Marley Engineered Products M Series User Manual

Dear Owner, Congratulations! Thank you for purchasing this new heater by Marley Engineered Products. You have made a wise invest-
ment selecting the highest quality product in the heating industry. Please carefully read the installation and maintenance instructions shown in this manual. You should enjoy years of efficient heating comfort with this product from Marley Engineered Products... the industry’s leader in design, manufacturing, quality and service.
... The Employees of Marley Engineered Products
Installation & Maintenance Instructions
Read Carefully - These instructions are written to help you prevent difficulties that might arise during installation of heaters. Studying the instructions first may save you considerable time and money later. Observe the following procedures and cut your installation time to a minimum. To reduce risk of fire, electric shock or falling:
1. Read all instructions before using the heater.
2. Do NOT use this heater as a residential or household heater.
3. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture and papers at least 5 feet from the front of the heater.
4. Always disconnect the heater when not in use.
5. To prevent possible electrical shock, disconnect ALL power coming to heater at main service panel before wiring or servicing.
6. All wiring must be in accordance with the National and Local Electrical Codes and the heater must be grounded as a precaution against possible electrical shock.
7. Verify the power supply voltage coming to the heater matches the ratings printed on the heater nameplate before energizing.
8. This heater is NOT suitable for use in hazardous locations as described by the National Fire Protection Association (NFPA). This heater has hot and arcing or sparking parts inside. DO NOT use in areas where gasoline, paint or other flammable liquids are used or stored.
9. This heater is intended for Ceiling Installation ONLY (except as noted below.). The following clearances MUST be maintained: a) Top of heater to ceiling - 24" (640 mm) b) Bottom of heater to floor - 10' (3048 mm) c) Side of heater to wall - 36" (914 mm) d) End of heater to wall - 36" (914 mm) e) Side of heater to side of adjacent heater - 36" (914 mm) f) End of heater to end of adjacent heater - 36" (914 mm)
10. Under special controlled conditions this heater may be converted for use as a movable heater by installation of the optional Portable Cart Kit, Cord Kits, Grille Kit and Tip Over Kits.
Extreme care must be taken when using this heater as a movable unit! The heater operates at very high temperatures and could cause a fire if placed too close to combustible materials. NEVER OPERATE THIS HEATER AS A MOVABLE UNIT WHILE UNATTENDED. Always maintain at
least the minimum clearances as stated above. If the Tip Over Kit is not provided, the heater could cause a fire if it falls over.
11. Heater MUST be securely fastened to the building structure to prevent it from falling.
12.DO NOT stack or store combustible materials in the radiation path under the heater. At least 5' (1524 mm) clearance MUST be maintained between bottom of heater and combustibles.
13. If used as a cord connected movable heater, always make sure the outlet or power source to which the heater is connected is properly grounded. Use of the heater with an extension cord is not recommended. If one must be used, it must be provided with a grounding conductor and must be rated to handle a load of at least 125% of the maximum heater ampere load. Always inspect the cord for damage before each use and do not use if damaged. Route cord so it is not subject to being damaged during use.
14. In order to prevent equipment damage, protect with a ground fault device such as Marley Engineered Products WMGF240 for 240V heaters and WMGF480 for 480 volt heaters.
15. Use this heater only as described in this manual. Any other use not recommended by the manufacturer may cause fire, electric shock or injury to persons.
WARNING
M Series
Fixed Overhead Radiant Heaters
SAVE THESE INSTRUCTIONS
!
INSTALLATION
The Marley Engineered Products radiant heater is shipped fully assembled. The heater can be hung from the ceiling with 4 chains or rigid angle brackets attached to the heater brackets located on the back of the heater, for 2 and 4.5 kW heaters, chains can be attached to the four holes in the corners of the back reflector. Optional hanging chain kits are available for these heaters that will allow for installations 2 to 6 feet from the ceiling. (
Model MHK) (See Figure 1.) Minimum spacings:
Ceiling to top of heater is 2 feet.
Wall to sides of heater is 3 feet.
Floor to bottom of heater is 10 feet. NOTE: Installer should consult state and local codes and meet
any applicable requirements regarding this installation.
WIRING
1. Use heater only at the voltage specified on the nameplate.
2. Branch circuit wire for connection to heater must be at least
90°C wire. Use copper conductors only.
3. Heater can be wired with rigid or flexible conduit.
4. Refer to Table 1 for proper supply wiring size.
5. The heater connection points are located in the gasketed
terminal enclosure. To remove cover, remove 4 screws on the cover. Remove the cover to expose wiring connection points.
6. A green ground terminal is provided in the bottom of the enclosure. The ground wire should be connected before other connections are made.
7. Attach power to pigtail leads L1 and L2 (or L1, L2 & L3 on 3 phase models) using appropriate listed connectors.
NOTE: All 3 element heaters are factory pre-wired for 3-phase delta operation. Some units can be converted to single phase operation by changing the wiring. Refer to Table 1 for those heaters that can be converted to single phase. The appropriate wiring diagram (Figure 2) is also located on the bottom of the enclosure.
INSTRUCTIONS FOR FIELD CONVERSION
FOR 3 PHASE TO 1 PHASE
1. Remove nuts from all terminals.
2. Remove all pigtail leads and hat shaped buss bar.
3. Remove end of lead wire on terminal 5 and slip onto
terminal 4.
4. Remove lead wire attached to instruction sheet and connect
between terminals 4 and 6.
5. Install hat shaped buss bar between terminals 3 and 5.
6. Place pigtail lead marked “L1” on to terminal 2 and pigtail lead
marked “L2” on to terminal 6.
7. Install nuts and tighten.
8. Connect entrance wiring to pigtail leads “L1” and “L2”. Connect
ground to screw provided.
9. Inspect to make sure wiring is per “Single Phase Wiring”
above.
2
TOP VIEW
SIDE VIEW
Heater
Wall
Wall
Wall
Floor
Ceiling
Chain
3' (914.4mm) Min.
3' (914.4mm) Min.
2' (609.6mm) Min.
10' (3048mm) Min.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property damage. Heater must be effectively grounded in accordance with the National Electrical Code, NFPA 70. All electrical wiring must be done by a qualified person in accordance with National Electrical Code (NEC) and meet all state and local regulations.
a
Figure 1
Figure 2
WARNING
!