Market Forge STM-E Service Manual

Page 1
STERILMATIC
ANALOG ELECTRIC STERILIZER
PARTS AND SERVICE MANUAL
EFFECTIVE APRIL 15, 2016
The Company reserves the right to make substitution in the event that items specied are not available.
ERRORS: Descriptive and/or typographic errors are subject to correction.
44 Lakeside Avenue, Burlington, Vermont 05401 USA Telephone: (802) 658-6600 Fax: (802) 860-3732
MARKET FORGE INDUSTRIES
www.mi.com
P/N 14-0412 Rev D
Page 2
TABLE OF CONTENTS
DOOR ASSEMBLY & ADJUSTMENT ....................................................3
FULCRUM AND DRAIN ASSEMBLY .....................................................5
PRESSURE ACTUATED TEMPERATURE CONTROL .....................................6
MISCELLANEOUS COMPONENTS .....................................................8
TROUBLESHOOTING ................................................................ 10
ILLUSTRATED PARTS LIST ...........................................................11
APRIL 15, 2016 2 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 3
DOOR ASSEMBLY & ADJUSTMENT
STERILMATIC DOOR ASSEMBLY
The Door of the Sterilmatic has been engineered to es­tablish a positive method of sealing the steam pressure within the sterilizing cylinder. As steam pressure builds up within the cylinder, the door seal will tend to become more positive.
However, the door should be adjusted to make a good initial seal between the door gasket and the door opening without the added assistance of internal cylinder steam pressure with the simple action of securing the door han­dle down in a locked position, the door gasket should be
sufciently compressed against the door opening, all the
way around to prevent any steam leakage from occurring.
DOOR ADJUSTMENT
The Door Adjustment is Located in the Fulcrum Casting at the base of the door opening. This adjustment employs the use of a screw and locknut in order to adjust the Steril­matic Door to a tighter closed position (to prevent steam from leaking by the door gasket as pressure builds up), it is necessary to loosen the locknut and back off the screw at least one-quarter of a turn and re-tighten the locknut.
Figure 1
Figure 2
THE DOOR GASKET
Keep the gasket clean. With normal closing and locking of the door assembly, a steam-tight seal should be made between the door gasket and the door opening. This seal cannot be maintained if particles of foreign matter are al­lowed to accumulate upon either of the contacting sur­faces.
If there is leakage by the door gasket before a steam build-up within the steam chamber and leakage does not stop when the sterilizer reaches sterilizing temperature and pressure than regard the door assembly as improp­erly adjusted. A re-adjustment must then be made of the seal adjustment door screw.
To change the door gasket, remove the entire door as­sembly as a unit. Discard the old gasket, replace it with a new one (no cement is required), and reinstall the door assembly. Make an operational check for leakage and ad­just the door, if necessary.
APRIL 15, 2016 3 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 4
DOOR ASSEMBLY & ADJUSTMENT
DOOR LIFT SPRING
Market Forge supplies door lift springs in sets only. This policy has been found to be in the best interest of the customer. Through continuous use, some of the original qualities of the springs are lost and it becomes advan­tageous to make replacements to both the left and right door lift springs in the event that one becomes damaged or broken.
Replacement door lift springs are marked with tabs at the factory prior to shipment to identify a right from a left spring. These springs must be installed with the right door lift spring on the right of the door and the left door lift spring on the left of the door as viewed from the front of the sterilizer.
TO REMOVE THE DOOR ASSEMBLY
The Door Assembly can be removed from the inner steril­izing chamber as a unit without the use of any special tools or equipment. However, a systematic approach to this is warranted as the clearances through the portal are close, and much confusion can result if not removed in the sequence described below:
1. First, lift off and remove the two pan supports to ex­pose the door linkage on either side of the inner steril­izing chamber .
2. Raise the door to a fully opened position, and dis­engage the door spring from each of the door spring studs. Accomplish this by counteracting the force of the door lift spring with one hand while working the end of the door spring off the spring stud with the free hand. Do this on both sides of the door assembly.
3. When the end of the door springs have been com­pletely freed from their respective door spring studs, the door springs on either side of the door assembly can easily be slipped off their studs.
4. Rotate the entire door assembly out through the door opening, passing the door handle through the
opening rst, and then one end of the door spring as
shown in the illustration. The remainder of the door assembly will then pass through the door opening quite easily.
5. To replace the door assembly, reverse the step-by­step procedure described above.
Figure 3
ITEM PART NO. DESCRIPTION
1 10-6765 Pivot Spring Bearing
2 91-2718 Right and Left Door Spring (sold as a pair)
3 10-1776 10-32 Machine Screw 1/2” Long
4 10-2666 Door Gasket
5 95-3204 Door & Door Spring Assembly
- 95-0124 Items 1 through 5
APRIL 15, 2016 4 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 5
FULCRUM AND DRAIN ASSEMBLY
THE FULCRUM & DRAIN ASSEMBLY
The fulcrum and drain assem­bly is located at the lower front of the sterilizing chamber and furnishes a sturdy anchorage for the door locking system of the door handle. Also provided in this assembly is a means for adjustment of the door seal. The drain port and drain valve pro­vide a means of discharging ac­cumulations of water from within the sterilizing chamber.
ROLLER ASSEMBLY (ITEMS 8 & 9)
The Roller Assembly must be kept free-rolling at all times. Should this assembly be allowed to become frozen due to lack of lubrication, undue strain will be put on the door handle and the fulcrum casting while the door is being locked. Use only a dry lubricant such as graphite; as oil or grease will tend to attract dirt to this area.
Figure 4
ITEM PART NO. DESCRIPTION
1 10-3116 1/4” - 20 X 5/8 helicoil
2 10-1999 10-32 Machine screw, 1 5/8” long
3 10-2358 1/4” - 20 fulcrum nut
4 10-2087 1/4” - 20 allen set screw
5 10-3111 1/4” - 20x 3/8 helicoil
6 10-2513 1/4” Shakeproof washer
7 10-1763 1/4” - 20 Machine screw 3/4” long
8 95-0120 Bearing spacer
9 95-0198 Bronze Bearing
10 10-3111 1/4” - 20 x 3/8 helicoil
11 10-2513 1/4” Shakeproof washer
12 10-1790 1/4” - 20 Cap screw 7/8” long
ITEM PART NO. DESCRIPTION
13 10-4485 Drain valve knob
14 10-2514 #10 Shakeproof lockwasher
15 10-2318 10-32 acorn nut
16 95-2643 Adapter - steinball valve
17 10-1950 6-32 Round head screw 1 5/8” long
18 95-2616 Front outer case lower
19 95-0116 Fulcrum and drain casting
20 10-1049
21 10-1041 Ball valve stein
- 95-0115
Nipple 1/2” IPS 2 1/4” long stainless steel
Fulcrum and drain assembly, Items 1 through 12, 14, 15, and 19
APRIL 15, 2016 5 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 6
PRESSURE ACTUATED TEMPERATURE CONTROL
STM-E AND STM-EL
The pressure actuated temperature control, located be­hind the control panel assembly, governs the manufac­ture of steam by controlling the input of electric current to the heating elements.
HOW IT WORKS
When the Timer is set, rear and front contactors will be­come energized allowing input of current to the tempera­ture control, thus closing the contacts completing the current to the heating elements. Steam will then be gen­erated within the sterilizing chamber.
The steam pressure within the sterilizing chamber is transmitted by means of a tube to the bellows of the tem­perature control; as the steam pressure increases, its compression action on the bellows is set to cause the Switch #1 on the control to cut out on rising pressure at
13.5 PSI and to cut in on falling pressure at 13 PSI (con­trolling the two outer banks of heating elements). Switch #2 is set to cut out on rising pressure at 15.5 PSI and cut in on falling pressure at approximately 15 PSI (controlling center heater element only).
Thus, a balancing effect of steam pressure build-up and heater element current is constantly maintained during
the sterilizing cycle. When the Timer signies the end of
the cycle, the electric current to the contactors will auto­matically be broken; the temperature control contacts will be broken; and steam generation will stop.
ADJUSTING THE RANGE OF OPERATION, STM-E
NOTE: These instructions should be performed by
qualied service personnel only.
The operational range of the temperature control is fac­tory set as follows: Outer bank of elements OFF at 13.0-
13.5 PSI; Center bank of elements OFF at 15.5- 15.0 PSI; minor compensating adjustments can be made by turning the adjusting screws counter-clockwise to increase pres­sure and clockwise to decrease pressure. Both screws should be turned the same amount when making an ad­justment.
NOTE: When resetting this control for elevations above
sea level a correction of 6/10 Ib. per thousand feet is necessary.
1. Before making adjustments, shut all electrical current to the sterilizer OFF to eliminate shock hazard.
Figure 5
CHECKING THE 230° SETTING, STM-EL
The Unit should be completely evacuated then tempera­ture selector dial should be turned on 230° Fahrenheit. Observe the current until it takes a sharp drop to ap­proximately one-third of the full load; at this instant, there should be a corresponding chamber pressure of 2 PSI
Observing the current further will show another sharp drop to approximately 2 Amps; at this instant, there should be a corresponding chamber pressure of 6.1 PSI and a temperature reading of 228° to 232° Fahrenheit, on the temperature gauge.
ADJUSTING THE RANGE OF OPERATION STM-EL
The range of operation of Model STM-EL is adjusted by simply turning the adjusting knob on the outside of the Control Panel. A counter-clockwise turn decreases the pressure while a clockwise turn increases the pressure. Observe pressure and temperature gauges and adjust knob as required.
NOTE: When resetting this control for elevations above
sea level, a correction of 6/10 Ibs. per thousand feet is necessary.
2. Remove the Flue Cover.
3. Make sure that all exposed wires are not in a hazard­ous position, and then turn on electrical power.
4. Run unit through cycle, observing pressure and tem­perature gauges, turn adjusting screws as required.
APRIL 15, 2016 6 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 7
PRESSURE ACTUATED TEMPERATURE CONTROL
STM-EX AND STM-ELX
The pressure actuated temperature control, located be­hind the control panel assembly, governs the manufac­ture of steam by controlling the input of electric current to the heating elements.
HOW IT WORKS
When the timer is set, rear and front contactors will be­come energized allowing input of current to the tempera­ture control, thus closing the contacts completing the current to the heating elements. Steam will then be gen­erated within the sterilizing chamber.
The steam pressure within the sterilizing chamber is transmitted by means of a tube to the bellows of the tem­perature control; as the steam pressure increases, its compression action on the bellows causes the contacts to make or break according to the condition of the pres­sure at that time (rising or falling).
Switch #1 on the control is set to cut out on rising pres­sure at 0.95 kg/cm2 and to cut in on falling pressure at
0.91 kg/cm2 (controlling the two outer banks of heating elements). Switch #2 is set to cut out on rising pressure at 1.09 kg/cm2 and cut in on falling pressure at approxi­mately 1.05 kg/cm2 (controlling center heater element only).
Thus, a balancing effect of steam pressure build-up and heater element current is constantly maintained during
the sterilizing cycle. When the Timer signies the end of
the cycle, the electric current to the contactors will auto­matically be broken.
CHECKING THE 110°C. SETTING, STM-ELX
The Unit should be completely evacuated then tempera­ture selector dial turned to 110oC Centigrade. Observe the current until it takes a sharp drop to approximately one-third of the full load; at this instant, there should be a corresponding chamber pressure of 0.14 kg/cm2.
Observing the current further will show another sharp drop to approximately 1 Amp; at this instant, there should be corresponding chamber pressure of 0.43 kg/cm2 and a temperature reading of 110°C Centigrade, on the tem­perature gauge.
ADJUSTING THE RANGE OF OPERATION, STM-ELX
The range of operation of Model STM-ELX is adjusted by simply turning the adjusting knob on the outside of the Control Panel. A counter-clockwise turn decreases the pressure while a clockwise turn increases the pressure. Observe pressure and temperature gauges and adjust knob as required.
NOTE: When resetting this control for elevations above
sea level, a correction of 0.13 kg/cm2 per kilo­meter elevation is necessary.
Figure 6
APRIL 15, 2016 7 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 8
MISCELLANEOUS COMPONENTS
CAST-IN HEATING ELEMENTS
Located under the sterilizing cylinder is a bank of (3) U­shaped heating elements. These elements are welded in place in a protective aluminum shield. The elements can­not be removed, and in the unlikely event that one or all fail, the complete cylinder must be replaced.
THE LOW WATER CUT-OFF (MANUAL RESET)
Fastened to a special mounting brace behind the front panel, the Low Water Cut-Off acts to shut off the complete unit, should the water run dry. The Low Water Cut Off is factory set, to shut the unit off when the cylinder tempera­ture rises between 380
When the Sterilmatic is turned on without water or the water has been evaporated away, the temperature of the aluminum sterilizing cylinder will rise and by heat in­duction effect the Low Water Cut-Off. Its inner electrical contacts will be forced open from heat expansion, thus cutting off the ow of electric current to the heating ele­ments. With the replacement of water into the cylinder the cylinder temperature will drop and the contacts of the Low Water Cut-Off can be again closed. The unit will only restart after the manual button has been re-set.
o
and 440° Fahrenheit.
THE ELECTRIC CONTACTORS
The Electric Contactors are located on the top of the unit, underneath the top ue cover. These important compo­nents receive an electrical impulse when the Timer is turned on. When the unit reaches a pre-set pressure of 13-13.5 PSI the #1 switch will cut out causing the front contactor to become de-energized. This, in turn, will dis­connect the left and right bank of heaters and the timer motor will start.
THE STEAM PRESSURE GAUGE
The Steam Pressure Gauge registers the pressure of steam, which is within the sterilmatic sterilizing chamber. To replace this unit, it is necessary to disconnect the cop­per tubing and to remove the two nuts holding the gauge framework in place.
THE SAFETY VALVE
The Safety Valve is factory set to automatically open and exhaust excess steam from within the sterilizing cylinder, thereby assuring that operating pressures remain within safe limits. The lever action of the safety valve must be free to operate unrestricted at all times. If the Safety Valve should leak continually with a pressure build-up or should it cause an interruption on a sterilizing cycle premature­ly (below 124° Centigrade on the temperature gauge), it must be replaced. However, the temperature gauge
should rst be checked for accuracy.
THE FLUE
The Flue serves as a protective shield for the steam trap safety valve, exhaust valve, and electrical components as well as a mounting base for the control panel. The pres­sure gauge, dial thermometer, exhaust valve switch and timer, protrude through the control panel. The Flue cover may be removed to allow more room for servicing the control components. The control panel face may then be removed by unscrewing the sheet metal screws, which mount it to the Flue.
THE EXHAUST SOLENOID VALVE
The exhaust solenoid is normally closed and only opens at the end of the cycle when it is energized.
THE TIMER
The Sterilmatic is put into operation with the manual set­ting of the timer. With the setting of the timer, an electrical current is directed to the pressure control. The current en­ergizes the pressure control, which activates the contac-
tor coils to cause a current ow to the heating elements.
When the cylinder pressure reaches 13 to 13.5 PSI, the timer motor and pilot light are energized. At the end of
the cycle the timer will cut off the ow of electricity to all
the components except the exhaust, the exhaust solenoid and the timer motor. They will revert back to their original deactivated state. The timer motor and pilot light will con­tinue to be energized after the timed sterilizer cycle has been completed and for two additional minutes. Only after this will the timer and white pilot light be de-energized. If the timer fails to operate the Sterilmatic, replace it. The timer is replaceable only as a complete unit as factory repairs to it would not be practical in the economical inter­ests of the customer.
APRIL 15, 2016 8 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Figure 7
Page 9
MISCELLANEOUS COMPONENTS
TO REPLACE A THERMOSTATIC ELEMENT:
1. Remove the cap of the steam trap (turn it counter­clockwise).
2. Unscrew the diaphragm and seat and discard.
3. Wipe all dirt and scale from the inside of the steam trap.
4. Place a new diaphragm and seat securely into the steam trap and replace the cap (New Style - Part No. 98-1719).
Figure 8
THE STEAM TRAP
The Steam Trap has the very important automatic, dual function of exhausting all air from the sterilizing compart­ment, and of making a suitable seal to allow a pressure build-up of live steam during a cycle of sterilization. Also, a slot is milled at an angle through the seat to allow a constant bleed-off of a slight amount of steam during the cycle to completely eliminate any air pockets in the cylin­der. Failure of the trap to operate properly will result in an uneven distribution of live steam within the compartment.
How it works
With the introduction of steam into the sterilizing com-
partment, cold air will escape. When sufcient generated
steam displaces the cold air, it will then start to exhaust through the steam trap to heat the thermostatic element. The expansion of the thermostatic element will make a seal against the seat to enclose the live steam within the sterilizing compartment and a steam pressure build-up will occur.
Figure 9
APRIL 15, 2016 9 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 10
TROUBLESHOOTING
STEAM TRAP TROUBLE-SHOOTING
Trouble can only occur either through the premature closing of the steam trap before all the cold air has been exhausted,
or by its failure to close sufciently to enable a proper steam pressure build-up. Either case warrants a replacement of the
thermostatic element.
TROUBLE POSSIBLE CAUSE CORRECTION
Sterilizer fails to operate at all (no pres­sure build up).
Sterilizer operates, but fails to build up
15.5 PSI pressure.
1. Not installed correctly.
2. Blown fuse.
3. Contactor burned out.
4. Wiring is defective.
1. Current not heating all of the ele­ments.
2. Steam trap fails to close.
3. Exhaust valve fails to hold pres­sure at 15.5 PSI.
4. Steam leaks around door.
5. Safety valve blows-off prema­turely.
1. Check wire diagram for correct hook up.
2. Replace fuse. If it blows, check that source of electric supply is 60 amps.
3. Replace.
4. Check all wiring. Repair or re­place.
1. Remove lower front panel and see if the heating elements are working.
2. Replace the thermometer within the steam trap.
3. Check for incorrect adjustment on temperature control. Readjust.
4. Check for worn gasket or make door adjustment.
5. Replace safety valve.
Unit releases pressure before cycle has terminated on timer.
Timer is erratic, or fails to return to zero. 1. Loose or broken electrical leads
Unable to obtain set temperature at peak of cycle.
One or both sides of the cast-in heating elements remain on when the timer is in an OFF position.
Heating element cutting out before 15 lbs. of pressure is reached.
1. Low water cut-off has functioned prematurely.
on timer.
1. Steam trap closing prematurely, preventing removal of air from the chamber.
1. Contactors of the temperature control switch remains closed.
2. Temperature control not properly calibrated.
1. Pressure cutting off at the tem­perature control too soon.
1. Replace low water cut-off.
1. Repair defective wiring.
1. Replace the thermostatic element in the steam trap.
1. Replace switches.
2. Recalibrate.
1. See adjusting the range of opera­tion and calibration of the tem­perature control. Readjust.
APRIL 15, 2016 10 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 11
ILLUSTRATED PARTS LIST
ITEM QTY. STM-EL (120V) STM-ELX (240V) DESCRIPTION
1 1 95-0438 95-0438 Nipple, 1/2" NPT x 1.5"
2 1 98-1718 98-1718 Steam Trap
3 1 10-1048 10-1048 Compression Fitting, 1/2" OD Tube x 1/2" NPT
4 1 95-2667 95-2667 Tube, Copper, 1/2" OD
5 2 10-1055 10-1055 Tee, Brass, 3/8" x 3/8" x 3/8"
6 3 08-7525 08-7525 Nipple, 3/8" NPT, Close
7 1 10-1058 10-0938 Valve, Solenoid
8 3 10-1054 10-1054 Elbow, Street, 3/8 NPT
9 1 10-1017 10-1017 Adapter, 5/8" OD Tube x 3/8"MNPT
10 1 10-1057 10-1057 Union, 3/8" NPT
11 1 10-7988 10-7988 Bushing, Hex, Reducing 1/4" MNPT
12 1 10-3741 10-3741 Bushing, Hex, Reducing 3/8"NPTx1/4"NPT
13 1 10-3918 10-3918 Fitting, 1/4" Comp. X 1/4" MNPT
14 1 10-7942 10-7942 Valve, Safety, 17PSIG
15 2 10-3352 10-3352 Tee, 1/2" NPT, Brass
16 1 10-3327 10-3327 1/2" NPT Square Plug
17 1 Temp. Probe, Available with Control Module Only
18 2 95-3730 95-3730 Elbow, 1/2" NPT, 90, Street, Modied
19 1 08-4980 08-4980 Nipple, Pipe, Male, 1/2 Npt x 3"
20 1 10-3684 10-3684 Adapter, 1/2" OD Tube to 3/8" NPT
APRIL 15, 2016 11 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 12
ILLUSTRATED PARTS LIST
ITEM
1 1 95-3434 1 95-3434 Barksdale Pressure Switch
2 1 95-2907 1 95-2907 Pressure Switch Gear Assy.
3 2 10-5944 - N/A Contactor, 120V Coil
3 - N/A 2 10-5943 Contactor, 240V Coil
4 1 10-6290 - N/A Timer, 120V
4 - N/A 1 10-6873 Timer, 240V
5 1 10-9268 1 10-9268 Temperature Gauge
6 1 10-6515 - N/A Relay, 120V
6 - N/A 1 10-6874 Relay, 208/240V
7 1 10-6005 1 10-6005 Terminal Block
8 1 10-9267 1 10-9267 Pressure Gauge
9 1 08-6469 1 08-6469 Fuse Holder
10 1 10-5990 1 10-5990 Low Water Cut-off
11 1 09-6483 - N/A Contactor, 75 Amps, 120V
11 - N/A 1 09-6484 Contactor, 75 Amps, 240V
12 1 10-7355 1 10-7355 Transformer, 100 KVA, 60Hz
STM-EL STM-ELX (EXPORT)
QTY. PART NO. QTY. PART NO.
DESCRIPTION
APRIL 15, 2016 12 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 13
ILLUSTRATED PARTS LIST
ITEM
1 1 95-3442 1 95-3442 Barksdale Pressure Switch
2 2 10-5944 - N/A Contactor 120V Coil
3 - N/A 2 10-5943 Contactor 240V Coil
3 1 10-6290 - N/A Timer 120V
4 - N/A 1 10-6873 Timer 240V
4 1 10-9268 1 10-9268 Temperature Gauge
5 1 10-6515 - N/A Relay, 120V
6 - N/A 1 10-6874 Relay, 208/240V
6 1 10-6005 1 10-6005 Terminal Block
7 1 10-9267 1 10-9267 Pressure Gauge
8 1 08-6469 1 08-6469 Fuse Holder
9 1 10-5990 1 10-5990 Low Water Cutt-Off
10 1 09-6483 - N/A Contactor, 75 Amps, 120V
10 - N/A 1 09-6484 Contactor, 75 Amps, 240V
11 1 10-7355 1 10-7355 Transformer, 100KVA, 60HZ
STM-E STM-EX (EXPORT)
QTY. PART NO. QTY. PART NO.
DESCRIPTION
APRIL 15, 2016 13 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 14
ILLUSTRATED PARTS LIST
ITEM
1 1 95-2558 Flue Cover Assy.
2 1 95-2652 Flue Outer Case Wrap
3 1 95-2650 Upper Case, Front
4 1 98-4371 Lower Case, Front w/cutout
5 1 10-6363 Insulation, Body
6 1 10-6365 Insulation, Back
7 1 10-6364 Insulation, Bottom
8 1 95-0465 Bottom Cover for Elements
9 1 98-4217 Cylinder, 208V - 240V (Shown with Door Assy.)
ALL MODELS
QTY. PART NO.
1 95-2616 Lower Case, Front (old style w/o cutout)
DESCRIPTION
APRIL 15, 2016 14 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 15
ILLUSTRATED PARTS LIST
ITEM
1 1 95-3196 Outside Case, Left Side
2 1 95-3195 Outside Case, Right Side
3 1 95-3194 Outside Case, Back
4 1 10-0226 Handle Bumper
5 1 95-3484 Terminal Box Cover
6 2 95-2545 Pan Rack, 1 Left & 1 Right
7 1 95-2637 Condensate Bafe, Upper
8 1 95-3207 Perforated Water (Splash) Bafe
9 4 95-3284 Wear Strip
ALL MODELS
QTY. PART NO.
DESCRIPTION
APRIL 15, 2016 15 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 16
ILLUSTRATED PARTS LIST
ITEM
1 10-0489 - 10-0489 - Bezel
2 10-1722 - 10-1722 - Round Head Machine Screw, 6-32
3 10-9280 - 10-9279 - Control Panel
4 10-5052 10-6669 10-5052 10-6669 Pilot Light, Red
5 10-9267 10-9271 10-9267 10-9271 Pressure Gauge
6 10-5999 - 10-5999 - Switch
7 10-9268 - 10-9268 - Temperature Gauge
8 10-0189 - 10-0189 - Timer Knob
9 10-5940 10-6876 10-5940 10-6876 Pilot Light, White
10 10-5990 - 10-5990 - Low Water Cut-Off
11 - - 10-0051 - Knob
STM-E
PART NO.
STM-EX
PART NO.
STM-EL
PART NO.
STM-ELX
PART NO.
DESCRIPTION
APRIL 15, 2016 16 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Page 17
ILLUSTRATED PARTS LIST
14
10
9
11
12
13
3
8
4
15
2
1
6
7
Door Handle Assembly
APRIL 15, 2016 17 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
5
16
Page 18
ILLUSTRATED PARTS LIST
DOOR HANDLE ASSEMBLY
ITEM PART NO. DESCRIPTION
1 10-2318 10-32 Acorn Nut
2 10-2514 #10 Shakeproof Lockwasher
3 10-1999 10-32 Machine Screw 1 3/8” Lg.
4 95-0120 Bearing Spacer
5 95-0136 Door Lock Casting
6 10-2517 3/8” Shakeproof Lockwasher
7 10-0050 Door Lock Knob
8 95-0134 Door Handle Casting
9 10-2359 1/4”-20 Acorn Nut
10 95-0658 Door Handle Bearing Stud
11 95-0659 Door Handle Bearing Plate
12 10-2513 1/4” Shakeproof Lockwasher
13 10-1731 1/4”-20 Machine Screw 5/8” Lg.
14 95-0190 Door Lock Casting Assy. (Items 1 through 6)
15 95-0145 Door Lock Knob Assy. (Items 1 through 7)
16 95-0144 Complete Door Handle Assy. (Items 1 through 13)
17 95-0198 Handle Bushing (Not Shown)
MISCELLANEOUS PARTS NOT SHOWN
STM-E(L) STM-E(L)X
QTY. PART NO. QTY. PART NO.
1 95-2606 Temperature Recorder, 120 V (Optional)
1 10-5343 Temperature Recorder, 240 V (Optional)
1 20-0316 - - Replacement Probe (For Recorder)
1 95-2653 - - Upper Mounting Plate
1 10-5788 - - 120v, 50/60 Hz Cycle Coil
1 95-3552 - - Wire Harness, Flue Assy.
1 95-3553 - - Wire Harness, Contactors
DESCRIPTION
APRIL 15, 2016 18 STM-E, STM-EL, STM-EX & STM-ELX STERILIZERS
Loading...