APRIL 6, 2016 2 F-PE, F-LE & FT-LE SERIES ELECTRIC KETTLES
MAINTENANCE
LOW WATER LEVEL
Proper water level must be maintained within the jacket
for the kettle to operate. Depletion of water may occur
from excessive opening of, or leakage through the safety
relief valve.
If water is below required operating level, either initially
at start-up or during use, the kettle will automatically shut
off, refuse to operate and the LOW WATER signal light
will come on.
In order for the kettle to operate, the following procedure
must be followed:
1. Trip the safety relief valve lever to relieve all pressure
from the kettle jacket.
2. At exterior rear of kettle jacket remove nut from Air
Vent.
3. Insert funnel into Air Vent opening and slowly add the
indicated amount of clean water for:
MODELSADD
20 & 25 gallon
30 gallon
40 gallon
60 gallon
80 gallon
100 gallon
140 ounces
(4.14 litres)
150 ounces
(4.44 litres)
220 ounces
(6.50 litres)
250 ounces
(7.39 litres)
330 ounces
(10.05 litres)
420 ounces
(12.42 litres)
IF COMPLETELY
EMPTY, ADD:
376 ounces
(11.12 litres)
504 ounces
(14.90 litres)
548 ounces
(16.20 litres)
586 ounces
(17.33 litres)
850 ounces
(25.12 litres)
1088 ounces
(32.17 litres)
4. Replace Air Vent nut.
5. Follow Air Venting Instructions below.
6. Continue normal Operating Procedure of kettle.
AIR VENTING INSTRUCTIONS
Periodically check Pressure Gauge when the kettle is
cold. Reading should be in (green) VACUUM zone between 20 to 25, otherwise air is present and efcient heating will not occur.
To remove air, set Thermostat Knob at 8 and heat empty
kettle until TEMPERATURE pilot light goes off.
Open Air Vent nut one full turn for 10 seconds to exhaust
air from kettle jacket. Close Air Vent nut.
SAFETY VALVE MAINTENANCE AND TESTING
CAUTION
Under normal operating conditions a “try lever
test” should be performed every two months.
Under severe service conditions, or if corrosion and/or deposits are noticed within the
valve body, testing must be performed more
often. A “try lever test” should also be performed at the end of any non-service period.
CAUTION
Hot, high pressure uid may be discharged
from body drain and vent during “try lever”
test. Care must be taken to avoid any bodily
contact.
CAUTION
High sound levels may be experienced during
“try lever” test. Wear proper safety equipment
and exercise extreme care! Test at, or near,
half of the operating pressure by holding the
test lever fully open for at least two seconds
to ush the valve seat free of sediment and
debris. Then release lever and permit the
valve to snap shut.
If lift lever does not activate, or there is no
evidence of discharge, turn off equipment immediately and contact a licensed contractor or
qualied service personnel.
APRIL 6, 2016 3 F-PE, F-LE & FT-LE SERIES ELECTRIC KETTLES
TROUBLESHOOTING
The table below gives information to assist service personnel in locating the general source of the problems, which occur
with the self-contained kettles. Before attempting to locate the source of difculty described, the technician should be familiar with basic functioning described in basic functioning under the introduction section.
PROBLEM (PROBABLE CAUSE)REMEDY
1. Indicator light fails to light with switch in ON position and thermostat dial set.
a. Power to kettle is OFF.
b. Kettle tilted (FT__LE Only).
c. Low water level in steam jacket, low water light on.
d. Indicator light burned out.
e. Faulty power switch.
f. Faulty thermostat.
g. Faulty tilt interlock switch of time delay (FT__LE Only).
h. Faulty level control.
i. Faulty wiring.
2. Kettle not hot enough to boil water with thermostat dial set at “10”.
a. Air in kettle jacket.
b. Faulty relief valve.
c. Burned out heating element.
a. Locate external circuit breaker shut-off for incoming
power and place in ON position.
b. Return to full vertical position.
c. Fill jacket.
d. Replace light.
e. Replace switch.
f. Replace thermostat.
g. Replace as required.
h. Replace control.
i. Inspect condition of wire and tightness of all connec-
tors. Correct as required.
a. Open bleed vent one full turn for 10 seconds and
close.
b. Replace valve.
c. Refer to #4. Heating Element Replacement.
3. Low water light on.
a. Low water level in jacket.
b. Defective level control.
4. Kettle hard to tilt (FT__LE models only).
a. Gears dry.
b. Worn trunnion bearings.
a. Fill jacket (refer to operating instructions).
b. Replace control.
a. Apply high quality bearing grease inside console.
b. Disassemble left and right side bearings and replace
as required.
APRIL 6, 2016 4 F-PE, F-LE & FT-LE SERIES ELECTRIC KETTLES
REPAIR AND REPLACEMENT
#1 GENERAL
In the parts section of this manual contains a listing of
alI replaceable parts and associated illustrations of the
kettle. Disassembly procedures will be obvious from the
illustrations, When replacing probes or gauges in the
steam jacket, it is essential to install replacements so as
to obtain a pressure tight seal. Tape sealant should be
used.
#2 MODEL SERIES FT__LE DISASSEMBLY
All controls are accessed by lowering the kettle to the full
tilt position and removing screw and bottom cover. The
tilting gear mechanism is contained inside the console.
Removal of screw and console cover permits access to
gears for service and periodic application of gear grease.
#3 MODEL SERIES F-__PE DISASSEMBLY
To access controls, screw is removed and bottom cover
F-__PE
1. Lay kettle on cover hinge.
2. Remove screws from both
halves of bottom cover.
3. Remove each cover half
separately,
4. Remove nuts from element
5. Remove element.
6. Install new element.
7. Reverse steps 1-4.
F-__LE
1. Lay kettle on cover hinge.
2. Remove anged foot from each leg.
3. Remove screws from bottom cover.
4. Remove cover.
5. Remove, nuts from element.
6. Remove element.
7. Install new element.
8. Reverse steps 1-5.
is slid down to the oor, Repair and testing of contactors
and water level contactors assisted by loosening the separate mounting plate for these components. For all other
controls, it is necessary to reach up inside the kettle.
NOTE: For more extensive repair, it is possible to disas-
semble the pedestal mounting and lift the kettle
off the base plate. After repairs are completed,
the base plate cover must be resealed to the oor
and the pedestal using Silicone sealant.
#4 HEATING ELEMENT REPLACEMENT
Heating elements are replaceable. The kettle is equipped
with three separate protective features – a low water level
control, a tilt shut-off switch and a thermostat control.
Defective elements are isolated by testing each element
with an ohmmeter. If a zero ohm reading cannot be obtained for any element, it is defective.
To replace defective element, proceed as follows:
FT__LE
1. Lay kettle on cover hinge (if so
equipped) or on rear of kettle.
2. Remove screws from bottom
cover.
3. Remove cover.
4. Remove nuts from element.
5. Remove element.
6. Install new element.
7. Reverse steps 1-4.
MODELSKWPHASE
20 gallon kettles12
30 gallon kettles15
40 gallon kettles2436758296358
60 gallon kettles2436758296358
80 gallon kettles2436758296358
F-100PE24
FT-100LE
Optional
F-100LE2436758296358
2436758296358
33391.679.439.750.145.9
1575025--
33429153229
1736332--
34237184037
111510050--
36758296358
280VAC
AMP
240VAC
AMP
480VAC
AMP
220/380VAC
AMP
240/415VAC
AMP
APRIL 6, 2016 5 F-PE, F-LE & FT-LE SERIES ELECTRIC KETTLES
KETTLE
APRIL 6, 2016 6 F-PE, F-LE & FT-LE SERIES ELECTRIC KETTLES
KETTLE
ITEMPART NO.DESCRIPTION
20304060/80100
197-6392Hex Bolt, 5/16 - 18 x 3/4"44444
**297-5019Element Assembly, 208V, 12 kW1
97-5020Element Assembly, 220/380V, 12 kW1
97-5021Element Assembly, 240/416V, 12 kW1
97-5022Element Assembly, 480V, 12 kW1
--Element Assembly, 600V, 12 kW1
97-5033Element Assembly, 208V, 15 kW1
97-5034Element Assembly, 220/380V, 15 kW1
97-5035Element Assembly, 240/416V, 15 kW1
97-5036Element Assembly, 480V, 15 kW1
--Element Assembly, 600V, 15 kW1
97-5037Element Assembly, 208V, 18 kW11
97-5038Element Assembly, 220/380V, 18 kW11
97-5039Element Assembly, 240/416V, 18 kW11
97-5040Element Assembly, 480V, 18 kW11
--Element Assembly, 600V, 18 kW11
97-5127Element Assembly, 208V, 24 kW11
--Element Assembly, 220/380V, 24 kW111
97-5128Element Assembly, 240/416V, 24 kW111
97-5130Element Assembly, 480V, 24 kW111
--Element Assembly, 600V, 24 kW111
97-5893Element Assembly, 208V, 33 kW111
--Element Assembly, 220/380V, 33 kW111
--Element Assembly, 240/416V, 33 kW111
97-5876Element Assembly, 480V, 33 kW111
--Element Assembly, 600V, 33 kW111
** SELECT AS REQUIRED
QUANTITY
ITEMPART NO.DESCRIPTIONQTY
397-5025Element Gasket
497-6513Power Switch
5--Pilot Light - Low Water
6--Pilot Light - Temperature1
797-5339Dial1
897-5012Bezel1
9--Thermostat1
1097-5620“O” Ring1
1197-5002Pressure Gauge1
APRIL 6, 2016 7 F-PE, F-LE & FT-LE SERIES ELECTRIC KETTLES