Marley 542, 548, 547, 558, 552 Instructions Manual

...
Ceiling Mounted
Fan Forced Heater
SERIES 500
Read Carefully - These instructions are written to help you
prevent difficulties that might arise during installation of heaters. Studying the instructions first may save you consid­erable time and money later. Observe the following proce­dures and cut your installation time to a minimum.
2. All wiring must be in accordance with the National and Local Electrical Codes and the heater must be grounded as a precaution against possible electric shock.
3. Verify the power supply voltage coming to heater match­es the ratings printed on the heater nameplate before energizing.
4. Do not install the heater closer than 12” (305mm) to any wall for models 548, 542, 547 and 24” (610mm) to any wall for models 558, 552 and 557.
5. Do not insert or allow foreign objects to enter any ventila-
tion or exhaust opening as this may cause an electric shock, fire, or damage to the heater.
6. To prevent a possible fire, do not block air intakes or exhaust in any manner. Keep combustible materials, such as crates, drapes, etc., away from heater.
7. A heater has hot and arcing (sparking) parts inside. Do not use it in areas where gasoline, paint, or flammable liquids are stored.
8. This heater is not approved for use in corrosive atmos­pheres such as marine, green house, or chemical storage areas.
9. The heater enclosure must be securely mounted to ceil­ing or framing capable of supporting the heater (45 lbs /
20.4 kg). Failure to do so could allow heater to fall.
10. Do not operate heater without outlet grilles installed. When installing grilles with louver guides, make sure guides drop into position so they cannot slide out during use.
WARNING
SA VE THESE INSTRUCTIONS
Dear Owner, Congratulations! Thank you for purchasing this new heater manufactured by a division of Marley
Engineered Products. You have made a wise investment selecting the highest quality product in the heat­ing industry. Please carefully read the installation and maintenance directions shown in this manual. You should enjoy years of efficient heating comfort with this product from Marley Engineered Products... the industry’s leader in design, manufacturing, quality and service.
... The Employees of Marley Engineered Products
Installation & Maintenance Instructions
1
Recessed Mount
Surface Mount
!
NOTE: Field wiring must be #10 AWG. min. rated 90°C,min. Wiring Compartment Volume: 252in
3
(4130cm3)
ADJUSTABLE DISCHARGE GRILLES
CUSTOM AIR FLOW PATTERNS
1. The discharge air pattern is determined by the arrange­ment of the discharge grilles.
2. Care must be taken when selecting location of heater.
NOTE: The discharge grill area is rectangular; the discharge grilles can only be installed parallel to the intake louvers.
UNPACKING INSTRUCTIONS
This heater is shipped in two cartons.
1. One carton contains the Heater Section, consisting of the fan, heating elements and controls (Models 542, 547, 548, 557 & 558).
2. The other carton contains the Mounting Enclosure. There are two types of enclosures: a) Recessed Mounting Enclosure, Type REA and b) Surface Mounting Enclosure, Type SEA. Either enclosure is acceptable with any of the Model 500 Series heater sections.
Both a Heater Section and a Mounting Enclosure are required to complete the installation of this heater.
INSTALLATION OF SURFACE MOUNTED HEATER
1. Determine the desired location of the heater. See warn­ing No. 4 for min. mounting clearances.
2. Remove the Surface Mounting Plate (Figure 1) from the carton containing the Surface Mounting Enclosure, Type SEA.
3. Remove one of the knockouts and install a cable or con­duit connector.
4. Install the optional disconnect switch (if required) as shown in Figure 1.
5. Run the power supply cable through the connector, leav­ing about 8” (203mm) of wire inside the surface mounting plate. (Power supply cable must be # 10 AWG min. rated 90°C min.)
6. Position the surface mounting plate against the ceiling and secure with bolts or screws (Figure 2). See Warning No. 9. Connect the ground wire to the green ground screw on the surface mounting plate.
7. Remove the heater section from its carton.
8. Install optional controls (if required) into the heater sec­tion in accordance with the Instruction Sheet packaged with the control.
IMPORTANT
Field Conversion for Lower Wattage Rating
(Figure 12)
To convert the heater to a lower wattage rating, completely remove one(1) red jumper wire from one heating element for 25% wattage reduction. Completely remove two (2) red jumper wires for a 50% wattage reduction. Discard the jumper(s). Be sure the remaining wires are securely connected.
Conversion for 3Ø Installation
Heater is factory wired for connection to 1Ø only. To convert to 3Ø, remove and discard blue jumper wire between L1 & L3. (See Fig. 12, page 5).
Figure 1
Figure 2
WARNING
FAILURE TO INSTALL THE FOUR MOUNTING NUTS COULD RESUL T IN THE HEA TER FALLING. (SEE FIG. 2)
WARNING
FAILURE TO INSTALL THE FOUR SCREWS, COULD ALLOW THE SURFACE WRAPPER TO FALL. (SEE FIG. 2)
Discharge Air
Grille Arrangement
Custom Air
Flow Pattern
NARROW AIR PATTERN for high ceiling applications (11’(3352mm) to 14’(4267mm)), concentrates the heated air to ensure full pen­etration to the floor level.
8’
(2438mm)
24’(7315mm)
17’(5181mm)
8’(2438mm)
10’(3048mm)
Heater Discharge Grilles
7/8”(22,2mm) & 1-1/8”(28.6mm) Nested Knockout
1/2”(12.7mm) Knockout
1/2”(12.7mm) Knockout
Cable or conduit connector
Optional Disconnect Switch
Surface Mounting Plate
7/8”(22,2mm) Knockout
Surface Mounting Plate
Screw (2)
Air Pattern on Floor
Air Pattern on Floor
Air Pattern on Floor
Screws or Bolts (Not Supplied)
Grounding Screw
Surface Mounting Plate
Power Supply Cable
Thumb Pin Hole (2)
Thumb Pin Hole (2)
Insure that “Thumb Pin” is pulled out before positioning the surface wrapper on the heater section. Depress “Thumb Pin” after surface wrapper is sealed firmly against the heater section.
Heater Section
Surface Wrapper
Screw (4)
12”(305mm) Min.4kw 24”(609mm) Min. 5kw
12”(305mm) Min.4kw 24”(609mm) Min. 5kw
Stud (4)
Nut (4)
WIDE AIR PATTERN for standard ceiling applications (8’(2438mm) to 10’(3048mm)), disperses the air to give a gentle, less pro­nounced pattern while circulating all the air from floor to ceiling.
ASYMMETRICAL AIR PATTERN directs heated air in a specific direction, allowing the heater to be located where space allows with the heated air delivered to where it is required.
2
!
!
!
Loading...
+ 4 hidden pages