
Writing / Reading
33
High / low temperature / humidity alarm delay
Whole
Writing / Reading
34
Start-up delay between heaters
Whole
Writing / Reading
48
Integration time P+1 ONLY
Whole
Writing / Reading
54
Cold 3p valve ramp start
Whole
Writing / Reading
55
Cold 3p valve ramp end
Whole
Writing / Reading
56
Warm 3p valve start ramp
Whole
Writing / Reading
57
Warm 3p valve end ramp
Whole
Writing / Reading
58
3p valve complete opening time
Whole
Writing / Reading
59
Fan switching on delay
Whole
Writing / Reading
61
Cold valve ramp limit
Whole
Reading
62
Warm valve ramp limit
Whole
Reading
Address
Description
Type
Communication type
1
Ambient temperature
Analog
Reading
2
Ambient humidity
Analog
Reading
5
Supply air temperature
Analog
Reading
6
Dead zone in temperature
Analog
Writing / Reading
7
Ambient humidity band
Analog
Writing / Reading
8
Ambient humidity set
Analog
Writing / Reading
9
Low temperature alarm offset
Analog
Writing / Reading
10
High temperature alarm offset
Analog
Writing / Reading
11
Low humidity alarm offset
Analog
Writing / Reading
12
High humidity alarm offset
Analog
Writing / Reading
13
Ambient temperature set
Analog
Writing / Reading
18
Water low temperature limit
Analog
Writing / Reading
19
Water high temperature limit
Analog
Writing / Reading
23
Cooling valve position
Analog
Reading
24
Heating valve position
Analog
Reading
Analog Variables
31
92908135-17
GND
TX/RX+
TX/RX-
GND
TX/RX+
TX/RX-
GENERAL MAINTENANCE
12 MONTHLY (or more frequently if conditions dictate)
1. Clean the feed water strainer and drain solenoid valve. Check hoses for wear and flush out the drain pipe.
2. Check all electrical connections are tight.
3. Check and clean the drain tray to prevent a build up of deposits.
CD3 AUTO CHANGEOVER
It is possible to connect two CD3 units to allow them to operate in Run/Standby operation, changing over on alarm or on
a timer to equalise component wear. One unit will be configured as the run unit, the second as the standby unit.
UNIT 1 UNIT 2
RUN
STANDBY
STANDBY
RUN
UNIT 1 starts as the run unit with UNIT 2 in standby mode. One of the following will cause the units to change modes.
1. Run time: If programmed, units will switch between run and standby on a timer basis to ensure even running of fans
and compressors. This is factory set at 168hrs and is factory adjustable by TEV Ltd.
2. Unit assist: The standby unit will switch on in the event the room load exceeds the running unit capacity.
3. Alarm: If the run unit is disabled by alarm or power loss (including switching off) the standby unit will take over.
4. Network: If communication is broken.
Critical alarms are set in the Engineering Level mask (see operating Instructions page 5of 9) note that only AL01 and ALO2
are used with Marstair condensing units. AL03, AL04, AL32 and AL33 are not available.
WIRING
WARNING !! Units can start automatically, isolate both units before beginning work..
Connections J11 J11
CAUTION:
Do not cross the polarity of theconnections.
UNIT 1 UNIT 2
Units are connected in parallel using a twisted pair shielded cable (min AWG20/22, 0.75/0.5mm²) via J11 on the controllers.
Communication is via an RS485 connection. Using correct shielded cable, units may be up to 200m apart.
32
92908135-17
UNIT ASSIST
In this mode the stand-by unit is enabled if the room temperature drifts out of limits, subject to a 3 Minute delay. This
allows the run unit to control the temperature, and not respond to fast transients.
Low temp alarm High temp alarm
Unit Run unit Run unit Unit
Assist heating cooling Assist
Heating cooling
1ºC 1ºC 1 ºC 1ºC 1ºC
1ºC Dead band 1ºC
Unit assist on Unit assist on
SETPOINT 20°C
This is a typical example: values will change for the run unit between one and two stage cooling, one and two stage heating,
L.P.H.W. and any combination depending upon conditions.
OPERATING INSTRUCTIONS
DESCRIPTION OF CONTROLS
All CD3 units are fitted with a microprocessor controller and display keypad, providing the functionality necessary for all
applications. Each unit is delivered tested, fully programmed and ready to run.
USER INTERFACE
The user interface is divided into 3 parts:
1. FIRST USER LEVEL, not protected by password, which allows the user to view monitored items, e.g. running
hours, display active /stored alarms and temperature /humidity set points.
2. SECOND USER LEVEL, protected by a password, which allows an authorised user to select various control
parameters including; set point limits, differentials and dead zones.
3. ENGINEERING LEVEL, protected by a password, allowing the commissioning/service/maintenance engineers
access to the time functions and hours run counters. This level also provides the facility for calibrating the
attached sensors and manually operating the fans, the cooling mode, the heating mode and the humidification
and de-humidification sequences during commissioning.
A fourth MANUFACTURES LEVEL, protected by password, is for configuring and programming the controller. This level
is only available to TEV and any changes to the operating software, which may be required for an individual application,
must be carried out by an TEV engineer.
PASSWORDS
A document is enclosed separately in the unit containing the passwords for the second level user and engineering levels.
This should be held by the installer and passed to the relevant person once the unit has been installed and
commissioned. Passwords may be altered by the user or Engineer, if changes are made ensure that a record of the new
passwords is kept in a safe location. Should passwords be lost, contact TEV Ltd. for assistance.
DISPLAY AND KEYPAD
The display/keypad is mounted on the front of the unit, connected by a 1.5m cable. It is fixed to the front panel of the unit
and if the panel is removed, the cable should be disconnected before moving the panel away from the unit.
33
92908135-17
00:00 00/00/00 Unit 1
Temperature 00.0 °C
Humidity 00.0%
Unit On
KEYPAD FUNCTIONS
KEY
FUNCTION
KEY
FUNCTION
1. Displays measured
values.
2. Returns operator to the
main mask window.
Setting of operating
parameters and safety
thresholds.
Displays working hours and
allows counter re-set.
Displays the version of the
application programme loaded
into the controller.
Not used.
Unit ON/OFF button.
The green LED is lit when the
unit is ON.
Displays current status of inputs
and outputs.
1. Displays alarm status.
2. Mute and reset alarms.
Red LED lit when alarm is
present.
Allows the time clock functions
to be displayed and
programmed.
Confirms data entry.
Yellow LED is lit when there is
power to the unit.
For setting and adjusting setpoints.
1. Toggle between display
screens.
2. Raise or lower set values.
Each function button has a green LED in the top left hand corner that is lit when the particular function button is operated.
This does not apply to the ON/OFF, ALARM and ENTER buttons that have LEDs as defined above.
34
92908135-17
Current time Date Mask Number
Actual
Temperature
and Humidity
Unit status
OPERATING SEQUENCE
00:00 00/00/00 M:01
TEMPERATURE 00.0°C
HUMIDITY 00.0%
UNIT ON
WORKING MODE
COOLING HEATING
HUMID DEHUMID
FAN HIGH LOW
AUTO RESTART
ACTUAL SET POINT
TEMPERATURE 21.0°C
HUMIDITY 50%
USER PASSWORD
0000
SET POINT
TEMPERATURE 21.0°C
HUMIDITY 50%
When the unit is first powered up the display will show; SELF TEST - PLEASE WAIT. Once the self test has been
completed the MAIN MASK will be displayed. This is the default screen.
The default screen will always be displayed during normal operation. To view the current operating mode of the unit:
Press or to toggle between the MAIN MASK and the WORKING MODE MASK.
SECOND USER LEVEL ACCESS (Password required)
SET BUTTON MENU
Press
To change parameters
To change screen
35
92908135-17
AUTO RESTART
AFTER BLACKOUT YES
ENABLE REMOTE ON/OFF YES
NEW USER
PASSWORD
0000
UNIT FAN SPEED
HIGH
SERVICE
PASSWORD
0000
LIMITS SET POINT TEMPERATURE:
MIN 15°C
MAX 30°C
LIMITS SET POINT HUMIDITY
MIN 20%
MAX 80%
TEMPERATURE
COOL DIFFER. 1.0°C
HEAT DIFFER. 1.0°C
DEAD BAND 0.5°C
HUMIDITY
BAND 7.5%
ENGINEERING LEVEL ACCESS (Password required)
PROGRAMME BUTTON MENU
Press
36
92908135-17
ALARM
DESCRIPTION
ALARM
DESCRIPTION
AL01
Compressor 1 General alarm
AL20
Return Air Temperature Probe Fault
AL02
Compressor 2 General alarm
AL21
Not used
AL03
Low Pressure Circuit 1
AL22
Not used
AL04
Low Pressure Circuit 2
AL23
Not used
AL05
Fan Fail (Serious alarm) Unit OFF
AL24
Return Air Humidity Probe Fault
AL06
Fan Overload (Serious alarm) Unit OFF
AL25
Not used
AL07
Heater 1 & 2 Over temperature
AL26
Not used
AL08
Not used
AL27
Not used
AL09
Smoke/Fire (Serious alarm) Unit OFF
AL28
Alarm E06 – Humidifier High Current
AL10
Filter Clog
AL29
Alarm E09 – Humidifier Low Water
TEMPERATURE ALARM
LOW OFF SET 5.0°C
HIGH OFF SET 5.0°C
HUMIDITY ALARM
LOW OFF SET 20%
HIGH OFF SET 20%
SEL. TYPE ALARM
S = SERIOUS N = NOT SERIOUS
AL01: NNNNS AL06: NNNS
AL10: NSSSS AL15: NNNN
SEL. TYPE ALARM
S = SERIOUS N = NOT SERIOUS
AL19: NSNNN AL24: SNNN
AL28: NNNNN AL33: NNSN
SEL. TYPE ALARM
S = SERIOUS N = NOT SERIOUS
AL37: N---- AL42: --- AL46: ------ AL51: ----
NEW USER
PASSWORD
0000
IDENTIFICAT. NUMBER
FOR THE SUPERVISORY:
001
The values shown in the above screen masks are the default settings when the unit leaves the factory.
ALARM DESCRIPTIONS
37
92908135-17
AL11
High Return Air temperature
AL30
Alarm E10 – Humidifier Low Current
AL12
Low Return Air temperature
AL31
Clock alarm
AL13
High Return Air humidity
AL32
High Pressure Circuit 1
AL14
Low Return Air humidity
AL33
High Pressure Circuit 2
AL15
Not used
AL34
Not used
AL16
Not used
AL35
Water Spill (Serious alarm) Unit OFF
AL17
Hours Run Compressor 1
AL36
Condensate High Level Cooling OFF
AL18
Hours Run Compressor 2
AL37
Humidifier Bottle Change
AL19
Hours run Fan
SERVICE
PASSWORD
0000
ENABLE AUTOMATIC
TEMPERATURE SET POINT
VARIATION
NO
TEMPERATURE
TIME ZONE N.1
START HOUR 00:00
SET POINT 00.0°C
TEMPERATURE
TIME ZONE N.2
START HOUR 00:00
SET POINT 00.0°C
TEMPERATURE
TIME ZONE N.3
START HOUR 00:00
SET POINT 00.0°C
TEMPERATURE
TIME ZONE N.4
START HOUR 00:00
SET POINT 00.0°C
REGULATION CLOCK
HOUR 00:00
DATE 00/00/00
DAY MONDAY
CLOCK BUTTON MENU
Press
38
92908135-17
ENABLE AUTOMATIC
HUMIDITY SET POINT
VARIATION
HUMIDITY
TIME ZONE N.1
START HOUR 00:00
SET POINT 000.0%
HUMIDITY
TIME ZONE N.2
START HOUR 00:00
SET POINT 000.0%
HUMIDITY
TIME ZONE N.3
START HOUR 00:00
SET POINT 000.0%
HUMIDITY
TIME ZONE N.4
START HOUR 00:00
SET POINT 000.0%
ANALOGUE INPUTS
RETURN AIR TEMPERATURE 21.0°C
RETURN AIR HUMIDITY 50.0%
DIGITAL INPUTS
C = CLOSE O = OPEN
01: CCCCC 06: CCCCC
11: -CCC
ANALOGUE OUTPUTS
COOL VALVE 00.0V
HEAT VALVE 00.0V
DIGITAL OUTPUTS
C = CLOSE O = OPEN
01: OOO 04: OOO
07: OOO 10: OOOO
Press to return to the MAIN MASK
INPUT /OUTPUT BUTTON MENU
Press
Only available when modulating
valves are fitted
39
92908135-17
WORK HOURS
FAN 000000
COMPRESSOR 1 000000
COMPRESSOR 2 000000
HISTORY ALARM 000
AL00 00:00 00/00/00
SET T: 00.0 T: 00.0
SET H : 000.0 H: 000.0
SERVICE
PASSWORD
0000
FAN
H. THRESHOLD 100 x 1000
RESET No 000000
COMPRESSOR 1
H. THRESHOLD 100 x 1000
RESET No 000000
COMPRESSOR 2
H. THRESHOLD 100 x 1000
RESET No 000000
PROBES SETTINGRETURN AIR HUMIDITY00.0%
PROBES SETTING
RETURN AIR TEMPERATURE 00.0°C
MANUAL PROCEDURE
WILL ONLY WORK
IN CONJUNCTION
WITH THE MAIN FAN
Press to return to the MAIN MASK
MAINTENANCE BUTTON MENU
Press
40
92908135-17
The manual operating procedure may only be activated when the unit is in standby mode.
MANUAL PROCEDURE
MAIN FAN NO
ENERGY SAVING NO
MANUAL PROCEDURE
DE-HUMIDIFIER NO
HUMIDIFIER NO
MANUAL PROCEDURE
COMP 1 / CW OPEN NO
COMP 2 / CW CLOSE NO
MANUAL PROCEDURE
HEAT 1 / LPHW OPEN NO
HEAT 2 / LPHW CLOSE NO
MANUAL PROCEDURE
COOL VALVE 00.0V
HEAT VALVE 00.0V
In this mode the ON/OFF button is in OFF.
Press to return to the MAIN MASK
NOTE:
Alarms and conditions referring to compressors, low pressure and high pressure are not relevant to Chilled Water units
unless an alternative Chilled Water option is displayed.
41
92908135-17
COMPONENT IDENTIFICATIONL
1
Coil 18
Filter 35
Electrics access
2
Drain tray
19
Transformer
36
Washable filter
3
Access panel
20
Discharge grille
37
Return air grille
4
Terminal
22
Relay 38
Humidity sensor
5
Contactor
24
Fan speed control
39
Isolator
6
Circuit breaker
25
Humidity control pcb
40
Temperature sensor
7
Condensate pump
26
Pressure switch
41
Vice latch
10
Heater element (2kW)
27
Grabber 42
Volt free pcb
11
Side panel assembly
28
Alarm indicator
43
Float switch
12
Swell latch
29
Touch control
44
High water level assembly
13
End stop
30
Humidifier assembly
45
Relay
14
Terminal
31
Membrane key pad
15
Heater cut out
32
Humidifier bottle
16
Blower assembly
33
Terminal 17
Fresh air fan
34
Panel surround
Note: The position of some of the controls shown in this diagram may vary from those in
the unit delivered.
42
92908135-17
DCU
ITEM No.
DESCRIPTION
ITEM No.
DESCRIPTION
1
Lid 13
Electrics access panel
2
Fan assembly
14
Handle
3
Right hand access panel
15
Suction service valve
4
Spire clip
16
Isolator
5
LP switch auto
17
End clamp
6
HP switch auto
18
Terminal
7
4 way terminal
19
Power board PCBA
8
Fused terminal
20
Overload (3 phase)
9
Compressor
21
Contactor
10
Crankcase heater
22
Fan capacitor
11
Expansion assembly (including restrictor)
23
Compressor capacitor (1 phase only)
12
Liquid service valve
COMPONENT IDENTIFICATION
43
92908135-17
CKC 30 – 100
ITEM No.
DESCRIPTION
ITEM No.
DESCRIPTION
ITEM No.
DESCRIPTION
1
Lid 15
Service valve
27
Motor
2
LP switch auto
16
Service valve
28
Fan
3
Contactor
17
Valve panel
30
Terminal end clamp
4
Overload (3 phase)
18
Base 31
Terminal
5
Heat exchanger
19
Mounting foot
32
Fuse
6
Rear access panel
20
Compressor
33
Fuse terminal
7
Mains terminal cover
21
Handle 34
Terminal 4 way
8
HP switch auto
22
Front access panel
35
Earth terminal
9
Fan capacitor
23
Fan guard
36
Fan speed controller
10
Switch bracket
24
Fascia panel
37
3 minute timer
11
Bulkhead panel
25
Corner panel
38
Compressor capacitor (1 ph)
14
Expansion assembly
26
Support bracket
39
Electrics box
Note: The fan, motor and fan guard are supplied as a single assembly.
44
92908135-17
ITEM No.
DESCRIPTION
ITEM No.
DESCRIPTION
ITEM No.
DESCRIPTION
1
Lid 13
HP switch auto
26
Handle
2
Fuse terminal
14
Switch bracket
27
Front access panel
3
Fuse 15
LP switch auto
28
Fan guard
4
Terminal
16
Switch bracket
29
Fascia panel
5
Terminal 4 way
17
Bulkhead panel
30
Support bracket
6
Contactor
19
Expansion assembly
31
Fan
7
Terminal
20
Service valve
32
Corner panel
8
Earth terminal
21
Service valve
33
Motor
9
Overload
22
Valve panel
35
Fan speed controller
10
Heat exchanger
23
Base 36
3 minute timer
11
Rear access panel
24
Mounting foot
37
Electrics box
12
Fan capacitor
25
Compressor
CKC 130 to 200
Note: The fan, motor and fan guard are supplied as a single assembly.
45
92908135-17
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.