Market Forge M24SC Service Manual

SERVICE & PARTS MANUAL
02149
MODELS:
Modular Steam Coil Steam Supply Generators
M24SC M36SC
Form Number S-5046A 7/84 Printed in USA
35 Garvey Street
Everett, MA
Tel. (617) 387-4100, Telex 94-9414, Cable MAFORCO
TABLE OF CONTENTS
SECTION 1 INTRODUCTION
1.1 How to use this Manual...................…. ... 1-1
1.2 Operating Instructions for Steam Coil
Boilers..........................................……….. 1- 1
1.3 Service ..............................................……. 1-1
SECTION 2 INSTALLATION INSTRUCTIONS
2.1 Receiving Instructions.....................….. ... 2-1
2.2 Setting in place.............................. …....... 2-1
2.2.1 Installing legs.................................…..... . 2-1
2.2.2 Leveling..........................................…….. 2-1
2.2.3 Panels.............................................….... 2-1
2.3 Important information on Steam Coil Steam
Generators to Steam Fitter.................. … . 2-1
2.4 Boiler horsepower and steam flow
information .......................................…...... 2-2
2.5 Steam Fitter and plumber ................….......2-3
2.5.1 Steam Connection. .........................…...... 2-3
2.6 Setting of Steam Generator Pressure Control
Switches Units before 1979...............….... 2-4
2.7 Pressure Control Switch adjustment (Units after
1979).........................................………..... 2-5
2.8 Water Level Control (Models before Feb.
1984)................................................. .…... 2-6
2.8.1 Disassembly Instructions.................... ... 2-6
2.9 Water Level Control (Models after Feb.
1984)....................................................….. 2- 6
2.9.1 To remove Water Level Control.......…... 2-6
2.10 Watts Pressure Reducing Valves 3/4" ..... 2-7
2.10.1 Operation of Watts 3/4" Reducing
Valve...............................................…... 2- 7
2.10.2 Adjusting Watts 3/4" Reducing Valve.…… 2-7
2.10.3 Inspection , Maintenance, Repairs ..…….. 2-7
2.11 Service Connections ..........................…….. 2-8
Wiring Diagram and Schematic
SECTION 3 OPERATION
3.1 Description...........................................……... 3-1
3.2 Basic Functioning ...............................…….... 3-1
3.3 Start up Instructions............................…….... 3-2
3.3.1 Automatic Drain Steam Generator...…….... 3-2
3.3.2 Daily Operating Instructions..............……... 3-2
3.3.3 Daily Operting Instructions (For units manufactured after June 1983, equipped with
"Momentary" heat switch)...........…………. 3-2
3.3.4 Daily Shut -down and cleaning.....……........ 3-2
3.3.5 Manual Drain Steam Generator....……....... 3-2
3.3.6 Daily Operating Instructions..........……....... 3-2
3.3.7 Daily Shut -down and cleaning.......……….... 3-2
SECTION 4 TROUBLE-SHOOTING
4.1 General.............................................……....... 4-1
4.2 Electrical Fault Isolation...................………..... 4-1
SECTION 5 ILLUSTRATED PARTS LIST
5.1 General.............................................………..... 5- 1
5.2 Ordering............................................………..... 5- 1
5.3 Index of Illustrated Parts List.............……….... 5-1
ii
Modular Steam Coil Steam Supply Generators
SECTION 1 INTRODUCTION
Market Forge, has designed these boilers with the latest type automatic controls in order to make it
easier for the operator to use and maintain this equipment. This Service and Parts Manual is written
and illustrated to cover all boiler equipment that uses a steam coil as a source of power other than
those which have been custom designed under special order.
1.1 HOW TO USE THIS MANUAL The illustrations of components are aids to the identification, disassembly and assembly of parts. The part listings provide information necessary for the ordering of replacement parts (proper part names and part numbers). When requesting parts or service, always furnish the model and serial number of your complete unit, which will indicate to Market Forge Service Division the type of boiler with which you are equipped. This information can be found on the nameplate attached to the boiler frame.
1.2 OPERATING INSTRUCTIONS FOR STEAM COIL BOILERS
Explanation of how the control system works on automatic steam coil boilers. With the boiler filled with water to its proper level and the heat switch turned to its on position the solenoid steam valve will be activated allowing outside steam to flow to the boiler steam coil. When the boiler builds up its set pressure, the pressure switch on the left side of the control box opens. This will open up the circuit to the solenoid coil in the steam valve
which in turn will stop the flow of outside steam to the boiler. As the pressure in the boiler drops off the pressure control switch will again come into operation and complete the circuit and build the boiler back up to its set pressure. When the operator wishes to stop all steam generation, he need only place the heat switch to the off position.
1.3 SERVICE Should repairs be required, a network of authorized service agencies is available to assist with prompt service. A current Directory of Authorized Service Agencies and service assistance may be obtained by contacting:
Product Service Department Market Forge Company 35 Garvey Street Everett, MA 02149 Telephone: (617) 387-4100
The model and serial numbers must be referenced when corresponding with Market Forge.
1-1
Modular Steam Coil Steam Supply Generators
SECTION 2 INSTALLATION INSTRUCTIONS
WARNING:
Read before opening the shipping containers. Do not at any time lay the equipment down on its back, side, top or front. To do so may damage the equipment and invalidate the warranty.
2.1 RECEIVING INSTRUCTIONS
Inspect the equipment before signing the bill of lading. The equipment supplied was tested and inspected before shipment. The carrier accepted it as complete and without damage.
This merchandise became your property when it was accepted by the carrier at the factory. Market Forge cannot assume responsibility for loss or damage during transit.
For this reason, you should immediately inspect for visible and concealed damage or shortages before signing for shipment as follows:
1. Count the number of cartons and packages received to be sure they coincide with the bill of lading.
2. Visually check all cartons for external
damage.
3. Remove all cartons from their skids to examine equipment for concealed damage. The carton is nailed and strapped to the skid. It will be necessary to cut the straps and pry off the container.
4. After inspection, replace the cartons over the equipment on the skids to protect and secure the equipment until it is ready for installation.
5. Sign for shipment if all is in order. Note shortages, external and concealed damage, if any, on the bill of lading before accepting a partial or damaged shipment.
6. If necessary, contact the carrier immediately to file a claim. All claims must be filed by the receiver.
7. Do not remove the cartons or the skids from the cooking equipment until the unit has been transported through the building to the actual set-up location. The cartons should remain on the equipment as protection against dents and scratches.
2.2 SETTING IN PLACE
2.2.1 Installing legs
Some models are shipped without legs. A separate carton will contain the legs. If your model is received this way be sure to follow the installation instruction sheet packed with the legs.
2.2.2 Leveling In order for the boiler to drain correctly it is important to use a level on cabinet top, both
left and right and front-to-back. If not level adjust feet. On compartment cookers check interior shelves to be level.
2.2.3 Panels and Doors Panels and doors for the cabinet may be shipped separate. Refer to installation instructions enclosed with panels and doors for method of attaching. It is recommended that panels and doors be installed after mechanical connections are made to avoid damage.
2.3 IMPORTANT INFORMATION ON STEAM COIL STEAM GENERATORS TO STEAM FITTER
The use of steam coil operated equipment is increasing, and it is important that you are aware of both the advantages and the limitations of this equipment.
A steam coil generator assures a supply of clean steam, and is generally recommended when steam is available but not considered clean enough to come in contact with food. Toxic steam generator cleaning compounds are often used to clean steam generators, and this is usually the reason for not recommending direct -connected cookers.
It is very important that a minimum of 15 PSI be available in the incoming steam line if a steam coil steam generator is to be installed for use with a 5 PSI compartment cooker. If the equipment connected to the steam generator operates at 15 PSI, minimum incoming pressure must be 30 PSI, except in the case of a single Steam-It, which can be operated on an incoming pressure of 20 PSI. Maximum recommended incoming steam pressure is 50 PSI.
(Table 2-1) shows Boiler Horse Powe r (BHP) generated by our steam coil boilers at various incoming pressures. One (1) BHP is required for each cooking compartment in "A" and "W" models. A jet cooker requires 3 BHP and a
Steam-It 1/2 BHP. It is not necessary to include steam requirements for kettles, as kettles may be direct connected since the steam does not come into contact with the food.
2-1
Section
2
Installation
Pressure maintained
Steam generator Steam generator
PSI
20 PSI
PSI
.8
3.4
4.0
of Incoming Pressure)
Steam Flow in
Lbs. Steam per
1/
2
on Incoming Steam Line
15
BHP OUTPUT set at 15 PSI set at 5 PSI
------
3.5
15 PSI. This is because the greater the temperature differential between the steam on the incoming line and the steam generated in the steam generator, the greater the BHP available. For proper
30 35 PSI
4.0
Table 2-1
Please note that a steam coil boiler set at 5 PSI
(Maximum BHP available regardless
cooking results you must have sufficient steam flow. Both pressure and volume are important.
This relates to pipe size and steam supply to the steam coil steam generator.
will generate more boiler horsepower than one set at
2.4 BOILER HORSEPOWER AND STEAM FLOW INFORMATION
Recommended boiler horsepower and steam flow in pounds per hour. (NOTE: 1 Boiler Horsepower 34.5 Ibs. of steam per hour. Do not confuse steam PRESSURE with steam FLOW.)
Delivered Boiler H.P.
Hour
Compartment steam cookers (Per compartment) 1 34.5 Steam-jacketed kettles (Per 20 gals.) 1 34.5
Direct connected Steam-It Direct connected Jet Cooker
2 1/2
17.25
86.25
Coffee Urn (Per 10 gals.) 1/10 3.4 Steam Table (Per square ft.)
1/20
1.7
Bain Marie (Per square ft.) 1/10 3.4 Warming Oven (Per square ft.) 1/20 1.7
Table 2-2
Flow of Steam in pipe, in pounds of steam per hour.
Line pressure in lbs. per square inch (PSI) Pipe size in inches:
5 10 15 20 25 30 40 50 60 70
1/2 3/4 1 1 1/4 1 1/2 2 60
70 75 80 85 90 100 108 114 120
110 125 135 145 155 165 185 200 214 226
200 220 240 255 270 285 320 345 368 390
390 430 470 505 530 565 615 680 730 770
550 610 665 715 740 800 885 965 1030 1095
970 1075 1170 1255 1300 1400 1550 1680 1800 1910
Table 2-3
2-2
Modular Steam Coil Steam Supply Generators
Capacities are based on allowing a pressure drop of 2
245
Actual run
20'.
Equivalent run
41.4'.
Rate of
PSI in a length of pipe equal to 240 diameters of the pipe. For ex ample, (Fig. 2-1) in one-inch pipe, at the steam flows shown, there would be a pressure drop of 2 PSI in 240 inches, (20 feet) of straight run.
If the rate of flow is increased, the pressure drop will be greater. If the rate of flow is decreased, the pressure drop will be less.
Elbows, valves, and other fittings cause greater pressure drop. (See next section)
In determining proper pipe size at a given line pressure to deliver the desired rate of steam flow and pressure at the steam cooker, it is necessary to know not only the actual length of the pipe run, but also the equivalent length of run. Each fitting or value causes resistance equal to a certain length of straight pipe. This equivalent length must be added to the actual length in order to determine the equivalent length of run. For example, (Fig. 2-2) assume an actual length of 20' of 20" pipe with two elbows, an angle valve, and a side outlet tee. Table 2-4 shows that to determine the equivalent length of run we must add 2.2' for each of the elbows , 12' for the angle valve, and 5' for the side outlet tee, giving us an equivalent length of run of
41.4' of straight pipe.
Resistance of fittings expressed in terms of equiv­alent length of straight pipe. (Measurements are in
feet)
Pipe
Standard
Size
Elbow
1.3' 3' .3' 14' 7'
1/2" 3/4" 1.8' 4' .4' 18' 10'
1" 2.2' 5' .5' 23' 12' 1
3.0' 6' .6' 29' 15'
1
3.5' 7' .8' 34' 18'
2" 4.3' 8' 1' 46' 22'
Side Outlet
Tee
Gate Valve
Globe Valve
Table 2-5
Temperature (degrees F) of steam at various altitudes and pressures.
Altitude 5 PSI 10 PSI 15 PSI Sea level
2000 feet 5000 feet 10,000 feet
227 224 220 213
240 237 234 228
Table 2-4
Rule-of-thumb Conversion Information
• 1 BHP —approximately 10 KW
• 1 BHP —approximately 34,000 BTU
These conversions are easily-remembered approximations. In making conversions, the efficiency of the steam generator must be considered. A gas steam generator with an input of 34,000 BTU and operating at 50% efficiency, will deliver 1/2 BHP.
Angle Valve
250 248
240
Flow: 240 Ibs. of steam per hour.
Fig. 2-2
2-3
2.5 STEAM FITTER AND PLUMBER
2.5.1 Steam Connection
It is recommended that, whenever possible, the steam input to the steam generator be a separate line from the source of supply. If the steam generator must be piped to a line which also supplies other steam consuming devices, the pipe sizes and pressures will have to be verified as to capacity.
Section
2
Installation
SUGGESTED STEAM CONNECTIONS:
ITEM 1 2 3
Fig. 2-3
(Fig. 2-3) shows a recommended system of the installation which includes the following equipment: A globe valve for shut off, a ball float trap which assures that the steam supply is clean and dry, a pressure gauge to measure inlet pressures from the source of supply.
DESCRIPTION 3/4" Globe Valve
Ball Float Trap Pressure Gauge
PART NO. 10-2821 10-5336
NOTE: If steam supply line has an extremely high
excess amount of condensate, it may be neces sary to install 2 ball float traps.
10% of recommended operating pressure, the pressure control switches are adjusted properly and the unit is operating satisfactorily.
4. Steam generator pressure switches are factory set and should not be adjusted unless absolutely necessary. If pressure is found to be other than above, proceed as follows:
a. Remove front cover from modular control
box.
b. With screwdriver adjust pressure switches (A) and
(B). Steam coil steam generators used to generated steam for a Steam-It, Jet Steam Cooker or Kettle which operate at 15 PSI should be set as follows: Switch (A) should be set at 12 PSI and Switch (B) at 20 PSI. If 15 Ib. steam generator is used for 5 Ib. operation, follow above instructions and then refer to "adjusting watts 3/4" pressure reducing valve".
c. Steam coil steam generators used to generate
steam for a compartment type steam cooker which operates at 5 PSI should be set as follows: Switch (A) should be set at 5 PSI and Switch (B) at 10 PSI. d. Dial C is the differential dial and should always be set at 1 PSI on both Switch (A) and (B).
e. The cold water condenser thermostat (Dial D) is
provided as standard equipment with all automatic drain steam generators. This thermostat is preset at the factory for 140°F and should not be re-adjusted in the field.
IMPORTANT
Before making final connection, blow out the steam line to remove all dirt, scale, packing, etc., that may be accumulated during pipe fittings.
If condensate coming out of the coil is to be returned to the customer's steam generator, disconnect the condensate tubing from the main drain and connect it to the optional condensate return fitting. See page 2-8 for location of this connection.
2.6 SETTING OF STEAM GENERATOR PRES­SURE CONTROL SWITCHES (On models before 1979) (Fig. 2-4)
To be sure steam generator pressure control switches are set properly, use the following procedure:
1. Start steam generator and allow it to build up to pressure- 5 Ibs. or 15 Ibs.
2. Release pressure into cooking chamber by turning on unit- Jet, Compartment Cooker, Steam-It.
3. Shut off cooking unit and let steam generator build back up to pressure. Check the steam generator pressure gauge. If pressure is within
2-4
NOTE: On earlier model steam generators,
adjustments of the pressure control switches may be done with a screwdriver as shown. Later model steam generators require the use of a special wrench, which may be obtained from Market Forge.
Modular Steam Coil Steam Supply Generators
2.7 PRESSURE CONTROL SWITCH ADJUST­MENT (On models after 1979) (Fig. 2-5) If
generator fails to maintain steam pressure in operating range, pressure control switch may require adjustment.
1. Start generator and allow pressure to build up to operating level -15 PSI 1 kg/cm2.
2. Check generator pressure gauge. If gauge indicates 12 to 14 PSI, pressure control switches are properly adjusted.
3. If generator does not come on when pressure gauge reads 12 PSI and does not go off when pressure gauge reads 14 PSI, proceed as follows:
a. Remove screws and lift front cover off
control box.
Warning: Because power must be on to adjust pressure switches, be sure to protect against electrical shock.
b. Hand adjust operating pressure control
switch (A) and high limit pressure control switch (B) by turning adjusting nut (Knurled knob) clockwise to raise and counter-
Fig. 2-5
clockwise to lower actuation point. Switch (A) should be set so that generator comes on when generator pressure gauge reads 12 PSI and goes off when gauge reads 14 PSI. Switch (B) should be set so that generator will shut off if pressure reaches 15 PSI. If 15 Ib. steam generator is used for 5 Ib. operation, follow above instructions and then refer to "adjusting watts 3/4" pressure reducing valve".
c. The actuation value (differential) is factory
set and cannot be changed.
d. The cold water condenser thermostat is
pre-set at factory at 130°F 54° C and should not be reset.
e. Repeat steps 1, 2, and 3. If 12 to 14 PSI
generator pressure gauge reading is obtained during generator operation, adjustment is correct. If proper adjustment cannot be made, consult Trouble-Shooting Guide in Section 4, in this manual.
f. After making adjustments, replace cover on
control box.
2-5
Section
2
Installation
2.8 WATER LEVEL CONTROL (On models before Feb. 1984)
The Water Level Control used by Market Forge is a float type switch with a float ball inside the boiler. The water level control is equipped with two microswitches which turn the water supply on and off and the power supply on and off. (Fig. 2-6)
Microswitch (A) prevents the source of power from coming on until there is an adequate supply of water in the boiler.
Microswitch (B) shuts off water supply when the water level has reac hed 2/3 full as viewed in the gauge glass.
CAUTION:
Before removing cover disconnect 115V power supply. When the boiler is full, water level should reach 2/3 full in gauge glass and the water feed should shut off. If this is not correct, remove cover to water level control and adjust Microswitch (B). To adjust, loosen lock nut and turn screw clockwise to raise level and counterclockwise to lower level.
If no water is visible in gauge glass and power comes on when water switch is reset, this indicates that:
1. Microswitch (A) is out adjustment and must be readjusted. To adjust, remove cover to water level control, loosen lock nut and turn adjusting screw in a clockwise direction. Continue this adjustment so that heat does not come on until the gauge glass is 2/3 filled with water.
2. Use Ohmmeter across to check for proper continuity through microswitches.
c. Remove the two screws (B) on either side of
housing. The housing, with all external wiring still attached, may then be removed to one side.
d. With an Alien set screw wrench remove the set
screws at the four corners of the mounting plate.
e. Pull ouy and remove the complete float assembly
and gasket from the boiler.
f. Clean the internal boiler parts of the water level
control. Use a tooth brush to clean the bellows. If the deposits are excessive, a flat blade putty knife may be used to clear accumilations from between the bellows fins. However, care should be used not to rupture them or twist bellows out of alignment. When satisfied that the complete float switch assembly is clean, and that the bellows are free to operate properly, reinstall assembly into the boiler using a new gasket to establish a firm seal. First, be sure that surfaces contacting the gasket are completely clean. Reverse the disassembly steps to reinstall into the boiler.
g. CAUTION: Be sure to check adjustments as shown.
2.8.1 Disassembly Instructions
Remove water level control as follows: (Fig. 2-7) a. Remove the two screws (A) on either side and remove the cover. b. Disconnect the 4 intial wires from their
terminals. Mark all wires and terminal posts to simplify reassembly.
2-6
2.9 WATER LEVEL CONTROL (On models after Feb. 1984)
CAUTION: Before removing cover, disconnect power supply.
The McDonnell-Miller Water Level Control is not adjustable. If not functioning properly, entire water level control must be replaced.
Loading...
+ 20 hidden pages