WARNING: Improper installation, adjustment, alternation,
service or maintenance can
cause property damage, injury or death. Read the installation, operation and maintenance instructions thoroughly
before installing or servicing
this equipment.
INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE
USER SMELLS GAS MUST BE
POSTED IN A PROMINENT LOCATION. This information may
be obtained by contacting your
local gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or
other ammable vapors or liquids in the vicinity of this or any
other appliance.
The information contained in this
manual is important for the proper installation, use, and maintenance of this steamer. Adherence to these procedures and
instructions will result in satisfactory baking results and long,
trouble free service. Please
read this manual carefully and
retain it for future reference.
ERRORS: Descriptive, typographic or pictorial errors are
subject to correction. Specications are subject to change
without notice.
Introduction
DESCRIPTION
The ST-10 is a pressureless steam cooker consisting of
two independently controlled compartments enclosed in
a single cabinet. Each compartment is equipped with a
separate three-piece door with inner gasket plate isolated from the exterior surface. Door latches operate by
slam action for positive sealing of inner door. Steam and
steam-condensing circuits are electrically controlled. Operating controls are displayed on a single front-mounted
panel and include separate timers with indicator lights for
selection of constant steam or 60-minute-long duration
cooking.
A separate steam source required for operation of the
Pressureless Cooker is normally purchased with it, please
refer to the respective manual for guidance.
BASIC FUNCTIONING
The Model ST-10 may be operated with only one compartment in use; or both may be used simultaneously. Each
compartment is equipped with identical controls, allowing
selection of constant steam or 60-minute timer operation.
The cooker becomes operational when it is set to constant steam, or the timer is set at the desired cooking time
and the compartment door is closed. The indicator light
comes on and the steam solenoid valve opens, allowing
steam to ow into the compartment.
When steam owing inside the compartment has raised
the interior temperature to 195°F, the contacts of a thermostatic switch automatically close, completing the circuit
to the timer motor and starting the cooking time period. At
the end of the set interval, timer contacts switch to shut
off the cooking operation and sound a signal buzzer. The
buzzer is silenced by returning the timer dial to the OFF
position. In the constant steam mode, operation will be
continuous.
Steam emitted from the compartment along with liquid
cooking drainage is directed through a drain screen inside
the compartment into the cooker drain line. A cold water
solenoid valve connected into the cooker drain line is automatically actuated by a thermostatic switch in the boiler
drain to condense the steam to water prior to discharge
into the boiler drain.
SERVICE
Required service, both preventive and corrective, is explained in Section 6. Should repairs be required, a net-
work of authorized agencies is available to assist with
prompt service. A current Directory of Authorized
Service Agencies may be obtained by contacting:
Market Forge
44 Lakeside Avenue, Burlington, VT 05401
802-658-6600
www.mi.com
The model and serial numbers must be referenced when
corresponding with Market Forge. The data plate containing the serial number pertaining to the equipment is located on the lower front trim of the cabinet.
INSTALLATION
2
ST-10M24E
Service Connections
ELECTRICAL REQUIREMENTS
24kW
3pH
208 (197-219)66100117--
240 (220-240)5887--116
480 (360-500)2944--58
Details of other electrical systems available upon request.
36kW
3pH
42kW
3pH
48kW
3pH
SERVICE CONNECTIONS
EPElectrical Connection - Use wire suitable for at least 90°C.
Nominal amp per line wire.
CW1 Cold Water - 3/8” (10mm) NPT for cold water to boiler. Cold
water lines will have a maximum of 50 PSI (3.5kg/cw2) and a
minimum of 25 PSI (1.8 kg/cw2) water pressure
CW2 Cold Water - 3/8” (10mm) NPT for cold water to condenser.
Cold water lines will have a maximum of 50 PSI (3.5kg/cw2)
and a minimum of 25 PSI (1.8 kg/cw2) water pressure.
DDrain - Pipe full 2” (50mm) NPT to flush floor drain capable
of receiving water flowing at a maximum rate of 5 gallons (19
liters) per minute. DO NOT MAKE SOLID CONNECTION TO
FLOOR DRAIN.
STSteam Take-off - Connection for operation of adjacent steam
powered equipment.
DIMENSIONS ARE IN INCHES [MM]
4 [102]
2.5 [64]
10.5
[267]
CW1
12.5
10.5
[318]
[267]
3 [76]
5 [127]
24 [610]
D
CW2
6 [152]
33
EP
ST
[838]
6 [152]
OPERATION WILL BE BY:
Electrically powered, A.S.M.E. constructed and National Board
Registered, 15 PSI (1 kg/cm2) steam boiler rated at 24kW, additional
ratings available as an option
NOTE: The only available space to supply utilities to the boiler is the 6”
(152mm) space between the floor and the cabinet base. PVC & CPVC
Pipe are not acceptable materials for drains.
CAUTION: REMOTE KETTLE OPERATION If this boiler is feeding a
remote kettle that will be more than 5 feet (1.5 meters) away, consult
factory before ordering.
WATER SUPPLY
Good quality water feed is the responsibility of the owner. Water quality
must be within the following general guidelines.
The best defense against poor water quality is a water treatment system
designed to meet your water quality conditions.
Figure 1
69.25
[1759]
22
[559]
ST
28
[711]
6 [152]
CW1
CW2
EP
D
3
INSTALLATION
Service Connections
ST-10M36E
ELECTRICAL REQUIREMENTS
24kW
3pH
208 (197-219)66100117--
240 (220-240)5887--116
480 (360-500)2944--58
Details of other electrical systems available upon request.
36kW
3pH
42kW
3pH
48kW
3pH
SERVICE CONNECTIONS
EPPower Supply - Use wire suitable for at least 90°C. Nominal
amp per line wire:
CW1 Cold Water - 3/8” (10mm) NPT for cold water to boiler. Cold
water lines will have a maximum of 50 PSI (3.5kg/cw2) and a
minimum of 25 PSI (1.8 kg/cw2) water pressure
CW2 Cold Water - 3/8” (10mm) NPT for cold water to condenser.
Cold water lines will have a maximum of 50 PSI (3.5kg/cw2)
and a minimum of 25 PSI (1.8 kg/cw2) water pressure.
DDrain - Pipe full 2” (50mm) NPT to flush floor drain capable
of receiving water flowing at a maximum rate of 5 gallons (19
liters) per minute. DO NOT MAKE SOLID CONNECTION TO
FLOOR DRAIN.
STSteam Take-off - Connection for operation of adjacent steam
powered equipment.
DIMENSIONS ARE IN INCHES [MM]
4 [102]
2.5 [64]
10.5
12.5
[318]
[267]
10.5
[267]
D
CW1
CW2
36 [914]
6 [152]
EP
33
[838]
6 [152]
OPERATION WILL BE BY:
Electrically powered, A.S.M.E. constructed and National Board Registered,
15 PSI (1 kg/cm2) steam boiler rated at
24kW
NOTE: The only available space to supply utilities to the boiler is the 6”
(152mm) space between the floor and the cabinet base. PVC & CPVC
Pipe are not acceptable materials for drains.
CAUTION: REMOTE KETTLE OPERATION If this boiler is feeding a
remote kettle that will be more than 5 feet (1.5 meters) away, consult
factory before ordering.
WATER SUPPLY
Good quality water feed is the responsibility of the owner. Water quality
must be within the following general guidelines.
The best defense against poor water quality is a water treatment system
designed to meet your water quality conditions.
Figure 2
69.25
[1759]
28
[711]
INSTALLATION
4
ST-10M24G
Service Connections
SERVICE CONNECTIONS
GGas Connection - 3/4” (19mm) NPT, 200,000 BTU
CW1 Cold Water - 3/8” (10mm) NPT for cold water to boiler. Cold
water lines will have a maximum of 50 PSI (3.5kg/cw2) and a
minimum of 25 PSI (1.8 kg/cw2) water pressure.
CW2 Cold Water - 3/8” (10mm) NPT for cold water to condenser.
Cold water lines will have a maximum of 50 PSI (3.5kg/cw2) and
a minimum of 25 PSI (1.8 kg/cw2) water pressure.
DDrain - Pipe full 2” (50mm) NPT to flush floor drain capable
of receiving water flowing at a maximum rate of 5 gallons (19
liters) per minute. DO NOT MAKE SOLID CONNECTION TO
FLOOR DRAIN.
ECElectrical Connection - 120 Volts AC, 60 Hz, single phase,
and a 9 foot Power Cord/NEMA 5-15.
STSteam Take-off - Connection for operations of adjacent steam
powered equipment. Requires steam take-off kit (optional at
extra cost).
OPERATION WILL BE BY
Gas fired, A.S.M.E. constructed and National Board Registered, 15PSI (1
kg/cm2) steam boiler rated at 200,000 BTU
Notes: If equipment is installed where elevation exceeds 2,000 feet
(609.6 meters) above sea level, specify installation altitude so that proper
gas orifices can be provided.
The only available space to supply utilities to the gas boiler is the 6”
(152mm) space between the floor and the cabinet.
Allow 3” (76mm) space from side wall and 6” (152mm) from rear wall if
adjoining walls are combustible.
PVC & CPVC PIPE ARE NOT ACCEPTABLE MATERIALS FOR
DRAINS.
CAUTION: REMOTE KETTLE OPERATION If this boiler is feeding a
remote kettle that will be more than 5 feet (1.5 meters) away, consult
factory before ordering.
DIMENSIONS ARE IN INCHES [MM]
4[102]
2.5 [64]
D
CW1
12.5
10.5
[318
[267]
3 [76]
69.25
[1759]
5 [127]
EC
24 [610]
EC
FLUE
CW2
ST
5 [127]
10.5
[267]
33
[838]
2.75 [70]
G
WATER SUPPLY
Good quality water feed is the responsibility of the owner. Water quality
must be within the following general guidelines.