24" BOILER BASE ................................................................... 14
PRESSURE SWITCH BOX, WITHOUT COVER......................................... 15
CONTROL BOX ASEMBLY, WITH & WITHOUT COVER ................................. 16
ELECTRIC BOILER, LEFT SIDE VIEW – 36” ........................................... 17
ELECTRIC BOILER, FRONT VIEW – 36” ............................................... 18
ELECTRIC BOILER, CONTACTOR BOX ............................................... 19
ELECTRIC BOILER, ELEMENTS ...................................................... 20
SEPTEMBER 2, 2014 2 M24E & M36E ELECTRIC BOILERS
GENERAL TROUBLESHOOTING
TROUBLEPOSSIBLE CAUSEREMEDY
Water does not enter the boiler.Water main shut-offTurn on
Power not reaching unitCheck main fuse or circuit
Probes dirtyRemove and clean
Water level control board defectiveRefer to test procedure in this manual
Solenoid valve defectiveIf 120V is veried at solenoid coil, but fails to
open, replace solenoid
Boiler fails to build up pressure
when water level is proper and
fuel switch is turned on.
Boiler fails to reach full operating
pressure of 5 lbs. or 15 lbs.
Water enters boiler very slowly.Dirty Strainer screen in solenoid valve.Clean or replace strainer screen, part no. 08-
Water level in gauge glass uctuates up and down.
Contactor chattersIncorrect supply voltage.Check to see that it matches it with coil contac-
15 lbs. safety valve blows off prematurely
Boiler build up to pressure, shuts
down and fails to come on
Check to see that circuit breaker in main is
turned on
Check to see that contactors are pulling inCheck continuity of coil, if open replace
Current ow is broken at water level control (ascertain with continuity check)
Current ow is broken at pressure control or
high limit control switches due to maladjustment
or defect (ascertain with continuity check)
Heating elements are defectiveReplace if continuity check through the circuit of
Pressure gauge reads inaccuratelyReplace
Pressure control and high limit control switches
are out of adjustment
Safety valve not seating properlyClean or replace
Contactor coils (one or both) not energizing and
closing circuit to the heating elements
Top shut off on water gauge is closed.Open
Dirty or worn contactor points.Clean or replace contactor
Weak coilReplace with correct voltage coil
Pressure set too highReadjust
Pressure gauge reads incorrectlyReplace
Mineral build-up or dirt on seat of valveClean
Weak spring valveReplace valve
High limit switch set too low or operating pressure control switch set too high
Check for voltage at terminal block
Check for voltage at L1 and L2, replace if defective
Readjust - to proper setting - refer to instructions for readjustment, replace if defective
each element shows defective
Follow instructions for readjusting or replace if
defective
Check - replace either contactor coils or complete contactor – if found defective. Measure
amperage at terminal block check to be sure
there is an even draw on all three phases - see
wiring diagrams for correct AMP draw. If uneven
or zero amperage draw is found on one of the
three phases, check for blown fuse. If fuse is
OK, shut off power, remove wires from heating
elements and run continuity check - replace if
defective.
4871.
tors
Follow instructions in this document for readjusting, or replace if defective
SEPTEMBER 2, 2014 3 M24E & M36E ELECTRIC BOILERS
GENERAL TROUBLESHOOTING
TROUBLEPOSSIBLE CAUSEREMEDY
Air vent leakingNot closingReplace
Cold water condenser does not
function
Product in cooker does not cook
properly on rst cycle, but cooks
alright after rst cycle is exhaust-
ed
Contactor chattersLow voltageCheck voltage condition. Check momentary
Welding or freezingAbnormal spike in currentCheck for grounds or shorts in system
Short contact button life and / or
overheating of contacts
Open circuitMechanical damageHandle and store carefully. Do not handle coils
Overheated CoilOver-voltage or high ambient temperatureCheck application and circuit
Main water line shut offTurn on
Thermostat defectiveReplace if defective
Tighten coil nutTighten coil nut
Check solenoid coil for continuity, if open replace
Air vent is closingReplace
Defective or incorrect coilReplace coil, rating of coil must match the line
Low voltage preventing magnet from sealingCorrect voltage condition
Short circuitRemove short fault and check to be sure fuse or
Filling or dressingDo not le silver tips. Rough spots or discolor-
Interrupting excessively high currentCheck for grounds, shorts or excessive current
Discolored contacts caused by insufcient contact pressure, loose connection, etc.
Dirt or foreign matter on contact surfaceClean with Acetone
Short circuitRemove fault and check to be sure fuse or
Burnt-out coil due to overvoltage or defectReplace coil
Wrong coilCheck rating (voltage and frequency) if incor-
Shorted turns causedReplace coil
Under voltage, failure of magnet to seal inCorrect system voltage. Install new coil
Check coil for continuity, if open replace
voltage dip during starting. Low voltage prevents magnet sealing. Check coil voltage rating
voltage
breaker size is correct
ation will not harm tips or impair their efciency
Check contact carrier for deformation or damage, clean and tighten connections
breaker size is correct
by the leads
rect, replace with proper coil
SEPTEMBER 2, 2014 4 M24E & M36E ELECTRIC BOILERS
PRESSURE ADJUSTMENT
OPERATING SWITCH
If boiler fails to maintain steam pressure in operating
range, pressure control switch may require adjustment.
1. Start boiler and allow pressure to build up to operating level - 15 PSI (1kg/cm²).
2. Check boiler pressure gauge. If gauge indicates 12
to 14 PSI, pressure control switches are properly adjusted.
3. If boiler does not come on when pressure gauge
reads 7 PSI and does not go off when pressure gauge
reads 14 PSI, proceed as follows:
Pressure Switch Adjustment
WARNING
Because power must be on to adjust pressure
switches, be sure to protect against electrical
shock.
1. Remove screw and lift front cover off control box.
HI LIMIT SWITCH
ter clockwise to lower actuation point. Switch should
be set so that boiler comes on when boiler pressure
gauge reads 12 PSI and goes off when gauge reads
14 PSI. Hi limit switch should be set so that boiler will
shut off if pressure reaches 15 PSI.
3. The actuation value (differential) is factory set and
cannot be changed.
4. The cold water condenser thermostat is preset at factory.
5. Repeat steps, 1, 2, and 3. If 12 to 14 PSI boiler pressure gauge reading is obtained during boiler operation, adjustment is correct. If proper adjustment cannot be made consult Trouble-Shooting Guide in this
manual.
6. After making adjustments, replace cover on pressure
switch box and screw.
2. Hand adjust operating pressure control switch and
high limit pressure control switch by turning adjusting nut (Knurled knob) clockwise to raise and coun-
SEPTEMBER 2, 2014 5 M24E & M36E ELECTRIC BOILERS
WATER CONTROL BOARD TESTING PROCEDURE
LED 1
LED 2
LED 3
RESET
LW2
GND
LW1
FW - HIGH
HTA NO
LO LITE (NC)
FW (NO)
L1
L2
This test procedure is to be used to determine if the control is working properly. It is not intended to determine why
the control may have failed.
If testing shows that the control is operating properly,
check all probe and solenoid wiring and the condition of
the electrodes in the steam chamber.
Contact the factory if the boiler still does not operate properly after completing the testing.
Tools Needed:
• Digital or Analog V-O-M meter.
• Alligator clip type test jumpers (2 sets min.).
Turn Off Power to Control:
• Use V-O-M to verify there is no power at terminals L
1 & L2.
• Use V-O-M to verify that there is no power at terminals ‘FW(NO)’, ‘LO LlTE(NC)’ & ‘HTR(NO)’. If there
is power at any of these terminals, you will need to
nd the source and turn it off.
Remove Wires from Probe and Relay Switch Terminals:
• DO NOT remove wires from L 1 & L2 terminals.
• Tag wires and remove from probe and relay contact
terminals including ‘GND’ terminal.
• Tag and remove wires from ‘RESET’ terminals.
• Connect jumper wire to both ’RESET’ terminals.
Turn Power On to Terminals L 1 & L2:
• ‘LED l’ should turn on.
• ‘LED 2’ should be off.
• ‘LED 3’ should be off.
• Use V-O-M to verify that there is power at ‘FW(NO)’
& ‘LO LlTE(NC)’ terminals and no power ‘HTR(NO)’
terminals
Test Feedwater Function:
• Connect jumper wire to ‘FW HIGH and ‘GND’ terminals.
• ‘LED l’ should turn off after a 10 second delay.
• Use V-O-M to verify that there is no power at the
‘FW (NO)’ terminal.
• Remove jumper from ‘FW HIGH’ and ‘GND’ terminals. . ‘LED l’ should turn on.
• Use V-O-M to verify that there is power at the
‘FW(NO)’ terminal.
SEPTEMBER 2, 2014 6 M24E & M36E ELECTRIC BOILERS
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.