Marley Engineered Products GV 16 User Manual

BLADE MAX MIN. INTAKE
CFM VOL TS WATTS AMPS HP RPM DIA. SHUTTER A TTIC AREA REQUIRED
*1520 120 255 2.6 1/5 1100 16” STD. WOOD 2170 5.1 Sq. Ft.
LOUVER Sq. Ft.
1860 120 250 2.6 1/5 1115 16” METAL 2656 6.2 Sq. Ft.
LOUVER Sq. Ft.
READ AND SAVE THESE INSTRUCTIONS
MODEL GV 16
GABLE MOUNTED
READ INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THE PATTON ATTIC VENTILATOR. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSON­AL INJURYAND/OR PROPERTY DAMAGE! RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
IMPORTANT SAFETY INSTRUCTIONS
WARNING:
TO REDUCE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY
TO PERSONS, OBSERVE THE FOLLOWING:
Description
The Marley Engineered Products gable mounted attic ventilator is fully automatic and designed for general ventilating use only in the attic spaces of houses, apartments and other small buildings. Unit can be installed behind existing attic louvers to exhaust hot air or pull in cool air. An accessory dehumidistat can be used with this unit to automatically activate in the winter to help eliminate exces­sive moisture. The ventilator comes complete with mounting brackets, 18” armored flexible cable, prewired automatic thermostat mounted in junction box, thermally protected motor, and heavy gauge plated steel housing.
Unpacking
Unpack carefully. Inspect for loose, missing or damaged parts. In the event of missing components or hidden damage, immediately contact your distributor or the delivering carrier concerning dis­crepancies. The motor/fan assembly has been carefully factory­balanced. Care should be taken when handling to avoid damage resulting in unnecessary vibration and noise.
Specifications
MOTOR
* H.V.I. Certified at 0.03 Static Pressure
Figure 2
Dimensions
1. Do not use this fan with any Solid-State Speed Control Device.
2. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
3. Before servicing or cleaning unit, switch power off at service panel and lock service panel to prevent power from being switched on accidentally.
4. Installation work and electrical wiring must be done by qualified per­son(s) in accordance with all applicable codes and standards, including fire-rated construction.
5. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturers guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating and Air Conditioning Engineers (ASHRAE), and the local code authorities.
Dimensions 7
16
9
16”
32
13
16”
8
5
8”
UNRESTRICTED WOOD LOUVER METAL LOUVER
5.1 Sq. Ft. 6.4 Sq. Ft. 5.9 Sq. Ft.
6. When cutting or drilling into wall or ceiling, Do Not damage electrical wiring or other hidden utilities.
7. CAUTION: This unit has an unguarded impeller. Do not use in locations readily accessible to people or animals.
8. CAUTION: For general ventilation use only! Do not use to exhaust hazardous or explosive materials and vapors.
INSTALLATION
NOTE: For maximum operating efficiency, proper intake air open­ing must be provided to allow replacement of exhaust air. One square foot of free open air inlet per 300 CFM of fan capacity is rec­ommended. The best location for air intake is at the opposite end of the attic. See:
MINIMUM A TTICINTAKEAREA REQUIRED
section.
1. This gable ventilator is designed to mount behind existing louvers in an attic. If a louver is not present and one must be installed, it should be mounted in the center of the uppermost portion of the gable. The area of the louver should be greater than outlet area of ventilator. (See Figures 4 and 5.)
2. There are four sets of holes spaced 90
º apart in housing, providing a choice of four depth positions. Reversing brackets produces eight positions. Select proper mounting holes to align bracket and mounting structure on louvers. (See Fig. 3.)
Figure 3
Mounting Housing to Brackets
3. Ventilator may be mounted directly against a gable louver as shown in Figure 4. If louver is sufficiently strong, mounting brackets may be nailed or screwed onto it.
Figure 4
Mounting to Gable Louvers
4. If mounting the vent directly to gable louver is undesirable, a pair of furring strips may be suspended vertically at a minimum of 16 3/4 apart.
5. Ventilator may also be mounted on rectangular louvers as shown in Figure 5.
6. For better performance, cover any open louvered area around vent with plywood or other suitable material. This will improve efficiency of air exchange between attic and outside air. It will also prevent thermostat from being directly affected by outside air.
Figure 5
Mounting to Rectangular Louvers
MINIMUM ATTIC
INTAKE
AIR REQUIRED
Sufficient intake area must be provided in the attic to ensure that fan will not be overloaded and that it will deliver its rated CFM. This can be accomplished with some type of attic venting such as gable louvers or undereave vents. The table below shows minimum intake area needed for each fan installed.
MINIMUM ATTIC INTAKE OPENING REQUIRED
Note: If openings are covered with 1/2 hardware cloth or large mesh expanded metal, increase area by 20%. Double area if fly screen is used.
WIRING WARNING: TO REDUCE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY SOLID STATE SPEED CONTROL DEVICE.
Note: This fan is designed to run on 120V, 60 HZ power only.
1. Thermostat box can be screwed or nailed to a rafter by mounting bracket provided. If nailed, remove thermostat from box before nailing to avoid damage. Connection to existing circuit must conform to local electrical code regulations.
2. Wiring of this unit is done inside attic. Remove cover from thermostat/junction box. Bring power cable at least 6 inches into the box. Fasten power cable to box with appropriate connector.
3. For standard installation, connect the two leads in thermostat/ junction box to the two supply leads. Attach ground wire from the supply to the green ground screw in the box. (See Fig. 6.)
F
igure 6 — Wiring Diagram
163⁄4” MIN.
16
3
4 MIN.
120V, 60 Hz
SUPPLY
WHITE
GROUND
BLACK
TO FAN MOTOR
THERMOSTAT & JUNCTION BOX ASSEMBLY
Loading...
+ 2 hidden pages