Mark MEGAFLEX Technical Manual

Page 1
EN
1
Technical manual
MARK MEGAFLEX
0660440
Page 2
2
INSTRUCTIONS FOR USER
If you have questions concerning the use of your boiler or heating system, please ask your installer. It is in your own interest and that of the installer that you are aware of how to operate your boiler and heating
system safely and efciently.
The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge. Children, even if being supervised, must not play with the appliance
In the case of failure or malfunction of the appliance, do not attempt to repair it yourself.
Please contact your installer. Repairs must only be carried out by qualied technicians. Failure to
comply with these requirements can compromise the safety of the appliance.
Operation
Water, coming from the radiators or from the DHW unit is heated in the aluminium heat exchanger. The CH or DHW pump guarantees circulation of water. The air needed for combustion is sucked in by a rpm
controlled fan. At low boiler temperatures the ue gases can be cooled sufciently for condensation of
the water. This water is drained to the sewer via a built in syphon. This drainage must never be blocked. A burner controller with built in micro processor provides the electrical control of the boiler.
Topping up
The built in manometer indicates if the waterpressure is sufcient. As soon as the water pressure drops
below 1 bar topping up is necessary. If topping up becomes a regular ocurrance, your installation should be checked by an installer.
Disconnect from the main. Connect the lling hose to the cold water tap and to the ll and drain valve of the boiler. Before tightning the coupling in the installation slowly ll the hose with water allowing any air present to escape. Open the ll and drain valve and slowly ll the installation until a pressure between
1.5 and 2.0 bar is reached. When nished connect again to the main.
Bleeding
To remove any air present in the heating system and boiler, bleeding is necessary. Disconnect from the main. Open all the radiator valves. Bleed the air from all the radiators starting with the ones at the lowest point in the system. After bleeding, check the water pressure and top-up if required (if water pressure has dropped below 1 bar). Connect to the main again.
Starting the boiler
Please ask your installer how to start the boiler. Depending on how your heating system is controlled, this could be via an external timeclock, thermostat, switch or otherwise. Once the boiler volt-free enable contacts are closed, the boiler will commence its starting sequence.
Boiler ow temperature
The burner controller can adjust the ow temperature between 20 ° and 85 °C. The temperature setting
can be changed using the control panel.
The installation manual provides the instructions for setting the ow temperature.
DHW (Hot Water) temperature ( if applicable)
From the factory, the DHW temperature is set to a value of 60 °C. This set value can be changed to any value between 35 and 65 °C using the buttons on the control panel. If the DHW device has a thermostat
the DHW temperature can be adjusted by setting this thermostat.
Page 3
EN
3
Switching off the boiler
During summer time the room thermostat can be set to a lower value to turn off the boiler. During winter or during a longer period of absence this temperature never should be set to a lower value than
15 °C. Don’t switch off the power. During a period of frost all the radiators should be partly or totally
opened to avoid danger of freezing.
The integrated pump control will activate the pump every 24 hours for a short period even if no demand is present. This prevents the pump jamming. Only when work on the boiler is being carried out may the main electricity supply and gas supply be turned off (your installer can show where these are located).
Errors
If an error occurs rst check the following
• Is the room thermostat properly set?
• Is the boiler connected to the main? Power supply present?
• Is the gas valve opened?
• Are the radiator valves open?
• Is the water pressure in the installation higher than 1 bar?
• Is the installation bled thoroughly?
An error is indicated by a code on the display. It is very important for the sake of a correct diagnosis to mention this code when calling your installer. Reset the burner controller by pressing the ok button on the control panel. If the error occurs frequently contact your installer.
Maintenance
A yearly inspection of the boiler must be done by your installer. The lifespan and the reliability of the installation are improved by doing so.The casing of the boiler may be cleaned with a soft cloth (no abrasives). Never use solvents like thinner!
Caution
The air supply (for air needed for combustion) and the ue parts are essential parts for safe and efcient operation of the boiler. Changes on these systems by non qualied persons are not allowed e.g. the
settings of the gas valve. The gas/air ratio is set to a lambda value of approximately 1.26. This corresponds with a CO2 level of 9,3 % (full load).
For further information see installation manual.
Page 4
4
1 Description boiler 6
2 Technical data 9
2.1 Component Matrix 10
3 Dimensions 11
4 Operation 13
4.1 General 13
4.2 Central Heating (CH) 13
4.2.1 On-off room thermostat 13
4.2.2 Optional 0-10V 13
4.2.3 Outside Temperature Control OTC (optional) 14
4.2.4 Optional digital communication 14
4.2.5 Slow start 15
4.2.6 Protection against insufcient ow through boiler 15
4.3 Domestic Hot Water (DHW) 16
4.3.1 External storage tank (choice by manufacturer between opt. 1 and opt. 2) 16
4.3.2 External storage tank with NTC sensor 16
4.3.3 DHW priority/General behaviour with external storage tank 17
4.4 Cascade 17
5 Boiler control 18
5.1 Control Panel 18
5.2 Push buttons on control panel 18
5.3 User menu 19
5.3.1 Parameter/value setting 19
5.3.2 Parameters accessible by user 19
5.4 Installer (technician) menu 23
5.4.1 Parameters accessible by installer (technician) 23
5.5 Manual Chimney sweep mode 30
5.6 Disabling CH request 30
5.7 Service code 30
5.8 Tacho fan speed 30
5.9 Errors 30
5.10 ECO working mode 30
5.11 Holiday mode 30
5.12 Schedules for CH and DHW 30
5.13 Cascade and Modbus 30
5.14 Parameter settings 30
6 Installation 34
6.1 Installing the boiler 34
6.2 Frost protection 34
6.3 Water connection 35
6.3.1 Pump 35
6.3.2 Minimum ow 35
6.3.3 Water-treatment 35
6.3.3 Water connection general 35
6.4 Gas connection 37
Page 5
EN
5
6.5 Air-supply and ue-gas connection 37
6.5.1 B23 37
6.5.2 C33 37
6.5.3 C63 38
6.5.4 Pressure drop calculations 39
6.5.5 Installing ue-exhaust and air inlet 41
6.6 Electrical connection 43
6.6.1 Wiring diagram 45
6.6.2 NTC resistance table 47
6.7 Pneumatic connections 48
6.8 PC-connection 48
7 Commissioning 48
7.1 Gas category 48
7.2 Adjustment % CO2 (O2 %) and check input 50
8 Errors 51
8.1 General 53
8.2 DHW errors 53
8.3 CH-errors 53
8.4 Errors (hard and soft lockouts) 53
9 Annual service 55
9.1 Service-maintenance table 57
Page 6
6
1 DESCRIPTION BOILER
1 Manometer 2 Display LCD 3 Power switch 4 Fuse 5 Burnerhood
6 Sight glass 7 Flow NTC
8 Ignition electrode 9 Ionisation ame detector
10 Inspection cover
Page 7
EN
7
11 Gas pipe 12 Gas valve 13 Air supply 14 Fan 15 Overheat limiter 16 Flow 17 Flue gas NTC
18 Exhaust
19 Return 20 Maxsys 21 Terminal strip 22 Syphon pressure switch 23 Air pressure switch
Page 8
8
24 Sump inspection cover 25 Syphon 26 Fill and drain valve 27 Water pressure switch
28 Return NTC
29 Automatic air vent 30 Venturi
Page 9
EN
9
2 TECHNICAL DATA
Technical data Megaex series
Type 850-11 range rated 1020-13 range rated
Central heating
Nominal input max load (Hi) 850 680 1020 850 kW Power range percentage %
Manual technician menu advanced setting CH 100 75 100 80
Nominal input min load (Hi) 170 170 204 204 kW
Nominal ouput max load 80-60 °C 828,8 663 994,5 828,8 kW Nominal output min load 80-60°C 165,4 165,4 198,5 198,5 kW Efciency max load 80-60 °C (Hi) 97,5 97,5 97,5 97,5 % Efciency min load 80-60 °C (Hi) 97,3 97,3 97,3 97,3 % Efciency max load 50-30 °C (Hi) 103,1 103,1 103,1 103,1 % Efciency 30 % load 30 °C (return) (Hi) 108,3 108,3 108,3 108,3 %
Flue gas
Temperature ue gas max load 80-60 °C 65-70 65-70 65-70 65-70 °C Temperature ue gas min load 80-60 °C 60-65 60-65 60-65 60-65 °C Mass ow ue gases at max load 1221 977 1465 1221 m3/h Mass ow ue gases at min load 245 245 294 294 m3/h Maximum ue resistance 500 310 500 480 Pa
Emission CO 96 96 ppm Emission NOx class 6 6 6 6 Types B23,C33,C63 yes yes yes yes
Gas
Gas ow max load G25 104,5 83,6 125,4 104,5 m3/h Gas ow min load G25 21 21 25,1 25,1 m3/h Gas ow max load G25.3 99,9 79,9 119,8 99,9 m3/h Gas ow min load G25.3 20 20 24 24 m3/h Gas ow max load G20 90 72 108 90 m3/h Gas ow min load G20 18 18 21,6 21,6 m3/h
CO2 content max load G25/G20/G25.3 9,3 9,3 9,3 9,3 % CO2 content min load G25/G20/G25.3 9,1 9,1 9,1 9,1 % O2 content max load G25 3,90 +0,10-0,30 3,90 +0,10-0,30 % O2 content min load G25 4,30 +0,35-0,20 4,30 +0,35-0,20 % O2 content max load G25.3 3,95 +0,10-0,35 3,95 +0,10-0,35 % O2 content min load G25.3 4,35 +0,35-0,25 4,35 +0,35-0,25 % O2 content max load G20 4,25 +0,10-0,35 4,25 +0,10-0,35 % O2 content min load G20 4,60 +0,40-0,20 4,60 +0,40-0,20 %
Water
Maximum ow temperature 90 90 90 90 °C Content heat exchanger 100 118 ltr Minimum/maximum operating pressure 0,8/6 0,8/6 bar Hydraulic resistance 200 225 mbar
(DT 20 nominal ow at full load 80-60 °C) Maximum DT max load/min load 25/35 25/35 25/35 25/35 °C Maximum water ow DT 10 K 71,3 57 85,6 71,3 m3/h
Page 10
10
Weight
Mass heat exchanger* 348,4 412,6 kg Total mass Megaex boiler kg
Sizes of casing
Width 877 877 877 877 mm Depth without manifold ange 2096 2096 mm
Height excluding feet 1551 1551 1551 1551 mm
Electrical
Electrical voltage/frequency 400V~3N/50 400V~3N/50 V/Hz Standby power consumption* 15 15 15 15 W Min load power consumption* W Max load power consumption* W Maximum allowable power consumption 6900 6900 W Fuse 400V~3N/10 400V~3N/10 V/A
* as coming from factory without extra devices connected
2.1 COMPONENT MATRIX
Overview of main components used in MegaFlex series
Part 850-11 1020-13
Boiler control Honeywell Maxsys S4966V2052 S4966V2052 Display (user interface) DSP 49G2193 DSP 49G2193 2 Line EMC Filter 250 V EPCOS B84112G Fan MVL 230 VAC G3G250MW5001 G3G250250MW5001 Gas-valve Dungs 230 VAC MBC-700-SE-S02 MBC-1200-SE-S02 Venturi type DT DT850 DT1020 Texi Burner round 140 mm Worgas 1011 1200
Silencer ue-gas round 250 mm L=500mm yes yes NTC-12k, L=50 mm x D5 , ¼” BSP 3 3
NTC 12 k OTC optional optional Water low pressure device 1,4/0,8 bar yes yes Pressure difference switch 40 Pa in and 25 Pa out yes yes Syphon pressure difference switch 15 mbar out yes yes Gas pressure switch : in 11,7-14,3 and out 8,6-11,4 mbar yes yes
Page 11
EN
11
3 DIMENSIONS
Page 12
12
The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge. Children, even if being supervised, must not play with the appliance.
In the case of failure or malfunction of the appliance, do not attempt to repair it
yourself. Please contact your installer. Repairs must only be carried out by qualied technicians.
Failure to comply with these requirements can compromise the safety of the appliance.
Page 13
EN
13
4 OPERATION
4.1 General
The Megaex is a oor standing boiler, equipped with a cast aluminium heat-exchanger. During heat
demand the controller activates the pump. The controller checks the air pressure switch (zero check)
and increases the fan speed to perform an airow-check. Once the air pressure switch closes, the fan
speed increases to ignition speed and a 5 second pre-purge is performed. The water pressure sensor, gas pressure switch and siphon pressure switch are checked. When all pressure switches are closed and the water pressure is ok, the ignition is started. The air needed for combustion is taken in from the outside (if room sealed) or the boiler house (type
B ue installation) by the fan. The air is transported through a gas/air mixing device creating a negative
pressure. This negative pressure is an indication of the amount of air being transported. The negative pressure is supplied to the gas valve by an internal tube. The gas valve automatically adjusts the amount
of gas that will be injected into the venturi and that will be mixed with the air-ow. This mixture is
supplied to the burner.
Ignition and ame-control of the mixture is done by two electrodes mounted on the burnerhood. Temperature control and safeguarding is done using two NTC’s. The boiler monitors the sensors
continuously in order to control operation and ensure safe operation.
4.2 Central Heating (CH)
4.2.1 On-off room thermostat
As standard the boiler is programmed for using an on-off room thermostat. The room thermostat has to be connected to the pin nrs. 1 + 2 on the terminal strip. Open Therm will be recognized if connected on
1 + 2. The desired ow temperature is adjustable, but as standard is set to 85 °C.
At CH heat request from the room thermostat (and no DHW heat request present) the CH-pump
is activated after 10 seconds. The controller will adjust the burner-input in such a way that a ow­temperature of 85 °C towards the CH-circuit is achieved.
Warning : do not supply any voltage to these terminals as you may damage the controller
4.2.2 Optional 0-10V
The boiler may be controlled using a 0-10 V DC signal. Connect the negative (0V DC) to No. 3, and the positive (0-10V DC) to No.4 on terminal strip C2. A loop of wire must be placed between the pin nrs. 1 and 2 of terminal strip C2. In the technician menu, enable 0-10V in the advanced CH settings menu by setting, CH request to either 0-10V DC % or 0-10V DC SP.
4.2.2.1 0-10V DC % power control
A value between 2 and 10V DC generates a CH power demand proportional to this value between 0
and 100% (0% = minimum load, 100% = nominal load). The heat demand is removed when the control
signal falls below 1 volt.
The setpoint of maximum ow temperature is set to 90°C.
In the user/technician menu, under diagnostics, boiler information the actual voltage input and target power are displayed.
4.2.2.2 0-10V DC Setpoint
A value between 2 and 10V DC generates a CH setpoint demand proportional to this value between
CH minimum ow temperature and maximum CH ow temperature. The heat demand is removed when
the control signal falls below 1 volt.
The minimum and maximum CH ow temperature can be set in the technician menu, advanced CH
settings, CH temperatures.
Page 14
14
In the user/technician menu, under diagnostics, boiler information the actual voltage input and boiler setpoint are displayed. Caution : Ensure that the 0-10V DC signal is free from electrical interference!
4.2.3 Outside Temperature Control OTC (optional)
The boiler may use an outdoor sensor to provide weather compensation (OTC). To activate weather compensation connect an oudoor sensor to numbers 5 and 6 on the terminal strip C2. Pin numbers 1 and 2 have to be bridged by a wire. Alternatively those pin numbers (1 and 2) can be used for connecting room thermostat on/off. In the technician menu, under advanced CH settings, CH request, OTC only must be selected. The outdoor sensor is then automatically detected by the
controller. The parameters corresponding with A-E in the gure below can be set in the technician menu
(advanced CH settings).
A OTC offset: minimum CH setpoint value B OTC setpoint maximum: maximum CH setpoint value C OTC weather cold: external temperature value at which the maximum CH value will be used. D OTC weather warm: external temperature value at which the minimum CH value will be used E OTC warm weather shutdown: external temperature value at which the CH demand will end
In the user menu an eco setpoint reduction (night reduction) can be set. Day, week and weekend options are also available (on, eco, off)
The outdoor sensor is available as an optional accessory.
The sensor should be installed on the north-side of the building at a height of approximately 2 meters.
Note: The resistance of the outdoor NTC should be 12 kOhm at 25 °C. Also see table of resistance for NTC’s at 6.6.2
4.2.4 Optional digital communication
The boiler supports digital communication with room thermostats using Open-Therm communication protocols (automatically recognised if connected to pins 1 + 2 on terminal strip C2, also see 4.2.1.)
Page 15
EN
15
4.2.5 Slow start
The boiler uses the “slow start” procedure to prevent the boiler from supplying excessive power in low
load situations.
After “zero check” APS and closure APS with pre purge ignition starts. Following, a stabilization period,
the boiler modulates down to low capacity and maintains this capacity for 1 minute. Subsequently the
boiler power increases at a target rate of 4°C/min until maximum capacity or set temperature has been reached. Once heat demand has nished the burner will turn off following a set post purge period.
The graph below illustrates this;
4.2.6 Protection against insufcient ow through boiler
When the requirements of 6.3.2 are fullled the boiler will protect itself against insufcient ow. This is done by checking the difference in temperature between ow and return (so called ΔT). In a low ow scenario the ΔT will rise rapidly. The ΔT safe-guarding principle is as follows ; At ΔT > 22 the boiler starts modulating At ΔT between 22 and 27 the boiler continues modulating At ΔT > 27 boiler the fan speed will reduce until ΔT < 25
Page 16
16
4.3 Domestic Hot Water (DHW)
4.3.1 External storage tank (choice to be made by manufacturer between option 1 and option 2)
4.3.1.1 Option 1. External storage tank with thermostat (hydraulic 3-way valve)
As standard the DHW conguration is factory pre-set for an external storage tank + tank thermostat.
For hydraulic connection of an external storage tank to the boiler one should either use :
the default conguration with 2 pumps: 230 VAC DHW pump (terminal strip C1:6,7,8) and CH pump (terminal strip C1: 9,10,11) or
a hydraulic 3-way valve (terminal strip C1: 6,7,8)
The 2 wires of the tank thermostat must be connected to numbers 7 and 8 on terminal strip C2.
In the case of using a hydraulic 3-way valve adjust setting in technician menu, system settings, boiler parameters, number of pumps to: pump and 3-way valve.
4.3.1.2 Option 2. External storage tank with thermostat (electric 3-way valve)*
As standard the DHW conguration is factory pre-set for an external storage tank + tank thermostat.
For hydraulic connection of an external storage tank to the boiler via an electric 3 way valve one should either use :
the default conguration 2 pumps: 230 VAC DHW pump (terminal strip C1: 6,7,8) and CH pump (terminal strip C1: 9,10,11)
an electric 3-way valve with a maximum travel time of 255 sec. (terminal strip C1: 6,7,8,9). At the end of the travel time in either direction DHW or CH the 230 VAC on the 3-way valve will be switched off.
The 2 wires of the tank thermostat must be connected to numbers 7 and 8 on terminal strip C2.
In the case of using an electric 3-way valve adjust the setting in the technician menu, system settings, boiler parameters, number of pumps to: pump and 3-way valve.
The 3-way valve travel time can be changed in the technician menu, system setting, boiler parameters, 3-way valve travel time.
*The 3-way valve can either be a hydraulic valve or an electric valve. This is an OEM factory setting and CAN NOT be changed from the (technician) menu. The default setting is a hydraulic 3-way valve
In case an electric 3-way valve should be the default one, please ask your OEM supplier for
the correcty settings
4.3.2 External storage tank with NTC sensor
In case the storage tank is equipped with an NTC sensor, adjust the setting in technician menu, advanced DHW settings, DHW request to sensor.
Note: The resistance of the NTC sensor must have a value of 12 kOhm at 25 °C. The 2 wires of the tank NTC sensor must be connected to numbers 7 and 8 on terminal strip C2.
Page 17
EN
17
The set point temperature of the storage tank is adjustable (default set at 60°C,the ow temperature is DHW setpoint + 20K). Warning : if a CH heat demand exists immediately after nishing the heat request for DHW, it is possible for high temperatures to ow into the CH system regardless of CH set point
(hot shot).
4.3.3 DHW priority/General behaviour with external storage tank
Disabling hot water operation: press Summer-Winter button R2-C4 (not active in main screen). See later in manual for further explanation.
Enabling hot water operation: press Summer-Winter button R2-C4 (active in main screen). See later in manual for further explanation.
In the default boiler conguration, (2 pumps-DHW and CH pump), a DHW request has priority over
CH request
In the technician menu, advanced DHW settings, DHW priority, the DHW priority over CH can either be disabled or a maximum DHW priority time may be set.
In the case where the DHW priority is disabled and both demands are active at the same, both pumps
(CH and DHW) will be activated. During this time the ow temperature is set to either 80 °C (tank thermostat) or DHW setpoint + 20K (NTC sensor).
Notice: At outputs ≥ 40 kW double separation between exchanging media is required.
4.4 Cascade
For cascade application see appendix “cascade”
Page 18
18
5 BOILER CONTROL
5.1 Control Panel
The control panel has 12 buttons and a display as shown in the gure below.
5.2 Push buttons on control panel
Description of push button use
R1-C1, R2-C1 and R3-C1 (back) buttons follow, if pressed, the associated icon in the display (left) R1-C2 and R3-C2 (up-down) buttons, scroll, if pressed, through the different menus
R2-C2 button conrms, if pressed, the highlighted selection, or conrms what is requiered by LCD
R1-C3 button (escape) returns, if pressed, to main screen R1-C4 (on-off) button puts boiler in off mode, main logo and date/time stay displayed R2-C3 (menu) button enables, if pressed, access to both user and installer menu R2-C4 (summer-winter) button enables-disables, if pressed, CH and DHW in main screens R3-C3 (holiday) button enables, if pressed, holiday function in main screens R3-C4 (eco) enables, if pressed, eco function in main screens
Page 19
EN
19
5.3 User menu
By pressing the “menu-button” the display will show the text as given in the gure below.
By pressing the button marked “3” in the gure above the user menu is accessed. Pressing the button marked “5” returns back to the main screen. By pressing the button marked “4” the installer menu is
accessed.
In the user menu the following options will be shown :
1. HEATING
2. DOMESTIC HOT WATER
3. HOLIDAY
4. MAINTENANCE
5. SETTINGS
6. CHIMNEY-SWEEPER
7. DIAGNOSTICS
By pressing up and down (R1-C2 and R3-C2) one of the six options as shown above will highlight the
desired parameter. By pressing the OK button (R2-C2) the chosen option will be selected.
Once an option has been slected it is possible to change the parameters corresponding with the chosen option
5.3.1 Parameter/value setting
Pressing the up and down (R1-C2 and R3-C2) buttons will highlight the desired parameter. Pressing the
OK button (R2-C2) will allow the chosen parameter to be modied. This is shown below.
The actual value can be changed by pressing the R1-C1 and R2-C1 buttons. The changed value can
be conrmed by pressing the OK (R2-C2) button. Pressing the back (R3-C1) button leaves the actual
displayed parameter. If there are more parameters shown in the parameter value area (4) the desired parameter can be selected by pressing the up and down ((R1-C2 and R3-C2) buttons.
5.3.2 Parameters accessible by user
An overview of the parameters accessible by the user is given on the next pages
Page 20
20
User menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
1. HEATING Heating user settings
1. CH temperature/OTC set Set the CH temperatures and OTC curves parameters
1. CH setpoint Adjust setpoint of CH circuit
2. Outside temperature for CH off Set the external temperature at which heat demand is
removed. If set OFF, heat demand will never be removed
by controller (only by removing RT or bridge between
terminal strip C2:1,2)
2. Eco setpoint reduction Set the temperature that will be subtracted from the actual
setpoint when ECO mode is activated
3. Scheduler set Invoke scheduler menu
1. Enable/disable on board scheduler Based on selection is possible to enable/disable on board
scheduler
Enable Enable on board scheduler
Disable Disable on board scheduler
2. Scheduler set Select to set scheduler
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
8 Monday-Friday
9 Monday-Sunday
10 Saturday-
Sunday
Used to program on board scheduler (On, Off, Eco)
2. DOMESTIC
HOT WATER
Domestic hot water user settings
1 DHW set point Set the DHW temperature (in case of a DHW with sensor
this is the actual DHW temperature, in case of DHW with
thermostat this is the base boiler ow temperature).
2. ECO set point reduction Set the temperature that will be substracted from the
actual setpoint when ECO mode is activated.
3. Scheduler set Invoke scheduler menu
1. Enable/disable on board scheduler Based on selection possible to enable/disable DHW on
board scheduler
Enable Enable on board scheduler
Disable Disable on board scheduler
Page 21
EN
21
User menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
2. Scheduler set Select to set scheduler
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
8 Monday-Friday
9 Monday-Sunday
10 Saturday-
Sunday
3. HOLIDAY Holiday temperatures settings
1. CH holiday set point Set CH temperature used when Holiday mode active
2. DHW holiday set point Set DHW temperature used during Holiday mode
4. MAINTE-
NANCE
1. Service information Used to display service company phone number or entered
info
2. Service due date Show next service due date. When date expire a MSG is
shown on lower part of main screen asking for service.
5. SERVICE Boiler option settings
1. Select Language Allow selection of different language
English Select for English
Italian Select for Italian
German Select for German
Russian Select for Russian
Spanish Select for Spanish
2. Select units Allow selection of different unit
Fahrenheit Select for Fahrenheit
Celsius Select for Celsius
3. Set date Allow RTC date setting
4. Set time Allow RTC time set. When selected a screen asking for
time format 24/12 Hours is opened. When selected appro-
priate format screens jump to time entering screen.
24 hours Select for 24 hours clock
12 hours Select for 12 hours clock
Page 22
22
5. Restore factory data Pressing OK all the user settings will be restored to the
original factory default settings. See 1)
6. CHIMNEY
SWEEPER
Manual mode. Hitting OK will force boiler to operate at
% of power Timeout 15 minutes. While test in progress
navigating through other menus is allowed.
7. DIAGNOS-
TICS
Will display boiler usage information and errors
1. Boiler information Boiler information
1 CH request
2 DHW demand
3 Firing rate
4 Flame ionization current
5 Boiler set point
6 Boiler supply temperature
7 Return temperature
8 Flue temperature
9 Outdoor temperature
10 DHW storage temperature
11 Boiler fan speed
12 CH ignitions
13 CH runtime
14 DHW ignitions
15 DHW runtime
16 System pressure
17 Heat Exchanger Temp.
18 0-10V input
19 Target power
Will display the information shown in SUBMENU 2. When
the line has a * at the end of the line means that hitting OK
when the line is highlighted will open a graph that shows
the latest 120 variable values stored every 12 minutes
(24 hour history)
Page 23
EN
23
5.4 Installer (technician) menu
If the button marked “4” (page 21) is pressed the screen as given in the gure below will appear.
The installer (technician) access code is 231 +- (R1-C1 and (R2-C1) buttons are used to increment/decrement value
Up and down (R1-C2 and R3-C2) buttons are used to select character to be modied ok (R2-C2) button conrms value
Once the menu is accessed by entering the code the following options will be shown
1. ADVANCED CH SETTINGS
2. ADVANCED DHW SETTINGS
3. SYSTEM SETTINGS
4. DIAGNOSTICS
5. USER SETTINGS
6. CASCADE
7. RESTORE FACTORY SETTINGS
Pressing the up and down (R1-C2 and R3-C2) buttons will highlight the desired parameter group.
Pressing the up and down (R1-C2 and R3-C2) buttons will highlight the desired parameter subgroup.
Pressing the OK button (R2-C2) selects the chosen parameter subgroup.
Once a parameter subgroup option has been chosen it is possible to change the parameters correspon­ding with the selected subgroup. Follow the instructions as per 5.3.1 to set or change a parameter.
5.4.1 Parameters accessible by installer (technician)
An overview of the parameters accessible by the installer (technician) is given on the following pages.
Page 24
24
Technician menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
Lockout history Show a list of recent errors. Hitting OK on the highlighted error will open screens
that contain details on boiler status when error occured.
1. ADVANCED CH
SETTINGS
Heating installer advanced settings
1. CH power set Set power of boiler in CH mode
1. Maximum power Set % of boiler maximum power in CH mode
2. Minimum power Set % of boiler minimum power in CH mode
2. CH temperatures Set (selecting OK) and show CH temperatures
1. Absolute max
temp
Set CH absolute max temperature (CH temperature boiler settings will never
exceed)
2. CH maximum set
point
Determine higher boundary of CH setpoint
3. CH minimum set
point
Determine lower boundary of CH setpoint
4. Setpoint Set CH setpoint hysteresis (temperature above setpoint at which boiler will be
switched off)
3. OTC parameters Set the OTC parameters
1. Outside temp for
max CH
Dene external temperature at which OTC will set maximum CH setpoint
2. Outside temp for
CH
Dene external temperature at which OTC will set the minimum CH setpoint
3. Outside temp for
CV off
Set the external temperature at which Heat demand is removed. If set OFF heat de-
mand will never be removed by controller (only by removing RT or bridge between
terminal strip C2:1,2)
4. OTC set point
table
Show in a table the link between external temperature and actual setpoint deter-
mined by the OTC parameter selection
5. OTC curve Show in a curve the link between external temperature and actual setpoint deter-
mined by the OTC parameter selection
4. CH pump settings Set pump usage related parameters
1. Post pump time Set the CH pump overrun time
5. CH anti cycling
timer
Set the anti cycling timer (minimum time between boiler goes off till next ignition)
6. CH request type Allow selection of different CH requests:
Only OTC Select OTC: outdoor Temperature controller 3)
Room Tstat Select RT/OT: Room Thermostat or OpenTherm
0-10V Signal (%) Select 0-10Vdc input for Power mode 3)
0-10V Signal (SP) Select 0-10Vdc input for setpoint mode 3)
Page 25
EN
25
Technician menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
2. ADVANCED
DHW SETTINGS
Domestic hot water advanced settings
1. DHW power Set power of boiler in DHW mode
1. Maximum power Set % of boiler maximum power in DHW mode
2. Minimum power Set % of boiler minimum power in DHW mode
2. DHW temperatures Set (selecting OK) and show DHW temperatures
1. Storage tempera-
ture set point
Set Flow temperature during DHW mode when DHW done via a thermostat
(Switch)
2. Boiler temperatu-
re set point
Set DHW temperature setpoint when DHW done with temperature sensor
3. DHW set point
hysteresis
Set DHW setpoint hysteresis (temperature below setpoint at which the boiler will
be switched on)
3. DHW pump set-
tings
Dene pump usage in DHW mode
DHW post pump
time
Set the DHW pump overrun time added to the prexed time of 3 minutes
4. DHW priority Dene DHW priority over CH
1. DHW priority
status
Enable/disable DHW priority over CH
Enabled Enable
Disabled Disable
2. DHW priority
timeout
Dene after how much time DHW priority is ended. (CH can be served if present
for the same amount of time).
Off Select for no timeout (while DHW priority status is enabled)
1...60 minutes Set timeout in minutes (while DHW priority status is enabled)
5. DHW request type Dene DHW request switch or sensor
Switch DHW start when DHW thermostat closes
Sensor DHW start based on requiered vs actual DHW temperature
3. SYSTEM
SETTING
Boiler and system parameters
1. Boiler parameters Boiler related parameters
1. Ignition power Set power % used when igniting burner
2. Delay siphon
check
Delay time to validate a syphon error 4)
Page 26
26
Technician menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
3. Number of boiler
pump
Dene pump and 3-way valve or 2 pumps
Pump and 3-way
valve
System with pump and 3-way valve
Two pumps System with 2 pumps
4. Pump speed max Maximum % of PWM pump speed
5. Pump speed max Minimum % of PWM pump speed
6. Antilegionella Based on selection possible to enable/disable Antilegionella protection
Enabled Enable Antilegionella protection
Disabled Disable Antilegionella protection
7. Modbus parame-
ters
Set Modbus parameters
Address Set address default: 1
Baudrate Set baudrate default: 38400 bps
Frame Set frame 8N!
8 3-way valve travel
time
Select for setting travel time 3Wv in seconds
1-255 sec Set travel time 3Wv (DHW<- ->CH)
2. User interface
settings
1. Select language Allow selection of a different language
English Select for English
Italian Select for Italian
German Select for German
Russian Select for Russian
Spanish Select for Spanish
2. Select unites Allow selection of different unit
Fahrenheit Select for Fahrenheit
Celsius Select for Celsius
3. Set date Set system date
4. Set time Set system time
3. Service settings Service information
1. Service informa-
tion
Used to insert service company phone number (selection done as per technician
password enter)
2. Service due date Next service due date (input done as per date entering)
Page 27
EN
27
Technician menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
4. DIAGNOTICS Boiler information and lockout history
1. Boiler information Boiler information
1. CH request
2. DHW demand
3. Firing rate
4. Flame ionization
current
5. Boiler set point
6. Boiler supply
temperature
7. Return tempera-
ture
8 Flue temperature
9 Outdoor tempe-
rature
10 DHW storage
temperature
11 Boiler fan speed
12 CH ignitions
13 CH ignitions
14 DHW ignitions
15 DHW runtime
16 System pressure
17 Heat Exchanger
Temp.
18. 0-10V input
19. Target power
Will display the information shown in SUBMENU 2.
When the line has a * at the end of the line means that hitting OK when the line is
highlighted will open a graph that shows the latest 120 variable values stored every
12 minutes (24 hour history).
2. Lockout history Shows the list of recent errors. Hitting OK on the highlighted error will open new
screen that contains details of the boiler status when the error occured.
3. Manuel test See chimney sweeper.
5. USER
SETTINGS
Access the user settings from the advanced menu
1. Heating Heating user settings
1. CH temperature/
OTC set
Set the CH temperature and OTC curves parameters
1 CH set point Adjust setpoint of CH circuit
2 Outside tempera-
ture for CH off
Set the external temperature at which Heat demand is removed
2. ECO set point
reduction
Set the temperature that will be substracted from the actual setpoint when ECO
mode is activated
Page 28
28
Technician menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
3. Scheduler set Invoke scheduler menu
1. Enable/disable on
board scheduler
Based on selection is possible to enable/disable on board scheduler
Enable Enable on board scheduler
Disable Disable on board scheduler
2. Scheduler set Select to set scheduler
1. Monday
2. Tuesday
3. Wednesday
4. Thursday
5. Friday
6. Saturday
7. Sunday
8. Monday-Friday
9 Monday-Sunday
10 Saturday-Sunday
Used to program on board scheduler
2. Domestic hot water Domestic hot water user settings
1. DHW set point Set the DHW temperature (in case of a DHW with sensor this is the actual DHW
temperature, in case of DHW with thermostat this is the base boiler ow tempera-
ture)
2. ECO set point
reduction
Invoke scheduler menu
3. Scheduler set Invoke scheduler menu
1. Enable/disable on
board/scheduler
Based on selection is possible to enable/disable on board scheduler
Enable Enable on board scheduler
Disable Disable on board scheduler
2. Scheduler set Select to set scheduler
1. Monday
2. Tuesday
3. Wednesday
4. Thursday
5. Friday
6. Saturday
7. Sunday
8. Monday-Friday
9 Monday-Sunday
10 Saturday-Sunday
Used to program on board scheduler
Page 29
EN
29
Technician menu Submenu 1 Submenu 2 Submenu 3 Submenu 4 Notes
3. Holiday Holiday temperatures settings
1. CH holiday set
point
Set CH temperature used when Holiday active
2 DHW holiday set
point
Set DHW temperature used during Holiday mode
6. CASCADE Access to cascade information and settings
1. Cascade set
1. Cascade switch
delay
Delay between switching on and off different boilers
2. Cascade min
power
Minimum power of boiler in cascade
3. Burner power Max power of SINGLE boiler in cascade
4. Boiler for DHW Number of boilers assigned to DHW
5. PI loop period Base time for PI loop calculation
6. Burner water ow
delay
Water propagation time delay
7. Different boiler
size
Heterogeneous mode with 2 power groups DHW+CH/CH only
Disabled Disable Heterogeneous mode
Enabled Enable Heterogeneous mode
8. Cascade pump
speed
Cascade pump full speed
9. Cascade pump min
speed
Cascade pump min speed
2. Cascade info 1. Cascade role Role of boiler in cascade mode = MASTER, SLAVE, TERMINAL SLAVE
If not in cascade mode: STANDALONE
2. System tempera-
ture*
Cascade temperature value. Hitting OK when highlighted will open graph that
shows the latest 120 variable values stored every 12 minutes (over the past 24
hours). Samples will not be averaged over the 12 minutes period.
3. Number of
burners on
Number of burners that are switched on
4. Modulation level Actual percentage of cascade modulation level
3. Cascade auto detect Pressing OK will start the auto detection of the cascade conguration. Can only be
started from the master boiler.
7. RESTORE FAC-
TORY SETTINGS
Pressing OK all the advanced settings will be restored to the original factory de-
faults 2)
Page 30
30
5.5 Manual Chimney sweep mode
For routine maintenance and/or service purposes a CH request can be generated to force the burner to
a specic load from minimum to nominal (0-100%). This is only possible if no error condition is present.
The chimney sweep function can be started from the user menu and will be active for 15 minutes.While active it is possible to navigate through other menus to check the boiler status and functionality.
5.6 Disabling CH request
The CH function can be disabled. See 5.3.2 parameters accessible by user at 1 HEATING nr 3 scheduler set.
5.7 Service code
To access the service-level of the controller it is necessary to enter the service-code. How this done is explained in 5.4 installer (technician) menu.
5.8 Tacho fan speed
For service purposes it is possible to read the fan speed. See 5.4.1 parameters accessible by installer (technician) at 4 DIAGNOSTICS nr 1 boiler information.
5.9 Errors
For service purposes it is possible to see a list of recent errors. See 5.3.2 parameters accessible by user at 6 DIAGNOSTICS nr error history.
5.10 ECO working mode
When the ECO button (R3-C4) is pressed a programmable value (see user menu 1.HEATING under 2 ECO set point reduction) is automatically subtracted from the ow temperature setpoint weather com­pensated (OTC) set point, or 0-10V setpoint. . The same principal is applicable for DHW (see user menu
2.DOMESTIC HOT WATER under 2 ECO set point reduction)
5.11 Holiday mode
When the Holiday button (R3-C3) is pressed a start and end date of a holiday period may be entered.
The desired ow temperature and the DHW temperature for this period can be set (see user menu 3.
HOLIDAY under 1 and 2).
5.12 Schedules for CH and DHW
For CH and DHW separate schedules can be set. Both schedules are set to enabled and always on by default. Schedules may be set (ON, ECO, OFF) for each day, for a group of weekdays, for weekend days or for an entire week. The status of the schedule is shown on the main screen (ON, ECO, OFF). The schedule can be set in the user menu, heating or domestic hot water or in the technician menu, user settings, heating or domestic hot water. Eco mode can also be forced by pushing the ECO button on the control panel (R3-C4).
5.13 Cascade and Modbus
Cascade and Modbus options are shown in two separate attachments “Modbus” and “Cascade”.
5.14 Parameter settings
The parameter settings are listed on the following pages
Page 31
EN
31
USER MENU
Recommended Min Max
After factory
reset
1. HEATING 1. CH tempera­ture/OTC set
1. CH setpoint 85 20 90/Technician 75
2. Outside temperature for CH off
OFF 7 30 OFF
2. ECO set­point reduction
50 0 50 50
3. Scheduler set 1. Enable/disable on
board scheduler
Enabled Disabled Enabled Enabled
2. Scheduler set ON ON|OFF ECO ON
2. DOMESTIC
HOT WATER
1. DHW setpoint (Switch) 80 35 85 80
1. DHW setpoint (NTC sensor) 60 10 65 60
2. ECO setpoint reduction 20 0 50 20
3. Scheduler set 1. Enable/disable on
board scheduler
Enabled Enabled Enabled Enabled
2. Scheduler set ON ON|OFF ECO ON
3. HOLIDAY 1. CH holiday setpoint 20 20 90/Technician 20
2. DHW holiday setpoint (Thermostated) 80 35 85 80
2. DHW holiday setpoint (NTC sensor) 60 10 65 60
4. MAINTENANCE 1. Service information Service tel. set by Technician
2. Service due date Date set by Technician
5. SETTINGS 1. Select language English
English|Italian|German|Russian|Spanish
2. Select units Celsius Fahrenheit Celsius
3. Set date set date
4. Set time 24 hours 24 hours 12 hours
5. Restore factory settings Reset to factory/check settings
6. CHIMNEY
SWEEPER
OFF 0 100
1. Boiler information Real time boiler status
2. Lockout history
Overview lockout history
Status boiler at time of lock/block
TECHNICIAN MENU
Recom-
mended
Min Max
After factory
reset
1. ADVANCED
CH SETTINGS
1. CH power set 1. Maximum power 100 0 100 100
2. Minimum power 0 0 100 0
2. CH temperatures
1. Absolute max. temperature 90 20 90 80 Higher than 90 not allowed
2. CH maximum setpoint
85 20
Abs. max CH
temp.
75
3. CH minimum setpoint 20 20 70 40
4. CH setpoint hysteresis 5 2 10 3
3. OTC parameters
1. Outside temp for max CH -10 -34 10 -10
2. Outside temp for min CH 18 15 25 18
3. Outside temp for CH off OFF 7 30 OFF
4. OTC setpoint table OTC table
5. OTC curve OTC curve
4. CH pump set­tings
1. Post pump time
10 1 30 5
5. CH anticycling timer 3 0 15
6. CH request type RT+SP/ OT
onlyOTC|RT
0-10Vdc %
| SP
RT+SP/OT
Page 32
32
Recom­mended
Min Max
After factory
reset
2. ADVAN­CED DHW SETTINGS
1. DHW power 1. Maximum power 100 0 100 100
2. Minimum power 0 0 100 0
2. DHW temperatures
1. Storage temperature setpoint 80 35 85 80
2. Boiler temperature setpoint 60 35 65 60
3. DHW setpoint hysteresis 6 2 10 3
3. DHW pump settings
1. DHW post time 1 OFF 180 30
4. DHW priority 1. DHW priority status Enabled Enabled Disabled Enabled
2. DHW priority TimeOut Off 1 60 Off
5. DHW request type Switch Switch Sensor Switch
3. SYSTEM SETTINGS
1. Boiler parameters
1. Ignition power 25 0 100
Higher than 30 not allowed
2. Delay siphon check 3 0 20
Check syphon is not empties by new value
3. Number of boiler pumps
2 pump
Pump
3-w-valve
2 pump 2 pump
4. PWM pump speed max 100 1 100 100
5. PWM pump speed min 40 1 100 30
6. Antilegionella Enabled Disabled Enabled Disabled
7. Modbus parameters Adress Baudrate Frame
8. 3 Way valve travel time 180 1 255 10
2. User interface settings
1. Select language
English
English|Italian|German|
Russian|Spanish
2. Select units Celsius Fahrenheit Celsius
3. Set date Set date
4. Set time 24 Hours 24 Hours 12 Hours
3. Service settings 1. Service information Set telephone number
2. Service due date Set service date
4. DIAGNOS­TICS
1. Boiler information Real time boiler status
2. Lockout history Overview lockout history Status boiler at time of lock/block
3. Manuel test See chimney sweeper
5. USER SETTINGS
0 Heating 1. CH tempera-
ture/OTC set
1. CH set point 85 20
90/abs max
CH temp
75
2. Outside tempe-
rature for CH off
off 7 25 off
2. ECO setpoint reduction 50 0 50
3. Scheduler set
1. Enable/disable
on board sche­duler
Enabled Disabled Enabled
2. Scheduler set Set time scheduler (Time/On/ECO/OFF)
2. Domestic hot water
1. DHW setpoint (NTC sensor) 60 35 65
1. DHW setpoint (Thermostated) 80 35 85
2. ECO setpoint (NTC sensor) 20 0 50
3. Scheduler set
1. Enable/disable
on board sche­duler
Enabled Disabled Enabled
2. Scheduler set Set time scheduler (Time/On/ECO/OFF)
3. Holiday 1. CH holiday setpoint 20 20
90/Abs max
CH temp
1 DHW holiday setpoint (Thermo­stated)
80 35 85
2. DHW holiday setpoint (Sensor) 60 10 65
Page 33
EN
33
Recom­mended
Min Max
After factory
reset
6. CASCADE 1. Cascade set 1. Cascade switch delay 30 0 255
2. Cascade min power 20 0 100
3. Burner power (default value x = 17,21,25,29 boiler specic)
x 0 2550
4. Boiler for DHW 0 1 6 0
5. Pi loop period 5 0 15 5
6. Burner water ow delay 30 0 255 30
7. Different boiler size Disabled Disabled Enabled Disabled
8. Cascade pump speed mx. 100 15 100 100
9. Cascade pump speed min 40 15 100 30
2. Cascade info 1. Cascade role: see Cascade auto
detection
Standalone Standalone Master|Slave
2. System temperature
Actual temperature cascade system sensor
3. Number of boilers on
Actual number of burners/boilers on in
cascade
4. Modulation level
Actual cascade modulation level
3. Cascade auto detect: press OK to start detecting role
boiler in cascade chain
Standalone Standalone Master|Slave
7. RESTORE FACTORY SETTINGS
Reset to factory/check settings
Page 34
34
6 INSTALLATION
6.1 Installing the boiler
The installation must be done in accordance with all local and national codes, regulations and standards, and in accordance with the directives of all relevant authorities.
1. The boiler must only be installed in an area where it is allowed to install it. Make sure that this area is protected against the danger of freezing.
2. The area should have sufcient ventilation and cooling to prevent overheating.
3. When delivered the boiler is on a pallet. Install the boiler on a at non-combustible oor and level it by using its positioning bolts.
4. A minimum free space of 50 cm should be left on each side of the boiler for service access.
5. Remove the sealing/protection caps from the connection tubes. Warning : take care as residual water from testing may drip
6. Fill the condensate trap with clean water. This can be done by ushing some water into the cast alu-
minium exhaust connection from the rear. This water will then drain into the syphon and ll it.
6.2 Frost protection
The boiler is protected against frost.
If the boiler detects an NTC ow temperature below 8 ºC, the CH-pump will be activated. If tempe­ratures continues to fall the boiler will start at a ow temperature of 6 ºC and it will run on minimum load until the ow NTC senses a temperature of 15 °C. The CH-pump will stay running for another
10 minutes. This only protects the boiler and does not protect the installation, pipework or
radiators against freezing.
During longer periods of absence in the winter, the installation itself should be protected by activating the heating periodically and by partly opening the radiator valves. Where a room thermostat is control-
ling the demand, do not set the room thermostat to a value below 15 °C.
To protect frost sensitive radiators against frost it is possible to connect a frost thermostat in parallel with a Volt free room thermostat. It is also possible to set the CH pump to activate automatically under OTC settings when an outdoor sensor is present (this must be set by the installer). In this case,the CH pump will be activated if the out-
door temperature drops below 8 ºC.
Page 35
EN
35
6.3 Water connection
6.3.1 Pump
The boiler does not have a built in CH-pump. Therefore a CH-pump must be mounted separately . Select a pump that matches the hydraulic resistance of the boiler and the installation. The graph below shows the resistance characteristics for the different boiler models.
For electrical connections see chapter 6.7.
6.3.2 Minimum ow
The minimum ows shown below must be guaranteed.
Input in kW Flow [m3/h] @ delta
T 25 full load
Flow [m3/h] @ delta
T 30 Start=25%
Flow [m3/h] @ delta
T 30 part load
850-11 29,2 9,7 4,9 680-11 23,4 9,7 4,9
1020-13 35,1 11,9 5,8
850-13 29,2 11,9 5,8
6.3.3 Water-treatment
Before lling up the installation (old and new), the installation should be rinsed
thoroughly with clean water from the tap.There are some rinsing/cleaning products listed below and it is recommended that these are used.
Page 36
36
The water hardness of the heating system must be according the German VDI guideline 2035. See table beneath.
Water hardness in heating systems according VDI 2035 guideliness
< 0,11 °dH means demine-
ralised °dH means German
hardness
installation < 20 ltr/kW installation between 20 and
50 ltr/kW
installation > 50 ltr/kW
50-300 kW total boiler capacity < 11,2 °dH < 8,4 °dH < 0,11 °dH
300-600 kW total boiler capa-
city
< 8,4 °dH < 0,11 °dH < 0,11 °dH
> 600 kW total boiler capacity < 0,11 °dH < 0,11 °dH < 0,11 °dH
This means for the Megaex boilers that the system should be lled with demineralised water (smallest capacity > 600 kW). Before lling, rinse the complete installation with water from the tap.
Note that water softening by means of ion exchange principle is not allowed. Check after lling with demineralised water that the pH is between 7 and 8,5. If not water must be trea­ted.
The pH must be kept between 7 and 8,5 at all times
• The maximum allowed content of chlorides is 150 mg/ltr
• The conductivity of the non treated installation water must not exceed the value of 300 μs/cm in
combination with max O2 of 0,1 mg/ltr. If the O2 content is lower than 0,02 mg/ltr a higher conducti­vity limit of 600 μs/cm is allowed.
If the conductivity is higher than the values mentioned, empty the system, ush and ll with clean tap
water, preferably by adding the recommended cleaning products. Especially in low tempereature hea-
ting systems normal degassing systems are insufcient. The use of an advanced system is required.
Water pressure must be higher than 0,8 bar
• The water quality must be checked on a regular base (at least once every year)
• There are many products available on the market which pretend to clean and
• protect heating systems. Unfortunately there are only a few that have really
• proven this in practice.Therefore Mark Climate Technology only allows the following quality
• products for water treatment ;
Producer : Fernox, www.fernox.com
- Cleaner F3 : removes corrosion, lime and sludge
- Protector F1 : protects against corrosion, lime and sludge
- Alphi-11 : anti-freeze and protection against corrosion and lime
Producer : Sentinel www.sentinelprotects.com
- X100 : Inhibitor scale and corrosion protection
- X200 : Noise reducer long life system treatment to eliminate noise
- X300 : System cleaner for new hydronic heating systems
- X400 : System restorer non acid cleaning of older systems
- X500 : Inhibites antifreeze against scale and corrosion in all types of indirect heating systems at low
temperatures
Note that these products must be used strictly in accordance with the water treatment manufactu­rers instructions.
Furthermore we strongly recommend the following ;
• Use the above mentioned water treatment protection products to ll and protect the installation
• Use a log book to record water lling, relling, topping up, water quality measurements and water
treatment
• Only use diffusion tight material, especially for under oor heating
Page 37
EN
37
• Always mount air vents at the highest points in the installation.
• Install isolation/check valves near the boiler and on strategic locations (anticipating any future expansi-
ons of the system) to avoid lls, rells and topping up as much as possible.
• Install a water meter to check the amount of lled, relled and topped up water.
• Install a lter (magnetite and dirt) in the return.
• Install an isolation heat-exchanger to separate the boiler from the installation to protect dirt or lime
in the secondary system from affecting the boiler.
• avoid leaks and if there is a leak, repair as soon as possible.
6.3.4 Water connection general
1. Water connections for ow and return are size DN125
2. The installation must have a pressure relief valve (with a capacity higher than the boiler output) and
an expansion vessel. The capacity of this vessel should be sufcient for the installation.
3. To avoid blocking and non volatile lock-out of the boiler control it is recommended to install a by-
pass in the installation to guarantee the minimum ow through the boiler. The by-pass valve should
be mounted as far away from the boiler as possible to have the biggest possible content of the by­pass-circuit (also a big radiator without valves could be used).
4. Drain the condensate via a tundish and an U-trap to the sewer.
5. At the highest point of the installation a de-airing device should be mounted.
6.4 Gas connection
1. The gas connection must be done in accordance with all local and national codes, regulations and standards, and in accordance with the directives of all relevant authorities.
2. The gaspipe of the boiler has a R 2” connection.
3. In order to avoid blockage of the gas valve, ensure that there is no dirt in the gas pipework prior to commissioning.
4. The maximum allowable inlet pressure for the gas valve is 50 mbar.
5. Check the heat input of the boiler.The load as given on the type plate should be checked.
6.5 Air-supply and ue-gas connection
Air connection : All types have air connection ø 200 mm Flue gas connection : ø 250 mm for all types
Allowed Appliance types:
Possibilities for air / ue system ; B23, C33, C63
6.5.1 B23
As standard the boiler is delivered as type B23 where the supply air is taken from the room where the boiler has been installed in.
If the inlet air contains dust or dirt one should install a lter or a leaf catcher in the air supply.
A vertical terminal is recommended.
Roof terminals and extensions and/or condensate trap/collector must be obtained by M&G. See page 40.
For pressure drop calculation of appliance type B23 use the table for pressure drop per component and the table for total pressure drop calculation. See page 39.
For total available pressure drop see table on page 38.
6.5.2 C33
Roof terminals and extensions and/or condensate trap/collector must be obtained from M&G. See page
39.
Page 38
38
For pressure drop calculation of appliance type C33 use the table for pressure drop per component and
the table for total pressure drop calculation. See page 38.
For total available pressure drop see table on page 38.
Terminals should be installed in the same pressure area (within a plane of 1m²)
6.5.3 C63
C63 appliances may only be equipped with Gastec QA materials and terminals or according
NEN14989-2
Note: When using a C63 type ue conguration it is essential to ensure that C63 is allowed in the country were the boiler is installed.
It is recommended to use a full aluminium ue system. A PP (Temperature class T120) or stainless steel ue system can also be used (See TPW table below). In this case the condensate must be drained before it ows back into the aluminium parts of the boiler. Otherwise aggressive condensate from the non-alu­minium ue system can corrode the aluminium parts of the boiler. A condensate trap/collector must be
mounted just before entering the silencer(s) of the boiler (also see 6.5.5.1 general).
T-P-W Class Temperature range T120 Pressure range P1 Condensate resistance
(W=wet / D=Dry)
W
The minimal combustion products temperature, mass ow rate and CO2 are given in the table below.
Vol. Flue Vol. Air CO
2
T uegas rho
MegaFlex part load m³/h m³/h % °C kg/m³
850-11 170 220 191 9,1 30 1,12 1020-13 204 264 229 9,1 30 1,12
The maximum allowed recirculation rate under wind conditions is 10 %
Maximum allowable combustion air temperature 45 °C
The tables below give an indication of maximum lengths (in mtrs) for parallel air supply and ue outlet pipes. The equivalent of pipe length in mtrs of bends 90° and 45° is given.
type max. allowed
pressure drop (*)
Parallel Air/Fluegas
Ø200/ø250 850-11 500 Pa 42 m (**) 1020-13 500 Pa 25 m
(*) : Without roof terminal, bend(sump) and condensate trap
(**) : Maximum allowed draught is 120 Pa, this means that in case of vertical ue the maximum length is
limited to 30 mtrs
Page 39
EN
39
Equivalent of pipe length in meters
Bend Parallel
Air/uegas
Ø200/ø250 mm
Bend 90° 5.8 Bend 45° 4.0
Warning : Do not install the terminals for supply of combustion air and for the exhaust of combustion products on opposite walls of the building Terminals should be installed in the same pressure area (within a plane of 1m²)
6.5.4 Pressure drop calculations
The rst 90 ° bend must be mounted directly to the boiler and followed by the chimney silencer (this
bend is not part of the calculation (as it is already taken into account).
Flue-outlet and air-supply calculations;
Total pressure drop available for ue-outlet and air-supply is given in the table below.
Air connection: All types have air connection ø 200 mm Flue gas connectio : ø 250 mm for all types
Type Boiler Total available Pressure drop In
[Pa] for B23, C33, C63
850-11 500 1020-13 500
For pressure drop calculation of appliance types B23,C33 use the next two tables on the following pages.
Pressure drop table per component
1 2 3 4
Component 680-850 (11) 850-1020 (13)
Pressure drop [Pa]
Flue gas [Pa] Air [Pa] Flue gas [Pa] Air [Pa]
Pipe length 1 m Ø 250mm
2,6 3,8
Pipe length 1 m Ø 200mm
6,2 8,9
Bend 90°
Ø 250mm
15,9 22,9
Bend 90°
Ø 200mm
35,4 50,9
Bend 45°
Ø 250mm
10,9 15,7
Bend 45°
Ø 200mm
23 33,2
Terminal C33 Ø250m­m,Ø250mm
128,9 185,6
Terminal B23 Ø250mm
38,0 54,6
Note : Maximum allowed draught is 120 Pa, this means that in case of vertical ue the maximum length is
limited to 30 mtrs
Page 40
40
Table for total pressure drop calculation
1 2 3 4 5 6 7 8 9
Number Flue
gas
Ø250mm
Number Air
Ø200mm
delta
pressure
component
Fluegas
delta
pressure
component
Air
Total
pressure
drop Fluegas
out [Pa]
(2*4)
Total
pressure
drop Air in
[Pa] (3*5)
Total
Pressure
Terminal In
[Pa]
Total
pressure
drop Fluegas + air in [Pa]
(6 + 7 + 8)
1 Meter Pipe
Bend 90°
Bend 45°
Terminal:
Total delta pressure [Pa]
How to use the table:
- Column 1 : used material
- Column 2: total number of used material of column 1 for ue gas out
- Column 3: total number of used material of column 1 for air in
- Column 4: pressure drop from pressure drop table /component for ue gas components
- Column 5: pressure drop from pressure drop table /component for air components Select the correct column for the selected boiler type
(850-11: 1,2 , 1020-13: 3,4)
- Column 6: total pressure drop ue gas: multiply column 2 *4
- Column 7: total pressure drop air: multiply column 3 *5
- Column 8: total pressure drop terminal
- Column 9: total pressure drop ue gas and air: column 6 + 7 + 8
- Finally add all together column 9
Total pressure drop must be lower than 500 Pa (Megaex 850-11) and (Megaex 1020-13).
If the combined inlet/outlet system exceeds the maximum allowed pressure, this will result in a decrease of more than 5 % of heat capacity. This is not allowed. All components must be obtained from M&G A list of allowed articles of M&G with corresponding OEM nrs is given below and on the next page.
APPLIANCE TYPE FLUEGAS OUTLET SUPPLY AIR INLET
ROOF TERMINAL ALU 250 LEAF CATCHER ALU
ROOF TERMINAL ALU 250/250-250/350
EXPANDER
B23
C33
Page 41
EN
41
Components OEM Art. no M&G
Roof terminals
ROOFTERM ALU 250 B23 40.045.26.65 ROOFTERM ALU 250/250-250/350 C33 41.007.65.59 EXPANDER AIR Ø200- Ø250 Pending LEAF CATCHER (AIR INLET GRILL) Pending
Flue gas
ALUMINUM Ø 250 mm
ELBOW ALU 250 90° 40.045.16.86
ELBOW ALU 250 45° 40.045.16.88
EXTENSION ALU 250x1000 40.045.16.84 EXTENSION ALU 250x500 40.045.16.83
Combustion air
ALUMINUM Ø 200 mm
ELBOW ALU 200 90° 41.008.05.40
ELBOW ALU 200 45° 41.008.05.41
EXTENSION ALU 200x2000 41.008.05.33 EXTENSION ALU 200x1000 41.008.05.32 EXTENSION ALU 200x500 41.008.05.31
PP Ø 200 mm
ELBOW PP 200 90° EPDM 41.007.04.11 ELBOW PP 200 45° EPDM 41.007.04.12
EXTENSION PP 200x1900 41.007.04.04 EXTENSION PP 200x1000 41.007.04.02 EXTENSION PP 200x500 41.007.04.01
GENERAL
WALL BRACKET 250 40.045.22.35
WALL BRACKET 200 41.008.71.98
SEAL SIL 250 mm ( for DN250 ALU) 40.045.18.15 SEAL SIL 200 (ALU 200) 41.002.73.70 SEAL EPDM 200 (PP DN 200) 41.007.52.95
WEATHER SLATE FLAT ALU 368 0° (for
41.007.65.59)
41.007.65.71
WEATHER SLATE FLAT ALU 275 (for 40.045.26.65) 40.045.31.98
6.5.5 Installing ue-exhaust and air inlet
6.5.5.1 General
• Do not use materials from different manufacturers for either exhaust or air inlet
• Only the manufacturers of exhaust gas and air inlet components as mentioned in this manual may be used
• Both systems (exhaust and air) should be mounted free of tension
Condensate, ice-free terminal, tundish and U-trap
The boilers can produce ue gasses with very low temperatures, which can lead to condensation in the ue pipes and ue terminal. Therefore one should always mount an ice free terminal.
Drain the condensate via a tundish and a U-trap to the sewer.
Page 42
42
Air inlet
If PP material is used for the air inlet a minimum distance of 35 mm between exhaust and air inlet should be respected. The minimum insert length of the sleeve, leaf catcher or pipe must be 40 mm.
Flue exhaust
A horizontal ue exhaust pipe must be installed with a fall of 3° (50 mm per mtr) downwards towards the boiler to allow condensate to ow back in the sump or condensate collector.
The minimum insert length into the sleeve and the minimum length of the pipe end for aluminium and stainless steel must be 40 mm.
If PP is used pay attention to the expansion (elongation) of the PP due to rise in ue gas temperature.
Insert the PP pipe into the sleeve and redraw over a length of 10 mm (10 mm for maximum pipe length of 2 mtr). After mounting the minimum insert length into the sleeve and the pipe end must be 40 mm.
Condensate trap/collector
The condensate trap/collector must be either connected by a tube to a syphon that provides the same height of water column as the one supplied with the boiler or by a T-piece to the syphon as supplied with the boiler Note: The chimney pieces (silencers) that are delivered with the boiler need to be mounted correctly as
shown in the gure beneath.
Silencer mounted on a 13 section boiler (850-1020 kW)
Page 43
EN
43
6.5.5.2 Brackets, mounting
Air inlet
The rst bracket should be mounted 0.5 mtr away from the boiler
Horizontal and non vertical pipes should be bracketed equally divided with a maximum distance of 1
mtr between the brackets
Vertical pipes should be bracketed equally divided with a maximum distance of 2 mtrs between the
brackets
In case of a chimney shaft, rst identify the air inlet. The end of the air inlet pipe should be at least 0.5
mtr above the shaft. The last component before entering the shaft should be xed. If a bend is the last component also x the component before the bend.
Flue exhaust
A bracket must be mounted to every component except in the case that the length of the pipe befo-
re and after the bend < 0.25 mtr. In this case mount the rst bracket at a length of max 0.5 mtr away
from the boiler
Horizontal and non vertical pipes that have a distance between the xing brackets > 1 mtr should be
equipped with a non clamping (to allow minor movement) bracket in between
Vertical pipes should be bracketed equally divided with a maximum distance of 2 mtrs between the
brackets
In case of a chimney shaft, rst identify the ue outlet. Check if the used shaft pipes are damaged or
blocked.The ends of the exhaust pipe should be at least 0.5 mtr above the shaft. The last component
before entering the shaft should be xed. If a bend is the last component also x the component
before the bend.
All brackets must be obtained from M&G
6.5.5.3 Seals and joining
Prevent incorrect or damaged seals by shortening pipes squarely and by deburring after shortening.
Joins or connections in the exhaust ue may not be screwed.
In the air inlet only aluminium or stainless steel joins or connections may be screwed. It is not allo-
wed to screw PP joins or connections.
Do not use glue or foam like silicon or PUR.
To assure soundness all components must be sealed.
For smooth joining only use a soap solution (1% in water). Do not use oil, grease or (acid free) Vase-
line
Important notice
If instructions as written above are not followed and or the materials for air inlet and ue gas exhaust
as quoted above are not used Mark Climate Technology can not be held responsible for eventual conse­quences.
6.6 Electrical connection
1. The electrical installation should be in accordance with national and local codes and regulations.
2. As standard the boiler is congured for 400 VAC + 3N/50Hz
3. The terminal strip is accessible by opening the side cover (unscrew with screw driver) behind which
the control is mounted.
4. A means of disconnection must be incorporated in the xed wiring in accordance with the wiring ru-
les. Use the cable guide indicated with a 400 VAC +3N/50 Hz sticker on the backpanel of the boiler. As it is a stationary appliance without means for disconnection from the supply a contact separation in all poles that provide full disconnection under voltage category III must be provided. The minimum cross section of the supply wire is 5 x 2.5 mm2 and must be connected to the circuit breaker 400V 4
Page 44
44
pole 10 A (see gure beneath).The supply wire should be secured by a pull relief.
5. It is not permissible to alter the internal wiring as tted by the manufacturer.
6. The enable connected to numbers 1 and 2 of the strip C2 must be Volt free (also see warning un-
der 4.2.1). To set, select from the technician menu, advanced settings, CH request to Room Tstat.
The 0-10 V DC (Power or Setpoint mode) should be connected to the numbers 3 (=negative-) and 4 (=plus+) and a short wire loop should be placed between the numbers 1 and 2 of strip C2. To set,
from the technician menu, advanced CH settings, CH request select either 0-10V % (power mode) or 0-10 V SP (setpoint mode). Digital communication (open Therm OT+ version 3.0) should be connec­ted to the numbers 1 and 2 of the strip C2. Select from the technician menu, advanced CH settings, CH request for Room Tstat. For digital communication with EBV like RS30 or Theta an additional communication module is required. For the internal OTC (outdoor temperature controller) a 12
kohm at 25º C (see NTC table at 6.2.2) should be connected to the numbers 5 and 6 of strip C2 and
a short wire loop should be placed between the numbers 1 and 2 of strip C2. Finally from the techni­cian menu, advanced CH settings, CH request, select only OTC.
7. If a storage tank is connected to the boiler, the tank thermostat (or the tank NTC) should be con-
nected to the numbers 7 and 8 on the strip C2. Select from the technician menu, advanced DHW settings, DHW request. Note that a tank NTC should be12 kohm at 25 ºC (see NTC table at 6.6.2.)
8. The CH system pump should be connected to the numbers 7 (=PE), 8 (=L), 9 (=N) on strip C1 if in
use in combination with a 3-way valve. (also see chapter 4.3). A PWM pump should be connected to
21 (=PE), and 22 (=N) on strip C1. If 230 VAC is applicable than 23,24 or 25 can be used for L.The
PWM signal should be connected to 14 (PWM signal) and 13 (PWM ground) om strip C2. From the technician menu, system settings, boiler parameters the max and min pump speed can be set.
9. The DHW pump (or 230 VAC 3-way valve) should be connected to 10 (=PE), 11 (=L1), and 12 (=N)
on strip C1. If a CH pump is used it should be connected to 13 (=PE), 14 (=L1) and 15 (=N) on strip
C1.
10. If the system pump, CH pump, PWM pump, DHW pump, alarm connection or the 3-way valve consu-
mes more than 0,8 A, it needs to be switched by an auxiliary relay.
11. The alarm output on the numbers 19 and 20 on strip C1 is a potential free relay output (230 VAC),
max 0,8 A).
12. The cascade/system pump output on the numbers 29 and 30 on strip C1 is a potential free relay
output (230 VAC, 0,8A).
13. The B-B (Burner Block) on the numbers 31 and 32 on strip C1 provides an external (remote) burner
block (error 76). The external contact must be a potential free contact (rated at 230 VAC).
14. The SPS_B (Burner Block) on the numbers 11 and 12 on strip C2 also provides an external (remote)
burner block (error 77). In this case the external contact must be a potential free contact (24 VDC).
15. The B-L (Burner Lock) on the numbers 9 and 10 on strip C2 provides an external burner lock (error
3). The external contact must be a potential free contact (rated at 24 VDC).
16. The main-fuse is a circuit breaker as shown in the gure below 4 pole 10 A.
17. If the supply wire needs to be replaced, act as described under 4.
18. Connect current carrying conductors in such a way that they become taut before earthing conduc-
tor. See gure next page.
Page 45
EN
45
General remarks : Use the 5 tubes on the left side on the back to guide the high voltage The lowest of the 5 is for 400 VAC + 3N/50 Hz (supply) The upper 4 are for 230 VAC or eventually 400 VAC + 3N/50Hz Use the 2 tubes on left side on the back to guide the low voltage connections from C2 and C3 Also see wiring diagram on next pages
6.6.1 Wiring diagram
BC Burner control D Display
AUT Automate 380V with fuse
C1 Connector high voltage C2 Connector low voltage C3 Connector service
C4 Connector 380V
CH-P Central heating pump DHW-P Domestic hot water pump PWM-P Modulating pump
A-P Appliance pump max 0,8A
HE Heat exchanger NTC1 Flow temperature sensor NTC2 Return temperature sensor NTC3 Domestic hot water sensor or switch NTC4 Outside temperature sensor NTC5 Flue gas temperature sensor NTC6 Cascade sensor MT Maximal thermostat (1-4) WPS Waterpressure sensor APS Air pressure switch SPS Siphon pressure switch GPS Gas pressure switch GV Gas valve S Swith on/off 3WV 3 way valve OT-RT Open therm or room thermostat on/off
OTC Outdoor temperature control 12K
SPS-B Siphon pressure switch block B-L Burner lock A Alarm C-P Cascade pump potential free contact B-B Burner block PE Earth cable or connector
N EMC netlter
Page 46
46
Page 47
EN
47
6.6.2 NTC resistance table
Temperature
[°C]
Resistance
[Ω]
12K
-30
-20 98.200
-15 75.900
-10 58.800
-5 45.900 0 36.100 5 28.600
10 22.800 15 18.300 20 14.700
25 12.000
30 9.800 35 8.050 40 6.650 45 5.520 50 4.610 55 3.860 60 3.250 65 2.750 70 2.340 75 1.940
80 1.710 85 1.470
90 1.260
95 1.100 100 950 105 110 115 120
Page 48
48
6.7 Pneumatic connections
A pneumatic diagram for the Intermodul 850 kW (11 sections) and the Intermodul 1020 kW (13 secti­ons) is given in the gure below.
The siphon pressure switch, connected to the sump, prevents overow of the syphon in the case of ex­cess back pressure in the ue.
The air pressure switch, connected to the venturi, checks the amount of air (by means of a Δp measure-
ment) before startup.
6.8 PC-connection
For information regarding connection of a PC to the boiler please contact your supplier.
7 PUTTING INTO OPERATION
1. Fill and bleed the system. Fill the boiler until a pressure between 1.5 and 2 bar is achieved. The maxi­mum working pressure is 6 bar. The boiler (not the installation !) is automatically bled by a built in automatic air vent.
2. Check all gas and water connections thoroughly for leaks.
3. Bleed the gas pipe.
4. As standard the boiler is set for G20 or G25 Check that the installation provides the correct type of gas to the boiler.
5. Check the inlet pressure : 20 mbar or 25 mbar
6. Turn on the boiler by setting the main switch on the control panel of the boiler to position 1 (on).
7. Generate (create) a heat demand.
8. Just before ignition the control checks if the contacts of the gas pressure,syphon pressure and water pressure switches are closed. If not, the boiler will block and the display will show E76.
9. If gas, water syphon pressure switches are closed the burner will be ignited.
10. Perform a thorough check on ue-gas joints for leakage.
11. Check the heat input and the gas pressure at maximum load.
12. Heat up the installation. Stop the heat request.
Page 49
EN
49
13. Bleed the installation again, topping up the water system pressure if required.
14. Explain the operation of the boiler to the user.
15. Explain to the user the signicance of error codes and the need to report them when requesting service engineer support.
16. After installation the datasheet as shown in chapter 9.1 should be lled in. This should be repeated at every service-interval.
17. Safely store the installation and the user manual preferably in close proximity to the boiler.
7.1 Gas category
The types of gas and supply pressures vary by country. In the table below the gas category and supply pressure are listed by country.
Countries Category Pressure
[mbar]
AT Austria 12H 20 BE Belgium 12E(R) 20/25 BG Bulgaria 12H 20 HR Croatia 12H 20 CY Cyprus 12H 20 CZ Czech Republic 12H 18 DE Germany 12E 20 DK Denmark 12H 20 EE Estonia 12H 20 ES Spain 12H 20 FI Finland 12H 20 FR France I2Esi , I2Er 20/25 GB United Kingdom 12H 20 GR Greece 12H 20 HU Hungary 12H 25 IE Ireland 12H 20 IT Italy 12H 20 LT Lithuania 12H 20 LU Luxembourg 12E 20 LV Latvia 12H 20 NL The Netherlands I2L , I2EK 25 PL Poland 12E 20 PT Portugal 12H 20 RO Romania I2E, I2H 20 SE Sweden 12H 20 SL Slovenia 12H 20 SK Slovakia 12H 20 NO Norway 12H 20 CH Switzerland 12H 20 LI Liechtenstein 12H 20 IS Iceland MT Malta
Page 50
50
As the responsible manufacturer of my products, I’m aware that the above mentioned countries have
adopted the Gas Appliance Directive 2009/142/EC in their national law. I understand that the CE mark has meaning only in these countries, where the GAD is implemented in the national regulations. Although other countries might value and respect the CE mark, it has no formal value.
This boiler can be adjusted for category K(I2K) and is in this case suitable for the use of G and G+ dis­tribution gasses according to the specications as shown in NTA 8837:2012 Annex D with Wobbe-index 43,46-45,3 MJ/m3 (dry, 0 °C, Hs) or 41,23 – 42,98 (dry, 15 °C, Hs)
This boiler can also be converted and re-adjusted for category E (I2E) This means that the boiler is : either is suitable for G+ gas and H-gas or provable suitable is for G+ gas
and provable can be made suitable for H-gas as meant by “Besluit van 10 Mei 2016” until changes in this
document are made.
7.2 Adjustment % CO2 (O2 %) and check input
The boiler is equipped with an automatic gas/air regulator. This means that the amount of gas is regulated depending on the amount of air. The % CO2 needs to be adjusted according to the table below;
Type of boiler Gas type inlet pressure %CO2 * on max load %CO2 * on min load 850-11 G20 / G25/G25.3 20 / 25 mbar 9,3 +0,2-0,05 9,1 +0,15-0,2 1020-13 G20 / G25/G25.3 20 / 25 mbar 9,3 +0,2-0,05 9,1 +0,15-0,2
*For O2 percentage see Chapter 2 Technical data
The boiler has a gas valve that is connected to a venturi. See gure below ;
Adjustment for max. load ;
• wait until the boiler is stable and measure % CO
2
• if required, correct CO2 with the throttle ; turning towards + gives a higher CO2 percentage (a ½ turn
(180°) causes a change of approximately 0,85 % CO2)
Adjustment for min. load ;
• wait until the boiler is stable
• if required, correct the CO2 with the off-set ; turning to-
wards + gives a higher CO2 percentage. Note : this offset ad-
justment is very sensitive : half a turn (180°) causes a change
of approximately 1 % CO2.
Check on heat input
In the table below the relationship between nominal maxi-
mum input and fan speed and gasow is given for
G20 as sample. The nominal fan speed can be ± 5% due to adjustments in production. Write down your
initial settings (between 680 and 850 or between 850 and 1020 kW) for input in the table as shown
in 9.1
Nominal input 850 1020 [kW Hi] Fan speed nominal 5800 6100 [rpm]
Gasow G20 90 108 [m3/h]
If the gas ow is too low it may be due to an obstruction (dirt) in the air/ue system. Check and if necessary clean. The gas ow must then be re-checked.
Throttle
Off-set
Page 51
EN
51
8 ERRORS
8.1 General
If there is no data visible on the display, the circuit breaker must be checked on the panel that can be
accessed after removal of the rst side panel on the right. Main switch on the front panel should be
checked (as well as the position of the on/off switch) and should if required be replaced (after the cause
for break down has been determined and rectied).
WARNING! THIS CIRCUIT BREAKER IS PART OF THE HIGH VOLTAGE CIRCUIT. DIS­CONNECT THE BOILER FROM THE MAINS ELECTRICITY SUPPLY BEFORE REPLA­CING!
If there is still no data visible on the display, one has to check if there is 230 VAC present on the connec-
tions “L” and “N” of connector X00 in the MAXSYS.
Also see electrical wiring diagram.
If there is 230 VAC present (terminal connector C1: 25,22) , then the 230 V fuses F1 and F2 inside the Maxsys should be renewed. Disconnect the boiler from the main supply and remove the connectors from the Maxsys. Notice : for this it is not necessary to unscrew the Maxsys from the mounting plate Release the six security clips with a long thin screw driver. Then remove the protective cover of the Maxsys. Replace the 230 V fuse(s) F1: T3.15 AL 250V and/or F2 T3.15 AL 250V inside the Maxsys.
A blown fuse in the Maxsys controller could be caused by a short-circuited pump. It is recommended to also check the CH-pump and also the DHW pump in this case.
If the 230 V fuses are OK and the display is still blank, then the cable of the display to the Maxsys (X15)
should be checked. If this is also ok, the Maxsys should be renewed.
six security clips
Page 52
52
F1: T3.15A 250 V F2: T3.15A 250 V
If you are not sure that there is any heat demand, you can force the boiler to start as described in 5.5.
On heat demand, the boiler control will perform a zero-check of the air pressure switch before starting the fan. Following this, the fan will start and wait for air pressure switch to close. As soon as APS has closed, starting procedure will continue.
APS closes at ΔP > 40 Pa.
If there is a problem with APS, the display will show blower speed error.
The boiler control checks the status of the built-in pressure switches for water, gas and syphon just befo­re ignition ;
Water pressure should be > 1,4 bar (E47); Gas pressure should be > 14 mbar (E76); Syphon pressure should be < 15 mbar (E77)
Page 53
EN
53
8.2 DHW errors
Boiler does not respond to DHW heat request
- Check the storage tank-NTC or thermostat and its wiring (also see electrical wiring diagram).
- Check if DHW is enabled using the control panel
Insufcient DHW ow
- Dirty lters in taps.
- Insufcient water pressure.
DHW temperature too low
- Tapping ow too high
- Temperature set point too low
- Leakage 3-way valve (towards CH-circuit), 3-way valve not fully in DHW position
- Faulty DHW pump
- DHW operation set to off
- Storage tank-NTC or thermostat and or wiring defect.
- Input too low due to too much resistance in air/ue system.
Boiler operates only for DHW
- Storage tank-NTC or thermostat defect and or its wiring.
- 3-way valve stuck (remains in direction towards storage tank)
8.3 CH-errors
CH circuit stays cold
- Incorrect connection to the mains electricity supply.
- Main switch on control panel is switched off (boiler off).
- Room thermostat defect, incorrect wiring, temperature set too low
- Outdoor sensor and/or its wiring defect.
- CH operation off
- 3-way valve defect (remains in direction towards storage tank)
8.4 Errors (hard and soft lockouts)
Errors are indicated by a text and an E-code on the bottom line on the display.
The error message can be displayed by pressing the ”information” button.
Following an error with a hard lockout, the boiler will not re again until a manual reset is performed (eg
max temp limit).
These errors can be found under column “hard lockout code” in the following table.
Following an error with a soft lockout the boiler will automatically resume normal operation after the
cause of block is solved (eg gas pressure too low). They can be found under column “soft lockout code”
in the following table.
The cause of error (hard or soft lockout) can be found with the help of the error-list below. After the cause of error has been determined and the error has been resolved, the boiler can be put back into operation again.
Page 54
54
Page 55
EN
55
9 ANNUAL SERVICE
Maintenance should only be done by a qualied installer or technician. the following main­tenance routine should be done annually (see also 9.1).
The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge. Children, even if being supervised, must not maintain or clean the appliance or play with
the appliance.
In the case of failure or malfunction of the appliance, do not attempt to repair it yourself. Please contact your installer. Repairs must only be carried out by qualied technicians. Failure to comply with these requirements can compromise the safety of the aplliance.
Put the boiler into operation on max. load (see section 5.5). Determine the heat input of the boiler. Check % CO2 . Compare the heat input with that measured at installation. If the heat input is now con-
siderably lower then there is probably an obstruction in the air inlet or the ue-outlet or in the boiler
itself.
Switch off the boiler. First check the air-inlet and the exhaust ue-outlet.
Disconnect from the mains electricity supply. Remove the front cover, top cover and side cover. Remove the syphon and clean it.
Remove the inspection cover* of the sump on the front side beneath the controls. The inner part of the sump and the bottom part of the heat-exchanger should be inspected and, if neces­sary, be cleaned. If the bottom part of the heat-exchanger is clogged, the inspection covers on the left-hand side of the
heat-exchanger should be removed*. Using a special tool (see gure below) makes it possible to clean
the heat-exchanger lids partially . In case of dirt in the sump it is also advisible to inspect the upper part of the heat-exchanger as well. Remove the fan* together with the burner hood*, the gas valve* and the gas pipe*. Now the burner* is visible and can be taken out and inspected. If necessary clean the cold side with a vacuum cleaner (or carefully with compressed air) and a nylon brush (never use a steel brush). Inspect the combustion chamber. In case of a dirty heat-exchanger it can be cleaned with water. Check the burner seal* and replace if necessary.
Rell the condensate trap with clean water and reconnect it.
Check the electrode, especially the distance between the two pins (3,5± 0,5 mm). Replace electrode if necessary. Put everything back in its place. Check the CO2-content and correct if necessary. Check the gas-parts for leakages.
Check the ue-gas parts for ue-gas leakages and condensate leakages.
*Note : be careful during inspection not to damage seals. Any seals damaged by ageing or other causes should be replaced.
Page 56
56
Page 57
EN
57
9.1 Service-maintenance table
When commissioning the boiler, it is recommended to measure load, CO2 or O2, CO, T ow, T return,
ΔP air pressure switch and Psyphon pressure switch and write the values down in the table below.
Measure these values when the boiler is in equilibrium at maximum load (also see chapter 5.5). During annual maintenance we advise to measure and write down these values also and compare them to the previous values and analyse any changes.
Date gasow [m3/h]
or load [kW]
CO2 [%] CO [ppm] T
ow
[ºC] T
return
[ºC]
ΔP air
pressure switch
[mbar]
ΔP siphon
pressure
switch [mbar]
At the factory the maximum load of the boiler was measured within 5% tolerance from the nominal maximum load.
In the eld the load can decrease due to increased resistance in the boiler, the air inlet or the exhaust
outlet or due to malfunctioning of the fan or other causes.
At maximum load the installation should be designed for nominal ΔT of 15 K to 20 K. When the ΔT is higher than 25 K, the boiler cannot continue at maximum load anymore and will start to modulate because water ow through the boiler is insufcient. T ow and T return can be read in “info mode” on the display (see 5.4 diagnostics) Valves, malfunctioning pumps, dirt, corrosion products from the installation, dirty lters etc. can have negative impact on water ow through the boiler.
Before ignition the boiler control checks ΔP aps during prepurge. During burner operation this check
will be carried out. If the value decreases over successive years, this could indicate a problem, e.g. malfunctioning of the fan, dirty air inlet, dirty burner, dirty heat exchanger or dirty exhaust system.
Syphon pressure (P sps) should be lower than the maximum allowable ue resistance. If P sps is too high (> 15 mbar), the boiler will be stopped.
In this case the exhaust system may be blocked.
Page 58
MARK BV
BENEDEN VERLAAT 87-89
VEENDAM (NEDERLAND) POSTBUS 13, 9640 AA VEENDAM
TELEFOON +31(0)598 656600 FAX +31 (0)598 624584
info@mark.nl www.mark.nl
MARK EIRE BV
COOLEA, MACROOM
CO. CORK
P12 W660 (IRELAND) PHONE +353 (0)26 45334
FAX +353 (0)26 45383
sales@markeire.com www.markeire.com
MARK BELGIUM b.v.b.a.
ENERGIELAAN 12
2950 KAPELLEN
(BELGIË/BELGIQUE) TELEFOON +32 (0)3 6669254
FAX +32 (0)3 6666578
info@markbelgium.be www.markbelgium.be
MARK DEUTSCHLAND GmbH
MAX-PLANCK-STRASSE 16
46446 EMMERICH AM RHEIN (DEUTSCHLAND)
TELEFON +49 (0)2822 97728-0 TELEFAX +49 (0)2822 97728-10
info@mark.de www.mark.de
MARK POLSKA Sp. z o.o
UL. KAWIA 4/16
42-200 CZE˛S T O C H O W A ( P O L S K A ) PHONE +48 34 3683443 FAX +48 34 3683553 info@markpolska.pl www.markpolska.pl
S.C. MARK ROMANIA S.R.L.
STR. KOS KAROLY NR. 1 A
540297 TARGU MURES (ROMANIA) TEL/FAX +40 (0)265-266.332
ofce@markromania.ro
www.markromania.ro
CERTIFICATION N°: 17.07.011 AIRSTREAM
CERTIFICATION N°: 17.07.011 AIRSTREAM
CERTIFICATION N°: 17.07.011 AIRSTREAM
Loading...