Marley CSLAS, CSLAM, CSLAL Instructions Manual

Type CSL
Commercial Sill Height
Commercial Sill Height Convection Heaters (Type CSL)
Convectors
Installation, Operation & Maintenance Instructions
IMPORTANT INSTRUCTIONS
General
This heater is designed to provide years of efficient, trouble free operation as a primary or supplemental heat source for comfort heating in residential (Model CSLAS, 250 watt max only) and commercial applications. Installation or use of this product in any manner not described within this manual will void the warranty and could result in injury, damage to property, or permanent damage to heater.
WARNING
WHEN USING ELECTRICAL APPLIANCES, BASIC PRECAU­TIONS SHOULD ALWAYS BE FOLLOWED TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, AND INJURY TO PERSONS, INCLUDING THE FOLLOWING:
1. Read all instructions before installing or using the heater.
2. A heater has hot and arcing or sparking parts inside. Do not use in areas where gasoline or flammable liquids are used or stored. Do not use in corrosive environment or any area where explosive materials are used or stored.
3. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture, pillows, bedding, papers, clothes, and cur-
RECEIVING
Material when shipped was in good order and Marley Engineered Products holds clear bill of lading, therefore any concealed damage must be reported at once to the carrier for inspection and settlement.
SAVE THESE INSTRUCTIONS
!
tains away from heater.
4. To prevent a possible fire, do not block air intakes or exhaust in any manner.
5. Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock, fire, or damage the heater.
6. Serious injury or death could result from electric shock. Make sure electrical power supply circuit coming to heater is disconnected at main disconnect or service panel before installing or servicing this heater.
7. This heater is not for residential or household use, except model CSLAS @ 250 watts per foot.
Note:
It is advisable to store cartons in a central area to be drawn upon as needed per room requirements. If called for on order, the cartons will have been tagged with proper room number.
SPECIFICATIONS
Type CSL Figure 1
Table A
Model CSLAS (H=5 1/2”; D=3”)
Catalog Length Total Amperage Number* “L” Watts/Ft. Watts 120V 208V 240V 277V
-2125 125 250 2.4 1.2 1.0 0.9
-2188 28” 188 375 3.1 1.8 1.6 1.4
-2250 250 500 4.2 2.4 2.1 1.8
-3125 125 375 3.1 1.8 1.6 1.4
-3188 3’ 188 564 4.7 2.7 2.4 2.0
-3250 250 750 6.2 3.6 3.1 2.7
-4125 125 500 4.2 2.4 2.1 1.8
-4188 4 188 750 6.2 3.6 3.1 2.7
-4250 250 1000 8.3 4.8 4.2 3.6
-5125 125 625 5.2 3.0 2.6 2.2
-5188 5 188 940 7.8 4.5 3.9 3.4
-5250 250 1250 10.4 6.0 5.2 4.5
-6125 125 750 6.2 3.6 3.1 2.7
-6188 6 188 1125 9.4 5.4 4.7 4.1
-6250 250 1500 12.5 7.2 6.2 5.4
-8125 125 1000 - 4.8 4.2 3.6
-8188 8’ 188 1500 - 7.2 6.2 5.4
-8250 250 2000 - 9.6 8.3 7.2
-10125 125 1250 - 6.0 5.2 4.5
-10188 10’ 188 1875 - 9.0 7.8 6.7
-10250 250 2500 - 12.0 10.4 9.0
Clearance Chart
For safe and efficient operation, maintain at least the following Minimum clearances at all times:
Bottom of heater to finished floor
Watts/Ft Heater Length Bottom Inlet Front Inlet 125, 188 and 250 1-3/4” (44 mm) 0” (0 mm) 376 500, 625, and 750 3” (76 mm) 0” (0 mm)
Top of heater to bottom of Drapes above heater:
Minimum 12 inches (305 mm)
Important Note: vinyl blinds) may become damaged by the heated air from the heater and should not be installed above the heater.
Front of heater to full length drapes in front of heater:
Minimum between bottom of drapes and floor - 2 1/2 inches (64 mm)
Minimum between top of drapes and ceiling - 1/2 inches (13 mm)
Minimum between front of heater and nearest fold of drape ­2 inches
Top of heater to bottom of window sill:
Minimum 12 inches (305 mm)
Certain fabrics and vinyl materials ( such as
Table A (continued)
Model CSLAM (H=7”; D=5”) Model CSLAL (H=14”; D=5”)
Amperage Catalog Length Total 208V 240V 277V Number** “L” Watts/Ft Watts 1Ø
-2125 125 250 1.2 - 1.0 - 0.9
-2188 188 375 1.8 - 1.6 - 1.4
-2250 250 500 2.4 - 2.1 - 1.8
-2375 28” 375 750 3.6 - 3.1 - 2.7
-2500 500 1000 4.8 - 4.2 - 3.6
-2564 564 1125 5.4 3.1 4.7 2.7 4.0
-2625 625 1250 6.0 3.5 5.2 3.0 4.5
-2750 750 1500 7.2 4.2 6.2 3.6 5.4
-3125 125 375 1.8 - 1.6 - 1.4
-3188 188 564 2.7 - 2.4 - 2.0
-3250 250 750 3.6 - 3.1 - 2.7
-3375 3’ 375 1125 5.4 - 4.7 - 4.0
-3500 500 1500 7.2 - 6.2 - 5.4
-3564 564 1690 8.1 4.7 7.4 4.3 6.1
-3625 625 1875 9.0 5.2 7.8 4.5 6.7
-3750 750 2250 11.0 6.5 9.4 5.4 8.1
-4125 125 500 2.4 - 2.1 - 1.8
-4188 188 750 3.6 - 3.1 - 2.7
-4250 250 1000 4.8 - 4.2 - 3.6
-4375 4’ 375 1500 7.2 - 6.2 - 5.4
-4500 500 2000 9.6 - 8.3 - 7.2
-4564 564 2250 10.8 6.2 9.4 5.4 8.0
-4625 625 2500 12.0 6.9 10.4 6.0 9.0
-4750 750 3000 14.4 8.3 12.5 7.2 10.8
-5125 125 625 3.0 - 2.6 - 2.2
-5188 188 940 4.5 - 3.9 - 3.4
-5250 250 1250 6.0 - 5.2 - 4.5
-5375 5’ 375 1875 9.0 - 7.8 - 6.7
-5500 500 2500 12.0 - 10.4 - 9.0
-5564 564 2820 13.5 7.8 11.8 6.8 10.2
-5625 625 3125 15.0 8.7 13.0 7.5 11.3
-5750 750 3750 18.0 10.4 15.6 9.0 13.5
-6125 125 750 3.6 - 3.1 - 2.7
-6188 188 1125 5.4 - 4.7 - 4.0
-6250 250 1500 7.2 - 6.2 - 5.4
-6375 6’ 375 2250 10.8 - 9.4 - 8.1
-6500 500 3000 14.4 - 12.5 - 10.8
-6564 564 3380 16.2 9.4 14.1 8.1 12.2
-6625 625 3750 18.0 10.4 15.6 9.0 13.5
-6750 750 4500 21.6 12.5 18.7 10.8 16.2
-8125 125 1000 4.8 - 4.2 - 3.6
-8188 188 1500 7.2 - 6.2 - 5.4
-8250 250 2000 9.6 - 8.3 - 7.2
-8375 8’ 375 3000 14.4 - 12.5 - 10.8
-8500 500 4000 19.2 - 16.7 - 14.4
-8564 564 4500 21.6 12.5 18.7 10.8 16.2
-8625 625 5000 24.0 13.9 20.8 12.0 18.0
-8750 750 6000 28.6 16.5 15.0 14.4 21.6
-10125 125 1250 6.0 - 5.2 - 4.5
-10188 188 1875 9.0 - 7.8 - 6.7
-10250 250 2500 12.0 - 10.4 - 9.0
-10375 10’ 375 3750 18.0 - 15.6 - 13.5
-10500 500 5000 24.0 - 20.8 - 18.0
-10564 564 5640 27.2 15.7 23.5 13.6 20.4
-10625 625 6250 30.0 17.3 26.0 15.0 22.6
-10750 750 7500 36.0 20.8 31.3 18.1 27.0
2
INSTALLATION INSTRUCTIONS
TO REDUCE THE RISK OF FIRE AND ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Before installing this heater, remove and discard shipping pads located within heater. Check to make sure heater is not damaged.
2. Serious injury or death could result from electric shock. Make sure electrical power supply circuit coming to heater is disconnected at main disconnect or service panel before installing this heater.
3. Wiring procedures and connections must be in accor­dance with the National Electrical Code (NEC) and local codes. Refer to Wiring Diagram on heater and Figure 9. Make sure all electrical connections are tight to prevent possible overheating. Use Copper Supply Wire Only.
4. Verify the electrical power supply voltage matches the voltage rating as printed on the heater nameplate.
CAUTION the nameplate voltage as this will damage the heater and could cause a fire.
5. Do not install the heater against combustible low-density
6. Do not install heater below an electrical convenience
CAUTION trical cords (including telephone and computer cables), drapes, and other furnishings away from heater. For efficient and safe operation, we recommend maintaining a minimum of 6 inches (152 mm) clearance above and in front of the heater at all times.
7. To reduce the risk of fire, do not store or use gasoline or
8. Do not install heater upside down or in any position other
9. Do not recess heater in wall or install heater inside any
10. When mounting heater, use care to secure heater to
11. Do not remove or bypass the safety limit control (thermal
12. The factory installed wires inside wireway are used to
13. Heaters that are not installed end to end must have end
- Never connect a heater to a voltage greater than
cellulose fiberboard surfaces, against or below vinyl wall coverings, or below any materials that may be damaged by heat such as vinyl or plastic blinds, curtains, etc. If heater is intended to be installed against vinyl wall cover­ings, Stand Off Kits, Cat. No. SO1 or SO2, must be used. See instructions supplied with kits.
receptacle (outlet).
– Heater operates at high temperatures. Keep elec-
other flammable vapors or liquids in the vicinity of the heater.
than as shown in this manual. Caution label with word “TOP” must be at the top when heater is installed.
type enclosure as this will cause heater to overheat and could create a hazard.
building structure and avoid damaging internal heater components.
protector) as this could allow heater to become a fire haz­ard – see heater wiring diagram supplied with heater.
connect the built-in controls. Limit the maximum current to no more than 45 total amps. Refer to instructions and current capacity rating as provided with the accessory.
caps installed to cover exposed ends of heater.
14. All field wiring brought in to heater must be rated mini­mum 75°C.
15 Do not allow objects to be placed on top of heater as they
may be damaged or create a fire hazard.
16. Before energizing, make sure that heater is completely assembled with grille, front cover, end caps and any accessories installed.
Rough-in Wiring
1. Run branch circuit of proper voltage and wire size to location of left or right junction box as indicated on heater wiring dia­gram. Basic heaters are prewired and can be connected to branch circuit at either end. Heaters with controls are prewired for connection to branch circuit at one end only (refer to heater wiring diagram), however, heater can be wired from opposite end by running wire through heater wire­way.
2. If it is necessary to run wires through the heater wireway, use Table B to size the field installed wiring.
3. The factory installed wires in the heater wireway can be loaded up to 45 amps. Refer to Table C for maximum length of heater run when the heaters are connected in parallel.
Thermostat
Transformer relay
05A units: 22 amps @ 120-240 VAC
07A-14A Units: 25 AMPS @ 120-240 VAC
Power relay
Disconnect switch
Table B. Sizing Field Installed Wiring
Copper Maximum no. wire size of wires Up to 3 4 to 6 7 thru 9 75º C in wireway Conductors Conductors Conductors
No. 12 AWG 9 11.5 amps 9.3 amps 8.1 amps No. 10 AWG 8 17.4 amps 14.0 amps 12.1 amps No. 8 AWG 4 24.0 amps 21.0 amps
Table C. Maximum Length of Heater Run (CSLAS-1Ø)
Watts/Ft. of Maximum allowable length of heater run (feet) the heaters 120 Volts 208 Volts 240 Volts 277 Volts
125 33 58 67 77 188 22 38 44 51 250 16 29 33 38
Note:
For mix of watt densities, calculate amp draw. Do not
exceed values indicated in step 3 above.
Table D. Maximum Length of Heater Run
(CSLAM and CSLAL)
Watts/Ft.
of Heaters
125 74 - 86 - 99 188 49 - 57 - 66 250 37 - 43 - 49 376 24 - 28 - 33 500 18 - 21 - 24 564 16 27 19 32 22 625 15 24 17 29 20 750 12 20 14 24 16
1 Ph 3 Ph 1 Ph 3 Ph 1 Ph
3
24 amps @ 120-240 VAC 22 amps @ 277 VAC Pilot duty– 125 VAC (all voltages)
19 amps @ 277 VAC
22 AMPS @ 277 VAC
25 amps @ 120-277 VAC- see wiring dia­gram on heater
20 amps @ 120-277 VAC
Maximum allowable current
Max. allowable length of heater run in feet (meters)
208V 240V 277V
4. Standard 75ºC wiring must be used in junction boxes, wire-
HEATER
HEATERS
BUTTED
TOGETHER
HEATER
FILLER
SECTION
HEATER
INSIDE
CORNER
HEATER
OUTSIDE
CORNER
HEATER
END CAP
TYPICAL INSTALLATION
SPLICE PLATE 
KIT
SPLICE PLATE 
KIT
ways, blank sections, filler sections, and corner sections.
Room Layout
Refer to heating plans for exact room arrangements of heaters (with or without thermostat and/or relays and/or switches and accessories.)
Check the heater section dimensions and the additional wall length required for telescoping accessories (Figure 2) before starting wall-to-wall type installation. Be certain all heaters and accessories needed are at hand and are of correct finish.
10
N
N
N
N
/4”
3
2-15/16”
-1/4”
1
1-7/16”
ACK PANEL
B
1-1/8” & 7/8” DIA.
CONCENTRIC K.O.’s
1-7/16”
/8” & 1-1/8” DIA.
7
CONCENTRIC K.O.’s
ACK PANEL
B
B
A
1-15/16”
-1/4”
1
2-1/2”
3/4”
1-3/8” & 1-3/4” DIA.
ONCENTRIC K.O.’s
C
1-9/16”
10
7
3
Figure 2 Typical Installation See page 8 for N dimensions
2
4
1
8
N
5
6
N
9
Installation of Single Unit
Note:
For ease of installation, it is important that the sequence
of operations indicated below be followed in order.
1. Remove front cover by removing mounting screws (Figure
3).
2. Remove appropriate electrical knockout from either junction box. See Figure 4 for location of knockouts.
1-3/8” & 1-1/8” DIA.
ONCENTRIC K.O.’s
C
BOTTOM VIEW
1-3/8” & 1-3/4” DIA.
ONCENTRIC K.O.’s
C
BOTTOM VIEW
CSLAM CSLAL
A B
4”
N/A
5” 5”
Figure 4
3. Install end caps (must be purchased separately) on both ends of the heater housing. Refer to Figure 5 for details of end cap installation.
4. If filler section is desired to terminate the heater, install the filler section in the end of the heater and extend to desired length. Mark the mounting hole locations, remove the filler section and drill the required mounting holes. Install the filler section in the heater and the end cap on the filler section as shown in Figure 3.
Note:
If a thermostat and/or disconnect switch are installed in the heater left junction box, it may be necessary to cut away a portion of the filler section to allow access to these controls (Figure 3).
5 Position heater housing on wall to check for evenness of
wall. Do not draw the heater against an uneven wall surface. If an uneven wall is encountered, use shims to keep the heater housing straight.
6. Run proper size branch circuit to the junction box through the
selected knockout.
Figure 3
HOUSING
MOUNTING
SCREWS END CAP
ACCESSORY
MOUNTING
END CAP
HOLES
Figure 5
4
7. Drill the required size mounting holes in the back of the heater housing and install the housing on the wall using screws, bolts or anchors (by installer) to suit the wall con­struction.
Note:
Predrilled 1/4” diameter mounting holes are provided in each junction box. Additional mounting holes will have to be drilled in the housing to support the weight of long length heaters (6’ and longer). Do not drill any additional holes in the junction boxes.
8. Tighten mounting screws and back off 1/4 to 3/4 turn to
allow for expansion and contraction of the heater.
9. Following the wiring diagram secured to the heater, make
electrical connections. Ground the heater using the ground screws provided (Figure 3).
10. Replace front cover and secure with mounting screws. (See
Figure 3).
Installation of Multiple Wall to Wall Units
Note:
For ease of installation, it is important that the sequence
of operations indicated below be followed in order.
1. Remove all the front covers from the heaters by removing
mounting screws (Figure 3).
2. Refer to wiring diagram for power supply entry and remove
appropriate electrical knockout (Figure 4) from the heater in which power supply connections are to be made. The power supply may be brought in to the end of only one heater and the remaining heaters may be connected in parallel using the wireway. Use Table B to size the field installed wiring in the wireway.
3. If conduit cover (must be purchased separately) is desired,
cut off the appropriate length and install to the wall.
4. If required by plan, install filler section (1), (Figure 1) to either
heater (2) or (3) by means of four #6 screws supplied with filler section. (Refer to Figure 6.) Discard filler section end cap in this application.
Note:
Heaters may butt against each other, thus eliminating the
filler piece, if so desired.
Note:
If a heater has a disconnect switch and / or thermostat and is to have a filler section or a corner section at the left end, the section must be mounted to the heater since the thermostat or disconnect switch will prevent the section from telescoping into the heater.
5 If the wall run has inside or outside corners, install corner (4
and 5) to the heater (2 and 9) by means of four #6 screws supplied with corner section. (Refer to Figure 6).
6. Install end caps (6) on the outer end of the last heater(7) and
(9) using four #6 screws supplied with end caps. (Refer to Figure 5 for details of end cap installation.)
7. Drill the required size mounting holes in all the heater housings. Note:
Predrilled 1/4” diameter mounting holes are provided in each junction box. These holes may be used only when no slip­in accessory is to be installed in that end of the heater ( such as when heater(3 and 7) are butted together as shown in Figure 2). Additional mounting holes will have to be drilled in the housing to support the weight of long-length heaters (6’ and longer). Do not drill any additional holes in junction boxes.
8. Check for evenness of wall. Do not draw the heaters
against an uneven wall surface. If an uneven wall is encountered, use shims to keep the heater housing straight.
9. Run proper size branch circuit to the junction box through
the selected knockout.
10. Mount the heater (2, Figure 2) on the wall using screws,
bolts or anchors (by installer) to suit the wall construction.
11. Telescope the heater housing (3) over the filler section (1)
by the desire amount and mount the housing to the wall.
12. Telescope the heater housing (8) over the corner section
(4) by the desired amount and mount the housing to the wall.
13. Mount the remaining heaters as described above, making
sure that the heaters with end caps are installed at the end of the run.
14. Blank sections, if any are installed in the same manner as
the heaters.
Note:
75ºC field wiring may be run through the blank sections, filler sections and corner sections.
15. Control sections, if any, are installed in the same manner
as heaters. Refer to wiring diagram on control sections for connecting the wiring to the heaters
Figure 6
Installation of Mullion to Mullion Units
The back of the heater housing contains no mounting holes (other than those at the ends) and therefore is ideal for installa­tion in front of glass curtain walls. The housing back presents an attractive appearance when viewed from the outside through the glass wall.
Installation procedures are similar to those for wall-to-wall instal­lation (Step Six) except for the following differences.
1. Attach the housing to the mullion using the mounting holes
provided in the junction boxes as shown in Figure 7.
2. On horizontal mullion installation, install support brackets as
shown in Figure 8.
5
OPERATION INSTRUCTIONS
1. This heater must be properly installed before it is used.
2. If the heater is equipped with a built-in thermostat, adjust the shaft to the mid-range and let the heater run for a few hours. If the room temperature is too hot, rotate the shaft counter­clockwise; if too cool, rotate the shaft clockwise until a com­fortable temperature is obtained. Let room temperature sta­bilize after each setting change. The heater will automatical­ly cycle around this set point on the thermostat.
Note:
If a thermostat or disconnect switch is provided in the heater, these components are accessible through the grille openings at the left or right end of the heater.
Figure 7
MAINTENANCE INSTRUCTIONS
For efficient and safe operation and to extend the life of the heaters, they should be cleaned and inspected for damage at least annually (preferably at the beginning fo the heater season) or more often in dirty environments. Other than cleaning, your heaters require no other preventative maintenance.
1. Serious injury or death could result from electric shock. Make sure electrical power supply circuit(s) coming to heater is/are disconnected at main disconnect or service panel before servicing this heater. Allow heater to cool before cleaning to prevent a possible burn.
Note:
More than one power source may enter heater. Be sure all power is disconnected to heater before cleaning or servicing.
2. Use care when cleaning element fins to avoiding damaging
fins. Note also that fins are sharp and may cause cuts so avoid contact.
1. The user can perform periodic cleaning of the outer cabinet. All other servicing is to be done by qualified service person­nel.
2. Heater cabinet may be cleaned using a damp cloth to remove dust that may have accumulated on surfaces. Do not use harsh cleaners or waxes on surfaces since these could damage the finish or discolor in use.
3. A vacuum cleaner and/or compressed air may be used to remove dust and lint that may have accumulated inside heater around element fins. If heater must be disassembled for cleaning, use care when cleaning element fins to avoid damaging fins.
4. After cleaning and servicing, always reassemble replacing any hardware removed, restore power and check to make sure the heaters are operating properly.
Important Note: the heaters including one or more over-temperature limit con­trols (Thermal Protector) - see Wiring Diagram on heater for specific controls provided. These safety controls are provided to cycle the heater off to maintain safe temperatures in the event of a blockage or other abnormal condition. DO NOT remove or bypass these important safety controls as they are provided to limit the temperatures and prevent a possible fire in the event the heater is subjected to an overheating condition. If it is deter­mined that the heater is cycling off on the safety controls during normal use, discontinue using the heater until it can be inspected and repaired by a qualified service personnel.
There are built-in safety devices provided within
Figure 8
Figure 9 - Wiring Diagram
6
RENEWAL PARTS
IDENTIFICATION:
CSLAS, CSLAM, CSLAL
THERMOSTAT
(OPTIONAL)
DISCONNECT
SWITCH
(OPTIONAL)
ELEMENT BUSHING
1213-2000-001
OVERLOAD
PROTECTOR
GRILLE
HEATING
ELEMENT
WIREWAY COVER
BACK PANEL
FRONT COVER
TRANSFORMER
RELAY
(OPTIONAL)
POWER RELAY
(OPTIONAL)
BACK PANEL
FRONT COVER
1402-0315-VAR (OSH07A) 1402-0314-VAR (OSH14A)
DISCONNECT
SWITCH
(OPTIONAL)
ELEMENT BUSHING
1213-2000-001
THERMOSTAT
(OPTIONAL)
OVERLOAD
PROTECTOR
4502-0007-VAR
GRILLE
HEATING
ELEMENT
WIREWAY COVER
6405-0053-VAR
Heater Element (Part No. Prefix 1802-2001)
Description Heater Length
28” 3’ 4’ 5’ 6’ 8’ 10’
125 W/ft. 120 Volts 085 087 089 091 093
per 208 Volts 086 088 090 092 094 095 096
Element 240 Volts 048 054 060 066 072 077 081
277 Volts 049 055 061 067 073 078 082
188 W/ft. 120 Volts 005 011 017 023 029
per 208 Volts 002 008 014 020 026 032 036
Element 240 Volts 001 007 013 019 025 031 035
277 Volts 000 006 012 018 024 030 034
250 W/ft. 120 Volts 004 010 016 022 028 ––
per 208 Volts 003 009 015 021 027 033 037
Element 240 Volts 002 008 014 020 026 032 036
277 Volts 001 007 013 019 025 031 035
TRANSFORMER
RELAY
(OPTIONAL)
POWER RELAY
(OPTIONAL)
Built-in Controls (Optional)
Description Part Number
CSLAM & CSLAS UNITS
CSLAL UNITS
Disconnect Switch 5216-0124-000 5216-0124-000 Transformer 120 Volts R13700002B001 410043001
Relay 208 Volts R13700002B002 410043002
240 Volts R13700002B003 410043003 277 Volts R13700002B004 410043004
Power 24 Volts 5018-2006-000 5018-2006-000
Relay 120 Volts 5018-2006-001 5018-2006-001
208/240 Volts 5018-2006-002 5018-2006-002
277 Volts 5018-2006-003 5018-2006-003
Thermostat 1 Pole 5813-0024-000 5813-0024-000
2 Pole 5813-0023-000 5813-0023-000
7
Renewal Parts Identification: Optional Controls: CSLAMBCS, CSLALBCS
Description Part Number
Mercury relay, 1 pole 30 amps, 24 Volt coil 5018-7050-001
Mercury relay, 1 pole 60 amps, 24 Volt coil 5018-7049-001 Mercury relay, 1 pole 30 amps, 120 Volt coil 5018-7050-002 Mercury relay, 1 pole 60 amps, 120 Volt coil 5018-7049-002 Mercury relay, 1 pole 30 amps, 208 Volt coil 5018-7050-003 Mercury relay, 1 pole 60 amps, 208 Volt coil 5018-7049-003 Mercury relay, 1 pole 30 amps, 240 Volt coil 5018-7050-004 Mercury relay, 1 pole 60 amps, 240 Volt coil 5018-7049-004 Mercury relay, 1 pole 30 amps, 277 Volt coil 5018-7050-005 Mercury relay, 1 pole 60 amps, 277 Volt coil 5018-7050-005
Circuit breaker, 2 pole 30 amps 1226-7009-013 Circuit breaker, 2 pole 60 amps 1226-7009-010 Circuit breaker, 3 pole 30 amps 1226-7009-005 Circuit breaker, 3 pole 60 amps 1226-7009-002
24V Transformer, 120 Volt primary 5814-7017-007 24V Transformer, 208 Volt primary 5814-7017-002 24V Transformer, 240 Volt primary 5814-7017-007 24V Transformer, 277 Volt primary 5814-7017-001
Disconnect Switch 5216-0124-000
Thermostat, 1 pole 5813-0024-000
Thermostat, 2 stage 5813-0023-000
Pneumatic Control 5216-7027-001
All products manufactured by Marley Engineered Products are warranted against defects in workmanship and materials for one year from date of installation, except
LIMITED WARRANTY
heating elements which are warranted against defects in workmanship and materials for five years from date of installation. This warranty does not apply to damage from accident, misuse, or alteration; nor where the connected voltage is more than 5% above the nameplate voltage; nor to equipment improperly installed or wired or maintained in violation of the product’s installation instructions. All claims for warranty work must be accompanied by proof of the date of installation.
The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor costs, and shipping costs incurred to return products to Marley Engineered Products Service Center. Within the limitations of this warranty, inoperative units should be returned to the nearest Marley authorized service cen­ter or the Marley Engineered Products Service Center, and we will repair or replace, at our option, at no charge to you with return freight paid by Marley. It is agreed that such repair or replacement is the exclusive remedy available from Marley Engineered Products.
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT. MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT, WHETHER BASED UPON NEGLIGENCE, TORT, STRICT LIABILITY, OR CONTRACT.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
For the address of your nearest authorized service center, contact Marley Engineered Products in Bennettsville, SC, at 1-800-642-4328. Merchandise returned to the fac­tory must be accompanied by a return authorization and service identification tag, both available from Marley Engineered Products. When requesting return authorization, include all catalog numbers shown on the products.
HOW TO OBTAIN WARRANTY SERVICE AND WARRANTY PARTS PLUS GENERAL INFORMATION
1. Warranty Service or Parts
2. Purchase Replacement Parts
3. General Product Information
Note:
When obtaining service always have the following:
1. Model number of the product
2. Date of manufacture
3. Part number or description
1-800-642-4328 1-800-654-3545 www.marleymep.com
470 Beauty Spot Rd. East Bennettsville, SC 29512 USA
Part No. 5200-2210-002
ECR 38636
12/10
Loading...
+ 16 hidden pages