Mars 39004 User Manual

®
Klixon Fan & Limit Switches
FAN COIL UNIT
HEATING
SIDE
LINE VOLTAGE
OPERATION
GND
LINE HOT
ROOM THERMOSTAT
COOLING SIDE
RETURN LINE
MOTORIZED VALVE
SUPPLY LINE
HOT OR COLD WATER
SL-8 CHANGE-OVER
SWITCH
➀ ➁ ➂
ORANGE COMMON
BLUE HEAT
RED COOL
LOW VOLTAGE TRANSFORMER
LINE
TO ROOM
THERMOSTAT
TO MOTORIZED
VALVE
LOW VOLTAGE OPERATION
®
MARS SERIES 390
Change-Over Switches for Fan-Coil Systems
COMPONENT
39004
39005
Leads thru top
1/2” conduit adapter
The MARS Series 390 change-over switches are used for summer-winter change-over of electric thermo-stats in hydronic heating - cooling fan-coil units.
Features:
Color coded lea ds allow easy installation
• SL-8 thermostat is enclosed in sealed case for trouble-free operation
• Snap-acting disc type, insures accurate temperature repeatability
• Can be mounted in any position
• UL and CSA listings available
Installation
The SL-8 change-over switch is located on the main run of the supply line where it can quickly sense the maximum temperature of the hot or cold water passing through. If the SL­8 switch is exposed to surrounding temperatures, thermal insulation should be wrapped around the switch case to maintain desired thermal response.
Specifications:
Pipe size: 5/8 in O.D. Leads: 12 in. color coded Switch Action: SPDT Temperature: 88°F (31°C)—terminals 1 & 2 close, 1 & 3
open 73°F (23°C)—terminals 1 & 3 close, 1 & 2 open Mounting: mounting clip supplied with each kit Electrical: terminals 1 & 3 25 amp at 120/240 VAC Terminals 1 & 2 10 amp at 120 VAC, 5 amp at 240 VAC
MARS KLIXON KLIXON
NO. KIT NO. NO. DESCRIPTION
39004 SL8-5 20425D27-160-356 leads thru
39005 SL8-5A 20425D69-160-287 leads thru top
Cross Reference
C-56
HONEYWELL MARS RODGERS MARS
NO. REPLACEMENT NO. REPLACEMENT
L6076A 39004 752-1 39004 L6076B 39005 752-2 39005