Dear Owner,
Congratulations! Thank you for purchasing this new heater manufactured by a division of Marley Engineered Products. You have made a wise investment selecting the highest quality product in the heating industry. Please carefully r ead and follow the installation and maintenance dir ections shown in this manual. You should enjoy years of efficient heating comfort with this product from Marley Engineered Products... the industry’s leader in design, manufacturing, quality and service.
... The Employees of Marley Engineered Products
Installation & Maintenance Instructions
!
Read carefully - These instructions are written to help
you prevent difficulties that might arise during installation of heaters. Studying the instructions first may save you considerable time and money later. Observe the follow­ing procedures and cut your installation time to a mini­mum.
TO REDUCE RISK OF FIRE AND ELECTRIC SHOCK:
1. Disconnect all power coming to the heater at main service panel before wiring or servicing. Note: More than one disconnect may be required.
2. All wiring must be in accordance with national and local electric codes and the heater must be ground­ed.
3. Verify the power supply voltage coming to heater matches the ratings printed on the heater nameplate before energizing.
4. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces.
5. Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause
electric shock, fire, or damage to heater.
6. Do not block air intakes or exhaust in any manner. Keep combustible materials at least 24” (610 mm) away from heater. Keep drapes at least 6” (153 mm) above top of front discharge grille. Do not use drapes above top discharge units. Do not install behind doors, furniture, towel rack, or boxes.
7. A heater has hot and arcing (sparking) parts inside. Do not use in areas where gasoline, paint, or flam­mable liquids are used or stored.
8. Use this heater only as described in this manual. Any other use not recommended by the manufacturer may cause fire, electric shock, or injury.
9. This heater is not approved for use in corrosive atmospheres such as marine, green house, or chem­ical storage areas.
10.
FOR DUCT CONNECTED HEATERS, Do not exceed 0.2 wg. external static pressure and do not mount heater on end panels.
11. Do not use
OPTIONAL 0-100% OUTSIDE AIR
DAMPER with bottom air inlet.
SAVE THESE INSTRUCTION SHEETS
900 Series
Cabinet Unit Heaters
Model B
1
Page 2
KW
2 3 4 5 6 7 8
4 6
8 10 12 14 16
6
8 10 12 14 16
6
9 12 15 18 21 24
8 12 16 20 24 28 32
BTU/hr
6,826 10,239 13,652 17,065 20,478 23,891 27,304
13,652 20,478 27,304 34,130 40,956 47,785 54,608
20,478 27,304 34,103 40,956 47,782 54,608
20,478 30,717 40,956 51,195 61,434 71,673 81,912
27,304 40,956 54,608 68,260 81,912 95,564
109,216
Series
935
945
958
968
978
Cabinet
Length
(in)
35
45
58
68
78
CFM*
250
500
750
750
1,000
208
1 ph
60 Hz
10 15 20 25 30 34 39
20 30 40
48 59 68 78
30
40
48 59 68 78
31
45
60
74
88
n/a n/a
41 60 79
n/a n/a n/a n/a
208
3 ph
60 Hz
6
9 12 15 17 20 23
12 18 23 29 34 40 46
18 23 29 34 40 46
19 27 35 44
52 60 69
24 36 47
58 69 80 91
240
1 ph
60 Hz
9 13 17 22 26 30 34
18 26 34 43
51 59 68
26 34 43
51 59 68
27 39
52 64 77 89
n/a
36
52 69 86
n/a n/a n/a
240 3 ph
60 Hz
6
8 10 13 15 18 20
11 16 20 25 30 35 40
16 20 25 30 35 40
16 24 31 38 45
52 60
21 31 41
50 60 70 79
277
1 ph
60 Hz
8 12 15 19 22 26 30
16 23 30 37 44
52 59
23 30 37 44
52 59
24 34 45
56 67 78
n/a
31 46
60 74
n/a n/a n/a
347
1 ph
60 Hz
7
9 12 15 18 21 24
13 18 24 30 36 41 47
18 24 30 36 41 47
19 28 36 45
n/a n/a n/a
25 37 48
n/a n/a n/a n/a
380
3 ph
60 Hz
4 5 7
8 10 11 13
7 10 13 16 19 22 25
10 13 16 19 22 25
11 16 20 25 29 34 38
14 20 27 33 39 45
n/a
480
3 ph
60 Hz
3 4 6 7 8 9
10
6
8 11 13 16 18 20
8 11 13 16 18 20
9 13 16 20 24 27 31
12 17 21 26 31 36 41
600
3 ph
60 Hz
3 4 5 6 7 7 8
5 7
9 11 13 15 17
7
9 11 13 15 17
8 11 13 16 19 22 25
10 14 18 21 15 29 33
HEATING
CAPACITY
- CIRCUIT BREAKERS or FUSED DISCONNECT required * - Value shown for HIGHSPEED on two speed units
Specifications
Total Line Amperage (includes motor amps)
2
Page 3
3
General Information
900 Series Cabinet Unit Heaters are designed and UL & cUL Listed to be applied as Standard Free Air heaters with both louvered intake and louvered discharge panels for recess or surface installation: a) on the floor, with front inlet and up flow air movement in the up flow, down flow, left or right direction or b) on the ceiling, or Ducted (0.2 wg external static pressure) flange for direct connection of field supplied ductwork to the inlet, discharge, or both inlet and discharge. Ducted heaters can be installed for recess or surface installation: a) on the floor, with front inlet and up flow air movement, b) on the wall, with air movement in the up flow or down flow direction or c) on the ceiling.
See Figure 1 for Mounting Clearances.
Note:
Keep all furniture or any other blocking material at least 24 (610mm) away from front of heater. When draperies are used, hang them so that when in use they are at least 6 (153mm) above the top of front discharge heater. Do not use draperies with top discharge heaters.
See Figure 2 for Mounting Dimensions See Figure 3 for Duct Collar Dimensions and Installation Details.
FLOOR MOUNTING
1.
Heaters with front inlet and up flow air movement
may be mounted directly on any floor surface includ­ing carpeting. Where wall to wall carpeting is installed after heater installation the carpeting can be run up to the front and around the heater body. See Figure 1 for mounting clearances.
2. Heaters can be mounted on either end with air movement
left or right directly on any floor surface including carpeting. See Figure 1 for mounting clearances.
3. If optional kick plate is not used, proceed to HEATER
INSTALLATIONsection.
INSTALLATION OF OPTIONAL 900 SERIES BASE
KIT
1. If desired, the heaters may be mounted off the floor with
optional kick plate panel.
2. Align panel on bottom of heater (Inlet side only.)
3. There should be a 1 (25mm) space from the panel to the
front and sides of the heater.
4. Match drill .140 (3.55 mm) diameter holes in the bottom of
the heater and secure with screws provided.
5. Proceed to “HEATER INSTALLATIONsection.
WALL OR CEILING RECESS MOUNTING
1. Create on opening in the wall 26-5/8 (676mm) high by the width of the heater plus 1/4 (6.4mm).
Example: If the heater was 68 inches long, the opening should measure 26-5/8 high x 68-1/4 long).
2. The depth of the recess will vary with the desired amount of heater recess.
3. Proceed to HEATER INSTALLATION section.
INSTALLATION OF OPTIONAL
900 SERIES RECESS TRIM KIT
1. Determine depth of heater recess.
2. Align recess trim frame so that the trim frame front edge will touch wall when heater is installed.
3. Match drill .140 (3.55mm) diameter holes in all four sides of the heater and secure trim frame with screws provided.
4. Proceed to “HEATER INSTALLATION section.
HEATER INSTALLATION
1. Rough-in electrical wiring. See Figure 2 for knockout locations.
2. Remove the proper knockout in the heater or punch the proper size hole in the bottom or right side of the heater as shown in Figure 2.
3. Remove the front cover by rotating the lock(s) counter­clockwise (ccw).
4. Remove Top (Discharge) Louver Panel by removing 2 screws (one on each end) that attach the louver panel to the end panels.
5. Refer to Figure 3 for location of mounting holes.
6. Mark and drill holes for heater attachment in wall or ceiling.
7. Install heater in opening and tighten screws (field supplied) to insecure tight fit of the heater against the mounting sur­face.
NOTE: Tightening the heater against an irregular wall will cause distortion of the back panel of the heater. If this is the case, shims should be used behind the back panel to keep it straight.
8. Reinstall the Top (Discharge) Louver Panel by sliding the panel into the heater. Position the panel tabs of the louver panel to rest on the top of the lip of the heater back. Position the louver panel top even with the top of the end panels. Tap the louver panel at the top front (both sides) to seat the panel. Reinstall 2 screws (one on each side) that attach louver panel to the end panels.
9. WIRING - See wiring section.
10.After wiring is complete, insure that the control box cover is closed and fastened and that the filter is installed.
11.Adjust the thermostat to the desired set point.
12.Adjust the heat selector to the heat and fan speed desired.
13.Replace front cover and secure by turning the locks clock­wise (cw) until tight. Replace plug buttons provided.
14.Leave the heater running a few hours before making any further change in thermostat setting.
CAUTION
TO PREVENT HEATER FROM FALLING AND CAUSING PERSONAL INJURY, EACH FASTENER, AS APPLIED, SHOULD HAVE THE HOLDING POWER OF AT LEAST 100 POUNDS (45 kg).
!
Page 4
DUCTED APPLICA TIONS
1. See Figure 3 for duct flange size and location.
2. Duct collars have been factory located (Bottom inlet, Front inlet, Top discharge, Front discharge) as ordered.
3. To change duct collar location:
A. Heater duct panels are supplied with a duct collar attached
to one surface and a blank-off plate attached to the other surface. The location of the duct collar and the blank-off plate can reversed.
B. Remove screws holding blank-off plate and remove blank-
off plate.
C. Remove screws holding duct collar and remove duct collar. D. Position duct collar to location desired, align screws holes,
insert and tighten screws to secure duct collar to duct panel.
E. Position blank-off plate to location desired, align screw
holes, insert and tighten screws blank-off plate to duct panel.
4. Position field ductwork to outside of heater duct flange.
5. Mark and drill starting holes in duct and flange.
6. Install and tighten screws (field supplied) to provide a secure seal.
OPTIONAL
0-100% OUTSIDE AIR DAMPER
1. Flange brackets for the rear mounted duct collar are pack­aged unassembled in the heater carton.
2. See Figure 2 for location of damper opening.
3. Position the top flange bracket with the flange at the top of the damper opening and holes in the flange align with holes in the cabinet back.
4. Attach flange to cabinet with screws provided.
5. Position and attach remaining three (3) flange brackets around damper opening.
6. Position field ductwork to outside of flange brackets.
7. Mark and drill starting holes in duct and flange.
8. Install and tighten screws (field supplied) to provide a secure seal.
OPERATION OF OPTIONAL
0-100% OUTSIDE AIR DAMPER
1. Controls, consisting of an OPEN-CLOSED switch and 0­100% positioning potentiometer, are located on the control panel door.
2. Place switch in OPEN position.
3. Adjust potentiometer to percentage of outside air desired.
4. The damper will remain open to the position selected until; the OPEN-CLOSED switch is moved to the closed posi­tion, the ON-OFF switch (if installed) is turned off, the night set back relay (if installed) is in the night position, or if there is a power failure.
TO REDUCE RISK OF FIRE AND ELECTRICAL
SHOCK:
DO NOT EXCEED 0.2” WG EXTERNAL STATIC
PRESSURE. DO NOT MOUNT HEATER ON END PANEL
(LEFT OR RIGHT AIR FLOW).
WARNING
!
TO REDUCE RISK OF FIRE AND ELECTRICAL
SHOCK: DO NOT USE 0-100% OUTSIDE AIR DAMPER
OPTION WITH BOTTOM AIR INLET. USE ONLY FRONT AIR
INLET WITH 0-100% OUTSIDE AIR DAMPER OPTION.
WARNING
!
4
Page 5
Figure 1
5
Minimum 2 (52mm) to side wall
HEATER:
Wall Mounted
AIR FLOW:
Up or Down
HEATER:
Wall Mounted on End Panel
AIR FLOW:
Left or Right
HEATER:
Ceiling Mounted
Upflow
Ceiling
Downflow
Upflow
Downflow
Wall
Zero or greater
Upflow
(semi-recessed)
Wall
Zero or greater
Ceiling mounted
Wall
Zero or greater
Ceiling mounted
24" min. (610 mm)
Floor
Ceiling
24" min. (610 mm)
Floor
Ceiling
24" min. (610 mm)
(semi-recess)
Downflow
Zero or greater
Wall
Ceiling
5" min. (127 mm)
24" min. (610 mm)
(semi-recessed)
24" min. (610 mm)
24" min. (610 mm)
5" min. (127 mm)
Upflow
(full recessed)
24" min. (610 mm)
Zero or greater
Ceiling mounted
24" min. (610 mm)
5" min (127mm)
Ceiling mounted (full recess)
Zero or greater
Downflow
(full recessed)
Zero or greater
24" min. (610 mm)
24" min. (610 mm)
Wall
End mounting
Zero or greater
Wall
24" min. (610 mm)
Wall End mounting
Zero or greater
Wall
Wall
Ceiling
End mounting
semi-recess
Zero or greater
Wall
24" min. (610 mm)
Wall
End mounting
semi-recess
Zero or greater
Wall
Wall
Ceiling
24" min. (610 mm)
Zero or greater
End mounting
full recess
Zero or greater
Wall
24" min. (610 mm)
Wall
End mounting
full recess
Zero or greater
Wall
Wall
Ceiling
Zero or greater
Floor
Zero or greater
Floor
Zero or greater
Floor
Page 6
Figure 2
6
Figure 2
MOUNTING DIMENSIONS
Including Front Cover
Heater Back
OPTIONAL
OUTSIDE AIR
Collar
4-1/2(114 mm)
1-3/8
(35 mm)
LEFT SIDE VIEW
(Typ. all lengths)
9-7/8
(251 mm)
3/4 (19 mm)
26-3/8
(670 mm)
8-7/16
(214 mm)
(457 mm)
Air Flow --->
OUTSIDE AIR
FRONT VIEW
35" (889 mm) CABINET
(889 mm)
18
(413 mm)
16-1/4
OPTIONAL
13
(330 mm)
35
13-1/2
(343 mm)
TOP
Front Cover
1-23/32", 1-23/64", 1-31/32" Concentric Knockouts
CONTROL
COMPARTMENT
3
(76 mm)
4
(102 mm)
(127 mm)
14-1/2
(368 mm)
(76mm)
5
3
7/8", 1-3/32" Concentric Knockouts
4-3/8
(111 mm)
NOTE: Knockout Size & Location Typical All Heaters
Drill location for conduit hole
RIGHT SIDE VIEW
(Typ. all lengths)
1-5/8
(41 mm)
8-7/16
(214 mm)
45
(1143 mm)
28
(711 mm)
16-1/4
(413 mm)
Air Flow --->
OPTIONAL
OUTSIDE AIR
27
(686 mm)
FRONT VIEW
45" (1143 mm) CABINET
68
25-1/2
(648 mm)
(1727 mm)
25-1/2
(648 mm)
(343 mm)
(365 mm)
Drill location for conduit hole
BOTTOM VIEW
(Typ. all lengths)
13-1/2
TOP
CONTROL
COMPARTMENT
14-3/8
13-1/2
(343 mm)
TOP
7
(178 mm)
8-7/16
(214 mm)
41
(1041 mm)
16-1/4
(413 mm)
Air Flow --->
OPTIONAL
OUTSIDE AIR
41
(1041 mm)
FRONT VIEW
58" (1473 mm) CABINET
78
32-5/8
(829 mm)
(1981 mm)
58
(1473 mm)
28-1/2
(724 mm)
13-1/2
(343 mm)
TOP
14-3/8
(365 mm)
COMPARTMENT
CONTROL
13-1/2
(343 mm)
TOP
16-1/4
(413 mm)
Air Flow --->
8-7/16
(214 mm)
OPTIONAL
OUTSIDE AIR
41
(1041 mm)
FRONT VIEW
68" (1727 mm) CABINET
14-3/8
(365 mm)
CONTROL
COMPARTMENT
16-1/4
(413 mm)
CONTROL
COMPARTMENT
8-7/16
(214 mm)
OPTIONAL
OUTSIDE AIR
55
(1397 mm)
14-3/8
(365 mm)
FRONT VIEW
78" (1981 mm) CABINET
Page 7
7
Figure 3
DUCT COLLARS DIMENSIONS and INSTALLATION DETAILS
(124 mm)
4-7/8
(103 mm)
4-1/16
Heater Back
4-1/16
(103 mm)
4-7/8
(124 mm)
LEFT SIDE VIEW BOTTOM INLET / TOP DISCHARGE
(Typ. all lengths)
(118 mm)
4-5/8
Air Flow --->
2 (51mm)
2 (51mm)
(908 mm)
35-3/4
(173 mm)
6-13/16
Air Flow --->
(173 mm)
6-13/16
(543 mm)
21-3/8
(543 mm)
21-3/8
FRONT VIEW
35" (889 mm) CABINET
(118 mm)
4-5/8
(173 mm)
6-13/16
(173 mm)
6-13/16
(186 mm)
7-5/16
Air Flow --->
Air Flow --->
9/16
(14 mm)
4-7/8
(124 mm)
(124 mm)
4-7/8
(14 mm)
9/16
RIGHT SIDE VIEW
FRONT INLET /
FRONT DISCHARGE
(Typ. all lengths)
(1102 mm)
43-3/8
2 (51mm)
2 (51mm)
Heater Back
(186 mm)
7-5/16
(92 mm) 3-5/8
(92 mm)
3-5/8
4-5/8
Air Flow --->
(908 mm)
35-3/4
FRONT VIEW
45" (1143 mm) CABINET
(1543 mm)
60-3/4
(1543 mm)
60-3/4
FRONT VIEW
68" (1727 mm) CABINET
(118 mm)(118 mm)
4-5/8
(186 mm)
7-5/16
(1102 mm)
45-3/8
(186 mm)
7-5/16
FRONT VIEW
58" (1473 mm) CABINET
(92 mm)
3-5/8
(92 mm)
3-5/8
(92 mm)
3-5/8
3-5/8
(92 mm)
(92 mm)
3-5/8
Air Flow --->
(92 mm)
3-5/8
(1797 mm)
70-3/4
(1797 mm)
70-3/4
FRONT VIEW
78" (1981 mm) CABINET
Page 8
8
WIRING
SEE WARNING STEPS 1, 2 & 3 ON PAGE 1 OF THIS INSTRUCTION SHEET.
1. Figure 4 shows a typical wiring diagram.
2. For actual wiring, see the diagram located on the inside of the front cover.
3. All field wiring must be 75˚ C min.
TO CONVERT 208, 240, 480 & 600 VOLT
STOCK 5 & 10 KW HEATERS
From Three Phase To Single Phase
1. Remove front cover.
2. Refer to wiring diagram located located inside front cover.
NOTE: Terminal block and wires that need to be
changed are
located in wire way above right hand (RH) blower
housing.
3. Remove two screws holding wireway cover to fan panel.
4. Rotate wireway cover up and out to remove.
5. Terminal block is located within wireway.
6. Relocate wires per wiring diagram located inside front cover.
7. Reinstall wireway cover and reinstall screws.
8. Reinstall front cover.
Typical Wiring Diagram
See wiring diagram on the inside of heater front cover.
SUPPLY
POWER
OPTIONAL DISCONNECT SWITCH
OPTIONAL CIRCUIT BREAKER
L 1
L 2
L 3
B
F
AL1-1
E1-1
R1-1
C
A
E1-3
R1-2
E1-2
AL1-2
B
C
A
R2-1
F2
F1
M
FDR-1
S1-2
L
H
FAOR-1
T 4
FAOS
FAOR
C 1
C 4
T 1
T 2
H
L
T
C
S1-1
ORANGE
RFHS
EMS
R-1
FDR
R2
MR1
S2
C
DM
SW
DAMPER
MOTOR
CONTROLLER
OPTIONAL
100% OUTSIDE AIR DAMPER
CLOSED
OPEN
S3
NSB-1
T5
T6
24 VAC EXTERNAL NIGHT SETBACK CIRCUIT RS MUST BE ENERGIZED FOR DAY OPERATION
BLUE
C 3
C 2
EMS=ENERGY MANAGEMENT SYSTEM TIE-IN (CONTACTS MUST BE CLOSED FOR DAY OPERATION) RFHS=REMOTE MOUNTED FAN/HEAT ON-OFF SWITCH (FIELD SUPPLIED)
NOTE: IF EMS AND/OR RFHS ARE INSTALLED REMOVE ORANGE WIRE BETWEEN C1 AND C4.
FOR EXTERNAL
CONTROL SUPPLY:
1. REMOVE BLUE JUMPER BETWEEN C2 AND C3.
2. CONNECT EXTERNAL CONTROL (24 VAC STANDARD, 120 VAC OPTIONAL) TO C1 AND C2.
S1 = FAN/HEAT HIGH-LOW SELECTOR SWITCH S2 = DOOR INTERLOCK SWITCH S3 = FAN/HEAT ON-OFF SWITCH (FACTORY INSTALLED OPTION) NSB = NIGHT SETBACK RELAY (FACTORY INSTALLED OPTION)
AL = AUTO RESET LIMIT MR = MANUAL RESET LIMIT (FACTORY INSTALLED OPTION) T = BUILT-IN OR REMOTE MOUNTED SINGLE POLE THERMOSTAT FAOS = FAN AUTO-ON SWITCH (BUILT-IN = FACTORY INSTALLED OPTION)
(REMOTE MOUNTED = FIELD INSTALLED OPTION) FDR = FAN DELAY RELAY FAOR = FAN AUTO-ON RELAY (FACTORYINSTALLED OPTION)
1609-2081-020
Page 9
9
208 208 240 240 277 347 380 480 600
CABINET 1 PH 3PH 1PH 3PH 1PH 1PH 3PH 3PH 3PH
LENGTH KW 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ
QTY VAR QYT VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR 2 1 041 1 050 1 041 1 050 1 024 1 017 1 010 1 010 1 059 3 1 042 1 050 1 042 1 050 1 024 1 017 1 010 1 010 1 059 4 1 043 1 050 1 043 1 050 1 025 1 018 1 010 1 010 1 059
35 in. 5 1 045 1 051 1 044 1 051 1 026 1 018 1 010 1 010 1 059
6 1 046 1 052 1 045 1 051 1 026 1 019 1 010 1 010 1 059 7 1 047 1 053 1 046 1 052 1 027 1 020 1 010 1 010 1 059 8 1 048 1 053 1 047 1 052 1 027 1 020 1 010 1 010 1 059
4 1 044 1 051 1 043 1 050 1 025 1 018 1 010 1 010 1 059 6 1 046 1 052 1 045 1 051 1 026 1 019 1 010 1 010 1 059 8 1 048 1 053 1 047 1 053 1 027 1 021 1 011 1 010 1 059
48 in. 10 1 049 1 055 1 048 1 054 1 007 1 022 1 012 1 011 1 059
12 2 046 1 056 2 045 1 055 1 007 1 023 1 012 1 011 1 060 14 2 046 1 057 2 045 1 056 1 021 1 068 1 013 1 012 1 060 16 2 048 1 058 2 047 1 057 1 022 1 068 1 014 1 013 1 061
6 1 046 1 052 1 045 1 051 1 026 1 019 1 010 1 010 1 059 8 1 048 1 053 1 047 1 053 1 027 1 021 1 011 1 010 1 059
58 in. 10 1 049 1 055 1 048 1 054 1 027 1 021 1 011 1 010 1 059
12 2 046 1 056 2 045 1 055 1 007 1 023 1 012 1 011 1 060 14 2 046 1 057 2 045 1 056 1 021 1 068 1 013 1 012 1 060 16 2 048 1 058 2 047 1 057 1 022 1 068 1 014 1 013 1 061
6 1 046 1 052 1 045 1 052 1 026 1 019 1 010 1 010 1 059 9 1 049 1 054 1 048 1 053 1 028 1 021 1 011 1 011 1 059
12 2 046 1 056 2 045 1 055 1 007 1 008 1 013 1 012 1 060 15 1 048 1 058 1 048 1 057 1 007 1 068 1 014 1 012 1 061
1 045 1 044 1 026
68 in. 18 3 046 1 056 3 045 1 058 1 028 N/A N/A 1 014 1 013 1 061
1 052 1 026
21 N/A N/A 1 057 3 046 1 056 1 015 N/A N/A 1 015 1 014 1 062
1 053 1 052
24 N/A N/A 1 058 N/A N/A 1 057 N/A N/A N/A N/A 1 009 1 014 1 063
1 053 1 053
8 1 049 1 054 1 047 1 054 1 027 1 021 1 011 1 010 1 059
12 2 046 1 056 2 045 1 055 1 007 1 008 1 013 1 012 1 060 16 2 048 1 058 2 047 1 058 1 022 1 068 1 014 1 013 1 061
78 in. 20 N/A N/A 2 055 2 049 2 054 1 068 N/A N/A 1 015 1 014 1 062
24 N/A N/A 2 055 N/A N/A 2 054 N/A N/A N/A N/A 1 009 1 014 1 063 28 N/A N/A 2 057 N/A N/A 2 056 N/A N/A N/A N/A 1 016 1 015 1 064 32 N/A N/A 2 058 N/A N/A 2 057 N/A N/A N/A N/A N/A N/A 1 016 1 065
CIRCUIT BREAKERS ORDER PARTNO. 410086+VAR NOTED BELOW
Page 10
10
208 208 240 240 277 347 380 480 600
CABINET 1 PH 3PH 1PH 3PH 1PH 1PH 3PH 3PH 3PH
LENGTH KW 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ 60HZ
QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR QTY VAR
2 1 100 1 100 1 101 1 101 1 102 1 103 1 100 1 102 1 103 3 1 107 1 107 1 114 1 114 1 104 1 105 1 107 1 104 1 105 4 1 106 1 106 1 107 1 107 1 108 1 109 1 106 1 108 1 109
35 in. 5 1 110 1 11 0 1 111 1 111 1 11 2 1 113 1 11 0 1 112 1 113
6 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105 7 1 107 1 107 1 108 1 108 1 104 1 105 1 107 1 104 1 105
1 106 1 106 1 107 1 107 1 108 1 109 1 106 1 108 1 109
8 1 107 1 107 1 108 1 108 1 112 1 113 1 110 1 112 1 113
1 110 1 110 1 111 1 111 1 112 1 113 1 110 1 112 1 113
4 2 100 2 100 2 101 2 101 2 102 2 103 2 100 2 102 2 103 6 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105 8 2 106 2 106 2 107 2 107 2 108 2 109 2 106 2 108 2 109
48 in. 10 2 110 2 110 2 111 2 111 2 112 2 113 2 110 2 112 2 113
12 4 107 4 107 4 108 4 108 4 104 4 105 4 107 4 104 4 105 14 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105
2 106 2 106 2 107 2 107 2 108 2 109 2 106 2 108 2 109
16 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105
2 110 2 110 2 111 2 111 2 112 2 113 2 110 2 112 2 113
6 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105 8 2 106 2 106 2 107 2 107 2 108 2 109 2 106 2 108 2 109
58 in. 10 2 110 2 110 2 111 2 111 2 112 2 113 2 110 2 112 2 113
12 4 107 4 107 4 108 4 108 4 104 4 105 4 107 4 104 4 105 14 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105
2 106 2 106 2 107 2 107 2 108 2 109 2 106 2 108 2 109
16 2 107 2 107 2 108 2 108 2 104 2 105 2 107 2 104 2 105
2 110 2 110 2 111 2 111 2 112 2 113 2 110 2 112 2 113
6 3 100 3 100 3 101 3 101 3 102 3 103 3 100 3 102 3 103
9 3 107 3 107 3 108 3 108 3 104 3 105 3 107 3 104 3 105 12 3 106 3 106 3 107 3 107 3 108 3 109 3 106 3 108 3 109 15 3 110 3 110 3 111 3 111 3 112 3 113 3 110 3 112 3 113
68 in. 18 6 107 6 107 6 108 6 108 6 104 N/A N/A 6 107 6 104 6 105
21 N/A N/A 3 107 3 108 3 108 3 104 N/A N/A 3 107 3 104 3 105
3 106 3 107 3 108 3 108 3 106 3 108 3 109
24 N/A N/A 3 107 N/A N/A 3 108 N/A N/A N/A N/A 3 107 3 104 3 105
3 110 3 111 3 110 3 112 3 113
8 4 100 4 100 4 101 4 101 4 102 4 103 4 100 4 102 4 103 12 4 107 4 107 4 108 4 108 4 104 4 105 4 107 4 104 4 105 16 4 106 4 106 4 107 4 107 4 108 4 109 4 106 4 108 4 109
78 in. 20 N/A N/A 4 110 4 111 4 111 4 112 N/A N/A 4 110 4 112 4 113
24 N/A N/A 8 107 N/A N/A 8 108 N/A N/A N/A N/A 8 107 8 104 8 105 28 N/A N/A 4 107 N/A N/A 4 108 N/A N/A N/A N/A 4 107 4 104 4 105
4 106 4 107 4 106 4 108 4 109
32 N/A N/A 4 107 N/A N/A 4 108 N/A N/A N/A N/A N/A N/A 4 104 4 105
4 110 4 111 4 112 2 113
ELEMENTS ORDER PARTNO. 1802-2083+VAR NOTED BELOW
Page 11
Description 935 945 958 968 978
QTY P/N QTY P/N QTY P/N QTY P/N QTY P/N
Filter (Permanent) 1 2010-7008-006 1 2010-7008-007 1 2010-7008-008 1 2010-7008-006 2 2010-7008-007
1 2010-7008-007
Filter (Throw-Away) 1 2010-7009-006 1 2010-7009-007 1 2010-7009-008 1 2010-7009-006 2 2010-7009-007
1 2010-7009-007
Motor 1 3900-2032-000 1 3900-2033-000 1 3900-2033-000 1 3900-2033-000 2 3900-2033-000
1 3900-2032-000 Manual Reset Limit 1 4520-2017-000 1 4520-2017-000 1 4520-2017-000 1 4520-2017-001 1 4520-17-002 Auto Reset Limit 4520-2048-000 Power Relay
(24V Control) 410101001
(120V Control) 410101003 Fan Delay Relay Single Stage Heater
(24V Control) 410171001
(120V Control) 410171002 Two Stage Heater
(24V Control) 410101001
(120V Control) 410101003 Transformer (Power)
277V Heater 490015025 490015024 347V Heater 490015026 490015027 380V Heater 490015011 490015023 480V Heater 490015025 490015024 600V Heater 490015026 490015027 Transformer (Control)
(24V Control) 490026007
(120V Control) 49002604 Thermostat (Built-in) Single Stage Heater 410127001
Two Stage Heater 5813-2008-000 High-Low Heat Switch 5216-2029-000 Heat On-Off Switch 5216-2029-001
11
REPLACEMENT PARTS LIST (cont.)
Basic Model Series
Page 12
LIMITED WARRANTY
All products manufactured by Marley Engineered Products are warranted against defects in workmanship and materials for one year from date of installation, except heating elements which are warranted against defects in workmanship and materials for five years from date of installation. This warranty does not apply to damage from accident, misuse, or alteration; nor where the connected voltage is more than 5% above the nameplate voltage; nor to equipment improperly installed or wired or maintained in violation of the products installation instructions. All claims for warranty work must be accompanied by proof of the date of installation.
The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor costs, and shipping costs incurred to return products to Marley Engineered Products Service Center. Within the limitations of this warranty, inoperative units should be returned to the nearest Marley authorized service center or the Marley Engineered Products Center, and we will repair or replace, at our option, at no charge to you with return freight paid by Marley. It is agreed that such repair or replacement is the exclusive remedy available from Marley Engineered Products.
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR APARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT. MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT, WHETHER BASED UPON NEGLIGENCE, TORT, STRICT LIABILITY, OR CONTRACT.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above exclusion or limita­tion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
For the address of your nearest authorized service center, contact Marley Engineered Products in Bennettsville, SC, at 1-800­642-4328. Merchandise returned to the factory must be accompanied by a return authorization and service identification tag, both available from Marley Engineered Products. When requesting return authorization, include all catalog numbers shown on the products.
HOW TO ORDER REPAIR PARTS
In order to obtain any needed repair or replacement parts, warranty service or technical information, please contact Marley Engineered Products Service Center toll-free by calling 1-800-642-HEAT.
When ordering repair parts, always give the information listed as follows:
1. The Part Number 3. The Part Description
2. The Model Number 4. Date of Manufacture
5/01
5200-2386-001
ECR 34345
12