Marley Engineered Products MUH0381, MUH0321, MUH0371, MUH0341, MUH0581 Installation Manual

...
MUH Series
Modular Unit Heaters
Installation, Operation & Maintenance Instructions
Specifications
asic Model Height Width Depth Weight Compartment
B No. in (mm) in. (mm) in. (mm) lbs. (kg) Volume
MUH0381 27 (12.2)
UH0321 27 (12.2)
M MUH0371 27 (12.2) MUH0341 30 (13.6) MUH0581 27 (12.2) MUH0521 MUH0571
16 14 7
(406.4) (355.6) (190.5)
MUH0541 30 (13.6) MUH0331 30 (13.6) MUH0361 30 (13.6) MUH0531 30 (13.6) MUH0561 30 (13.6) MUH078 38 (17.2) MUH072 38 (17.2) MUH077 38 (17.2) MUH074 38 (17.2) MUH108 MUH102
3
/
4
19 71/
21
(552.5) (482.6) (190.5)
MUH107 38 (17.2) MUH104 38 (17.2) MUH073 38 (17.2) MUH076 38 (17.2) MUH103 38 (17.2) MUH106 38 (17.2)
Mounting Wiring
1
27 (12.2)
/
2
27 (12.2)
38 (17.2) 100 in
2
38 (17.2)
90 in
(14.70 cm
(1639 cm
ounting Wiring
Basic Model Height Width Depth Weight Compartment
M
MUH158 54 (24.5) MUH152 50 (22.7) MUH154 50 (22.7) MUH208 MUH202
3
MUH204 55 (24.9)
3
)
MUH156 55 (24.9)
3
21
/
19 123/
4
(552.5) (482.6) (323.9)
60 (27.2)
4
55 (24.9)
140 in
(2295 cm
3
3
)
MUH206 55 (24.9) MUH252 89 (40.4) MUH254 89 (40.4) MUH308 MUH302 MUH304 89 (40.4)
30 26
(76.2) 676.4) (298.5)
5
/
113/
8
89 (40.4)
3
4
89 (40.4)
504 in
(8260 cm
3
)
MUH256 89 (40.4) MUH306 89 (40.4) MUH402 119 (54.0)
3
MUH404 119 (54.0)
3
)
MUH508 MUH502 MUH504 119 (54.0)
30 26
(76.2) 676.4) (435.1)
5
/
8
171/
4
119 (54.0) 119 (54.0)
648 in
(10620 cm
3
3
)
MUH406 119 (54.0) MUH506 119 (54.0)
ECR 40559 07/15 5200-11106-001
IMPORTANT INSTRUCTIONS
WARNING
WHEN USING ELECTRIC APPLIANCES, BASIC PRECAU­TIONS SHOULD ALWAYS BE FOLLOWED TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, AND INJURY TO PER­SONS, INCLUDING THE FOLLOWING:
1. Read all instructions before installing or using this heater.
2. This heater is a commercial/industrial product not intended for use in a residential setting.
3. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture, pillows, bedding, papers, clothes, etc. and curtains at least 3 feet (0.9 m) from the front of the heater.
4. Extreme caution is necessary when any heater is used by or near children or invalids and whenever the heater is left operating and unattended.
5. This heater has hot and arcing or sparking parts inside and is not intended for use in hazardous atmospheres where flammable vapors, gases, liquids or other combustible atmospheres as defined in the National Electrical Code are used or stored. Failure to comply can result in explosion or fire.
6. Do not operate any heater after it malfunctions. Disconnect power at service panel and have heater inspected by a rep­utable electrician before using.
!
7. Do not use outdoors.
8. To disconnect heater, turn controls to off, and turn off power to heater circuit at main disconnect panel.
9. Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock, fire, or damage to the heater.
10. To prevent a possible fire, do not block air intake or exhaust in any manner.
11. Use this heater only as described in this manual. Any other use not recommended by the manufacturer may cause fire,
12. This heater is not intended for use in special environments. Do not use in damp or wet locations such as marine or greenhouse or in areas where corrosive or chemical agents are present.
13. When installing, see INSTALLATION INSTRUCTIONS for additional warnings and precautions.
14. For safe and efficient operation, and to extend the life of your heater, keep your heater clean - See MAINTENANCE INSTRUCTIONS.
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
WARNING
To prevent a possible fire, injury to persons or damage to the heater, adhere to the following:
1. Disconnect all power coming to heater at main service panel before wiring or servicing.
Important Note: This heater must be installed by a qualified person.
2. All wiring procedures and connections must be in accor­dance with the National and Local Codes having jurisdiction and the heater must be grounded.
3. Verify the power supply voltage coming to heater matches the ratings as shown on the heater nameplate.
CAUTION: ENERGIZING HEATER AT A VOLTAGE GREATER THAN THE VOLTAGE PRINTED ON THE NAMEPLATE WILL DAMAGE THE HEATER AND VOID THE WARRANTY AND COULD CAUSE A FIRE.
Heater Location Instructions
Arrange units so that discharge air streams: a. are subjected to a minimum of interference from columns,
machinery and partitions; b. wipe exposed walls without blowing directly at them; c. are directed away from room occupants in comfort heating; d. are directed along the windward side when installed in a
building exposed to a prevailing wind.
!
4. To reduce the risk of fire, do not store or use gasoline or other flammable vapors and liquids in the vicinity of the heater.
5. The ceiling or wall mounting structure and the anchoring provisions must be of sufficient strength to support the com­bined weight of the heater and mounting bracket.
6. All built-in thermostats: If the heater is used to prevent pip­ing or liquids from freezing, and if the thermostat is set below 45° F (7°C), the fan must run continuously.
7. The heater must be mounted at least 7’ (2134 mm) above the floor to avoid accidental contact with the fan blade which could cause injury.
8. Keep at least 5’ clearance in front of the heater. Refer to Table 1 for side, top and back clearance requirements.
9. Do not mount mercury type thermostat directly on unit. Vibration could cause heater to malfunction.
Locate thermostats approximately 5' (1524mm) above the floor on interior partition walls or post away from cold drafts, internal heat sources and away from heater discharge air streams.
Small rooms can be heated by one unit heater. Large rooms require multi-unit installations. Number and capaci-
ty of units will be determined by volume of building and square feet of floor area to be heated. Arrange units to provide perimeter air circulation where each unit supports the air stream from another.
2
Mounting the Heater - General
A
B
C
D
The heater may be mounted to discharge the heated air either horizontally or vertically. When the heater is mounted for vertical discharge, it is recommended that the heater be positioned so that the access door will open away from the wall to provide greater access to the wiring and control compartment. If the heater is to be mounted with the access door facing a wall, the heater must be mounted far enough from that wall to allow full opening of the access door (a distance approximately equal to the width of the heater, check clearance before installing). Refer to Table 1 for wall and ceiling clearances before mounting heater.
The heater may be mounted for either vertical or horizontal dis­charge by the use of threaded rods. (Refer to Table 2 for thread­ed rod sizes required.) Observe the detailed procedures in the following installation instructions.
Horizontal Discharge (Rod-mount from Ceiling)
1. Install four threaded mounting rods in the threaded holes and secure in place using lock nuts. (See Table 2).
2. Securely attach the four mounting rods to the ceiling. (Refer to Table 1 for wall and ceiling clearances, and Table 2 for mounting rod spacing).
Table 3. Rod Thread and Spacing Dimensions, inches (mm)
for Vertical Discharge
Rod Thread
Unit Type EFGH
3 - 5 kW
7.5 - 20 kW
145/
3
/
4
8
24
25
69
152.4) 247.7) (50.8) (103.1)
5
/
- 18
6
1
(
7
8
/
8
225.6) (371.6) (50.8) (130.3)
(
1
/
16
1
/
8
The heater may also be suspended from the wall or ceiling by means of an optional mounting bracket (type MMB or MCMB) which permits horizontal pivoting of the heater.
After the heater is installed, the louvers may be positioned to direct the heated air in the desired direction. When the heater is installed for horizontal discharge, the louvers should direct the air either straight ahead or downward. Directing the air upward may cause the heated air to remain in the ceiling area and waste energy.
Table 1. Wall and Ceiling Clearance, inches (mm)
nit Discharge Ceiling Side Wall Back Wall
U
Horiz. 2 (50.8) 6 (152.4) 9 (228.6)
3 & 5 kW
Vert. 6 (152.4) 18 (457.2) 18 (457.2)
Horiz. 6 (152.4) 6 (152.4) 13 (330.2)
7.5 to 10 kW
15 to 10 kW
25 to 50 kW
MOUNTING ROD
LOCK NUT
B A C K
W A L L
Vert. 6 (152.4) 24 (609.6) 24 (609.6)
Horiz. 6 (152.4) 9 (228.6) 12
1
/2(317.5)
Vert 6 (152.4) 24 (609.6) 24 (609.6)
Horiz. 16 (406.4) 12 (304.8) 18
1
/2(470.0)
Vert. 12 (304.8) 39 (914.4) 39 (914.4)
CEILING
UNIT HEATER
THREADED
OUNTING
M HOLES
A
BACK WALL
B
(TOP VIEW)
D
C
S I D E
W A L L
Figure 1. Horizontal Discharge Mounting and Spacing.
Table 2. Rod Thread and Spacing Dimensions, inches (mm)
for Horizontal Discharge
Rod Thread
Unit Type ABCD
1
51/
/
16
16
16
3 - 5 kW
7.5 - 10 kW
5
/16- 18
15 - 20 kW
25 - 30 kW
3
/8- 16
40 - 50 kW
61/
16
(153.9)
3
/
11
(289.0)
9
10
/
16
(268.2) (368.3) (157.2) (16.0)
1515/
(404.9) (368.3) (157.2) (16.0)
64
(152.4) (103.1) (19.0)
87/
8
(225.6) (130.3) (19.0)
8
14 - 12 63/
14 - 12 63/
16
3
/
4
3
8
/
4
5
/
8
5
/
8
25 - 30 kW
CEILING
ACCESS DOOR
B A C K
W A L L
CLEARANCE EQUAL TO WIDTH OF HEATER TO PERMIT FULL OPEN­ING OF THE ACCESS DOOR
Figure 2. Vertical Discharge Mounting and Rod Spacing
Vertical Discharge (Rod-Mount from Ceiling)
1. Remove bolts from the threaded holes in the back of the heater.
2. Install four threaded mounting rods in the threaded holes and and secure in place using lock nuts.
3. Securely attach the four mounting rods to the ceiling. (Refer to Table 1 for wall and ceiling clearances, and Table 3 for mounting rod spacing dimensions.)
Wiring Branch Circuit (Power)
1. Connect heater only to the voltage, amperage and frequency specified on the nameplate.
2. Field wiring must be properly sized to carry the amperage in accordance with the NEC.
3. The access door is hinged. There are either one or two screws accessible from the side that must be loosened to gain access. These screws are the captive type; do not try to remove them.
4. A knockout is provided in the back of the heater close to the power terminal block and the control terminal board. The con­trol terminal board knockout is 1/2 inch (12.7 mm) conduit size. The power terminal block knockout is multiple diameter. Use the diameter that fits the required conduit size.
5. A ground terminal is provided near the power terminal board. The ground wire should be connected before other connections are made.
6. The power terminal block is equipped with box terminals sized to accept the correct size power supply wire. Branch circuit wire rated min 600V, 60° C is acceptable for heaters rated up to 80 amps. For heaters rated more than 80 amps, branch circuit wire must be rated at least 75°C. Either aluminum or copper wire is satisfactory for connection to the heater power terminal block box terminal. Copper wire is recommended and must be used with built-in disconnect switch.
3
LOCK NUT
3
/8- 16
1
14
/
211/
2
368.3) (539.8) (56.0) (157.2)
(
MOUNTING ROD (4)
THREADED MOUNTING HOLES
G
(TOP VIEW)
23/
4
16
ACK WALL
B
E
63/
16
S I D E
W
F
A L L
H
7. Each heater has a wiring diagram affixed to the inside of the
A
B
LEAD WIRE
"B1"
ELEMENTS
CONTACTOR
(OR P2)
POWER TERMINAL BLOCK
HEATER FRONT
LEAD WIRE
"A1"
3 PHASE BLOCK
TO ELEMENTS
A
B
LEAD WIRE
"B1"
ELEMENTS
CONTACTOR
(OR P2)
POWER TERMINAL BLOCK
HEATER FRONT
LEAD WIRE
"A1"
3 PHASE BLOCK
TO ELEMENTS
FACTORY-WIRED FOR SINGLE-PHASE POWER FIELD-WIRED FOR THREE-PHASE POWER
B
3 PHASE BLOCK
FACTORY-WIRED FOR SINGLE-PHASE POWER
C
1
D
1
D
1
C
1
C
D
B
C
D
3 PHASE BLOCK
B
3 PHASE BLOCK
FIELD-WIRED FOR THREE-PHASE POWER
C
1
D
1
D
1
C
1
C
D
B
C
D
3 PHASE BLOCK
access door. Consult this diagram before making any field connections.
Important Note - Installation Screw Lug Torque:
During transportation it is possible screw lug connections can loosen. After installation, before power is turned on to the heater, check all screw lug connections for tightness to a recommended minimum torque of 35 in-lbs. (3.9 N-m). Loose connections may present a hazard.
8. Single or three-phase power connections may be used with heater models MUH0521, MUH0581, MUH072, MUH078, MUH102, MUH108, and MUH158. These units are factory wired for single-phase operation. If these heaters are for use with three-phased power, reconnect the wires as indicat­ed in the wiring diagram attached to the heater. Additional information can be found by looking at the wiring illustrations in Figures 3a and 3b and following the directions shown below.
On models MUH0521,MUH0581, MUH072, MUH078, MUH102, and MUH108 (Figure 3a), move only the two wires marked “A1” and marked “B1”; do not move or change any other wiring. The element lead wire marked “B1” which is factory connected to the power terminal block (terminal located closest to the elements) must be moved to terminal “B” on the three-phase terminal block.
Figure 3a. Wiring Connections for Single-Phase and Three -Phase Power(MUH0521, MUH0581, MUH072, MUH078, MUH102 and MUH108)
Figure 3b. Wiring Connections for Single-Phase and Three -Phase Power (MUH158)
4
The relay (contactor) lead wire “A1” must be moved from the end
MT-1
MT-2
2-STAGE INTERNAL THERMOSTAT
BLACK
RED
RED
BLACK
P2
H2
F 1
F 2
S
REMOTE SUMMER FAN SWITCH (MRFS-1) OR SUMMER FAN SWITCH MCFS (MANUAL)
P1
H1
T
T
MT-1
MT-2
BLACK TO W1
RED TO R
2-STAGE INTERNAL THERMOSTAT
MHRT HEAT RECOVERY THERMOSTAT OR REMOTE FAN SWITCH (MRFS-2)
BLACK
RED
RED
BLACK
C
RW1
W2
F 2
F 1
G
T R
T
S
S
REMOTE SUMMER FAN SWITCH (MRFS-1)
FAN RELAY (FOR MRFS-2 AMD MHRT)
SUMMER FAN SWITCH
terminal of the power terminal block (terminal closest to the con­tactor or control terminal board) to the “A” terminal of the lower terminal block (center terminal).
Model MUH158 (Figure 3b) has two three-phase terminal blocks located adjacent to the relays (contactors). Move only the two wires marked “C1” and “D1” on each of these two three-phase terminal blocks to terminal “B”. Do not move or change any other wires.
9. Electrical Accessories, either kits or factory-installed options, are shown connected by a dash line on the heater wiring diagram.
10. 208/240 VOLT HEATER: The heaters are wired for 240V from factory. When heater is to be connected to 208V sup­ply, the transformer leads MUST BE interchanged. For units rated 30/40kW or higher, interchange ORANGE and RED primary leads. The black colored lead is the COMMON for the transformer (50VA) provided with the high wattage units. For lower kW rated heaters, interchange BLACK and RED primary leads. The WHITE colored lead is the COMMON for the control transformer provided with these heaters. Always refer to the wiring diagram on the cover of the heater before making this reconnection of tranformer primary leads.
Control Wiring
LINE VOLTAGE IS PRESENT ON SOME OF THE TERMINALS ON THE CONTROL TERMINAL BOARD. ALWAYS DISCON­NECT THE POWER FROM THE HEATER BEFORE MAKING ANY CONNECTIONS TO THE CONTROL BOARD TO PRE­VENT ELECTRIC SHOCK HAZARD.
1. Use min. 600 volts, NEC Class 1 insulated wire for all control circuit wiring.
2. Use a crimp-on type fork terminal on the wire ends that attach to the control terminal board if more than one connec­tion is to be made under the terminal screw.
3. On units not
provided with internal contactor (3 & 5 KW),
refer to Figure 4 for wiring diagram.
NOTE: Thermostat and control circuit wiring must be suitable to handle the full load of the heater (example MUH0581 is rated 24 amps)
4. On units provided with internal contactor (units rated 7 KW and higher) refer to Figure 5 for wiring diagram. Control wiring must be rated minimum 18 AWG.
OPERATING
Figure 4. Control Terminal Board (for Heaters Without Contactors)
Figure 5. Control Terminal Board (for Heaters With Contactors)
INSTRUCTIONS
1. Heater must be properly installed before operation.
2. Turn power supply to heater “ON” at main switch panel.
3. Where applicable, refer to control accessory instructions regarding proper operation of any controls or accessories used with the heater.
NOTES:
1. THIS STYLE CONTROL TERMINAL BOARD USED WITH MODELS
MUH0321, MUH0371, MUH0381, MUH0521, MUH0571, AND MUH0581.
2. WHEN UNIT IS WIRED FOR SINGLE-PHASE, JUMPER H1 TO H2.
IF SINGLE-POLE THERMOSTAT IS USED WITH SINGLE-PHASE UNIT, CONNECT THERMOSTAT LEADS TO P1 AND H1.
3. EXTERNAL LINE VOLTAGE THERMOSTATS SHOULD BE TREAT-
ED AS SINGLE STAGE ONLY.
NOTES:
1. THIS STYLE CONTROL TERMINAL BOARD USED WITH MODELS EXCEPT MUH0321, MUH0371, MUH0381, MUH0521, MUH0571, AND MUH0581.
2. REMOVE JUMPER W1 TO W2 WHEN 2-STAGE THER­MOSTAT IS USED.
3. *ONLY ONE OF THESE ACCESSORIES MAY BE INSTALLED IN A SINGLE HEATER.
4. EXTERNAL LINE VOLTAGE THERMOSTATS SHOULD BE TREATED AS SINGLE STAGE ONLY.
5
How To Reset Over -Temperature Safety Control (Factory Installed Option Only.):
The limit switch is located internally on the rear of the heater. On the 3KW and 5KW models, the access to the reset button is on the right side (when facing rear of heater); on all other mod­els it is near the top rear of the heater.
The manual reset limit is in series with the automatic recycling protector (limit). The manual reset limit will not reset until the heater has cooled and the button is pushed in.
DO NOT TAMPER WITH OR BYPASS ANY SAFETY LIMITS INSIDE HEATER.
CAUTION - DO NOT CONTINUE TO ATTEMPT TO USE THE HEATER IF THE SAFETY CONTROL REPEATEDLY OPER­ATES AFTER BEING RESET. TO DO SO COULD PERMA­NENTLY DAMAGE THE HEATER OR CREATE A FIRE OR SAFETY HAZARD.
It is important to keep this heater clean. Your heater will give you years of service and comfort with only minimum care. To assure efficient operation follow the simple instructions below.
ALL SERVICING BEYOND SIMPLE CLEANING THAT REQUIRES DISASSEMBLY SHOULD BE PERFORMED BY QUALIFIED SERVICE PERSONNEL.
MAINTENANCE INSTRUCTIONS
It is important to keep this heater clean. Your heater will give you years of service and comfort with only minimum care. To assure efficient operation follow the simple instructions below.
ALL SERVICING BEYOND SIMPLE CLEANING THAT REQUIRES DISASSEMBLY SHOULD BE PERFORMED BY QUALIFIED SERVICE PERSONNEL.
TO REDUCE RISK OF FIRE AND ELECTRIC SHOCK OR INJURY, DISCONNECT ALL POWER COMING TO HEATER AT MAIN SERVICE PANEL AND CHECK THAT THE ELEMENT IS COOL BEFORE SERVICING OR PERFORMING MAINTENANCE.
User Cleaning Instructions:
1. After the heater has cooled, a vacuum cleaner with brush attachment may be used to remove dust and lint from exterior surfaces of the heater including the grille openings.
2. With a damp cloth, wipe dust and lint from grille and exterior surfaces.
3. Return power to heater and check to make sure it is operat­ing properly.
TO REDUCE RISK OF FIRE AND ELECTRIC SHOCK OR INJURY, DISCONNECT ALL POWER COMING TO HEATER AT MAIN SERVICE PANEL AND CHECK THAT THE ELEMENT IS COOL BEFORE SERVICING OR PERFORMING MAINTENANCE.
User Cleaning Instructions:
1. After the heater has cooled, a vacuum cleaner with brush attachment may be used to remove dust and lint from exterior surfaces of the heater including the grille openings.
2. With a damp cloth, wipe dust and lint from grille and exterior surfaces.
3. Return power to heater and check to make sure it is operat­ing properly.
Maintenance Cleaning Instructions:
(To be performed only by Qualified Service Personnel)
At least annually, the heater should be cleaned and serviced by a qualified service person to assure safe and efficient operation. This should include as necessary, vacuuming dust and debris from the elements and fan, and checking all screw lug connec­tions for tightness to a recommended minimum torque of 35 in­lbs. (3.9 N-m). After completing the cleaning and servicing, the heater should be fully reassembled and checked for proper operation.
6
2
4
3
1
5
9
7
12
11
9
10
8
6
MUH
Built-in Controls
Key No. Description Part Number
1 Thermostat, One Pole (MT-1) 5813-0036-000
Thermostat, Two Stage (MT-2) 5813-0035-000
2 Knob, Thermostat 3301-0060-000
3 Label, Thermostat 3502-1781-000
4 Screws, Fl. Hd., 6-32 x 1/4 5202-7009-021
5 Clip, Thermostat 1403-0041-000
6 Switch, 25A, OEM 5216-0132-000
Switch, 25A, K & N 5216-0204-000
Switch, 63A, OEM 5216-0131-000
Switch, 63A, K & N 5216-0203-000
Switch 25A, Electro 5216-0200-000
7 Screw, M4 x 10, Rd. Hd., (25A)
Screw, 63A, M5 x 16, Rd. Hd.
8 Knob, 25A, OEM “T1” OEM “T1”
Knob, 25A, K & N K & N S1B 6001
nob, 63A, OEM OEM “S4”
K
nob, 63A, K & N K & N S2B G001
K
nob, Electro EI 141747
K
Switch, Toggle, 600V 5216-0130-000
9
10 Relay, Fan, 24V Coil 5018-0008-000
11 Switch Assembly 5216-0199-000
12 Manual Reset Limit 4520-0012-000
Heater Replacement Parts
ey No. Description Part Number
K
Spring, Element (used on MUH03 thru MUH-20 only) 5208-0073-000
1
pring, Element (used on MUH-25 thru MUH-50 only) 5208-0073-001
S Spring, Capillary Tube 5208-0072-000
2
Spring, Element Retainer 5208-0074-000
3
Switch (used on MUH-25 thru MUH-50 only) 5216-7076-001
4
Insulator (used on MUH-25 thru MUH-50 only) 2900-0031-000
5
Bracket Extension
6
(used on MUH-15, MUH-20, MUH-40 and MUH-50 only) 1215-0282-000 7 Switch Bracket 1215-0256-000 8 Fan Delay 4520-0010-000
14 Speed Nut 4100-7036-026 15 Bracket, Captive Screw (used on MUH-03 thru MUH-20 only) 1215-0291-000
Bracket, Captive Screw (used on MUH-25 thru MUH-50 only) 1215-0289-000
17 Protector, Linear Limit (used on MUH03 thru MUH05 only) 4520-0011-000
Protector, Linear Limit (used on MUH-07 thru MUH-20 only) 4520-0011-001
Protector, Linear Limit (used on MUH-25 thru MUH-50 only) 4520-0011-002
20 Clamp (used on MUH-20 thru MUH-50 only) 1417-5004-000
Bracket, Mounting Capacitor (used on MUH-20-8 only) 1215-0314-000
22 Terminal Lug (used on MUH-07 thru MUH-50 only) 3504-7002-001 25 Bushing (used on MUH-20 thru MUH-50 only) 25221-60131 26 Washer, Ground (used on MUH03 thru MUH05 only) 6401-0084-000 27 Screw, Ground (used on MUH03 thru MUH05 only) 5202-0290-002 28 Louver (used on MUH03 thru MUH05 only) 3503-0036-000
Louver (used on MUH-07 thru MUH-20 only) 3503-0036-001
Louver (used on MUH-25 thru MUH-50 only) 3503-0036-002
29 Spring, Louver 5208-7005-001 32 Terminal Block, 3-Phase (used on MUH05-21,
MUH-07-02,and MUH-10-2 only) 5823-0003-000
Terminal Block, 3-Phase (used on MUH05-81,
MUH-07-8, and MUH-15-8 only) 5823-0003-000
33 Terminal Doublers (used where required) 5819-7012-005
BUILT-IN CONTROLS — Made-to-Order Units Only
POWER
DISCONNECT
SWITCH
SINGLE-POLE
THERMOSTAT, TWO-STAGE
THERMOSTAT, HEAT
RECOVERY THERMOSTAT
SUMMER
FAN
SWITCH
7
7
8
9 10 11 12 13 16 18 19 21
odel No. Back Case Transformer** Motor Fan Blade Cover Front Case Element Assy. Element Guard Capacitor
M
UH03-21 1425-2004-000 3900-2002-006 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-000 2504-0011-000
M MUH03-41 1425-2004-000 5814-0003-002 3900-2005-000 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-002 2504-0011-000
UH03-71 1425-2004-000 3900-2002-007 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-001 2504-0011-000
M MUH03-81 1425-2004-000 3900-2002-006 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-024 2504-0011-000
MUH05-21MG 1425-2004-000 3900-2002-006 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-003 2504-0011-000
UH05-41 1425-2004-000 5814-0003-002 3900-2005-000 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-005 2504-0011-000
M MUH05-71 1425-2004-000 3900-2002-007 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-004 2504-0011-000 – UH05-81MG 1425-2004-000 3900-2002-006 1210-2000-000 1402-0336-001 1425-0009-005 1802-0087-025 2504-0011-000
M
UH-07-2 1425-0010-004 5814-0003-000 3900-2014-002 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-006 2504-0013-001
M MUH-07-4 1425-0010-004 5814-0003-002 3900-0347-005 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-008 2504-0013-001
UH-07-7 1425-0010-004 5814-0003-001 3900-2014-003 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-007 2504-0013-001
M MUH-07-8 1425-0010-004 5814-0003-000 3900-2014-001 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-031 2504-0013-001
MUH-10-2 1425-0010-004 5814-0003-000 3900-2014-002 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-031 2504-0013-001 – MUH-10-4 1425-0010-004 5814-0003-002 3900-0347-005 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-011 2504-0013-001 – MUH-10-7 1425-0010-004 5814-0003-001 3900-2014-003 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-010 2504-0013-001 – MUH-10-8 1425-0010-004 5814-0003-000 3900-2014-001 1210-0090-000 1402-0339-002 1425-0009-006 1802-0087-036 2504-0013-001
UH-15-2 1425-0014-000 5814-0003-000 3900-0361-000 1210-0090-001 1402-0339-003 1425-0009-007 1802-0087-012 2504-0012-001
M MUH-15-4 1425-0014-000 5814-0003-002 3900-0361-001 1210-0090-001 1402-0339-003 1425-0009-007 1802-0087-013 2504-0012-001 – MUH-15-8 1425-0014-000 5814-0003-000 3900-0361-002 1210-0090-001 1402-0339-003 1425-0009-009 1802-0087-031 2504-0012-001
UH-20-2 1425-0013-000 5814-0003-000 3900-0362-000 1210-0096-000 1402-0339-003 1425-0009-007 1802-0087-014 2504-0012-001 1432-0002-003
M MUH-20-4 1425-0013-000 5814-0003-002 3900-0362-001 1210-0096-000 1402-0339-003 1425-0009-007 1802-0087-015 2504-0012-001 1432-0002-003 MUH-20-8 1425-0013-000 5814-0003-000 3900-0362-002 1210-0096-000 1402-0339-003 1425-0009-011 1802-0087-026 2504-0012-001 1432-0002-003
MUH-25-2 1425-0011-003 5814-0003-000 3900-0364-000 1210-0098-000 1402-0340-002 1425-0012-003 1802-0087-016 2504-0014-001 1432-0002-001 MUH-25-4 1425-0011-003 5814-0003-002 3900-0363-001 1210-0098-000 1402-0340-002 1425-0012-003 1802-0087-017 2504-0014-001 1432-0002-003
UH-30-2 1425-0011-003 5814-0003-000 3900-0364-000 1210-0098-000 1402-0340-002 1425-0012-003 1802-0087-018 2504-0014-001 1432-0002-001
M MUH-30-4 1425-0011-003 5814-0003-002 3900-0363-000 1210-0098-000 1402-0340-002 1425-0012-003 1802-0087-019 2504-0014-001 1432-0002-003 MUH-30-8 1425-0011-003 5814-0003-000 3900-0364-000 1210-0098-000 1402-0340-002 1425-0009-009 1802-0087-028 2504-0014-001 1432-0002-001
UH-40-2 1425-0011-001 5814-0003-000 3900-0350-000 1210-0097-000 1402-0340-003 1425-0012-002 1802-0087-020 2504-0015-001 1432-0002-004
M MUH-40-4 1425-0011-001 5814-0003-002 3900-0350-001 1210-0097-000 1402-0340-003 1425-0012-002 1802-0087-021 2504-0015-001 1432-0002-004
MUH-50-2 1425-0011-001 5814-0003-000 3900-0350-000 1210-0097-000 1402-0340-003 1425-0012-002 1802-0087-022 2504-0015-001 1432-0002-004 MUH-50-4 1425-0011-001 5814-0003-002 3900-0350-001 1210-0097-000 1402-0340-003 1425-0012-002 1802-0087-023 2504-0015-001 1432-0002-004 MUH-50-8 1425-0011-001 5814-0003-000 3900-0350-002 1210-0097-000 1402-0340-003 1425-0012-002 1802-0087-030 2504-0015-001 1432-0002-004
23 24 30 31 34 35
Model No. Relay*** Insulator Terminal Block, Power Terminal Block, Control Fuse Block Fuse
MUH03-21 ––5823-0004-000 5823-0001-000 –– MUH03-41 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH03-71 2900-0030-000 5823-0004-000 5823-0001-000 –– MUH03-81 ––5823-0004-000 5823-0001-000 ––
MUH05-21MG 5018-0003-002 5823-0004-000 5823-0002-000 ––
MUH05-41 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH05-71 2900-0030-000 5823-0004-000 5823-0001-000 ––
MUH05-81MG 5018-0003-002 5823-0004-000 5823-0002-000 ––
MUH-07-2 5018-0003-000 5823-0004-000 5823-0002-000 –– MUH-07-4 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH-07-7 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH-07-8 5018-0003-000 5823-0004-000 5823-0002-000 ––
MUH-10-2 5018-0003-000 5823-0004-000 5823-0002-000 –– MUH-10-4 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH-10-7 5018-0003-000 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH-10-8 5018-0004-100 5823-0004-000 5823-0002-000 ––
MUH-15-2 5018-0005-004 5823-0004-001 5823-0002-000 –– MUH-15-4 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH-15-8 5018-0005-008 5823-0004-003 5823-0002-000 2025-0002-000 2019-0007-010
MUH-20-2 5018-0006-000 5823-0004-002 5823-0002-000 –– MUH-20-4 5018-0004-100 2900-0030-000 5823-0004-000 5823-0002-000 –– MUH-20-8 5018-0005-000 5823-0004-002 5823-0002-000 2025-0002-000 2019-0007-008
MUH-25-2 5018-0005-004 5823-0004-002 5823-0002-000 2025-7002-000 2019-7008-077 MUH-25-4 5018-0005-004 2900-0030-000 5823-0004-001 5823-0002-000 ––
MUH-30-2 5018-0005-004 5823-0004-003 5823-0002-000 2025-7002-000 2019-7008-079 MUH-30-4 5018-0005-004 2900-0030-000 5823-0004-001 5823-0002-000 –– MUH-30-8 5018-0006-000 5823-0005-000 5823-0002-000 2025-7002-000 2019-7008-080
MUH-40-2 5018-0005-004 5823-0005-000 5823-0002-000 2025-7002-000 2019-7008-079 MUH-40-4 * 2900-0030-000 5823-0004-002 5823-0002-000 2025-7002-000 2019-7008-079
MUH-50-2 5018-0005-004 5823-0005-000 5823-0002-000 2025-7002-000 2019-7008-080 MUH-50-4 * 2900-0030-000 5823-0004-002 5823-0002-000 –– MUH-50-8 5018-0006-000 5823-0005-000 5823-0002-000 2025-7002-000 2019-7008-078
* Two relays are used: 35A relay P/N 5018-0004-000 and 40A relay P/N 5018-0006-000.
** 24V secondary shown. For 120V secondary, increase last digit by 3. (i.e. for MUH03-41, 24V secondary use 5814-0003-002; for 120V secondary use 5814-0003-005.)
*** 24V H.C. shown. For 120 H.C., increase last digit by 1. (i.e.: for MUH03-41, 24V H.C. use 5018-0004-000; for 120V H.C. use 5018-0004-001.)
9
Loading...
+ 21 hidden pages