Market Forge ST-10M24D Service Manual

ST-10M SERIES
10 PAN CONVECTION STEAMERS
PARTS AND SERVICE MANUAL
EFFECTIVE AUGUST 12, 2014
The Company reserves the right to make substitution in the event that items specied are not available.
ERRORS: Descriptive and/or typographic errors are subject to correction.
44 Lakeside Avenue, Burlington, Vermont 05401 USA Telephone: (802) 658-6600 Fax: (802) 860-3732
MARKET FORGE INDUSTRIES
www.mi.com
P/N 14-0288 Rev A (8/14)
TABLE OF CONTENTS
PRINCIPLES OF OPERATION ..........................................................3
TROUBLESHOOTING ..................................................................5
WIRING DIAGRAMS & SCHEMATICS ...................................................9
REPAIR AND REPLACEMENT ........................................................ 13
ILLUSTRATED PART LIST
DOOR ASSEMBLY ................................................................... 15
CABINET ASSEMBLY ................................................................ 16
CONTROL PANEL ASSEMBLY ........................................................ 18
CONDENSER ASSEMBLY ............................................................ 19
COMPLETE CONDENSER ASSEMBLY ................................................ 20
POWER PLUS ....................................................................... 21
AUGUST 12, 2014 2 ST-10M SERIES CONVECTION STEAMERS
PRINCIPLES OF OPERATION
GENERAL
The ST-10 Pressureless Steam Cooker consists of two identical cooking compartments, one above the other, in
a single cabinet assembly. Each compartment is tted
with independent electrically controlled steam circuits and spring-loaded, self-sealing doors with slam action latches. Compartments can be used separately or simultaneously for either constant steam or 60-minute timing. The prin­ciples of operation in this section include an explanation of steam, steam condensing, and electrical circuits and their functioning.
PLUMBING CIRCUITS
The plumbing circuits consist of the piping, steam sole­noid valves, orice, drain, and cold water condenser re­quired to provide controlled steam application to the cook-
ing compartments. A simplied diagram of these circuits
is shown below.
Steam inlet lines for compartments are equipped with normally closed solenoid valves operated by the electri­cal control circuits. The inlet valves are opened whenever the compartment control circuit is activated by use of the 60-minute timers.
STEAM INLET LINE
A steam supply line is plumbed from the boiler output (or direct-connected steam control) to a 1/2-inch barb tting
connected to the input sides of both steam inlet solenoid valves. When a cooking compartment is not in use, the valve for the compartment remains closed to prevent steam from entering. During operation, the appropriate inlet solenoid valve is opened by activation of the con­trol circuit. Steam is projected onto the surface of pans
of food loaded into the compartment by an orice located inside the compartment. Steam continues to ow through
the compartment in this manner until the control circuit closes the solenoid valve.
STEAM EXHAUST AND DRAIN LINES
Perforated strainers at the drain line openings inside each compartment allow only steam, condensation, and liquid cooking drainage to enter. Prior to discharge into the boil­er drain system, steam is converted to water by the cold water condensing systems for each compartment.
Figure 1
NOTE: This is strictly a pictorial schematic diagram and
is not intended to show the actual conguration of the plumbing. All components are shown in cor­rect relationship with each other. However, the diagram does not show their actual locations or position within the cooker.
As shown in the diagram, steam inlet and exhaust con­nections are connected at the factory directly into a steam boiler or direct-connected steam plumbing enclosed within the base cabinet on which the cooker is mounted. The boiler (or direct-connected steam control system) is equipped to supply constant, regulated steam at 14–15 PSI. Steam exhaust, having been reduced to water by the cold water condenser, is directed into the boiler (or direct- connected steam control) drain system.
STEAM EXHAUST CONDENSING SYSTEM
The steam condensing system consists of the identical, two-position, normally closed cold water solenoid valves, with outlet sides connected into the exhaust plumbing for each cooking compartment. A spray nozzle directs cold water about the inside of the drain lines to increase cold water contact with exhausted steam. Valve inlet sides are connected remote from the supply line of the steam boiler (or direct-connected steam plumbing). The valves respond to a thermostatic switch located inside the com­partment. When the timer starts the cold water solenoids will energize.
ELECTRICAL CIRCUITS
The electrical circuits of the cooker control the power to activate timer motors and energize solenoid-operated valves and circuits, which in turn control application of steam to the cooking compartment and condensation of steam from the exhaust line. The cooker operates on 120V, 2 amp, 60Hz electrical service connected to all cir­cuits from the circuits of the steam boiler (or direct-con- nected steam controls) contained within the cabinet on which the cooker is mounted. Power is supplied to the control circuit at all times when the shut-off device for the unit (supplied by the user) is in the ON position.
PRINCIPLES OF OPERATION
CONTROL CIRCUIT COMPONENTS
A brief description of the electrical circuit elements fol­lows.
60 Minute Timer/Constant Steam
The timer contains a 120-volt AC synchronous motor that drives a timing dial through a gear reduction and clutch mechanism. The timer dial is manually set for any interval of operation from 0 to 60 minutes or constant steam as read on the calibrated dial face. The manual rotation of the dial moves the common element (1) of the timer switch from the neutral (OFF) position to contact (3), which con­nects with the steam inlet solenoid valve operating circuit.
The cooker is placed into automatic operation with the setting of the timer dial. Its timing cycle, however, is auto­matically delayed by a thermostatic switch, which assures operating temperature is achieved before the timer motor begins to “time out.” When the timer motor has operated for the preset duration, the common element is trans­ferred to contact (4), returning the inlet solenoid valve to the closed position and energizing the buzzer. Contact to the buzzer circuit remains closed until the dial is manu­ally turned to the OFF position, returning the common ele­ment (1) of the timer switch to the neutral position.
DOOR INTERLOCK SWITCH
The interlock switch is a single-pole proximity switch with normally open contacts. The switch is operated by the proximity of a magnet within the door. When the door is open, the switch contacts remain in the open position. When the door is closed and securely latched in place, the magnet is near the switch to close the contacts. Con­nected between the operating contact (3) of the timers and the steam inlet solenoid valve, the door switch acts as a protective device to interrupt valve operation unless the door is closed.
THERMOSTATIC SWITCH
The thermostatically operated switch is a two-position, normally open switch mounted on the cooking compart­ment. The switch functions to activate the cold water sole­noid valves of the steam condensing system and to delay timer motor operation until the compartment temperature reaches 195°F, thus assuring that cooking temperature exists throughout the timed duration.
INDICATOR LIGHTS
An indicator light is included for both compartments. The light remains on (red) at all times when the coinciding tim­er dial is set and the door interlock switch is closed. The light turns off at the end of the timed cooking duration.
BUZZER
The buzzer is an alarm device that operates by oscillation of a striker against the core of an electromagnet. When the 60-minute timer dials reach the “0-Minute” position, the buzzer coil is energized to sound the buzzer. Move­ment of the timer dial to the OFF position opens the con­tact to the buzzer coil to shut it off.
TROUBLESHOOTING
ELECTRICAL FAULT ISOLATION
Correction of an electrical failure rst requires isolation of
the fault to a single circuit or component. In most cases, the nature of the failure and its effect upon the operation
of the cooker will be sufcient to narrow it down to one or
more circuit elements.
ELECTRICAL TROUBLE-SHOOTING PROCEDURES
Before performing the trouble-shooting procedures in this section, the serviceman must be familiar with the function of all controls as well as with the Principles of Operation described the Operation Section.
GENERAL TROUBLE-SHOOTING GUIDE
PROBLEM PROBABLE CAUSE REMEDY
Indicator light fails to light with timer set.
1. Power to cooker off.
2. Door interlock switch contacts not closed.
3. Door interlock switch faulty.
4. Indicator light burned out.
5. Faulty timer contacts.
The electrical trouble-shooting procedures that follow re­quire access to components and terminals of the electri­cal control panel. Electrical controls are reached by re­moving screws that fasten the control panel to the frame. The panel may be pulled forward for testing while inter­connected to the cooker circuits or disconnected at the pin connection for complete removal and repair.
1. Locate external circuit breaker for incom­ing power and place in ON position.
2. Shut cooker door to close switch contacts. Check alignment of door with switch.
3. Replace switch.
4. Replace light.
Steam fails to enter cooking com­partment with indicator light on.
Steam enters compartment contin­uously. Timer dial not turning.
Steam continues to ow into com­partment and/or buzzer fails to sound at end of timer cycle.
Steam ows continuously from
boiler (or direct connected steam control) drain line with cooker in op­eration.
6. Faulty wiring.
1. Faulty steam solenoid valve.
2. Faulty wiring.
1. Constant steam position.
2. Faulty thermostatic switch.
3. Faulty timer motor.
4. Faulty steam solenoid valve.
5. Faulty wiring.
1. Timer contacts faulty.
2. Buzzer faulty.
3. Faulty wiring.
1. Cold water not connected.
2. Faulty thermostat.
3. Faulty cold water solenoid.
4. Faulty wiring.
1. Replace valve.
2. Inspect condition of wire and tightness of all connections. Correct as needed.
1. Move knob to timing location.
2. Replace switch.
3. Replace Timer.
4. Replace valve.
5. Inspect condition of wire and tightness of all connections. Correct as needed.
1. Replace timer.
2. Replace buzzer.
3. Inspect condition of wire and tightness of all connections. Correct as needed.
1. Turn on external shut-off valve.
2. Replace thermostat. Replace valve.
3. Inspect condition of wire and tightness of all connections. Correct as needed.
TROUBLESHOOTING
Incoming Power
Before trouble-shooting any of the electrical parts or as­semblies, verify that power is being supplied to the cook­er. Incoming power is connected at the boiler (or direct- connected steam) control box located in the base cabinet. With power connected to the cooker, an AC volt-meter is used to measure 120 volts across L1 and L2. If 120 volts is present, and the cooker will not operate, the fault lies within the electrical circuits of the cooker.
Electrical Inspection
The rst step in any electrical trouble-shooting procedure
is a thorough physical inspection of all wiring connections. To access electrical components, remove the control pan­el.
ELECTRICAL FAULT ISOLATION GUIDE
FAILURE FAULT LOCATION
Will not operate in either CONSTANT STEAM or 60-MINUTE TIMER position. 1. Incoming power.
WARNING
Before removing control panel or checking connections and wiring, be sure that the cir­cuit breaker for incoming power is OFF. When power is supplied, all exposed terminals of the control panel carry 120 volts.
Check all wiring connections by hand to assure that both ends of all connection points are tightly secured. Use a screwdriver to tighten connection points. If necessary, vi­sually inspect all quick-disconnect terminals for evidence of corrosion. Terminals in this condition should be sepa­rated, cleaned with emery cloth until shiny, and tightly re­connected.
2. Timer.
3. Door interlock switch.
4. Wiring.
Operating in CONSTANT STEAM position but not in 60-MINUTE TIMER posi­tion.
Operating in 60-MINUTE TIMER position but not in CONSTANT STEAM posi­tion.
Steam solenoid valve fails to open with indicator light on. 1. Solenoid valve coil.
Indicator light OFF with steam solenoid open. 1. Indicator light.
With indicator light ON and steam solenoid valve OPEN, timer dial fails to turn.
Buzzer fails to SOUND at end of 60-MINUTE TIMER mode. 1. 60-Minute timer.
Steam ows continuously from boiler drain line. 1. Thermostatic switch.
1. 60-Minute timer.
2. Wiring.
1. 60-Minute timer.
2. Wiring.
2. Wiring.
2. Wiring.
1. Compartment thermostatic switch.
2. Constant steam position.
3. Timer motor.
4. Wiring.
2. Buzzer.
3. Wiring.
2. Cold water solenoid valve.
3. Wiring.
TROUBLESHOOTING
60 MINUTE TIMER
Timer Contacts
Defective timer contacts will result in failure of either cook­er compartment to operate. When this occurs, remove the control panel, and proceed as follows:
4. Turn off power to the cooker at external circuit break­er.
5. Disconnect all ve wires from timer terminals.
6. Connect an ohmmeter between terminals 1 and 3.
7. Rotate timer dial beyond the “0-Minute” point (any setting) to obtain a reading of zero ohms on the ohmmeter. If zero ohm reading cannot be obtained, timer contacts are defective and the timer must be replaced.
8. Move ohmmeter leads to terminals 1 and 4.
9. Rotate timer dial to “0-Minute” position (an audible click indicates correct position). If zero ohm reading cannot be obtained, the timer is defective and must be replaced.
10. Remove ohmmeter and replace all ve leads on timer terminals.
Timer Motor
A defective timer motor will cause continuous operation in the TIME mode, with the timer dial failing to return to the “0-Minute” position. Since thermostatic switch failure can
cause the same symptom, fault must rst be isolated to
the timer by testing the thermostat.
To conrm timer motor condition, proceed as follows:
1. Carefully check motor wire leads and tighten loose connections.
WARNING
Use care while working with control panel. Terminals carry 120 volts.
2. Turn on power to the cooker.
3. Set timer dial (any setting beyond “0-Minute”). If op­eration is correct, the motor will turn the dial toward “0-Minute.” If the motor fails to operate, it is defective and the entire timer must be replaced.
DOOR INTERLOCK SWITCH
Malfunction of the cooker door interlock switch prevents timer indicator lights from turning on and steam solenoid from opening when the timer dial is set. If steam does not enter the compartment and the indicator light fails to turn on with the door latch securely engaged, the fault may be in the door interlock switch.
Proceed as follows:
1. Turn off power to the cooker.
2. Disconnect wires to the door switch terminals
3. Connect an ohmmeter between the terminals of the switch.
4. Actuate the switch by closing the cooking compart­ment door. If a zero reading cannot be obtained, the switch is defective and must be replaced.
5. Remove the ohmmeter and replace the leads on switch terminals.
STEAM SOLENOID VALVES
When either inlet solenoid valve fails to operate, the fault may be a defective coil. A defective coil is found using an AC volt-meter to check the voltage at the coil wire ter­minals, with the cooker compartment operating in either CONSTANT STEAM or 60-MINUTE TIMER mode. If volt­age of 120 volts is present and the coil fails to open the valves, the fault is in the valve coil. Defective valve coils are not separately replaceable, requiring complete valve replacement.
INDICATOR LIGHTS
If the cooker compartment functions correctly, with the single exception that the indicator light fails to light during operation, the fault is a defective indicator light. A “burned
out” or defective light is veried by using an AC volt-meter
at the leads, with input power on the selector switch in the correct position for that timer, the timer set, and the door latches closed. If 120 volts is present, the fault is in the indicator light and requires replacement. If 120 volts is not present, the fault is in the wiring or control components (selector switch, timer, or door switch).
4. Shut off power to the cooker.
TROUBLESHOOTING
COOKING COMPARTMENT THERMOSTATIC SWITCH
A thermostatic switch included in the circuit for the timer
motor delays timer operation until steam owing into the compartment satises the temperature-actuated switch
device. If a timer motor fails to operate within about one minute after the indicator light comes on (with cooker compartment empty), the cause may be a defective ther­mostatic switch. To test the switch, proceed as follows:
1. Disconnect the two wires connected to the thermo­static switch terminals.
2. Connect an ohmmeter between the two terminals of the switch.
3. Place the cooker into operation and observe ohmme­ter dial. Within one minute of operation, the switch contacts close automatically to register a zero ohm reading on the dial. If a zero ohm reading is not ob­tained, the switch is defective.
4. Shut off cooker, disconnect ohmmeter leads, and re­place wires on switch terminals.
BUZZER
If the buzzer does not sound at the termination of the op­erator-selected timer setting (timer dial returned to “0-Min­ute” position), the fault may be a defective buzzer. Buzzer
operation is veried using an AC volt-meter at buzzer coil
connections with input power on and selector switch and coinciding timer dial set at the “0-Minute” position. If volt­age is 120 volts, the fault is in the buzzer,
which must be replaced. If 120 volts is not present, the fault is in the wiring or control components (timer or selec­tor switch).
WIRING
All of the electrical components of the cooker (timers, in­dicator lights, etc.) are connected to each other by wiring
shown in wiring diagram. If all of the electrical compo­nents are operating correctly (and the incoming power has been checked), but the cooker fails to operate, the fault lies in the wiring.
The wiring diagram shows all terminals and interconnec­tions within the electrical circuits. All numbered terminals are identied and all leads number coded as shown. Con­nections can be easily removed. Wiring Schematic shows the same information schematically and is an aid in isolat­ing circuits for testing.
Using an ohmmeter, wiring continuity between the con-
nections shown on the wiring diagram is readily veried.
This is best done in stages, removing only those wires required for each continuity check. As each lead is re­placed, it should be checked for evidence of corrosion, and cleaned if necessary. All leads must be tightly at­tached so as to provide a good electrical connection.
COLD WATER CONDENSER CIRCUIT
If during cooker operation steam exits from the drain line opening (located in lower boiler compartment) and the condensing system fails to operate, as evidenced by repeated discharge of water from the drain line, the condensing circuit is malfunctioning. The failure can be caused by a defective condenser thermostat or cold water solenoid coil, or by wiring failure.
If the condenser thermostat functions correctly, but ei­ther of the cold water solenoid valves fails to operate, the cause might be a faulty valve coil. A defective coil is found using an AC volt-meter to check the voltage at the coil wire terminals with the cooker compartment in operation. If voltage of 120 volts is present and the valve fails to open, the fault is in the valve coil. Defective valve coils are separately replaceable.
WIRING DIAGRAMS & SCHEMATICS
WIRING DIAGRAMS & SCHEMATICS
WIRING DIAGRAMS & SCHEMATICS


WIRING DIAGRAMS & SCHEMATICS



WIRING SCHEMATIC FOR STEAMER

WIRING SCHEMATIC FOR POWER PLUS
REPAIR AND REPLACEMENT
WARNING
Under no circumstances should hardware (or parts) be replaced with a different length,
size, or type other than as specied in the
parts list. The hardware used in the cooker
has been selected or designed specically for
its application, and the use of other hardware may damage the equipment and will void any warranty.
Door Gasket Replacement
The cooking compartment door gaskets are made of a silicone-type rubber material that is very durable but sub­ject to wear during normal operation. Should the gasket leak, readjust the door gasket to the unit or replace it.
Procedure—Replace Gasket:
1. Open the cooking compartment door.
2. Remove the six screws on the outside of the door, and remove the inner door assembly.
3. Remove the eight nuts from the door gasket mount­ing plate on the inside of the inner door assembly.
4. Remove the door gasket mounting plate and the door gasket.
Exterior Panel Removal
WARNING
To prevent hazard in servicing the cooker, be certain that the steam supply boiler is shut down, the cold water shut-off valve is closed, and the electrical disconnect circuit breaker for the cooker/boiler unit is off before remov­ing side panels.
Access to all internal plumbing and electrical assemblies is from the right side and right front. The left-side panel is removed by removing the bottom screw and pushing up on the panel until the lower lip disengages the frame.
The electric control panel may also be removed as a unit by removing screws and pulling the panel forward. Re­moval of the control panel is completed by unplugging interconnecting wiring at the pin housing.
Steam and Water Solenoid Valve Replacement
Replacements for the 1/2-inch steam solenoid valves and the 1/4-inch water valves are available as complete units from Market Forge Authorized Service Agencies. It is nec­essary to replace an entire steam valve when the coil is faulty or the diaphragm ruptures. Replacement coils are available for the water valves.
5. Install the new door gasket to the mounting plate.
6. Reassemble the mounting plate with gasket to the in­side of the inner door assembly using the eight nuts.
7. Reassemble the inner door assembly using the six screws on the outside of the door.
NOTE: Remember that the lip on the door gasket mount-
ing plate must t into the channel on the inside edge of the gasket to insure a proper seal.
Procedure—To Adjust Gasket to Unit:
To prevent steam leaks around the door, adjust the gasket tension to cavity. Adjust the gasket by loosening the six screws on top and bottom of door, move inner door plate in or out, left side or right side, and tighten the six screws.
REPAIR AND REPLACEMENT
DOOR LATCH TENSION ADJUSTMENT
CAUTION
SHUT OFF MAIN ELECTRICAL POWER TO UNIT.
Procedure:
1. Open the cooking compartment door.
2. Remove the control panel by removing the eight mounting screws and disconnecting the wire plug and restraining wire.
3. Tighten both nuts down until the springs are fully compressed.
4. Back each nut off 1/2 turn.
5. Remount the control panel, reconnecting wire plug and restraining wire.
Door Handle Tension Adjustment
Procedure:
1. Open the cooking compartment door.
2. Remove the six screws and washers from the top edge and bottom edge of the door.
3. Remove the inner door gasket mounting plate assem­bly from the outer door. Do not disassemble these three components—remove them as an assembly.
4. Tighten both nuts down until the springs on the outer door are fully compressed.
5. Back each nut off 1/2 turn.
6. Remount the inner door gasket mounting plate as­sembly by assembling the six screws and washers.
DOOR ASSEMBLY
ITEM PART NO. DESCRIPTION QTY.
1 91-7692 OUTER DOOR 1
2 91-7694 INNER DOOR 1
3 91-7696 GASKET RETAINING PLATE 1
4 91-7783 DOOR GASKET 1
5 91-5745 DOOR HANDLE 1
6 09-1608 STRIKER 1
7 08-5027 MAGNET 1
8 91-5901 MAGNET BRACKET 1
9 08-4600 COMPRESSION SPRING 2
AUGUST 12, 2014 15 ST-10M SERIES CONVECTION STEAMERS
CABINET ASSEMBLY
AUGUST 12, 2014 16 ST-10M SERIES CONVECTION STEAMERS
CABINET ASSEMBLY
ITEM PART NO. DESCRIPTION QTY.
1 91-7616 POST, REAR 2
2 REF CONDENSER ASSEMBLY 1
3 10-5859 INLET SOLENOID 2
4 08-4892 BARB, 1/2” IPS x 3/8” ID TUBE 2
5 10-8823 ELBOW, STREET, 1/2” IPS 2
6 91-7595 INLET ADAPTER ASSEMBLY 2
7 91-6474 INLET GASKET 2
8 10-9174 RELAY TUBE 2
9 91-6477 BRACKET, LINER HOLD DOWN 2
10 08-4978 BARB, 1/4” IPS FEMALE x 1/4” ID TUBE 2
11 08-4866 SPRAYER NOZZLE (MODEL ST-10 ONLY) 2
12 08-4833 REDUCING TEE, 1” x 1” x 1/4” IPS 2
13 08-1207 BARB, 1” IPS 2
14 91-7638 STIFFENER, BACK 1
15 91-7639 BRACKET, LINER TIE 1
16 91-7493 PANEL, BACK 1
17 91-7619 PANEL, TOP 1
18 91-7569 PANEL, SIDE 2
19 91-7690 BRACKET, REED SWITCH 2
20 08-6308 REED SWITCH 2
21 10-8105 THERMOSTAT, CONDENSER (MODEL ST-10 ONLY) 2
22 10-3739 REDUCER, 1/2” IPS x 3/8” IPS 2
23 10-4586 NUT, SEALER, 1/2” IPS 4
24 10-9175 RELAY, SOCKET 2
25 91-6470 CONTROL PANEL ASSEMBLY 1
26 91-7698 BAFFLE, RACK SLIDE 2
27 98-1599 RACK, WIRE 4
28 91-6486 DOOR ASSEMBLY 2
29 91-7684 STRAINER 2
30 08-4600 COMPRESSION SPRING 4
31 91-6475 HINGE, TOP 2
32 91-6476 HINGE, BOTTOM 2
33 91-6492 LATCH, RECEIVER 2
34 91-6491 GROMMET 2
35 08-6538 VACUUM BREAKER 2
36 91-6940 RELAY BRACKET 2
AUGUST 12, 2014 17 ST-10M SERIES CONVECTION STEAMERS
CONTROL PANEL ASSEMBLY
ITEM PART NO. DESCRIPTION QTY.
1 91-6489 CONTROL PANEL 1
2 91-7612 ARTWORK, CONTROL PANEL 1
3 08-6464 60 MINUTE TIMER 2
4 08-6541 TERMINAL STRIP 2
5 91-6471 BRACKET, TERMINAL STRIP 2
6 10-7395 BUZZER 2
7 08-3826 KNOB, TIMER 2
8 10-5052 LIGHT, RED 2
AUGUST 12, 2014 18 ST-10M SERIES CONVECTION STEAMERS
CONDENSER ASSEMBLY
ITEM PART NO. DESCRIPTION QTY.
1 08-6538 3/8” CHECK VALVE 1
2 08-7970 NEOPRENE HOSE 21” 2
3 08-7975 CLAMP 2
4 08-4978 HOSE BABS 1
5 10-3539 BUSHING 1/2 x 1/4 HEX 1
6 08-5438 TEE, BRASS 1” x 1/2” x 1” 1
7 08-1207 HOSE FITTING 1” NPT 1
8 15-7208 BRAIDED STAINLESS STEEL HOSE 2-1/2” 1
9 08-4864 HOSE BARB, 90o, 1/8” IPS 2
10 08-1206 HOSE CLAMP 2
11 08-7923 TEE 1/8” NPT 1
12 08-4890 HOSE COUPLER, 1/8 IPS x 1/4 ID 2
13 91-6491 GROMMET 1
14 08-4866 SPRAY NOZZLE (MODEL ST-10 ONLY) 1
15 08-4821 CONDENSER SOLENOID (MODEL ST-10 ONLY) 2
16 91-7640 CONDENSER BRACKET 1
AUGUST 12, 2014 19 ST-10M SERIES CONVECTION STEAMERS
COMPLETE CONDENSER ASSEMBLY
ITEM PART NO. DESCRIPTION QTY.
1 08-6538 3/8” CHECK VALVE 1
2 08-7970 NEOPRENE HOSE 21” 2
3 08-7975 CLAMP 2
4 08-4978 HOSE BABS 1
5 10-3539 BUSHING 1/2 x 1/4 HEX 1
6 08-5438 TEE, BRASS 1” x 1/2” x 1” 1
7 08-1207 HOSE FITTING 1” NPT 1
8 15-7208 BRAIDED STAINLESS STEEL HOSE 2-1/2” 1
9 08-4864 HOSE BARB, 90o, 1/8” IPS 2
10 08-1206 HOSE CLAMP 2
11 08-7923 TEE 1/8” NPT 1
12 08-4890 HOSE COUPLER, 1/8 IPS x 1/4 ID 2
13 91-6491 GROMMET 1
14 08-4866 SPRAY NOZZLE (MODEL ST-10 ONLY) 1
15 08-4821 CONDENSER SOLENOID (MODEL ST-10 ONLY) 2
16 91-7640 CONDENSER BRACKET 1
AUGUST 12, 2014 20 ST-10M SERIES CONVECTION STEAMERS
POWER PLUS
ITEM PART NO. DESCRIPTION QTY.
1 10-9175 RELAY SOCKET, (ONE PER COMPARTMENT) 2
2 10-9174 CUBE RELAY, (ONE PER COMPARTMENT) 2
3 08-6502 PRESSURE SWITCH 2
4 98-4206 POWER SUPPLY, 5 VDC 1
5 97-6455 TIME DELAY RELAY 2
AUGUST 12, 2014 21 ST-10M SERIES CONVECTION STEAMERS
Loading...