24" BOILER BASE CABINET .......................................................... 10
PRESSURE SWITCH BOX, WITHOUT COVER..........................................11
CONTROL BOX ASSEMBLY, WITH AND WITHOUT COVER ............................. 12
PLUMBING, LEFT SIDE GAS BOILER, 24” ............................................. 13
FRONT VIEW GAS BOILER, 24”, 200K ................................................ 14
GAS TRAIN, 200K BTU BOILER SHOWN .............................................. 15
AUGUST 29, 2014 2 M24G & M36G GAS BOILERS
TROUBLEPOSSIBLE CAUSE(S)REMEDY
Pilot will not ignite or does not
hold.
TROUBLESHOOTING
Gas not reaching unit.Check to make sure gas is on and gas
line is purged of air.
Main “gas cock knob” not in ON position. Depress and turn “main gas cock” to pilot
position - (refer to lighting instructions).
Air pocket or clog in gas line.Purge or blow out gas line.
Defective wiring or poor connection at pilots at power unit.
Defective switching across either the water level control or pressure switches.
Defective gas valve.Replace gas valve.
Water enters boiler very slowly.Clogged strainer screen on water ll so-
lenoid valve
Debris or lime accumulation on seat of
water ll valve.
Boiler overlls with water.Probes scaled.Clean.
Water supply valve fails to close.Clean valve seat or replace valve.
Defective water level control.Follow the test procedure. Replace if de-
Main Burners will not ignite or will
not remain lighted.
Boiler fails to build up any pressure when the water is at the
correct level and the fuel switch is
turned on.
Boiler fails to cut off after reaching
operating pressure.
No water in boiler.Check to be sure water switch is on.
Main gas cock or supply line not open.Open.
Pressure switch set too low.Reset - if continuity check shows to be
No voltage to gas valve.Check main fuse.
Gas valve defective.Replace.
Check to see that main gas is turned on. Turn on.
Check to see that gas valve is in burners
“on” position.
Current ow is broken at water level control (ascertain with continuity check).
Current ow is broken at pressure control
or high limit control switches (ascertain
with continuity check).
Pressure switch set too high or defective. Adjust or replace if defective.
Check - replace or tighten.
Make continuity check – replace units
that are defective.
Clean or replace strainer screen. (P/N
08-4871).
Clean valve seat
fective.
Check to be sure main water supply is on
and the electrical supply to unit is on.
defective - replace.
Turn to burners “on”.
Check for voltage thru right side of control
board, replace if defective.
Re-adjust to proper setting -refer to instruction for re-adjustment, replace if defective.
Gas valve fails to cut off gas supply when
demands of pressure switch have been
met.
Water level in gauge glass uctuates up and down.
AUGUST 29, 2014 3 M24G & M36G GAS BOILERS
Top shutoff valve on water gauge glass
is closed.
Replace gas valve.
Open.
TROUBLESHOOTING
TROUBLEPOSSIBLE CAUSE(S)REMEDY
Boiler fails to reach full operating pressure of 5 lbs. or 15 lbs.
Safety valve blows off prematurely.Pressure set too high.Readjust pressure control.
Boiler builds up to pressure, shuts
down, fails to come back on.
Water does not enter boiler.Main water supply off.Turn on.
Cold water condenser does not function.
Air vent leaking.Not closing.Replace.
Pressure gauge reads inaccurately.Replace.
Pressure control and high limit control
switches are out of adjustment.
Safety valve not seating properly.Purge manually or replace.
Water level too high.Adjust water level control - check wa-
Air vent not venting properly.Replace.
Insufcient ames on burners or im-
proper gas supply.
Pressure gauge reads incorrectly.Replace.
Lime or debris on seat of valvePurge or replace.
High limit switch set to low or operating
pressure control switch set too high.
Power not reaching unit.Check main fuse or circuit.
Probes Dirty.Remove & Clean
Water level control board defective.See test procedure.
Solenoid valve defectiveIf Voltage is veried at solenoid coil, but
Main water supply off.Turn on.
Thermostat defective.Replace if defective.
Loose coil nut.Tighten coil nut.
Solenoid coil not energized.Check coil for continuity, if open re-
Follow instructions for readjusting
ter feed valve for sticking - clean or replace.
See instructions on gas adjustments
Follow instructions for readjusting Replace if defective.
fails to open, replace solenoid.
place.
AUGUST 29, 2014 4 M24G & M36G GAS BOILERS
GAS PRESSURE ADJUSTMENTS
If gas pressure is too low
Check your gas supply line for a restriction. If no restriction exists, check with your Natural gas supplier to provide
at least 5” of water column pressure in the gas supply line.
If no restriction exists and Propane gas is being used, the
tank pressure regulator should be adjusted to supply at
least 11” of water column pressure in the gas supply line.
If this adjustment cannot be made to your satisfaction, the
gas supplier should be notied.
If gas pressure is too high
Adjust the pressure regulator on the boiler gas valve to reduce the pressure if Natural gas is being used. If Propane
gas is being used, adjust the pressure regulator supplied
by the gas supplier. If the regulator cannot be adjusted,
notify the gas supplier.
Pressure control switch adjustment
If boiler fails to maintain steam pressure in operating
range, pressure control switch may require adjustment.
1. Start boiler and allow pressure to build up to operating level - 7 PSI (1kg/cm²).
2. Check boiler pressure gauge. The gas burners should
cycle ON at 5 PSI and cycle OFF at 7 PSI.
3. If boiler does not come on when pressure gauge
reads 5 PSI and does not go off when pressure gauge
reads 7 PSI, proceed as follows:
WARNING
Because power must be on to adjust pressure
switches, be sure to protect against electrical
shock.
a. Remove screw and lift front cover off control box.
b. Hand adjust operating pressure control switch
and high limit pressure control switch by turning
adjusting nut (Knurled knob) clockwise to raise
and counter clockwise to lower actuation point.
Switch should be set so that boiler comes on
when boiler pressure gauge reads 5 PSI and
goes off when gauge reads 7 PSI. Hi limit switch
should be set so that boiler will shut off if pressure reaches 15 PSI.
c. The actuation value (differential) is factory set
and cannot be changed.
d. The cold water condenser thermostat is preset
at factory.
e. Repeat steps, 1, 2, and 3. If 5 to 7 PSI boiler
pressure gauge reading is obtained during boiler
operation, adjustment is correct. If proper adjustment cannot be made contact an authorized service agent.
f. After making adjustments, replace cover on pres-
sure switch box and screw.
OPERATING SWITCH
HI LIMIT SWITCH
AUGUST 29, 2014 5 M24G & M36G GAS BOILERS
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.