Market Forge M24E Service Manual

M24E & M36E
ELECTRICALLY OPERATED BOILERS
PARTS AND SERVICE MANUAL
EFFECTIVE SEPTEMBER 2, 2014
The Company reserves the right to make substitution in the event that items specied are not available.
ERRORS: Descriptive and/or typographic errors are subject to correction.
44 Lakeside Avenue, Burlington, Vermont 05401 USA Telephone: (802) 658-6600 Fax: (802) 860-3732
MARKET FORGE INDUSTRIES
www.mi.com
P/N 14-0310 Rev A (9/14)
TABLE OF CONTENTS
GENERAL TROUBLESHOOTING .......................................................3
PRESSURE ADJUSTMENT .............................................................5
WATER CONTROL BOARD TESTING PROCEDURE .....................................6
WIRING DIAGRAMS
NEW GENERATION ELECTRIC BOILERS ...............................................8
18 KW, 24 KW ....................................................................... 10
36 KW, 42 KW, 48 KW ................................................................ 12
36 KW, 48 KW ....................................................................... 13
ILLUSTRATED PARTS LIST
24" BOILER BASE ................................................................... 14
PRESSURE SWITCH BOX, WITHOUT COVER......................................... 15
CONTROL BOX ASEMBLY, WITH & WITHOUT COVER ................................. 16
ELECTRIC BOILER, LEFT SIDE VIEW – 36” ........................................... 17
ELECTRIC BOILER, FRONT VIEW – 36” ............................................... 18
ELECTRIC BOILER, CONTACTOR BOX ............................................... 19
ELECTRIC BOILER, ELEMENTS ...................................................... 20
SEPTEMBER 2, 2014 2 M24E & M36E ELECTRIC BOILERS
GENERAL TROUBLESHOOTING
TROUBLE POSSIBLE CAUSE REMEDY
Water does not enter the boiler. Water main shut-off Turn on
Power not reaching unit Check main fuse or circuit
Probes dirty Remove and clean
Water level control board defective Refer to test procedure in this manual
Solenoid valve defective If 120V is veried at solenoid coil, but fails to
open, replace solenoid
Boiler fails to build up pressure when water level is proper and fuel switch is turned on.
Boiler fails to reach full operating pressure of 5 lbs. or 15 lbs.
Water enters boiler very slowly. Dirty Strainer screen in solenoid valve. Clean or replace strainer screen, part no. 08-
Water level in gauge glass uctu­ates up and down.
Contactor chatters Incorrect supply voltage. Check to see that it matches it with coil contac-
15 lbs. safety valve blows off pre­maturely
Boiler build up to pressure, shuts down and fails to come on
Check to see that circuit breaker in main is turned on
Check to see that contactors are pulling in Check continuity of coil, if open replace
Current ow is broken at water level control (as­certain with continuity check)
Current ow is broken at pressure control or
high limit control switches due to maladjustment or defect (ascertain with continuity check)
Heating elements are defective Replace if continuity check through the circuit of
Pressure gauge reads inaccurately Replace
Pressure control and high limit control switches are out of adjustment
Safety valve not seating properly Clean or replace
Contactor coils (one or both) not energizing and closing circuit to the heating elements
Top shut off on water gauge is closed. Open
Dirty or worn contactor points. Clean or replace contactor
Weak coil Replace with correct voltage coil
Pressure set too high Readjust
Pressure gauge reads incorrectly Replace
Mineral build-up or dirt on seat of valve Clean
Weak spring valve Replace valve
High limit switch set too low or operating pres­sure control switch set too high
Check for voltage at terminal block
Check for voltage at L1 and L2, replace if de­fective
Readjust - to proper setting - refer to instruc­tions for readjustment, replace if defective
each element shows defective
Follow instructions for readjusting or replace if defective
Check - replace either contactor coils or com­plete contactor – if found defective. Measure amperage at terminal block check to be sure there is an even draw on all three phases - see wiring diagrams for correct AMP draw. If uneven or zero amperage draw is found on one of the three phases, check for blown fuse. If fuse is OK, shut off power, remove wires from heating elements and run continuity check - replace if defective.
4871.
tors
Follow instructions in this document for read­justing, or replace if defective
SEPTEMBER 2, 2014 3 M24E & M36E ELECTRIC BOILERS
GENERAL TROUBLESHOOTING
TROUBLE POSSIBLE CAUSE REMEDY
Air vent leaking Not closing Replace
Cold water condenser does not function
Product in cooker does not cook
properly on rst cycle, but cooks alright after rst cycle is exhaust-
ed
Contactor chatters Low voltage Check voltage condition. Check momentary
Welding or freezing Abnormal spike in current Check for grounds or shorts in system
Short contact button life and / or overheating of contacts
Open circuit Mechanical damage Handle and store carefully. Do not handle coils
Overheated Coil Over-voltage or high ambient temperature Check application and circuit
Main water line shut off Turn on
Thermostat defective Replace if defective
Tighten coil nut Tighten coil nut
Check solenoid coil for continuity, if open re­place
Air vent is closing Replace
Defective or incorrect coil Replace coil, rating of coil must match the line
Low voltage preventing magnet from sealing Correct voltage condition
Short circuit Remove short fault and check to be sure fuse or
Filling or dressing Do not le silver tips. Rough spots or discolor-
Interrupting excessively high current Check for grounds, shorts or excessive current
Discolored contacts caused by insufcient con­tact pressure, loose connection, etc.
Dirt or foreign matter on contact surface Clean with Acetone
Short circuit Remove fault and check to be sure fuse or
Burnt-out coil due to overvoltage or defect Replace coil
Wrong coil Check rating (voltage and frequency) if incor-
Shorted turns caused Replace coil
Under voltage, failure of magnet to seal in Correct system voltage. Install new coil
Check coil for continuity, if open replace
voltage dip during starting. Low voltage pre­vents magnet sealing. Check coil voltage rating
voltage
breaker size is correct
ation will not harm tips or impair their efciency
Check contact carrier for deformation or dam­age, clean and tighten connections
breaker size is correct
by the leads
rect, replace with proper coil
SEPTEMBER 2, 2014 4 M24E & M36E ELECTRIC BOILERS
PRESSURE ADJUSTMENT
OPERATING SWITCH
If boiler fails to maintain steam pressure in operating range, pressure control switch may require adjustment.
1. Start boiler and allow pressure to build up to operat­ing level - 15 PSI (1kg/cm²).
2. Check boiler pressure gauge. If gauge indicates 12 to 14 PSI, pressure control switches are properly ad­justed.
3. If boiler does not come on when pressure gauge reads 7 PSI and does not go off when pressure gauge reads 14 PSI, proceed as follows:
Pressure Switch Adjustment
WARNING
Because power must be on to adjust pressure switches, be sure to protect against electrical shock.
1. Remove screw and lift front cover off control box.
HI LIMIT SWITCH
ter clockwise to lower actuation point. Switch should be set so that boiler comes on when boiler pressure gauge reads 12 PSI and goes off when gauge reads 14 PSI. Hi limit switch should be set so that boiler will shut off if pressure reaches 15 PSI.
3. The actuation value (differential) is factory set and cannot be changed.
4. The cold water condenser thermostat is preset at fac­tory.
5. Repeat steps, 1, 2, and 3. If 12 to 14 PSI boiler pres­sure gauge reading is obtained during boiler opera­tion, adjustment is correct. If proper adjustment can­not be made consult Trouble-Shooting Guide in this manual.
6. After making adjustments, replace cover on pressure switch box and screw.
2. Hand adjust operating pressure control switch and high limit pressure control switch by turning adjust­ing nut (Knurled knob) clockwise to raise and coun-
SEPTEMBER 2, 2014 5 M24E & M36E ELECTRIC BOILERS
WATER CONTROL BOARD TESTING PROCEDURE
LED 1
LED 2
LED 3
RESET
LW2
GND
LW1
FW - HIGH
HTA NO
LO LITE (NC)
FW (NO)
L1
L2
This test procedure is to be used to determine if the con­trol is working properly. It is not intended to determine why the control may have failed.
If testing shows that the control is operating properly, check all probe and solenoid wiring and the condition of the electrodes in the steam chamber.
Contact the factory if the boiler still does not operate prop­erly after completing the testing.
Tools Needed:
Digital or Analog V-O-M meter.
Alligator clip type test jumpers (2 sets min.).
Turn Off Power to Control:
Use V-O-M to verify there is no power at terminals L 1 & L2.
Use V-O-M to verify that there is no power at termi­nals ‘FW(NO)’, ‘LO LlTE(NC)’ & ‘HTR(NO)’. If there is power at any of these terminals, you will need to
nd the source and turn it off.
Remove Wires from Probe and Relay Switch Termi­nals:
DO NOT remove wires from L 1 & L2 terminals.
Tag wires and remove from probe and relay contact
terminals including ‘GND’ terminal.
Tag and remove wires from ‘RESET’ terminals.
Connect jumper wire to both ’RESET’ terminals.
Turn Power On to Terminals L 1 & L2:
‘LED l’ should turn on.
‘LED 2’ should be off.
‘LED 3’ should be off.
Use V-O-M to verify that there is power at ‘FW(NO)’
& ‘LO LlTE(NC)’ terminals and no power ‘HTR(NO)’ terminals
Test Feedwater Function:
Connect jumper wire to ‘FW HIGH and ‘GND’ termi­nals.
‘LED l’ should turn off after a 10 second delay.
Use V-O-M to verify that there is no power at the
‘FW (NO)’ terminal.
Remove jumper from ‘FW HIGH’ and ‘GND’ termi­nals. . ‘LED l’ should turn on.
Use V-O-M to verify that there is power at the ‘FW(NO)’ terminal.
SEPTEMBER 2, 2014 6 M24E & M36E ELECTRIC BOILERS
Loading...
+ 14 hidden pages