Market Forge F-100LF Service Manual

Page 1
SERVICE & PARTS MANUAL
Models:
Direct Connected Steam Jacketed Kettles
Table-Top
Tilting
Page 2
TABLE OF CONTENTS
…………………...
2.2.1
Table
-
Top Kettles
......…………………......
2-1
Paragraph Page Paragraph Page
SECTION 1 INTRODUCTION
1.1 Description ……............……………….... 1-1
1.1.1 Table-Top Kettles............……………….. 1-1 4.2 Preventive Maintenance.………..……………...... 4-1
1.1.2 Stationary Kettles ........………………….. 1-1
1.1.3 Tilting Kettles .......….…………………...... 1-2
1.2 Service ..................………………………... 1-2 4.3.1 Draw-off Valve Repairs .......……………………... 4-1
SECTION 2 INSTALLATION
2.1 Receiving ..................……………………….. 2-1
2.2 Installation. ............………………………...... 2-1 5.2 Ordering Information ………………………….......... 5-1
2.2.2 Leg Mounted Kettles....………………...... 2-1
2.2.3 Pedestal Mounted Kettles ……………..... 2-2
2.3 Installation Check-Out ....………………….. 2-3
2.3.1 Stationary & Table-Top Kettles ………... 2-3
2.3.2 Tilting Kettles ..........…………………...... 2-3
SECTION 3 OPERATION
3.1 Operation ...........………………………....... 3-1
3.2 Cleaning Procedure.........…………..…….. 3-1
Figure Page Figure Page SECTION 2 INSTALLATION SECTION 5 ILLUSTRATED PARTS LIST
2-1 2-2 2-3 2-4
Table-Top Kettle Mounting .....….. 2-1 5-1 Tilting Kettle Components .....………….. 5-2
Flange Detail — Leg Mounting .... 2-2
Pedestal Assembly ......……......... 2-2
Pedestal Sealing .............……….. 2-3
LIST OF ILLUSTRATIONS
SECTION 4 MAINTENANCE
4.1 General .....................……….……………………. 4-1
4.2.1 Tilting Mechanism Lubrication
4.3 Repair and Replacement .………………………..
SECTION 5 ILLUSTRATED PARTS LISTS
5.1 General ...................……………………………….... 5-1
4-1 4-1
LIST OF TABLES
Table Page Table Page
SECTION 5 ILLUSTRATED PARTS LIST
Tilting Kettle Components ....…... 5-2 5-3 Cover Components ...........…………………. 5-3 5-1
5-2
Draw-off Valve Components ....... 5-3
iii
Page 3
A-1
APPENDIX A
STEAM INPUT REQUIREMENTS OF DIRECT CONNECTED KETTLES
The table below lists recommended delivered boiler horsepower for each kettle, and includes conversions to steam flow expressed in pounds of steam per hour. The required delivered steam pressure for all kettles is 15 PSI (7 kg/cm2}.
KETTLE MODEL
FT-5, LFT-5 5 19 .32 11
FT-10, LFT-10 10 38 .64 21.9
F-20L, F-20P, FT-20L, FT-20P, FT-20LV, FT­20PV
F-30L, F-30P, FT-30L, FT-30P, FT-30LV, FT­30PV
F-30LF, F-30PF 30 114 3.82 131.7
F-40L, F-40P, FT-40L, FT-40P, FT-40LV, FT­40PV
F-40PF, F-40LF 40 152 5.09 175.6
CAPACITY
gals. liters
20 76 1.27 43.9
30 114 1.91 65.9
40 152 2.49 85.9
DELIVERED
BOILER HP
STEAM FLOW
(Ibs./hr)
F-60L, F-60P, FT-60L, FT-60P, FT-60LV, FT­60PV
F-60LF, F-60PF 60 227 6.36 219.5
F-80L, F-80P, FT-80L, FT-80P, FT-80LV, F-80PV
F-80LF, F-80PF 80 303 7.95 274
F-100L, F-100P, FT-100L, FT-100P, FT-100LV, FT-100PV
F-100LF, F-100PF 100 379 9.54 329
F-125L, F-125P 125 474 7.95 274
F-150L, F-150P 150 565 9.54 329
60 227 3.82 131.7
80 303 5.09 175.6
100 379 6.36 219.5
S-2209
Page 4
SECTION 1 INTRODUCTION
1-1
S-2209
This service and pa
rts manual contains general information, installation, operating, trouble
-
shoot
ing, and
maintenance information for the Market Forge direct connected steam jacketed kettle. Also included are parts
lists, with accompanying diagrams showing each replaceable part.
1.1 DESCRIPTION
The Market Forge direct connected steam jacketed kettle is a steam operated pressure ves ­sel designed for cooking. It consists of a stain less steel kettle with double-wall construction, forming a surrounding chamber around the lower 2/3 of the kettle into which steam is intro­duced as a source of heat for cooking. Steam in­put plumbing is equipped with a manual control valve. Units are supplied mounted on legs or a pedestal base, in tilting and stationary models, and in capacities ranging from 5 to 150 gallons (19 to 565 liters). Safety valves are standard on all units except table-top models, on which a safety valve is optional.
1.1.1. Table-Top Kettles
Table-top kettles are available in 5 to 10 gal lon (19 and 38 liter) capacities, and are mounted in trunnion assemblies which must be mounted to a cabinet top. The trunnion pivots contain steam input and return connections. Tilting is accomplished manually by pulling a handle af fixed to the kettle rim to rotate the kettle in its trunnion mounts. Applicable model designations include: FT-5 [5 gallon (19 liter) capacity] FT-10 [10 gallon (38 liter) capacity]
1.1.2 Stationary Kettles
These units consist of larger capacity kettles
mounted in fixed position on legs or pedestal bases. They are equipped with tangent draw-off valves for the removal of kettle contents. Hinged, self-leveling, counterbalanced lids cover the kettle openings. Units are available with a steam jacket around the lower 2/3 of the kettle surface ("2/3 jacketed") or around the entire kettle sur face ("full jacketed"). Applicable model designations include:
F -30PF. F-40PF. F-60PF. F-80PF. F-100PF:
Pedestal mounted, full jacketed, stationary kettles of 30, 40, 60, 80, 100 gallon (114, 152, 227, 303, 379 liter) capacity.
F -30LF, F-40LF. F-60LF. F-80LF. F-100LF:
Leg mounted, full jacketed stationary kettles of
30. 40, 60, 80, 100 gallon (114, 152, 227. 303, 379 liter) capacit y.
F -20P. F-30P, F-40P. F-60P. F-80P. F-100P, F -125P. F-150P:
Pedestal mounted, 2/3 jacketed stationary ket tles of 20, 30, 40. 60, 80, 100, 125, 150 gallon (76, 114, 152, 227, 303, 379, 474, 565 liter) capacity.
F -20L F-30L. F-40L F-60L. F-80L F-100L, F -125L F-150L:
Leg mounted, 2/3 jacketed stationary kettles of 20, 30. 40, 60, 80, 100, 125, 150 gallon (76,114,
152, 227, 303, 379, 474, 565 liter) capacity.
Page 5
30, 40, 60, 80, 100
gallon
(76, 114, 152,227,
40. 60, 80, 100
gallon
(76, 114, 152,227,
1-2 DIRECT CONNECTED KETTLE
1.1.3 Tilting Kettles
These units consist of larger capacity kettles mounted on legs or pedestal bases, suspended from trunnion mounts, and fitted with heavy duty tilting mechanisms operated by manually turning a ha ndwheel. A drain valve in the bottom of the jacket permits removal of excess conden-sate.
Applicable model designations include:
FT-20L FT-30L FT-40L, FT-60L. FT-80L FT-100L:
Leg mounted, 2/3 jacketed tilting kettles of 20, 30, 40, 60, 80, 100 gallon (76, 114, 152, 227, 303, 379 liter) capacity.
FT-20P. FT-30P, FT-40P, FT-60P. FT-80P, FT-100P:
Pedestal mounted, 2/3 jacketed tilting kettles of 20,
FT-20PV, FT-30PV, FT-40PV. FT-60PV, FT-80PV. FT­100PV:
Pedestal mounted, 2/3 jacketed tilting kettles of 20, 30, 303, 379 liter) capacity, equipped with integral steam
trap, check valve, and blow-down tube on safety valve.
1.2 SERVICE
Required service, both preventive and corrective, is explained in Section 3. Should repairs be required, a network of authorized agencies is available to assist with prompt service. A current directory of Authorized Service Agencies may be obtained by contacting:
Product Service Department Market
Forge 35 Garvey Street Everett,
Massachusetts 02149 Telephone:
303, 379 liter) capacity.
FT-20LV, FT-30LV, FT-40LV. FT-60LV. FT-80LV. FT-100LV:
Leg mounted, 2/3 jacketed tilting kettles of 20, 30, 40, 60, 80, 100 gallon (76, 114, 152, 227, 303, 379 liter) capacity, equipped with integral steam trap, check valve, and blow-down tube on safety valve.
(617) 387-4100
Product Service Department Market Forge
Canada Ltd. 1375 Aimco Blvd., Unit 5
Mississauga, Ontario, Canada L4W 1B5
Telephone: (416) 621-9252 The model and serial numbers must be referenced
when corresponding with Market Forge.
S-2209
Page 6
SECTION 2 INSTALLATION
POUR
2.2.2
Leg
-
Mounted Kettles
2.1 RECEIVING
The kettle is shipped strapped and bolted to a skid and covered in most cases by a carton which is nailed to the skid; these must be carefully removed prior to installation. Inspect each unit carefully. If any damage has been incurred during shipment, report same within 2 days to both the carrier and Market Forge.
boiler DOES provide for condensate return. both a Vz" {13mm) steam trap and a W {13mm} check valve must be installed.
2.2 INSTALLATION
2.2.1 Table-Top Kettles
1. Make W (19mm) holes for kettle legs on cabinet top using a knockout punch. Locate holes at least 15" {381mm} from rear wall for FT-5 and 16" {406mm) from rear wall for FT-10. See Figure 1.
2. Remove mounting locknuts from kettle legs and install in proposed location.
3. Replace the locknuts, fastening down until hand tight. Place a level on the kettle rim. If the unit is level, tighten locknuts. If not, level cabinet top before tightening locknuts.
4. Install service connections to tagged locations, i.e. steam in, condensate return, as required. (The steam inlet is at the right side of the kettle seen from front).
NOTE
Service lines to kettle should be clean and checked for foreign matter before final hook -up to kettle, and be installed by qualified personnel.
PATH
NOTE
If the steam boiler to which this kettle isto be installed does NOT providefor condensate return, a Vi" {13mm} steam trap must be installed in lieu of a return line. If the
1. Level the unit in proposed location by turning the adjustable flanged feet. The location selected should provide drainage as close to the drain valve (if supplied) as possible.
2. Install unit using 5/16" lag bolts and shields (by others), 3 bolts per foot. See Figure 2-2.
2-1 S-2209
Page 7
2-2 DIRECT CONNECTED KETTLE
Figure 2-2 Flange Detail — Leg Mounting
3. Install service connections, i.e. steam in, condensate return, to tagged locations as required.
NOTE
Service lines to kettle should be clean and checked for foreign matter before final hook -up to kettle, and be installed by qualified personnel.
NOTE
If the steam boiler to which this kettle is to be connected does NOT provide for condensate return, a steam trap must be installed in lieu of a return line. If the boiler DOES provide for condensate return, both a steam trap and check valve must be installed in the return line.
2.2.3 Pedestal Mounted Kettles
1. Lay the kettle on its side on a cushioned surface to prevent scratching, and slide the base collar up the pedestal to expose the plate for removal. See Figure 2-3.
2. Remove the four cap screws securing the plate and slide it off the pedestal.
3. Prepare location by installing a %" (19mm} cast-in stud at the plate center point.
S-2209
Figure 2-3 Pedestal Assembly
NOTE
A W (19mm) bolt and shield may be substituted for a cast-in stud. The shield is installed in the floor and the lag bolt threaded down through the base plate after completion of Step 5.
4. Thread the four %" (10mm} leveling bolts into the plate from the top and insert the plate over the stud.
5. Adjust the bolts until the plate is level.
6. Install a nut on the W (19mm} bolt (insert lag bolt if alternate fastener is used) and secure plate to floor.
7. Check for level "set" of kettle by placing ket tle on base-plate with screw holes aligned and applying a carpenter's level at the kettle rim. If the kettle is level, it can be fastened in plate with the four cap screws. If not, the ket tle must be removed from the base, the plate loosened, and leveling bolts readjusted until level installation is attained.
Page 8
2.
3.
4.
3.
4.
5.
6.
7.
INSTALLATION
8. Slide base collar down to floor and seal top and bottom using silicone sealant. See Figure 2-4.
Turn steam supply valve on slowly. Pull safety valve lever. Observe that steam escapes freely.
2-3
9. Install service connections, i.e. steam in, condensate return, as required.
NOTE
Service lines to kettle should be clean and checked for foreign matter before final hook-up to kettle, and be installed by qualified personnel.
NOTE
If the steam boiler to which this kettle is to be connected does NOT provide for condensate return, a steam trap must be installed in lieu of a return line. If the boiler DOES provide for condensate return, both a steam trap and check valve must be installed in the return line.
2.3 INSTALLATION CHECK-OUT
2.3.1 Stationary and Table-Top Kettles
1. Fill kettle part way with water.
Avoid valve outlet when operating safety valve.
Observe that water comes to a boil in the ket ­tle. Allow approximately 2 to 5 minutes per
gallon of water.
2.3.2 Tilting Kettles
1. Fill kettle part way with water.
2. Open the petcock in the bottom of the jacket.
Use care in opening and closing petcock when steam is in jacket. Turn steam supply valve on slowly.
Allow steam to circulate in the jacket. This will cause a large amount of condensate to form, which will drain out of the bottom pet cock. When live steam starts to emit, close the pet cock. Pull safety valve lever. Observe that steam
es capes freely.
Avoid valve outlet when operating safety valve. Observe that water comes to a boil in the ket
tle. Allow approximately 2 to 5 minutes per gallon of water.
WARNING
WARNING
WARNING
S-2209
Page 9
SECTION 3 OPERATION
Wash kettle and cover (if supplied) with mild
lon
brush. If food is stuck to the surface, soak, using a
3.1 OPERATING PROCEDURE
1. Ensure that steam supply to kettle is operat - ing.
2. Ensure that draw-off valve (if supplied) is tightly closed.
3. If draw-off valve is supplied, place solid disc or perforated disc in kettle depending on whether liquid is to be retained or drained.
4. Fill kettle with product to desired level.
5. Turn steam control valve on (counter-clock wise) to full open position.
6. When product has reached desired tempera ture, regulate heat as needed by turning
valve clockwise.
7. When product is cooked, close steam control valve and remove product from kettle im- mediately to prevent overcooking.
3.2 CLEANSlNG PROCEDURE
As with cleaning food soil from any cook- ware, an important part of kettle cleaning is to
prevent foods from drying on. For this reason, cleaning should be completed immediately after cooked foods are removed. If time cannot be al-
lotted for immediate thorough cleaning, fill the
kettle with warm water and a mild detergent.
1. detergent and lukewarm water, using a ny
little heat to loosen the food.
NOTE
NEVER use ordinary steel wool, or a steel scraper of any description.
2. Drain the kettle and remove the disc in the draw-
off valve (if supplied). Rinse and dry.
3. If draw-off valve is supplied, it must be taken
apart and cleaned. a) Turn the handle counter-clockwise. b) Loosen the hex nut on the end of the handle
by turning it counter-clockwise. c) Remove the valve carefully. d) Wash the draw-off valve area thoroughly,
using a nylon brush. e) Rinse and dry.
3-1
Page 10
SECTION 4 MAINTENANCE
4-1 S-2209
4.1 GENERAL
This section contains both preventive and corrective maintenance information. Preventive
maintenance may be performed by maintenance personnel at the establishment in which the ket -
tle is installed. It is recommended that user per sonnel never attempt to make repairs or replace ment to the equipment without the assistance of authorized service. Assistance in service meth­ods or a current directory of Authorized Service
Agencies may be obtained by contacting Market Forge. See Subsection 1.2.
4.2 PREVENTIVE MAINTENANCE
The most important preventive maintenance operation on the steam jacketed kettle is the
cleaning procedure after each use detailed in Section 2. Additional preventive maintenance operations are presented in this section.
4.2.1 Tilting Mechanism Lubrication
Lubrication of the hand wheel tilting mech­anism on kettles so equipped is the only required
preventive maintenance other than daily clean­ing. Inspect the worm screw, tilting gears and bearings occasionally (at least once a year). Lu­bricate as required, using a graphite lubricant (part #10-3512) or equivalent.
4.3 REPAIR AND REPLACEMENT
In the event that the kettle fails to operate correctly, the difficulty should first be isolated to
either the kettle itself or its steam supply. While mechanical problems are obvious faults of the kettle, any deficiency in volume or pressure of steam should be traced to the steam generator
and the cause det ermined. Steam input require­ments are listed in Appendix A, Steam Input
Requirements of Direct Connected Kettles.
4.3.1 Draw-off Valve Repairs
4.3.1.1 Common Leak Repairs
To repair a valve leak, the source must first be determined. Leaks from around the valve
stem are corrected by replacing the "0" ring. Dripping from the valve outlet which occurs with the valve tightly closed indicates faulty seating of the valve disc against the valve seat. Dripping of this kind is often corrected by cleaning residue from disc and seat using very fine emery.
4.3.1 2 Valve Seat Lapping
Should either the disc or seat be found to be damaged, it is necessary to either replace the entire valve, or perform the lapping procedure as follows:
1. Disassemble the valve and clean both the disc and the valve seat.
2. Attach the handle to the stem with the valve bonnet removed.
3. Apply a good grade of fine lapping compound to the disc and insert it into the valve to make
light contact against the seat.
4. Rotate the stem disc against the seat by turn­ ing the handle, allowing the stem to wobble in the space normally occupied by the bon net. Continue with light pressure until com pound dries.
5. Reassemble and test for leaks with valve closed. If dripping occurs, repeat the lapping procedure as many times as required to ob­ tain a watertight seal.
Page 11
SECTION 5 ILLUSTRATED PARTS LISTS
5-1 S-2209
5.1 GENERAL
This section contains a complete listing of all
replaceable parts of direct connected steam jacketed
kettles.
5.2 ORDERING INFORMATION
Orders for repair parts should be directed to the nearest authorized part s distributor. For a current Market Forge Authorized Parts Distributor list, contact:
Product Service Department Market Forge 35 Garvey Street Everett, Massachusetts 02149 Telephone:
(617) 387-4100
Product Service Department Market Forge Canada, Ltd. 1375 Aimco Blvd., Unit 5
Mississauga, Ontario, Canada L4W 1B5
All orders should contain the Market Forge part
number, the part description, and the model and serial
number of the kettle for which the part is ordered.
Page 12
FIG. 5-1
ITEM NO. PART NO. DESCRIPTION
1 20-0035 Worm Gear 2 10-0200 Trunnion '0' Rings
3 10-4755 Steam Trap 4 20-01 22 'Y' Strainer 5 20-0119 Check Valve 6 20-0024 Handwheel 7 20-0131 Bearing, Bronze 8 20-01 34 Bearing, Thrust
9 20-0221 C-Clips 10 20-0033 Worm 11 20-0036 Worm Locking Key
12 10-3661 Steam Control Valve
13A 20-0207 Shaft. 20 Gallon Kettle
13B 20-0208 Shaft, 30 Gallon Kettle 13C 20-0026 Shaft, 40 Gallon Kettle 13D 20-0209 Shaft, 60 Gallon Kettle
13E 20-0210 Shaft, 80 Gallon Kettle
S-2209
Page 13
Faucet, 1 1/2
"
Valve
10-
4928
Hinged Cover:
20
gallon unit
20-
0160
ILLUSTRATED PARTS LIST
TABLE 5-2 DRAW -OFF VALVE COMPONENTS
DESCRIPTION PART NUMBER
Faucet, 2" Valve 20-0105 Faucet, 3" Valve 20-0106 Stem, 1 1/2" Valve 10-4967 Stem, 2" Valve 20-01 79 Stem, 3" Valve 20-0180 Nut, 1 1/2" Valve 10-4970 Nut, 2" Valve 20-01 90 Nut, 3" Valve 20-0191 Knob, 1 1/2" Valve 10-4971 Knob, 2" Valve 20-0192 Knob, 3" Valve 20-0193 Wing Nut, 1 1/2" Valve 10-4972 Knob Nut, 2" Valve 20-01 94 Knob Nut, 3" Valve 20-0195 Bonnet, 1 1/2" Valve 10-4968 Bonnet, 2" Valve 20-0196 Bonnet, 3" Valve 20-0197 "0" Ring, 1 1/2" Valve 10-4969 "0" Ring, 2" Valve 20-0198 "0" Ring, 3" Valve 20-0199 Drain Screen 1 1/2" Valve 20-0016 Drain Screen 2" Valve 20-0200 Drain Screen 3" Valve 20-0201
TABLE 5-3 COVER COMPONENTS
DESCRIPTION PART NUMBER
30 gallon unit 20-0161 40 gallon unit 20-0001 60 gallon unit 20-0162 80 gallon unit 20-0163 100 gallon unit 20-01 64 Lever for cover: 20 gallon unit 20-0165 30 gallon unit 20-0166 40 gallon unit 20-0003 60 gallon unit 20-0167 80 gallon unit 20-01 68
100 gallon unit 20-0169
S-2209
Loading...