Maretron MS-1035, MS-1055-N, MS-1085-N, MS-1075 User Manual

®®
Installation Instructions
MS-1035, MS-1055-N, MS-1075, MS-1085-N Magnetic Switches
Instructions
1. Connect the two alarm contact terminals of the sensor portion of the magnetic switch to a free switch channel. The example in Figure 1 shows the sensor portion of the magnetic switch connected to switch channel 1 with one wire connected to “SW1A”, and the second wire connected to “SW1B”.
2. Use a Maretron DSM250 display (firmware 1.3.5 or higher), the DSM250 viewing function of the Maretron N2KAnalyzer software, or other Maretron display product capable of configuring the SIM100 to set the switch channel mode (indicated as “Channel #x Mode” on the DSM250) for the appropriate channel to “No End of Line Resistor”. For this example, you would set “Channel #1 Mode” to “No End of Line Resistor”.
3. Supply Power to the NMEA 2000 network and verify that the switch channel indicates an “off” (alarm) state using Maretron N2KView software, N2KAnalyzer, or other product capable of displaying switch indicator state.
4. Place the magnetic portion (the part with no connected wires) of the switch close to the sensor portion (the part with connected wires) of the switch and verify that the switch channel indicates an “on” (normal) state during the test.
1 2 5 4 3 6 7 8 9 10 11 12
SW1A SW2B
For installation support, please contact:
SW1B SW2A SW3A SW3B SW4A SW4B SW5A SW5B SW6A SW6B
Telephone: (+1) 877-550-9100
E-mail: support@maretron.com
Web: http://www.maretron.com
MS-1035, MS-1055-N,
MS-1075, or MS-1085-N
Sensor Portion
SIM100 Screw Terminals
Figure 1 - Wiring Diagram
Maretron, LLP
rd
9014 N. 23
Ave #10
Phoenix, AZ 85021-7850
Magnetic Portion
Copyright © 2008 Maretron, LLP All Rights Reserved P/N: M001805 Rev.1.1 9/08