Market Forge M24E18 Installation Manual

Page 1
ELECTRICALLY OPERATED
(617) 387
-
4456
35 Garvey St., Everett, MA
02149
-
4403
Tel.
(617) 387
-
STEAM GENERATOR
OWNERS MANUAL
OUTSIDE MA (800) 227-2659
Form No. S-2379 Printed in U.S.A. 3/90
MODELS:
M24E18, M24E24, M24E32, M24E36, M24E42, M24E48, M36E18, M36E24, M36E32, M36E36, M36E42, M36E48
4100, Telex 94-9414, Cable MAFORCO
Page 2
TABLE OF CONTENTS
Page
Introduction................................................................. 1
How To Use This Manual ..................................... 1
Theory of Operation ................................. 1
Receiving Instructions..................................... 2
Installation Instructions........................ 2,3
Operating Instructions................................................... 4,5
Liquid Level Control Diagram..................................... 6, 8
Trouble Shooting Liquid Level Control Board ..................... 7, 9
General Trouble Shooting Guide ......................................... ....................10,11,12
Operation/Adjustment of Pressure Reducing Valves ............. 13
Adjustment, Pressure Control Switches ........................ 14
Control Box Wiring Diagram ..................................... 15
Wiring Diagram, Heating Circuit ............................... 16
Wiring Diagram, Heating Circuit (Export) ..................... 17
24" Cabinet Base .................................... 18
36" Cabinet Base ................................................ 19
Steam Generator - Right Side View............................. 20
Control Box Assy. (Covered & Uncovered) .......................... 21
Heating Elements......................................................... 22
Plumbing Section (Left Side View)................................ 23
Contactors & Liquid Level Control Box ................................ 24
A - Small Generator w/Contactor Box ................................... 25
B - Large Generator w/Contactor Box.................................. 25
C - Electric Modular Base Steam Generator.......................... 25
Page 3
INTRODUCTION
Market Forge, in the interest of both costs and efficiency to the purchasers of its equipment, has designed these steam generators with the latest type automatic controls in order to make it easier for the operator to use and maintain this equipment. In addition, standard components are utilized on all models of steam generator equipment unless variances in size or capacity dictate a divergence from this policy for more efficiency in operation. This parts and service manual is written and illustrated to cover all steam generator equipment that uses electricity as a source of power other than those which have been custom designed under special order.
HOW TO USE THIS MANUAL
The pictures of components are aids to the identification, disassemb ly and assembly of parts. The parts listings provide information necessary for the ordering of replacement parts (proper part names and part numbers). When requesting parts or service, always furnish the model and serial number of your complete unit, which will indicate to Market Forge Service Division the type of steam generator with which you are equipped. This information can be found on the nameplate attached to the steam generator frame.
THEORY OF OPERATION FOR ELECTRIC STEAM GENERATORS
Explanation of how the control system works on manual and automatic electric steam generators. With the steam generator filled with water to its proper level and the fuel switch turned to its on position, the contactors will
pull in and permit the completion of the electric circuit to the heating elements. When the steam generator builds up to its set pressure the pressure switch on the left side in the control box opens. This will open up the circuit to the coil in the contactor, which in turn will drop out the contacts in the contactor and shut off the electricity. As the pressure in the steam generator drops off, the pressure control switch will again come into operation and complete the circuit and build the steam generator back up to its set pressure. When the operator wishes to stop all generation of steam he need only to place the fuel switch in the off position.
Product Service Dept. Market Forge Co.
35 Garvey Street Telephone 617-387-4100
Page 4
35 Garvey St., Everett, MA 02149 Tel. (617) 387-4100
ELECTRICALLY OPERATED STEAM GENERATORS
WARNING: READ THIS BEFORE OPENING THE SHIPPING CONTAINERS DO NOT AT ANY TIME LAY THE EQUIPMENT DOWN ON ITS BACK, SIDE, TOP OR FRONT. Doing so may damage
the equipment and invalidate the warranty.
RECEIVING INSTRUCTIONS: Inspect the equipment before signing the bill of lading. The equipment supplied was tested and inspected before
shipment. The carrier accepted it as complete and without damage. This merchandise became your property when it was accepted by the carrier at the factory. Market Forge cannot assume
responsibility for loss or damage during transit. For this reason, you should immediately inspect for visible and concealed dama ge or shortages before signing for
shipment as follows:
1. Count the number of cartons and packages received to be sure they coincide with the bill of lading.
2. Visually check all cartons for external damage.
3. Remove all cartons from their skids to examine equipment for concealed damage. The carton is nailed and strapped to the skid. It will be necessary to cut the straps and pry off the container.
4. After inspection, replace the cartons over the equipment on the skids to protect and secure the equipment until it is ready for installation.
5. Sign for shipment if all is in order. Note shortages, external and concealed damage, if any, on the bill of lading before accepting a partial or damaged shipment.
6. If necessary, contact the carrier immediately to file a claim. All claims must be filed by the receiver.
7. Do not remove the cartons or the skids from the cooking equipment until the unit has been transported through the building to the actual set -up location. The cartons should remain on the equipment as protection against dents and scratches.
Installation Instructions
SETTING IN PLACE:
INSTALLING LEGS: Some models are shipped without legs. A separate carton will contain the legs. If your model is received this way be sure
to follow the installation sheet packed with the legs.
LEVELING:
In order for the steam generator to drain correctly it is important that it be level. Place level on cabinet top - both left and right and front to back. If not level, adjust feet. On compartment cookers, check cooking compartment pan supports to insure they are secure. Check by installing cooking pan to see if the pan supports are level.
PANELS AND DOORS:
Panels and doors for the cabinet may be shipped separate. Refer to installation instructions enclosed with panels and doors for method of attaching. It is recommended that panels and doors be installed after mechanical connections are made to avoid damage.
2
Page 5
Volts 18KW 24KW 32KW 36KW 42KW
1ph 3ph 3ph 3ph
3ph 3ph 3ph
240(220
-
240) 75 32 60 77 91
116
480 (360
-
500) 36 22 32 39 47
58
HW
2
amps.
adjacent steam powered equipment.
INSTALLATION ROUGH-IN REQUIREMENTS
EP Power Supply —Use wire suitable for at least
90°C. Nominal amp per line wire:
208(197.219) 86 50 66 89 100 117 —
Details of other electrical systems available upon request.
Hot Water— 3/8" N.P.T. for hot water to steam generator. Hot water line shall have a maximum of 50 PSI (3.5 kg/cm2 and a minimum of 25 PSI (7.8 kg/cm22) water pressure.
CW
Cold Water—3/8" N.P.T. for cold water to condenser. Cold water line shall have a maximum of 50 PSI (3.5 kg/cm2) and a minimum of 25 PSI (1.8 kg/cm2) water pressure.
D
Drain—Pipe full 2" (50mm) I.P.S. to flush floor drain capable of receiving water flowing at a maximum rate of 5 gallons 19 liters per minute. DO NOT MAKE SOLID CONNECTION TO FLOOR DRAIN. PVC and CPVC are not acceptable materials for drains.
EC Electrical Connection—120 volts AC, 60Hz,' single phase,
1/2" 13mm conduit connection or equivalent. Use wire suitable for at least 90°C. Amp draw for generator controls:
ST Steam Take-off—Connecting locations for operation of
CAUTION: Before connecting water to this unit, water supply
should be analyzed to make sure hardness is no greater than 2.0 grains and pH level is within the range of 7.0-8.5. Water which fails to meet these standards should be treated by installation of a water conditioner. EQUIPMENT FAILURE CAUSED BY INADEQUATE WATER QUALITY IS NOT COVERED UNDER WARRANTY .
3
Page 6
Operating Instructions
MARKET FORGE MODULAR STEAM GENERATOR OPERATING INSTRUCTIONS
WARNING: The installation of this appliance is to be in accordance with the current CAN 1-B149. 1 of CAN1-
B149.2 - Installation Code for Gas Burning Appliances and Equipment and/or Local Codes. WARNING: All Electrical connections are to be made in accordance with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.
Market Forge has two types of steam generators; one has an automatic drain, the other a manual one. To determine which you have, open cabinet doors and you will see a control box with 2 switches and an indicator light. Instruction label on the control box will identify the steam generator as being automatic or manual.
DAILY OPERATING, SHUT DOWN & CLEANING INSTRUCTIONS FOR
AUTOMATIC STEAM GENERATORS
First check to be sure that:
A. WATER switch is in the off position.
B. WATER supply valve is OPEN.
C. ELECTRICITY is connected.
D. That STEAM is turned on.
E. Proceed with daily operating procedure.
DAILY OPERATING PROCEDURE
STEP 1 Flip WATER switch from OFF to ON.
STEP 2 Wait 6 minutes for water to fill in steam generator.
(Gauge glass should indicate approx. 2/3 full.)
STEP 3 Flip heat switch from ON to OFF and release back to ON. Indicator
light will come on immediately (This is necessary to manually reset the unit.) This also turns on HEAT.
DAILY SHUT-DOWN AND CLEANING
STEP 1 Flip WATER switch OFF. (Indicator light will go out and
steam generator will automatically drain.)
STEP 2 After steam generator has completely drained, repeat Steps 1 & 2.
Water is to remain in steam generator until next day use.
STEP 3 Repeat Steps 1 & 2.
Water is to remain in steam generator until next day use
NOTES: If generator is not to be in use for extended periods, (2-3 mos.) contact your authorized
service dealer, for it must be cleaned and drained completely. Then add PM-Plus as per instructions on Bottle.
If steam generator does not automatically drain when water switch is shut off, open manual drain by turning knob counter clockwise. Electric steam generators should be blown-down and refilled after every 4 hours of operation.
Page 7
DAILY OPERATING, SHUT-DOWN & CLEANING INSTRUCTIONS
First check to be sure that:
A. WATER and HEAT switches are in the OFF position. B. WATER supply valve is OPEN.
C. ELECTRICITY is connected to ALL units. D. STEAM is turned on.
E. Proceed with daily operating procedure.
DAILY OPERATING PROCEDURE
STEP 1 Close STEAM GENERATOR DRAIN VALVE. STEP 2 Flip WATER switch from OFF to ON. STEP 3 Wait 6 minutes for water to fill in steam generator. (Gauge glass should be 2/3 full.) STEP 4 Flip WATER switch from ON to OFF and back to ON immediately.
Indicator light will come on. (This is necessary to manually reset the unit.)
STEP 5 Flip HEAT switch from OFF to ON. This turns on HEAT.
DAILY SHUT-DOWN AND CLEANING
STEP 1 Flip HEAT and WATER switches to OFF. (Indicator light will go out.) STEP 2 Open steam generator drain valve, and drain completely. STEP 3 Repeat Steps 1 & 2 of DAILY OPERATING PROCEDURE, (Water to
remain in steam generator until next daily use.)
STEP 4 For shutdown for extended periods steam, generator must be cleaned and drained
completely. Refer to steam generator cleaning instructions for modular steam generators S-2299 for complete instructions.
CAUTION: BE SURE TO READ
Keep this appliance area free and clear from combustibles. Do not obstruct the flow of ventilation air. Keep this manual for future reference. Contact the factory, the factory representative, or a local service company to perform maintenance and repairs.
In the event of a power failure, attempt should not be made to operate the appliance during power failure. Be sure water switch is in the down position.
Page 8
Page 9
TEST PROCEDURES - MARKET FORGE #08-6328 (120V)
MARKET FORGE #08-6329 (240V)
The following is a troubleshooting guide designed to find out if the Dual Function Control is working properly. It is not designed to find out why the control has failed.
The Series Dual Function control is two controls in one, one half being the feed water control, the other half the low level cutoff portion.
Tools Needed: A digital or analog V-O-M (volt-Ohm-milliamp meter) and a set of test jumpers (alligator type).
1) Turn off power to the control.
2) Remove the wires #-100, #101, #102 from the probe connections "H, "LLCO" and "G".
3) Remove the wires from the contact connections "COM", #104 and "N.O." from both relays. CAUTION:
Internal Jumper from "L1" to "COM" will be hot when power is reapplied. Temporarily tape free end.
4) Using the Ohm meter, check to see if the normally opened contact is open and the normally closed contact is closed.
5) Turn power on to control. Check with the voltmeter to see if the voltage being applied to "L1" & "L2" is 120 VAC (+10% -15%), or 240 VAC if so equipped.
6) When power is turned on, the LED on the side away from the transformer should light and the relay next to the LED should be energized. Checking with the Ohm meter, the normally open contact should be closed and the normally closed contact should be open. Bringing power to the control should not change the side of the control that contains the transformer.
7) Place a test jumper wire from either "G" terminal to the "H" terminal. After a 10 second (+/-2) time delay, the LED will go out and the relay next to this LED should deenergize returning the contacts to their original state,
(Normally open should be open, Normally closed should be closed)
8) Removing the test jumper from "G" and "H" should relight the LED and energize the relay.
9) Place a test jumper wire from either "G" terminal to the "LLCO" terminal. The LED next to the transformer
should light and the relay next to the transformer should energize. Checking with the Ohm meter, the normally open contact should be closed and the normally closed contact should be open.
10) Remove the test jumper from "G" and "LLCO". The LED should remain lit for about 3 seconds (+/-) before going out. The relay should deenergize at this time. The contac ts should return to their original state.
11) If the above test shows that the control is operating properly, check all probe and solenoid wiring and the condition of the electrodes (clean insulator) in the steam chamber. Check the conductivity of the liquid to make
sure it is below 4.7K ohms/cm.
12) If after replacing all wires, the system still does not operate properly, contact the factory.
Page 10
Page 11
TEST PROCEDURES - MARKET FORGE #08-6407 (120V) (CALIF.)
The following is a troubleshooting guide designed to find out if the Dual Function and Series 26 Controls are working
properly. It is not designed to find out why the controls have failed.
The Series Dual Function control is two controls in one, one half being the feed water control, the other half the low level
cutoff portion. The Series 26 is strictly a secondary low level cutoff.
Tools Needed: A digital or analog V -O-M (volt-Ohm-milliamp meter) and a set of test jumpers (alligator type).
1) Turn off power to the control package.
2) Remove the wires #100, #101, #102 from the probe connections "H", "LLCO" and "G" on the dual function and
"LLCO/130" and "G" on the Series 26.
3) Remove the wires from the contact connections "COM", #104, and "N.O" from both relays on the dual function and the relay on the Series 26. CAUTION: The Internal Jumper from "L1" & "COM" will be hot when power is reapplied. Temporarily tape free end.
TESTING THE DUAL FUNCTION:
6) When power is turned on, the LED on the side away from the transformer should light and the relay next to the LED
should be energized. Checking with the Ohm meter, the normally open contact should be closed and the normally closed contact should be open. Bringing power to the control should not change the side of the control that contains the transformer.
7) Place a test jumper wire from either "G" terminal to the "H" terminal After a 10 second (+/-2) time delay, the LED will go out and the relay next to this LED should deenergize returning the contacts to their original state. (Normally open should be open, Normally closed should be closed)
8) Removing the jumper from "G" and "H" should relight the LED and energize the relay.
9) Place a test jumper wire from either "G" terminal to the "LLCO" terminal. The LED next to the transformer should light and
the relay next to the transformer should energize. Checking with the Ohm meter, the normally open contact should be closed and the normally closed contact sh ould be open.
10) Remove the test jumper from "G" and "LLCO". The LED should remain lit for about 3 seconds (+/-) before going out. The relay should deenergize at this time. The contacts should return to their original state.
TESTING THE SERIES 26:
11) With power still applied to control package, place a test jumper wire from "G" terminal to the "LLCO" terminal. The LED
should light and the relay should energize. Checking with the Ohm meter, the normally open contact should be closed and the normally close d contact should be open.
12) Remove the test jumper from "G" and "LLCO". The LED should remain lit for about 3 seconds (+/-) before going out. The relay should deenergize at this time. The contacts should return to their original state.
13) If the above test shows that the control is operating properly, check all probe and solenoid wiring and the condition of the electrodes (clean insulator) in the steam chamber. Check the conductivity of the liquid to make sure it is below 4.7L ohms/cm.
14) If after replacing all wiring, the system still does not operate properly, contact the factory.
Page 12
GENERAL TROUBLE SHOOTING GUIDE
Current flow is broken at water level control
Current flow is broken at pressure control or
L2, replace if
Replace if continuity check through the
if found defective.
check to be sure there is an even draw on
ing diagrams for
fuse is O.K. shut off power, remove wires
TROUBLES POSSIBLE CAUSE REMEDY
Water does not enter steam generator.
Water enters steam generator very slowly.
Indicator light on control box does not light when water switch is manually reset.
Water level in gauge glass fluctuates up and down.
Steam generator fails to build up pressure when water level is proper and fuel switch is turned on.
1. Water main shut-off.
2. Power not reaching unit.
3. Probes Dirty
4. Water level control board defective
5. Solenoid valve defective
1. Dirty strainer screen in solenoid valve 1. Clean or replace strainer screen.
1. Indicator light defective.
2. Time delay relay loose or defective.
1. Top shut off on water gauge is closed. 1. Open
1. Check to see that circuit breaker in main is turned on.
2. Check to see that contactors are pulling in.
3. (ascertain with continuity check).
4. high limit control switches due to maladjustment or defect (ascertain with continuity check).
5. Heating elements are defective.
1. Turn on.
2. Check main fuse or circuit.
3. Remove & Clean
4. See page #9 for test procedure
5. If 120 Volt is verified at solenoid coil, but fails to open, replace solenoid.
P/N 08-4871
1. Replace.
2. Check for good connections. If alright ­replace.
1. Check for voltage at terminal block.
2. Check continuity of coil, if open replace.
3. Check for voltage at L1 & defective.
4. Readjust - to proper setting - refer to instructions for re-adjustment, replace if defective.
5. circuit of each element shows defective.
Steam generator fails to reach full operating pressure of 5 Ibs. or 15 Ibs.
1. Pressure gauge reads inaccurately.
2. Pressure control and high limit control switches are out of adjustment.
3. Safety valve not seating properly.
4. Contactor coils (one or both) not energizing and closing circuit to the heating elements.
1. Replace.
2. Follow instructions for re-adjusting or replace if defective.
3. Clean or Replace.
4. Check - replace either contactor coils or complete contactor ­Measure amperage at terminal block
all three phases - see wir correct AMP draw. If uneven or zero amperage draw is found on one of the three phases, check for blown fuse. If
from heating elements and run continuity check - replace if defective.
Page 13
GENERAL TROUBLE SHOOTING GUIDE
See
adjust for proper operation or replace
TROUBLES POSSIBLE CAUSE REMEDY
Contactor chatters.
15 Ib. Safety valve blows off prematurely
Steam generator builds up to pressure, shuts down and fails to come on.
Steam generator cuts out after 10-15 minutes of operation.
Airvent and vacuum breaker leaking. 1. Not closing. 1. Replace.
Cold water condenser does not function.
1. Incorrect supply voltage.
2. Dirty or worn contactor points.
3. Weak coil.
1 Pressure set too high. 2 Pressure gauge reads incorrectly.
3. Mineral build-up or dirt on seat of valve.
4. Weak spring in valve.
1. High limit switch set too low or operating pressure control switch set too high.
1 Defective time delay relay.
2. Poor solder connections on relay socket.
1. Main water line shut off.
2. Thermostat out of adjustment or defective.
3. Tighten coil nut
Check solenoid coil for continuity, if open
replace.
1. Check to see that it matches it with coil in contactors
2. Clean or replace contactor
3. Replace with correct voltage coil.
1. Re-adjust.
2. Replace.
3. Clean.
4. Replace valve.
1. Follow instructions for re-adjusting
page No. 13
2. Replace if defective.
1. Replace relay.
2. Resolder connections on relay socket.
1. Turn on.
2 Re-
if defective.
3. Tighten coil nut.
4. Check coil for continuity, if open replace.
Pressure reducing valve cannot be adjusted.
Pressure reducing valve vibrates or hums.
Product in cooker does not cook properly on first cycle, but cooks alright after first cycle is exhausted.
1. Dirty screen and seat.
2. Disc assembly defective.
3. Diaphragm ruptured.
1. Adjustment of sensitivity adjuster. 1. Re-adjust.
1. Air vent and vacuum breaker is closing. 1. Replace.
1. Clean.
2 Replace.
3. Replace.
Page 14
TROUBLE SHOOTING THE MARKET FORGE CO. CONTACTOR
The following table lists the major causes of trouble encountered with contactors and the suggested remedies:
CONTACTS
TROUBLE CAUSE REMEDY
Contactor Chatter
Welding or Freezing
Short Contact Button Life and/or overheating of contacts
1. Low Voltage
2. Defective or incorrect coil.
1. Abnormal inrush of current.
2. Low Voltage preventing mag net from sealing.
3. Short Circuit.
1. Filing or dressing.
2. Interrupting excessively high current.
3. Discolored contacts caused by insufficient contact pres sure, loose connections, etc.
4. Dirt or foreign matter on contact surface.
5. Short Circuit.
1. Check voltage condition. Check momentary voltage dip during starting. Low voltage prevents magnet sealing. Check coil voltage rating.
2. Replace Coil, rating of coil must match the line voltage.
1. Check for grounds or shorts in system.
2. Correct voltage condition.
3. Remove short fault and check to be sure fuse or breaker size is correct.
1. Do not file silver tips. Rough spots or dis coloration will not harm tips or impair their efficiency.
2. Check for grounds, shorts or excessive current.
3. Check contact carrier for deformation or damage, clean and tighten connections.
4. Clean with Acetone.
5. Remove fault & check to be sure fuse or breaker size is correct.
COILS
TROUBLE CAUSE REMEDY
Open Circuit 1. Mechanical damage.
2. Burnt -out coil due to over­voltage or defect.
Overheated Coil 1. Over-voltage or high ambient
temperature.
2. Wrong coil.
3. Shorted turns caused.
4. Under voltage, failure of
magnet to seal in.
1. Handle and store carefully. Do not handle coils by the leads.
2. Replace coil.
1. Check application and circuit.
2. Check rating (voltage and frequency) if incorrect, replace with proper coil.
3. Replace coil.
4. Correct system voltage. Install new coil.
Page 15
1 10-1083
ITEM NO PART NO. DESCRIPTION
Adjusting Spring 2 10-1082 3 10-1075 4 10-1076
5 10-1077 6 10-1078 7 10-1079
8 10-1080 9 10-1081
10 10-1033
10A 10-1034
11 NPN 12 10-0893
Valve Stem Guide
WATTS PRESSURE REDUCING VALVES-3/4"
To provide adequate steam pressure regulation, your unit may be equipped with a Watts steam pressure reducing valve. The 34" Watts pressure reducing valve is designed to operate from a 7 to 50 P.S.I. source of steam pressure and reduce this to 5 P.S.I. for delivery to your cooker. Installation must be made from your source of steam supply, through the pressure reducing valve, and into the manifold input part of the steam cooker.
WARNING: Before final connection is made, blow down your steam line to remove all dirt, scale, packing and compound which ma y have accumulated during the installation of piping to the cooker.
OPERATION OF WATTS 3/4" REDUCING VALVE Steam enters the valve at the inlet port and passes upward
through the seat (8) into the discharge side of the valve. As pressure in the discharge side increases, it forces the
diaphragm (2) upward, overcoming the tension of the adjusting spring (1) and closing valve. As the pressure drops, the
Diaphragm
Diaphragm Gasket
Diaphragm Button & Stem
Assembly
Strainer
Bottom Plug Gasket
Bottom Spring
Seat
Disc Assembly
3/4" Complete Valve-Painted
3/4" Complete Valve-Chrome
Bottom Plug
adjusting spring forces the diaphragm down, reopening the valve. Where demand and initial pressures are fairly constant, the valve opens to the proper position and maintains the desired reduced pressure.
ADJUSTING WATTS 3/4" REDUCING VALVE
1. Release the adjusting screw lock nut and loosen the adjusting screw enough to release all tension on adjusting spring (1).
2. Turn steam on slowly. Then turn adjusting screw clockwise just enough to allow the valve to open slightly. Allow cooker to operate in this manner several minutes.
3. Turn adjusting screw down slowly, at intervals, until reduced pressure reaches the desired point. (5 P.S.I.)
4. Tighten adjusting screw lock nut.
5. If chattering noise should occur turn adjusting screw located in bottom half of valve body, clockwise or counter-clockwise, until chattering stops.
INSPECTION - MAINTENANCE Reports of unsatisfactory regulation of the pressure reducing valve is usually due to dirt, pipe compound, etc.,
blocking the internal strainer, or gumming up the seat and disc assembly. To clean the strainer, seat, and disc assembly remove the bottom plug (6) and remov e strainer screen (5), bottom spring (7) and disc assy. (9) Clean the lower part of the valve. This can be accomplished without removing the valve from the line or unbolting the cover. If cleaning the strainer and disc assy. does not correct fault, the disc assy. and seat should be replaced Also the top cover should be removed and the diaphragm button stem assembly should be removed, cleaned and re-installed.
REPAIRS The following item should be cleaned or replaced should
the valve fail to operate properly .
1. Both the disc assembly (9) and strainer (5) are removed by removing the bottom plug (11) and bottom spring (7). Upon cleaning or replacing these items, be sure that the disc assembly (9) is seated properly on the stem assembly (4) otherwise the stem assembly will be bent restricting its movement and the regulation of steam through the valve.
2. Should there be a restriction in the diaphragm button and stem assembly (4) it will cause a drop in steam flow or large fluctuations in steam pressure. It is then necessary to replace diaphragm button and stem assembly (4), valve stem guide (12) and diaphragm gasket (3) as well as those items in step 1.
Upon completion of the above and removal of any loose scale, which may be found in the valve, the valve should be reassembled: and upon installation, function properly.
13
Page 16
Setting of Steam Generator Control Pressure Switches
PRESSURE CONTROL SWITCH ADJUSTMENT
If generator fails to maintain steam pressure in operating range, pressure control switch may require adjustment.
1. Start generator and allow pressure to build up to operating level -15 PSI 1 kg/cm2.
2. Check generator pressure gauge. If gauge indicates 12 to 14 PSI, pressure control switches are properly adjusted.
3. If generator does not come on when pressure
gauge reads 12 PSI and does not go off when pressure gauge reads 14 PSI, proceed as follows: a. Remove screws and lift front cover off control
box.
Warning: Because power must be on to
adjust pressure switches, be sure to protect against electrical shock.
b. Hand adjust operating pressure control switch
(A) and high limit pressure control switch (B) by turning adjusting nut (Knurled knob) clock
wise to raise and counterclockwise to lower actuation point. Switch (A) should be set so that generator comes on when generator pressure gauge reads 12 PSI and goes off when gauge reads 14 PSI. Switch (B) should be set so that generator will shut off if pressure reaches 15 PSI. If 15 Ib. steam generator is used for 5 Ib. operation, follow above instructions and then refer to "adjusting watts 3/4" pressure reducing
valve".
c. The actuation value (differential) is factory set
and cannot be changed.
d. The cold water condenser thermostat is preset
at factory at 150°F 60°C and should not be reset.
e. Repeat steps 1, 2, and 3. If 12 to 14 PSI
generator pressure gauge reading is obtained during generator operation, adjustment is correct. If proper adjustment cannot be made, consult Trouble-Shooting Guide in this manual.
f. After making adjustments, replace cover on
control box.
14
Page 17
Page 18
Page 19
Page 20
24"
Cabinet
ITEM NO. PART NO.
1 90-2657 Rear Panel St. Steel * 9 10-5561 Maqnetic Catch
Kit 90-3013 Rear Panel St. Steel Kit *10 10-1869 No. 10-32 x 1/2" Flat Head Screw
2 90-2661 Side Panels R & L St. Steel *11 91-5481 Cabinet Hinqe Top Left &
Kit 90-9039 Side Panels R & L St. Steel Kit
3 10-0631 Leo
* 4 98-0427 Ass'v 24" x 33" Modular Frame
5 91 -5476 Door Ass'v. 24" *12 10-2365 Lock Nut
* 6 98-0418 Panel MTG Bracket *13 10-2511 Washer
7 91-9154 Feature Strip ST. ST. *14 10-2307 Hex Nut
* 8 90-3210 Bracket Maqnetic Catch
*not shown
DESCRIPTION ITEM NO. PART NO.
91 -5482 Cabinet Hinqe Top Riqht &
DESCRIPTION
Bottom Riqht
Bottom Left
18
Page 21
36"
Cabinet
ITEM NO. PART NO.
*not shown
DESCRIPTION ITEM NO. PART NO. DESCRIPTION * 1 98-0418 Panel Mounting Bracket *10 10-1869 No. 10-32 x 1 /2" Flat Head * 2 10-2405 Washer * 3 10-2307 Hex Nut 5/16-18 11 91 -5475 Door Ass'y 18" Specify L or R
* 4A 91-6132 Rear Panel 18" Aluminized *12 10-5561 Magnetic Latch * 4B 91-2656 Rear Panel 18" Stainless *13 90-3210 Bracket Magnetic Latch
5 10-0631 Leg 14 91-9153 Feature Strip ST. ST.
6 90-2661 Side Panels R & L St. Steel *15 10-0453 Cabinet Hinge Left Bottom Kit 90-9039 Side Panels R & L St. Steel Kit *17 10-2511 Lockwasher 5/16 * 7 10-2365 Self-Locking Nut *18 10-2147 Hex Bolt 5/16-18 * 8 Ref. Only Ass'v 36" x 33" Modular Frame * 9 91 -5481 Cabinet Hinge R. Bottom
19
Machine Screw
Page 22
12" & 8" ELECTRIC STEAM GENERATOR CYLINDRICAL
ITEM # PART NO. DESCRIPTION
1 91-8651 12" DIA. STEAM GENERATOR ASS'Y.
2 91-8750 8" DIA. STEAM GENERATOR ASS'Y. 3A 91 -8771 INSULATION (BLANKET COVER) - 12" STEAM GENERATOR 3B 91-8772 STRAP
3C 10-4479 CLIP
4A 91 -8770 INSULATION (BLANKET COVER) - 8" STEAM GENERATOR 4B 91 -8764 STRAP
4C 10-4479 CLIP
5 10-5320
6 10-4741 3/4" 8 LBS. SIDE OUTLET SAFETY VALVE
7 08-6427 LIQUID LEVEL PROBE L.W. 6 1/4 LG. 12" DIA. STEAM GENERATOR
8 08-6338 LIQUID LEVEL PROBE 5 5/16" LG. BOTH 8" & 12" DIA. STEAM GENERATOR
9 10-3832 10 10-3428
11 10-7978 AIR VENT 12 91 -8654 STEAM GENERATOR FRONT PLATE 13 91-8661 STEAM GENERATOR FRONT PLATE GASKET 14 08-6337 LIQUID LEVEL PROBE 4 1/2 LG" 8" DIA. STEAM GENERATOR
3/4" 15 LBS. SIDE OUTLET SAFETY VALVE
ELBOW 90° STREET 1/4 IPS PORT OF ENTRY (TOTAL CONCEPT) PLUG SQ. 1/ 4 IPS PORT OF ENTRY (TOTAL CONCEPT)
20
Page 23
CONTROL BOX ASSEMBLY
ITEM# PART NO. DESCRIPTION
1 91 -8703 COMPLETE CONTROL BOX ASSY. 120 VOLT AUTO DRAIN 2 91 -8704 COMPLETE CONTROL BOX ASSY. 240 VOLT AUTO DRAIN (Export) 3 91 -8705 COMPLETE CONTROL BOX ASSY. 120 VOLT MANUAL DRAIN 4 91 -8706 COM PLETE CONTROL BOX ASSY. 240 VOLT MANUAL DRAIN (Export) 5 91 -8701 COMPLETE CONTROL BOX ASSY. 120 VOLT (For A-Plus w/Kettle) AUTO DRAIN 6 91 -8702 COMPLETE CONTROL BOX ASSY. 240 VOLT (For A-Plus w/Kettle) AUTO DRAIN 7 10-8411 PRESSURE SWITCH (CYCLE ON-OFF) E15-F15-PLS 91 -6085 8 10-8410 PRESSURE SWITCH (HIGH LIMIT CUT OFF) E15-H15-PLS Both Assy. 9 08-4821 WATER SOLENOID VALVE 120 VOLT
10 08-4810 WATER SOLENOID VALVE 240 VOLT 11 08-4871 REMOVABLE STAINLESS STEEL STRAINER 12 10-4653 DRAIN CONDENSATE THERMOSTAT 13 10-5184 COMMON TERMINAL STRIP 14 10-4634 TIME DELAY RELAY 120 VOLT
15 10-6970 TIME DELAY RELAY 240 VOLT (Export) 16 10-6512 RELAY SOCKET 17 10-5484 HEAT SWITCH DPDT MOMENTARY 18 10-5022 WATER FILL SWITCH SPST 19 10-6169 PILOT LIGHT
21
Page 24
HEATING ELEMENTS
ITEM PART NO. VOLTAGE DESCRIPTION
1 08-6412 208 FIREBAR HEATING ELEMENT 208 VOLT 9KW 1 or 3 PH 2 08-6413 240 FIREBAR HEATING ELEMENT 240 VOLT 9KW 1 or 3 PH 3 08-6414 480 FIREBAR HEATING ELEMENT 480 VOLT 9KW 1 or 3 PH 4 08-6415 208 FIREBAR HEATING ELEMENT 208 VOLT 12KW 5 08-6416 240 FIREBAR HEATING ELEMENT 240 VOLT 12KW
6 08-6417 480 FIREBAR HEATING ELEMENT 480 VOLT 12KW 3 PH 7 08-6418 208 FIREBAR HEATING ELEMENT 208 VOLT 16KW Only 8 08-6419 240 FIREBAR HEATING ELEMENT 240 VOLT 16KW 9 08-6420 480 FIREBAR HEATING ELEMENT 480 VOLT 16KW
10 08-6421 208 FIREBAR HEATING ELEMENT 208 VOLT 14KW
22
Page 25
PLUMBING SECTION (LEFT SIDE VIEW)
ITEM# PART NO. DESCRIPTION
1 10-5869 WATER GAUGE GLASS (NOT INCLUDED IN ITEM #2) 2 10-4940 WATER GAUGE GLASS ASSY. 3 90-0039 RUBBER & BRASS WASHER (NOT SHOWN) 4 10-1311 DRAIN VALVE 120 VOLT 5 10-0864 DRAIN VALVE 240 VOLT (EXPORT) 6 08-4845 WATER FEED HOSE 7 08-4843 WATER FEED HOSE 8 08-1201 DRAIN HOSE
9 10-3661 10 10-3490 TEE, SIDE OUTLET 3/4" 11 91-3312 DRAIN SUB. ASSEMBLY
12 10-1025
MANUAL DRAIN VALVE 3/4"
UNION 90° ELBOW 3/4"
23
Page 26
ITEM# PART NO. DESCRIPTION
1 10-5945 CONTACTORS 30 AM P 115V 50/60 Hz 2 10-5944 CONTACTORS 40 AMP 115V 50/60 Hz 3 10-5943 CONTACTORS 40 AMP 240V 50/60 Hz (Export) 4 97-4617 TERMINAL BLOCK ASS'Y. 3-SECTION 5 97-4616 TERMINAL BLOCK ASS'Y. 4-SECTION (E xport) 6 08-6328 LIQUID LEVEL CONTROL BOARD 7 10-5570 TERMINAL BLOCK END SECTION (1) REQ'D
7A 10-5503 TERMINAL BLOCK CONTACT SECTIONS (2) REQ'D
8 91 -8666 CONTACTOR CONTROL BOX ASS'Y. 36, 42 & 48KW 3PH 8A 91 -8667 CONTACTOR CONTROL BOX ASS'Y. 36 & 48K W (Export) (4 Wire), 3PH 8B 91-8767 CONTACTOR CONTROL BOX ASS'Y. 18, 24 & 32KW, 3PH, 60 Hz (USA) 8C 91 -8768 CONTACTOR CONTROL BOX ASS'Y. 18KW 1 PH, 60 Hz (USA) 8D 91 -8769 CONTACTOR CONTROL BOX ASS'Y. (Export) 50 Hz, 18, 24, 32KW, 3PH, 4 Wire
REF 91 -8550 WIRING DIAGRAMS FOR 18, 24, 32, 42, & 48KW
9 10-4804 PRESSURE GAUGE
10 08-0034 ANODE (NOT SHOWN, INSIDE STEAM GENERATOR)
24
Page 27
REF: SMALL GENERATOR
WITH CONTACTOR BOX
ITEM # PART NO. DESCRIPTION
1 10-7974 SIGHT GLASS WINDOW 2 91 -3368 REFLECTOR
REF: LARGE GENERATOR
WITH CONTACTOR BOX
REF: ELECTRIC MODULAR BASE STEAM GENERATOR
FINAL ASSY. BOTH LARGE & SMALL
25
Loading...