Mars 70801 Installation And Operating Instructions Manual

Page 1
®
70801-IM 12/14/06 3:06 PM Page 1
Model 70801
INSTALLATION AND OPERATING INSTRUCTIONS
Non-Programmable Electronic Thermostat Heat/Cool
Page 2
70801-IM 12/14/06 3:06 PM Page 2
WARNING!
• To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
• Do not use this thermostat on applications with voltages above 30VAC.
• Wiring must conform to all local and national building/electrical codes and ordinances.
• Do not short (jumper) across terminals on the gas valve or at the system control to test the installation. This will damage the thermostat and void the warranty.
• This thermostat is equipped with automatic compressor protection to prevent damage due to short cycling. The short cycle protection provides a 5-minute delay between heating (heat pump models) or cooling cycles to prevent the compressor from being damaged.
• Do not switch the system to cool if the outdoor temperature is below 50 F (10 C). This may damage the cooling system and may cause personal injury.
• This thermostat should be used only as described in this manual.
SPECIFICATIONS
Electrical Rating: 24 Volt AC (18-30 VAC)
1 Amp Maximum per Terminal
2 Amps Total Load Control: 1 Heat / 1Cool Non-Heat Pump Set Point Range: 45 F – 90 F (7.0 C – 32.0 C) Accuracy: +/- 1 F (.5 C) Terminations: RC, RH, C, G, Y, W, B, O Power: 24VAC
2
Page 3
70801-IM 12/14/06 3:06 PM Page 3
Removing The Existing Thermostat
1) CAUTION: Make certain the power to the system has been disconnected.
2) Remove the cover of the old thermostat and locate the wires that are connected to the terminal board.
IMPORTANT: Before removing these wires, NOTE (ON A PIECE OF PAPER) THE COLOR OF EACH WIRE AND THE CORRESPONDING TERMINAL MARKING ON THE OLD THERMOSTAT.
3) Remove the wires from the terminals. Remove the old thermostat and mounting base from the wall.
Installing The New Thermostat
1) CAUTION: Make certain the power to the system has been disconnected.
2) If this is a new installation, locate the thermostat 4 to 5 feet above the floor in accordance with applicable
codes. Select a location that provides good airflow. Avoid locations in direct sunlight, near sources of heat, or near air vents. NOTE: The display is designed to be best viewed from a front downward angle.
3) Remove the back plate of the thermostat by gently depressing the bottom locking tab and swinging the back
plate up and away.
4) Place the back plate against the wall in the desired mounting location with the thermostat wires protruding
from the wall through the large rectangular whole in the back plate.
5) Mark placement of the (2) mounting holes (oval shaped holes in back plate) on the wall, remove the back
plate, and drill (2) 3/16” holes.
6) Tap supplied plastic anchors into the holes.
7) Secure the back plate to the wall with the supplied screws making certain the thermostat wires have been
inserted through the large rectangular hole in the back plate.
8) Carefully attach the thermostat wires to the appropriate connections on the terminal board on the back plate.
Use the notes taken from step 2 of Removing The Existing Thermostat to determine their location on the new thermostat. Reference wiring diagrams are available in the back of this manual.
9) Carefully place the thermostat body face down on a soft surface to expose the main circuit board. Gently set
the following switches in the correct position for the application.
3
Page 4
70801-IM 12/14/06 3:06 PM Page 4
GAS / ELECTRIC: Configures the thermostat to either gas/oil or electric heating systems.
C / F: Sets the display in either Celsius or Fahrenheit.
NORM / HP: Configures the thermostat for normal heating/cooling systems or heat pump systems (single
stage).
10) Attach the thermostat body to the back plate by resting the top of the thermostat body on the two clips on
the upper portion of the back plate. Then gently press the front body into place until the bottom locking tab snaps into place. NOTE: The terminal board pins must be properly aligned with the sockets on the terminal board (on the back plate) in order for the front body to properly snap into place.
11) Set the system switch to the OFF position.
12) Set the fan switch to the AUTO position.
13) Remove the clear plastic film from the display.
Testing The New Thermostat
WARNING!
Do not switch the system to cool if the outdoor temperature is below 50 F (10 C). This may damage the
cooling system and may cause personal injury.
This thermostat is equipped with automatic compressor protection to prevent damage due to short cycling.
The short cycle protection provides a 5-minute delay between heating (heat pump models) or cooling cycles to prevent the compressor from being damaged.
1) Restore the system power. The LCD (liquid crystal display) will dis-
play the room temperature. The LCD will illuminate at the touch of the red or blue arrow keys. LCD will return to its normal state after 10 seconds.
2) Set the fan switch to the ON position. The system blower should start.
3) Set the fan switch to the AUTO position. The system blower should stop.
4) Set the system switch to the HEAT position and depress the red arrow key until the temperature set point
is at least 3 degrees above the room temperature. The LCD will display a flame icon to indicate heat. The heating system should start within several seconds (the system blower may not come on immediate­ly).
Image shows room temperature of 78.
4
Page 5
70801-IM 12/14/06 3:06 PM Page 5
5) Set the system switch to the OFF position. The system should shut down within several seconds. The LCD will again display
Image shows room temperature of 70 and HEAT set point of 73.
only the room temperature.
6) Set the system switch to the COOL position and depress the blue arrow key until the temperature set point is at least 3 degrees below the room temperature. The LCD will display a
Image shows room temperature of 78 and A/C set point of 68.
snowflake icon to indicate A/C. The cooling system should start within several seconds. WARNING: Do not perform this test if the outdoor temperature is below 50 F.
7) Set the system switch to the OFF position. The system should shut down within several seconds. The LCD will again display only the room temperature.
Programming The User Settings
Temperature Differential is factory set at .5 F (0.25 C) for both heating and cooling cycles. The room tempera-
ture must change .5 F (0.25 C) from the set point temperature before the thermostat will initiate a call for heat or A/C. This should be appropriate for most applications. However, if the system is cycling on and off too frequently, the setting can be adjusted as follows.
1) With the system setting in the OFF position, simultaneously depress the red and blue arrow keys. The LCD (liquid crystal display) will display the temperature differential setting. Using
Image shows temperature differential setting of 0.5.
the red and blue arrow keys set the differential to the desired setting of .5, 1, or 2. The higher the setting, the less frequent­ly the system will cycle.
2) When the desired setting is made, release the key and the unit will automatically store the setting after 5 sec­onds.
5
Page 6
70801-IM 12/14/06 3:06 PM Page 6
Operating The New Thermostat
1) Set the System switch to either the HEAT or COOL position and the Fan switch to either the AUTO or ON
position. NOTE: In AUTO, the system blower will run only when the A/C or heat is running. In ON, the system blower will operate continuously.
2) Use the red and blue arrow keys to select the desired temperature set point.
3) The LCD (liquid crystal display) displays the room temperature on
the left and the set point temperature on the right. Note: The set point temperature may sometimes differ slightly from the room temperature due to a rapidly changing room temperature or a dif­ferential setting of 1 or 2.
Image shows room temperature of 78 and A/C set point of 68.
Understanding Additional Features
High Temperature Protection: While in the HEAT position, if the room temperature reaches 93 F (34 C),
the thermostat will automatically shut off. In the unlikely event the room temperature reaches 99 F (37 c), a mechanical bimetal switch will shut off the thermostat.
Low Temperature Protection: While in the HEAT position, if the room temperature drops below 40 F (4
C), the thermostat will automatically initiate a call for heat.
Compressor Protection: To protect the system compressor(s) from damage, the thermostat features a 5
minute delay. After the cooling system (or heat pump turns off), the thermostat will not allow it to re-start until the 5 minute delay expires. A blinking snowflake indicates this feature has been activated. Once the 5 minute delay expires, the snowflake will illuminate continuously and the system will be able to re-start when called upon.
NOTE: For the purpose of unit installation, this delay can be overridden by
depressing the RESET button. This will erase any programmed settings.
System Reset: The thermostat can be reset to factory software settings. All user entered settings will be
lost. The reset will also override the 5 minute compressor protection feature. To reset the thermostat, gen­tly press the reset button on the front panel using a paper clip or similar small pointed object.
6
Page 7
70801-IM 12/14/06 3:06 PM Page 7
Troubleshooting
SYMPTOM CORRECTIVE ACTION
Display is blank Check thermostat wiring & connections.
No heat Set system switch to HEAT and raise set point above room temperature.
No cool Set system switch to COOL and lower set point below room temperature
System turns on/off Adjust the differential setting on the thermostat. too frequently or A high differential decreases cycle rate and a low differential increases not enough cycle rate.
Display is not illuminated Touch the up or down arrow key. Display will illuminate for 10 seconds. Room temperature and Normal (depending on differential setting). set point disagree Check for drafts that could quickly change the room temperature
System fan runs continuously Set fan switch to AUTO.
HI is displayed Reduce room temperature or allow a newly installed thermostat to
LO is displayed Increase room temperature or allow a newly installed thermostat to
Check circuit breaker/fuse panel.
Check thermostat wiring and connections. Check pilot light or HSI system on furnace.
If snowflake is blinking, allow the 5 minute compressor lock-out to expire. Check thermostat wiring & connections.
before the system is able to correct it.
Check thermostat wiring & connections.
acclimate. HI indicates a room temperature reading greater than 90 F (32 C).
acclimate. LO indicates a room temperature reading less than 45 F (7 C).
7
Page 8
Typical 4-Wire System
RC RH
C
G
Y
WBO
FAN
CONTROL
HEAT
CONTROL
Install Jumper
24 VAC
TRANSFORMER
COOL
CONTROL
COM
HOT
70801-IM 12/14/06 3:06 PM Page 8
Wiring Diagrams
8
Page 9
Typical 5-Wire System
RC RH
C
G
Y
WBO
FAN
CONTROL
HEAT
CONTROL
COOL
CONTROL
HEAT 24 VAC
TRANSFORMER
COM
HOT
COOL 24 VAC
TRANSFORMER
COM
HOT
70801-IM 12/14/06 3:06 PM Page 9
Wiring Diagrams
9
Page 10
Typical 2-Wire Millivolt System
RC RH
C
G
Y
WBO
HEAT
CONTROL
24 VAC
TRANSFORMER
COM
HOT
Typical Single Stage Heat Pump System
RC RH
C
G
Y
WBO
FAN
CONTROL
COMPRESSOR
CONTROL
REV. VALVE
COOL ENERGIZED
REV. VALVE
HEAT ENERGIZED
24 VAC
TRANSFORMER
COM
HOT
Install Jumper
Install Jumper
70801-IM 12/14/06 3:06 PM Page 10
Wiring Diagrams
10
Page 11
70801-IM 12/14/06 3:06 PM Page 11
Warranty
ONE YEAR LIMITED WARRANTY
Motors & Armatures Inc. warrants each new MARS thermostat against any defects due to non-conforming material or workmanship for a period of one year after the original date of purchase by a professional service technician and does not include the cost of removal or re-installation. This warranty extends to the contractor or dealer who purchased the product from a wholesaler. For warranty claims, consumers should contact the contractor or dealer who installed the thermostat.
This warranty and Motors & Armatures’ liability does not include damage to merchandise or thermostat resulting from accident, alteration, neglect, misuse, improper installation, or any other failure to follow Motors & Armatures’ installation and operating instructions. Contact Motors & Armatures Inc. for full details on product warranty policy.
Motors & Armatures Inc.
250 Rabro Drive East
Hauppauge, NY 11788
11
Page 12
®
70801-IM 12/14/06 3:06 PM Page 12
INSTALLATION AND OPERATING INSTRUCTIONS
Non-Programmable Electronic Thermostat Heat/Cool
Model 70801
Loading...