Marley CDF552SE, CDF547SE, CDF548SE, CDF557SE, CDF547RE Instructions Manual

...
Description
CDF500 Series
Ceiling Mounted
Marley downflow ceiling mounted heaters are designed for recessed or surface applications. Surface mounted heaters extend only six inches into the room. Recessed mounted
eaters recess only seven inches into the ceiling. Mounts
h easily into 2 X 2 foot ceiling grids.
Fan Forced Heaters
Installation, Operation & Maintenance Instructions
Specifications
Model Kw
CDF552SE 5/3.8/2.5 17.2/13.0/8.5 240 1-3 20.8/15.8/10.4 283 (133.5) 45 CDF547SE 4/3/2 13.7/10.2/6.8 277 1 14.5/10.8/7.2 283 (133.5) 51 CDF548SE 4/3/2 13.7/10.2/6.8 208 1-3 19.2/14.4/9.6 283 (133.5) 51 CDF557SE 5/3.8/2.5 17.2/13.0/8.5 277 1 18.1/13.7/9.0 283 (133.5) 45 CDF558SE 5/3.8/2.5 17.2/13.0/8.5 208 1-3 24.0/18.2/12.0 283 (133.5) 45
Model Kw
CDF552RE 5/3.8/2.5 17.2/13.0/8.5 240 1-3 20.8/15.8/10.4 283 (133.5) 45 CDF547RE 4/3/2 13.7/10.2/6.8 277 1 14.5/10.8/7.2 283 (133.5) 51
CDF548RE 4/3/2 13.7/10.2/6.8 208 1-3 19.2/14.4/9.6 283 (133.5) 51 CDF557RE 5/3.8/2.5 17.2/13.0/8.5 277 1 18.1/13.7/9.0 283 (133.5) 45 CDF558RE 5/3.8/2.5 17.2/13.0/8.5 208 1-3 24.0/18.2/12.0 283 (133.5) 45
(1) Factory wired for highest wattage, field convertible to lower wattages. (2) Factory wired 1Ø, field convertible to 3Ø. (3) On dual phase units, maximum amp draw is listed. (4) Temperature difference at highest rated wattage.
1
1
BTU/Hr. (000) Volts Phase
BTU/Hr. (000) Volts Phase
Surface Mounted
Recessed Mounted
2
2
Amps
Amps
3
3
CFM (dm3/s) °F
CFM (dm3/s) °F
4
4
CAUTION - TO REDUCE RISK OF FIRE AND ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. To prevent electrical shock, disconnect all power coming to heater at main service panel before wiring or servicing.
2. All wiring must be in accordance with the National and Local Electrical Codes and the heater must be grounded as a pre­caution against possible electric shock.
4. This heater is intended for ceiling installation ONLY. Do not install the heater closer than 12” (305 mm) to any wall for 4000W models and 24” (609 mm) to any wall for 5000W models.
SAVE THESE INSTRUCTIONS
WARNING
6. To prevent a possible fire, do not block air intakes or exhaust in any manner. Keep combustible materials, such as crates, drapes, etc., away from heater.
7. A heater has hot and arcing (sparking) parts inside. Do not use it in areas where gasoline, paint, or flammable liquids are used or stored.
8. This heater is not approved for use in corrosive atmos­pheres such as marine, green house, or chemical storage areas.
9. The heater enclosure must be securely mounted to ceiling or framing capable of supporting the heater (45 lbs/20.4 kg). Failure to do so could allow heater to fall.
10. Do not operate heater without outlet grilles installed. When installing grilles with louver guides, make sure guides drop into position so they cannot slide out during use.
!
IMPORTANT SAFETY INFORMATION
FAILURE TO INSTALL THE FOUR MOUNTING NUTS TO SECURE HEATER TO MOUNTING FRAME COULD RESULT IN THE HEATER FALLING (SEE FIGURE 2).
FAILURE TO INSTALL THE FOUR SCREWS COULD ALLOW THE SURFACE ENCLOSURE TO FALL (SEE FIGURE 2).
IMPORTANT NOTICE: This heater is wired so the fan will come
n with no delay when energized as the thermostat is calling for
o heat. When the thermostat is satisfied, the fan must continue to run until the heater has cooled to a safe temperature. If an external thermostat or controls are to be used, DO NOT wire heater so thermostat shuts power to fan. The heater will be damaged and the warranty will be voided. Thermostat must be connected as shown on wiring diagram (Figure 13, page 7) for correct operation.
NOTE: Field wiring must be #10 AWG min. rated 90°C min. Max run length 125’ at 208V/5 kW. Wiring Compart-ment Volume:
3
252 in
(4130 cm3).
INSTALLATION
Installation of Surface Mounted Heaters (See Figures 1 and 2)
1. Determine the desired location of the heater. See Warning No. 4, page 1 for minimum mounting clearances.
2. Remove Surface Mounted Heater assembly from carton. Heater assembly includes (1) surface mounting plate, (1) heater, (1) surface mount enclosure and (1) set of discharge grilles, Figure 2, page 3.
3. Remove Surface Mount Enclosure from assembly. Remove four (4) nuts from studs so heater can be removed from sur­face mounting plate. Do not discard nuts since these will be used in Step 11 to mount heater back on to surface plate.
4. Remove one of the knockouts and install a cable or conduit connector.
7/8”(22.2 mm) & 11/8” (28.6 mm) Nested Knockout
Screw (2)
Optional Disconnect Switch (CDFDS)
7/8” (22.2 mm) Knockout
FFiigguurree 11
5. Install the optional disconnect switch CDFDS (if required) as shown in Figure 1. Refer to accessory installation manual for proper wiring.
6. Run the power supply cable through the connector, leaving about 8” (203 mm) of wire inside the surface mounting plate. (Power supply cable must be #10 AWG min. rated 90°C min­imum. Maximum run length 125' at 208V/5kW.)
1/2”(12.7 mm) Knockout
Surface Mounting Plate
1/2” (12.7 mm) Knockout
Cable or Conduit Connector
Surface Mounting Plate
7. Position the surface mounting plate against the ceiling and secure with bolts or screws (Figure 2). See Warning No. 9,
age 1. Connect the ground wire to the green ground screw
p on the surface mounting plate.
8. Install optional controls (if required) into the heater section in accordance with the Instruction Sheet packaged with the control.
. To wire the heater, thermostat, reduce wattage or convert
9
from single to three-phase voltage, refer to “Field Conversion for Lower Wattage Rating” or “Conversion for 3ø Installation” on page 7 and wiring diagrams, Figure 13, page 7.
TO REDUCE THE RISK OF FIRE OR PERMANENT DAMAGE TO THE HEATER, THERMOSTAT MUST BE WIRED AS SHOWN IN WIRING DIAGRAM. DO NOT CONNECT THER­MOSTAT IN MAIN POWER LINES BECAUSE IT WILL DEFEAT THE FAN DELAY FUNCTION.
10. Position the heater section over the studs on the surface
mounting plate (Figure 2).
NOTE: The end of the heater section with the terminal block must be positioned at the end of the surface mounting plate where the supply wiring enters.
11. Push the heater section onto the studs and securely tighten
four (4) nuts (removed from step 3) on the studs to secure the heater section to the surface mounting plate (Figure 2).
FAILURE TO INSTALL THE FOUR MOUNTING NUTS COULD RESULT IN THE HEATER FALLING (SEE FIGURE 2).
NOTE: Insure that the “thumb pin” in each end of the discharge grille opening is pulled outward to allow the body of the thumb pins to fit into the holes in the heater section (Figure 2).
12. Position the surface mounting enclosure over heater sec-
tion/surface mounting plate, making sure that the thumb pins are in the holes in the heater section.
13. With the surface enclosure seated firmly against the heater
section, depress the “thumb pins”. This will cause the thumb pins to expand and will temporarily hold the surface enclosure in place.
NOTE: The thumb pins are an aid to help position and hold the surface mounting enclosure during installation. Additional sup­port (step 14) is required. See Warning.
FAILURE TO INSTALL THE FOUR SCREWS COULD ALLOW THE SURFACE WRAPPER TO FALL (SEE FIGURE 2).
14. Install and securely tighten four screws (supplied) to secure
the surface mounting enclosure to the heater section (Figure 2).
15. Install discharge air grilles. (Refer to “Installation of
Discharge Air Grilles”, page 6.)
2
Grounding Screw
Screws or Bolts (Not Supplied)
Nut (4)
2” (305 mm) Min. 4 kW
1
4” (609 mm) Min. 5 kW
2
Surface Mounting Plate
Power Supply Cable
12” (305 mm) Min. 4 kW 24” (609 mm) Min. 5 kW
Thumb Pin Hole (2)
Heater Section
Surface Mounting Enclosure
Stud (4)
able or
C
onduit
C
onnector
C
Screw (2)
Screw (3)
1/2” (12.7 mm) Knockout
7/8” & 11/8” (22.2 mm & 28.5 mm) Knockout
Optional Disconnect Switch (CDFDS)
7/8” & 11/8” (22.2 mm &
28.5 mm) Nested Knockout
Side Panel
1/2” (12.7 mm) Knockout
Grounding Screw
Stud (4)
Thumb Pin Hole (2)
Screw (4)
FFiigguurree 22
Insure that “Thumb Pin” is pulled out before positioning the surface mounting enclosure on the heater section. Depress “Thumb Pin” after surface enclosure is sealed firmly against the heater section.
Installation of Recess Mounted Heaters in T-Bar Ceiling (See Figures 3 and 4)
The recess mounted heater will mount in any standard 2’ x 2’ (609 mm x 609 mm) T-Bar (drop) ceiling. See Warning No. 4 for minimum mounting clearance and Warning No. 9, page 1.
1. Remove Recess Mounted Heater assembly from carton. Heater assembly includes (1) recess mounting box, (1) heater, (1) recess mount face plate and (1) set of discharge grilles, Figure 3.
2. Remove recess mount box from assembly. Remove four (4) nuts from studs so heater can be removed from recess mounting box. Do not discard nuts since these will be used in Step 9 to mount heater section back on to the recess mounting box.
3. Remove three screws and the side of the recess mounting box to allow for easier wiring (Figure 3).
4. Remove one of the knockouts and install a cable or conduit connector (Figure 3).
5. Install the optional disconnect switch CDFDS (if required as shown in Figure 3). Refer to accessory instal lation manual for proper wiring.
6. Install optional controls (if required) into the heater section in accordance with the Instruction Sheet packaged with the control.
7. To wire the heater, thermostat, reduce wattage or convert from single to three-phase voltage, refer to “Field Conversion for Lower Wattage Rating” or “Conversion for 3ø Installation” on page 7 and wiring diagrams, Figure 13, page 7.
Recess Mounting Box
Heater Section
Recess Face Plate
Screw (4)
FFiigguurree 33
Heater
Wall
12” (305 mm) Min. 4 kW 24” (609 mm) Min. 5 kW
FFiigguurree 44
3
Thumb Pin Hole (2)
Nut (4)
Thumb Pin (2)
Insure that “Thumb Pin” is pulled out before positioning the face plate on the heater section. Depress “Thumb Pin” after face plate is sealed firmly against the heater section.
T-Bar Grid
Power Supply Cable
Wall
12” (305 mm) Min. 4 kW 24” (609 mm) Min. 5 kW
TO REDUCE THE RISK OF FIRE OR PERMANENT DAMAGE TO THE HEATER, THERMOSTAT MUST BE WIRED AS SHOWN IN WIRING DIAGRAM. DO NOT CONNECT THER­MOSTAT IN MAIN POWER LINES BECAUSE IT WILL DEFEAT THE FAN DELAY FUNCTION.
8. Position the heater section over the studs in the recess ounting box (Figure 3).
m
NOTE: The end of the heater section with the terminal block
ust be posi tioned at the end of the recess mounting box where
m the supply wiring enters.
9. Push the heater section onto the studs and securely tighten
the four (4) nuts (removed from step 3) on the studs to secure the heater section to the recess mounting plate (Figure 3).
16. Connect the ground wire to the green ground screw on the recess mounting box.
17. After wiring is complete, replace and secure the side of the recess mount ing box previously removed in Step 3.
18. Install discharge air grilles. Refer to “Installation of Discharge Air Grilles”, page 6.
Installation of Recess Mounted Heaters in Permanent Ceiling (See Figures 5, 6, 7 and 8)
1. Determine the desired location of the heater. See Warning
No. 4 for minimum mounting clearance and Warning No. 9, page 1.
1
2. Cut a 22
ceiling for the recess mounting box (Figure 5).
. Remove Recess Mounted Heater assembly from carton.
3
Heater assembly includes (1) recess mounting box, (1) heater, (1) recess mount face plate and (1) set of discharge grilles.
⁄4” x 221⁄4” (565 mm x 565 mm) mounting hole in the
FAILURE TO INSTALL THE FOUR MOUNTING NUTS COULD RESULT IN THE HEATER FALLING (SEE FIGURE 3).
NOTE: Insure that the “thumb pin” in each end of the discharge grille opening is pulled outward to allow the body of the thumb pins to fit into the holes in the heater section (Figure 3).
FAILURE TO INSTALL THE FOUR SCREWS COULD ALLOW THE SURFACE WRAPPER TO FALL (SEE FIGURE 3).
10. Position the recess face plate over the heater section/recess mounting box, making sure that the thumb pins are in the holes in the heater section.
11. With the recess face plate seated firmly against the heater section, depress the “thumb pins”. This will cause the thumb pins to expand and will temporarily hold the recess face plate in place.
NOTE: The thumb pins are an aid to help position and hold the recess face plate during installation. Additional support (Step 12) is required.
FAILURE TO INSTALL THE FOUR SCREWS COULD ALLOW THE SURFACE WRAPPER TO FALL (SEE FIGURE 3).
12. Install and securely tighten four screws (supplied) to secure the recess face plate to the heater section (Figure 3).
13. Determine the desired location of the heater.
14. Position the heater in the T-bar grid (Figure 4) and secure as required.
THE HEATER ENCLOSURE MUST BE SECURELY MOUNT­ED TO CEILING OR FRAMING CAPABLE OF SUPPORTING THE HEATER (45 LBS/20.4 KG). FAILURE TO DO SO COULD ALLOW HEATER TO FALL.
1
2
2
/4”
565 mm)
221/4” (565 mm)
12” (305 mm) Min. 4 kW 24” (609 mm) Min. 5 kW
Wall
8’ (2438 mm) to Floor Min. 14’ (4267 mm) to Floor Max.
(
12” (305 mm) Min. 4 kW
Wall
24” (609 mm) Min. 5 kW
FFiigguurree 55
4. Remove recess mount box from assembly. Remove four (4) nuts from studs so heater can be removed from recess mounting box. Do not discard nuts since these will be used in Step 13 to mount heater section back on to the recess mounting box.
5. Remove one of the knockouts and install a cable or conduit connector (Figure 7).
6. Install the optional disconnect switch (if required) as shown in Figure 7.
7. Run the power supply cable through the connector, leaving about 8” (203 mm) of wire inside the recess mounting box. (Power supply cable must be #10 AWG min. rated 90°C minimum.)
8. Place the recess mounting box in the ceiling opening and align the marks on the sides of the mounting box with the bottom of the finished ceiling (Figure 6). This will position the edge of the mounting box 3/8” (9.5 mm) below the ceiling and will allow the recess face plate to lay flat against the ceiling.
9. Secure the recess mounting box to the building structure using a mini mum of four fasteners (not supplied).
15. Run the power supply cable through the connector, leaving about 8” (203 mm) of wire inside the recess mounting box. (Power supply cable must be #10 AWG min. rated 90°C minimum.)
FFiigguurree 66
4
Recess Mounting Box
3/8” (9.5 mm)
Wall
Wall
1/2” (12.2 mm) Knockout
1
7/8” & 1
/8” (22.2 & 28.5 mm) Nested Knockout
Recess Mounting Box
Optional Disconnect Switch (CDFDS)
Recess Mounting Box
Screw (2)
7/8” & 11/8” (22.2 & 28.5 mm) Nested Knockout
1/2” (12.2 mm) Knockout
Cable or Conduit Connector
FFiigguurree 77
THE HEATER ENCLOSURE MUST BE SECURELY MOUNT­ED TO CEILING OR FRAMING CAPABLE OF SUPPORTING THE HEATER (45 LBS/20.4 KG). FAILURE TO DO SO COULD ALLOW HEATER TO FALL.
10. Install optional controls (if required) into the heater section in accordance with the Instruction Sheet packaged with the control.
11. To wire the heater, thermostat, reduce wattage or convert from single to three-phase voltage, refer to “Field Conversion for Lower Wattage Rating” or “Conversion for 3ø Installation” on page 7 and wiring diagrams, Figure 13, page 7.
TO REDUCE THE RISK OF FIRE OR PERMANENT DAMAGE TO THE HEATER, THERMOSTAT MUST BE WIRED AS SHOWN IN WIRING DIAGRAM. DO NOT CONNECT THER­MOSTAT IN MAIN POWER LINES BECAUSE IT WILL DEFEAT THE FAN DELAY FUNCTION.
12. Position the heater section over the studs in the recess mounting box (Figure 8).
Note: The end of the heater section with the terminal block must be posi tioned at the end of the recess mounting box where the supply wiring enters.
13. Push the heater section onto the studs and securely tighten the four (4) nuts (removed from step 4) on the studs to secure the heater section to the recess mounting box (Figure 8).
FAILURE TO INSTALL THE FOUR MOUNTING NUTS COULD RESULT IN THE HEATER FALLING (SEE FIGURE 8).
rounding
G
crew
S
Stud (4)
Nut (4)
Thumb Pin Hole
Thumb Pin
Recess Face Plate
FFiigguurree 88
Heater Section
Screw (4)
Power Supply Cable
Insure that “Thumb Pin” is pulled out before positioning the face plate on the heater section. Depress “Thumb Pin” after face plate is sealed firmly against the heater section.
14. Connect the ground wire to the green ground screw on the recess mounting box.
15. Position the recess face plate over the heater section/recess mounting box, making sure that the thumb pins are in the holes in the heater section.
16. With the recess face plate seated firmly against the heater section, depress the “thumb pins”. This will cause the thumb pins to expand and will temporarily hold the recess face plate in place.
Note: The thumb pins are an aid to help position and hold the recess face plate during installation. Additional support (Step 17) is required. See Warning, page 2.
17. Install and securely tighten four screws (supplied) to secure the recess face plate to the heater section (Figure 8).
18. Install discharge air grilles. (Refer to “Installation of Discharge Air Grilles.”)
Installation of Discharge Air Grilles (See Figures 9, 10 and 11)
1. Refer to “Adjustable Discharge Grilles Custom Air Flow
Patterns”, page 6 of this instruction sheet to determine desired air flow direction.
2. Place the two discharge grilles onto a flat surface in the
desired configura tion with tabs on each end of grilles upward.
3. Fit the two louver guides over the two discharge grilles as
shown in Figure 9.
4. While holding the assembly together with both hands, fit one
side of assembly into the opening of the enclosure, and slide this side inward while fitting the opposite side into the enclo­sure. (See Figure 10.) Slide the assembly into position so that the bottom portion of each guide locks into the opening.
5
9
FFiigguurree 9
Slide grille assembly
1
into opening far enough to clear louver ends.
2
Push grille assembly up into opening.
3
Slide grille assembly into position in opening.
FFiigguurree 1100
Discharge Grille (2)
Louver Guides
Tabs on Discharge Grilles Must Upward
Louver Guide
Face
Adjustable Discharge Grilles Custom Air Flow Patterns (Figure 12)
1. The discharge air pattern is deter mined by the arrangement of the discharge grilles.
2. Care must be taken when selecting location of heater. Refer to “Installation of Discharge Air Grilles”, page 5.
Note: The discharge grill area is rectang ular; the discharge grilles can only be installed parallel to the intake louvers.
DDiisscchhaarrggee AAiirr
1
2
3
1
GGrriillllee AArrrraannggeemmeenntt
NARROW AIR PATTERN for high ceiling applications (11’ (3352 mm) to 14’ (4267 mm)), concentrates the heated air to ensure full penetration to the floor level.
8’ (2438 mm)
WIDE AIR PATTERN for standard ceiling applications (8’ (2438 mm) to 10’ (3048 mm)), disperses the air to give a gentle, less pronounced pattern while circulat­ing all the air from floor to ceiling.
CCuussttoomm AAiirr
FFllooww PPaatttteerrnn
Heater Discharge Grilles
Air Pattern on Floor
1
Bottom of each louver
1
guide Must position in opening.
lock in
1
Louver Guide
FFiigguurree 1111
TO PREVENT THE DISCHARGE GRILLE GUIDES FROM FALLING, THE GUIDES MUST BE FITTED (LOCKED) IN POSITION AS SHOWN IN FIGURE 12.
1
FFiigguurree 1122
Air Pattern on Floor
8’ (2438 mm)
24’ (7315 mm)
ASYMMETRICAL AIR PATTERN directs heated air in a specific direction, allowing the heater to be located where space allows with the heated air delivered to where it is required.
Air Pattern on Floor
10’ (3048 mm)
17’ (5181 mm)
6
Wiring Diagrams
Standard Wiring Diagram
(Factory Wired)
Optional Field Installed Wall Thermostat SPST or Internal CDFT Thermostat Accessory
White
Blue
Power Block
Blue
Black
White
High Limit
Black
Black
Blk
Fan Delay
Yellow
L1
L2
L3
Black
Black
Yellow
T1
2
T
T3
Red
Contactor
Red
Element 1
Black
Element 2
Black
Fan
Wiring
Conversion
for 3Ø
Installation
Wiring
Conversion
to Lower Wattage
(1Ø)
Optional Field Installed Wall Thermostat SPST or Internal CDFT Thermostat Accessory
White
Power Block
Optional Field Installed Wall Thermostat SPST or Internal CDFT Thermostat Accessory
White
Blue
Power Block
Blue
Blue
Black
White
High Limit
Black Black
Black
White
High Limit
Black
Black
Blk
Blk
Fan Delay
Yellow
1
L
L2
3
L
Fan Delay
Yellow
L1
L2
L3
Black
Black
Black
Element 1
Black
Element 2
Element 1
Black
Element 2
Black
Fan
Black
Fan
Yellow
1
T
2
T
3
T
Yellow
T1 T2
T3
Red
Contactor
Red
Black
Red
Contactor
Red
FFiigguurree 1133 EElleeccttrriiccaall WWiirriinngg
OPERATION
1. Set the thermostat (internal or remote) to highest setting. This will energize the heating elements and the fan causing air to flow from the center of the heater.
2. After the operational check, set the thermostat to obtain the desired comfort level.
Note: Heater contains a fan delay on shut down. – The fan energizes immediately when the thermostat turns on
the elements.
– Fan will operate for a short time after the heating elements
are turned off (approx. 1 minute).
Remove One (1) Red Jumper to Obtain 3/4 Nameplate Wattage
Field Conversion for Lower Wattage Rating (Figure 13)
To convert the heater to a lower watt-age rating, completely remove one (1) red jumper wire from one heating element for 25% wattage reduction. Completely remove two (2) red jumper wires for a 50% wattage reduction. Discard the jumper(s). Be sure the remaining wires are securely connected.
Conversion for 3Ø Installation
Heater is factory wired for connection to 1Ø only. To convert to 3Ø, remove and discard blue jumper wire between L1 & L3. (Figure 13).
7
MAINTENANCE
TO PREVENT ELECTRICAL SHOCK, DISCONNECT ALL POWER TO HEATER AT MAIN SERVICE PANEL BEFORE SERVICING.
1. Once each year the heater should be cleaned to remove ust and foreign material which has collected during the
d heating season.
2. Turn off all electrical power at the circuit breaker or fuse box
to discon nect the electrical power to heater.
3. Remove dust and other foreign material with a vacuum leaner nozzle or dust cloth.
c
4. Turn on the main line switch to restore power to the heater.
IMPORTANT INFORMATION
NAMEPLATE
MODEL NO. 557 DATE CODE: 1195
CEILING HEATER FAN DECK
BÀTI DU VENTILATEUR, APPAREIL DE PLAFOND
OLTS WATTS AMPS
V
277VAC 5000 18.1
OR SUPPLY CONNECTIONS USE NO. 10AWG
F OR LARGER WIRES SUITABLE FOR 90°C MIN.
UTILISER UN CÁBLE D´ALIMENTATION D´AU MOINS NO. 10AWG CONVENANT À UNE TEMPERATURE
´AU MOINS 90°C.
D
774G LISTED AIR HEATER
Figure 14
8
SURFACE
1
7
MOUNTING
ENCLOSURE,
2
6
8
RECESS
4
3
FFiigguurree 1155 RReeppaaiirr PPaarrttss IIlllluussttrraattiioonn ffoorr CCeeiilliinngg MMoouunntteedd FFaann FFoorrcceedd HHeeaatteerrss
8
7
MOUNTING
ENCLOSURE,
Repair Parts List for Ceiling Mounted Fan Forced Heaters
Ref. Part Number for Models: No. Description CDF552SE CDF547SE CDF548SE CDF557SE CDF558SE Qty.
1 Element 302012813 302012803 302012801 302012814 302012812 2 2 Fan Delay 1414-2039-000 1414-2039-000 1414-2039-000 1414-2039-000 1414-2039-000 1 3 Fan Blade 1210-2000-000 1210-2000-000 1210-2000-000 1210-2000-000 1210-2000-000 1 4 Motor 3900-2011-000 3900-2011-001 3900-2011-000 3900-2011-001 3900-2011-000 1 5 High Limit 4520-0011-000 4520-0011-000 4520-0011-000 4520-0011-000 4520-0011-000 1 6 Contactor 5018-0004-102 5018-0004-103 5018-0004-102 5018-0004-103 5018-0004-102 1 7 Outlet Grille 2501-2020-001 2501-2020-001 2501-2020-001 2501-2020-001 2501-2020-001 2 8 Louver Guides 1215-2059-001 1215-2059-001 1215-2059-001 1215-2059-001 1215-2059-001 2
(Surface)
Ref. Part Number for Models: No. Description CDF552RE CDF547RE CDF548RE CDF557RE CDF558RE Qty.
1 Element 302012813 302012803 302012801 302012814 302012812 2 2 Fan Delay 1414-2039-000 1414-2039-000 1414-2039-000 1414-2039-000 1414-2039-000 1 3 Fan Blade 1210-2000-000 1210-2000-000 1210-2000-000 1210-2000-000 1210-2000-000 1 4 Motor 3900-2011-000 3900-2011-001 3900-2011-000 3900-2011-001 3900-2011-000 1 5 High Limit 4520-0011-000 4520-0011-000 4520-0011-000 4520-0011-000 4520-0011-000 1 6 Contactor 5018-0004-102 5018-0004-103 5018-0004-102 5018-0004-103 5018-0004-102 1 7 Outlet Grille 2501-2020-001 2501-2020-001 2501-2020-001 2501-2020-001 2501-2020-001 2 8 Louver Guides 1215-2059-000 1215-2059-000 1215-2059-000 1215-2059-000 1215-2059-000 2
(Recessed)
9
Loading...
+ 21 hidden pages