Among other sources, outbreaks of Legionnaires’ disease have
reportedly been traced to cooling towers. Maintenance procedures
that prevent amplification and dissemination of Legionella and other
airborne bacteria should be formulated and implemented BEFORE
systems are operated and continued reqularly thereafter to avoid
the risk of sickness or death
CLEANING–New installations should be cleaned and treated with biocides
by a water treatment expert before startup. Remove any dirt and trash which
has accumulated in the cold water basin. Remove any sediment from the cold
water collection basin, sump, and screens. Use a water hose to flush cold
water collection basins.
OPERATE WATER SYSTEM–Start the circulating water pumps. Increase the
flow of circulating water gradually to match design water flow rate. Circulate
water over the cooling tower continuously for several days before starting
the mechanical equipment and placing the cooling tower into continuous
operation.
Note
When starting in cold weather, follow procedures outlined in Cold
Weather Operation.
INSPECTION–It is imperative that all operating assemblies be inspected
before they are placed in operation. The following is a list of components to
be checked before starting the tower:
1–Check drive shaft alignment. Realign if necessary. See Marley Drive Shaft
Service Manual.
2– Check tightness of bolts in fan cylinder joints.
3–Check tightness of the following bolted joints in the fan and drive assem-
blies:
a–Fan hub clamp bolts. See Marley Fan User Manual for correct torque
setting).
b–Fan hub cover bolts.
c–Geareducer® and motor mounting bolts.
d—Drive shaft coupling and guard bolts.
4–Check Geareducer oil for sludge or water by draining off and testing a
sample as outlined in the Geareducer User Manual. Check Geareducer
oil level at “oil level” mark on the side of the case. Add oil as required. The
3
➠
oil level placard must be adjusted so that its “full” mark is at the same elevation as the “full” mark on the side of the Geareducer case. Check oil lines
to be sure there are no leaks. See Geareducer User Manual for oil filling
procedure and list of recommended lubricants.
5–Rotate fan by hand to be sure of free rotation and ample tip clearance. See
Fan User Manual.
6–Check motor insulation with a “Megger”. See Maintenance Section of Marley
Electric Motor User Manual.
7–Lubricate the motor according to motor manufacturer’s instructions.
8–Test run each fan separately for a short time. Check for excessive vibration
or unusual noise. If either is present, see Troubleshooting Guide on pages
14 and 15 of this manual. Fan must rotate clockwise when viewed from
above. Recheck Geareducer oil level.
9–Check functioning of make-up water supply.
10–Make sure the blowdown will carry the proper amount of water.
Starting Procedure
WATER SYSTEM–Fill the cold water collection basin and circulating water
system until the operating water level is reached. See Operation Section, below.
Prime and start the circulating water pumps. Increase the flow of circulating
water gradually to design water flow rate to avoid water hammer which could
damage the distribution piping system.
Note
Note
Caution
Clean the sump screens several times during the first weeks of
operation. After this, clean sump screens weekly.
When starting in cold weather, follow procedures outlined in Cold
Weather Operation.
STARTING FAN–Start the fan. After 30 minutes of operating time to permit
Geareducer oil to come up to operating temperature, check motor load with
watt meter, or take operating volt and ampere readings and calculate motor
hp. Refer to Marley Fan User Manual for instructions. Pitch fans to pull cor-
rect contract horsepower when circulating design water rate at design hot
water temperature.
Operation
Entering water temperature in excess of 125°F may result in fill
deformation.
4
TOWER PERFORMANCE–Keep the cooling tower clean and water distribution uniform to obtain continued maximum cooling capacity.
The capacity of a cooling tower to cool water to a given cold water temperature varies with the wet-bulb temperature and the heat load applied to the
cooling tower.
As the wet-bulb temperature drops, the cold water temperature also drops.
However, the cold water temperature does not drop linearly with the wet-bulb
temperature.
A cooling tower will not control heat load. The flow rate of water circulated
through the cooling tower will determine the temperature range of cooling in
conjunction with a given heat load. The hot water and cold water temperatures
will increase with higher heat loads.
HOT WATER DISTRIBUTION SYSTEM–Maintain uniform water distribution
at the nozzles (uniform spray cone). The amount of water circulated should
approximate the contract requirements and the nozzle pressure should be kept
constant. Lower pressures may indicate excessive losses in the piping system
and/or insufficient pump capacity; greater pressures might indicate clogged
nozzles and/or overpumping. If a greatly reduced water flow rate is desired, it
may be advisable to change nozzle sizes to obtain the desired pressure and
maintain proper water distribution. An SPX Cooling Technologies engineer
can advise minimum and maximum flow rates for even distribution.
COLD WATER COLLECTION BASIN–A suitable depth must be maintained
to keep the pumps from pulling air into the line. The amount of “make-up”
water required to keep the water in the collection basin at the required depth
depends upon the “evaporation loss” and “blowdown” .
FAN DRIVE–When using two-speed motors, allow a time delay of 20 seconds
minimum after de-energizing the high-speed winding and before energizing
the low-speed winding. Tremendous stresses are placed on driven machinery
and motors unless the motors are allowed to slow to low-speed RPM or less
before the low-speed winding is energized.
COLD WEATHER OPERATION–During periods of low temperature operation,
35°F to 40°F or below, ice will form on the relatively dry parts of the cooling
tower that are in contact with the incoming air. Primarily, this includes the air
inlet and adjacent structural framing. Your understanding of cold weather
➠
5
operation will be enhanced if you read “Operating Cooling Towers in
Freezing Weather” Marley Technical Report #H-003.
Ice forming characteristics on any given cooling tower will vary, depending on
velocity and direction of wind, circulating water rate, and heat load. Excessive
ice formation may be controlled by regulating air and water flow through the
tower by one or more of the following procedures:
1–Shut the fan down. This reduces the cooling air rate to a minimum and in-
creases the quantity of warm water at the air inlet to a maximum. However,
normal “fan off” operation causes reverse air flow by aspiration and may
cause water blowout and therefore must be done with caution and moni-
toring. For automatic operation, a timer switch can be provided to shut the
fan down for a few minutes each hour.
2–When a cooling tower has two-speed motors, operate the fans at half speed
forward. This reduces the cooling air rate (heat transfer) and increases the
quantity of warm water at the air inlet.
3–With no heat load on the circulating water, icing cannot be controlled. Towers
must not be operated with reduced water rate and/or no heat load during
freezing weather. If a bypass directly into the cold water basin is used, all
water must be bypassed.
Caution
Warning
Reverse operation of fans is not recommended . See “Fan Drive”
for fan speed change precautions.
INTERMITTENT OPERATION–When the unit is operated intermittently during winter weather, it is necessary that the water be drained from the tower
piping to insure protection against freezing and possible rupture.
Tower Maintenance
Always shut off electrical power to the tower fan motor prior to
performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
Well-maintained equipment gives the best operating results and the least
maintenance cost. SPX recommends setting up a regular inspection schedule
to insure effective, safe operation of the cooling tower. Use the schedule on
page 16 to obtain continuously good performance with the least tower main-
6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.