Marathon Special Products FPB23580 Data Sheet

r
A
A
A
A

Product Data Sheet

FPB23580
Power Distribution Block 175 Amps, 600 Volts (AC/DC)
Wire Range:
Line side: (1) 2/0 - #14 AWG Load Side: (6) #4 - #14 AWG
Electrical Ratings:
175A copper wire, 135A aluminum wire (Based on NEC Table 310-16, 75°C columns)
CE Rated Voltage (Ui): 1,000 V AC/DC per IEC 60947-7-1
600 Volts AC/DC (Service Equipment according to National Electrical Code, NFPA 70)
Minimum enclosure size: 16 X 12 X 6
Factory and Field Wiring
NOTE: Use outside these ratings must be judged in end-use application
Short Circuit Current Ratings (Copper wire only):
Su i tabl e C ond uctors Over c urrent Protect i on Fus e Requir ed
Class /M ax Am p Ratin g(kcmil/AWG)
Line Load J T RK1 RK5 G CC
2/0 - 6 4 - 14 2 00 2 00 200 100 6 0 30 10 0,000 600
Overcurrent Protection Circuit Breaker Required
Line Load Mf 2/0 -2 4 - 8 Square D JLL36250 250 65,000 480 2/0 -6 4 - 12 2/0 -6 4 - 12 2/0 -4 4 - 8 2/0 -4 4 - 8
llen Bradley 14OU-H6 125 50,000 480 llen Bradley 14OU-H0 125 50,000 480 llen Bradley 14OU-J6 125 35,000 480 llen Bradley 14OU-J0 125 35,000 480
Type Max Amp SYM Amps Max
SCCR, RMS Volts
SYM Amps Max
SCCR, RMS Volts
Mechanical Ratings:
Insulator base temperature: -40°C/F to 125°C (257°F) UL RTI
Maximum insulator base plate temperature: 130°C (266°F) UL RTI
Flammability rating of insulator base: UL 94 V-0
Materials:
0
Connector: High conductivity aluminum, tin plated
Insulator base and covers: Glass filled polycarbonate (thermoplastic)
Insulator base plate: Phenolic laminate
Terminal set screws: Steel, nickel plated and Aluminum, zinc plated
Mounting screws: Steel, zinc plated Agency Approvals:
UL Listed, File No. QPQS.E309401
Investigated to UL 1953
UL 508A Feeder Circuit Terminal Spacing for up to 600 Volts
CSA Certified, CSA C22.2 No. 158, File No LR 19766
600V Rating for Class 6228 01 – Use Groups A, B, C
CE compliant to IEC 60947-7-1
RoHS Compliant Wire Ranges:
Line Side Wire Range:
Copper Wire Stranding Cl asses - Number of Conductors
W ire Si ze To rqu e S o lid Clas s B Class C
N.m in. lbs
2/0 AW G 13.6 120 1 1
1/
1 13.6 120 1 1 2 13.6 120 1 1 4 13.6 120 1 1 6 13.6 120 1 1
84.540 1 1 10 4.0 35 1 1 1 12 4.0 35 1 1 1 14 4.0 35 1 1 1
13.6 120 1 1
Aluminum stranded wire range: 2/0 – 14 AWG (70 – 2.5 mm²)
Load Side Wire Approvals:
Copper Wire Stranding Classes - Number of Conductors
Wire Size Torque Solid Class B Class C
N.m in. lbs
4 AWG 4.0 35 1 1
64.035 1 1
84.035 1 1 10 4.0 35 1 1 1 12 4.0 35 1 1 1 14 4.0 35 1 1 1
Aluminum stranded wire range: #4 – #14 AWG
Loading...
+ 1 hidden pages