Product Data Sheet
FPB33553
Power Distribution Block
335 Amps, 600 Volts (AC/DC)
Wire Range:
Line side: (1) 400kcmil - #6 AWG
Load Side: (6) #2 - #14 AWG
Electrical Ratings:
• 335A copper wire, 270A aluminum wire (Based on NEC Table 310-16, 75°C columns)
• CE Rated Voltage (Ui): 1,000 V AC/DC per IEC 60947-7-1
• 600 Volts AC/DC (Service Equipment according to National Electrical Code, NFPA 70)
• Minimum enclosure size: 16 X 12 X 6
• Factory and Field Wiring
NOTE: Use outside these ratings must be judged in end-use application
Short Circuit Current Ratings (Copper wire only):
Su i tabl e Conduct ors Overcurre nt Protect ion F use Required
Class/Max Amp Rating(kcmil/AWG)
Line Load J T RK1 RK
40 0 - 3/0 2 - 8 4 00 40
2/0 - 6 2 - 14 20 0 20
Overcurrent Protection Circuit Breaker Required
Line Load SYM Amps Max
2/0 - 6 2 - 10 35,000 480
400 - 3 2 - 3 35,000 480
350 - 4 2 - 8 50,000 480
Mfr Type Max Amp
Square D 250JDL36250
Square D
Square D
Square D
Allen Bradley 14OU-K6 400
Allen Bradley 14OU-J6 250
Allen Bradley 14OU-J0 250
400 100 6
200 100 6
JGL36250
JJL36250
JLL36250
GCC
30 100,000 600
30 100,000 600
250
250
250
Mechanical Ratings:
• Insulator base temperature: -40°C/F to 125°C (257°F) UL RTI
• Maximum insulator base plate temperature: 130°C (266°F) UL RTI
• Flammability rating of insulator base: UL 94 V-0
SCCR, RMS Volts
SYM Amps Max
SCCR, RMS Volts
18,000 480
65,000 480
65,000 480
50,000 480
![](/html/b1/b18e/b18e9c70e959a4dca61c1c07d0271134779df9ad8335a972c37a648ea16b4f13/bg2.png)
Materials:
• Connector: High conductivity aluminum, tin plated
• Insulator base: Glass filled polycarbonate (thermoplastic)
• Insulator base plate: Phenolic laminate
• Terminal set screws: Steel, nickel plated and aluminum, tin plated
• Mounting screws: Steel, zinc plated
Agency Approvals:
• UL Listed, File No. QPQS.E309401
• Investigated to UL 1953
• UL 508A Feeder Circuit Terminal Spacing for up to 600 Volts
• CSA Certified, CSA C22.2 No. 158, File No LR 19766
• 600V Rating for Class 6228 01 – Use Groups A, B, C
• CE compliant to IEC 60947-7-1
• RoHS Compliant
Wire Ranges:
Line Side Wire Range:
Copper Wire Stranding Classes - Number of Conductors
Wire Size Torque Solid Class B Class C
N.m
40 0 kc m i l 3 1.1 2 75 1 1
350 31.1 27
300 31.1 27
250 31.1 275 1 1
4/0 31.1 27
3/0 31.1 27
2/0 31.1 275 1 1
1/0 31.1 27
131.127
2 31.1 275 1 1
431.127
31.1 27
in. lb
11
11
11
11
11
11
11
11
Aluminum stranded wire range: 400 - 6 AWG
Load Side Wire Approvals:
Copper Wire Stranding Classes - Number of Conductors
Wi re Siz e T or que S oli d Class B Cla ss C
N.m in. lb
2 AW G 5.6 50 1 1
45.14
65.14
84.540 1 1
10 4.0 3
12 4.0 3
14 4.0 35 1 1 1
11 1
11 1
11
11
Aluminum stranded wire range: #2 – #14 AWG