![](/html/68/6866/6866817a864520900f94fc9754f017897a69168ea557a0ec41498aa0c6363407/bg1.png)
Product Data Sheet
FPB23572
Listed Power Splicer Block
175 Amps, 600 Volts UL (AC/DC)
Wire Range:
Line side: (1) 2/0 - #14 AWG
Load Side: (1) 2/0 - #14 AWG
Electrical Ratings:
• 175A copper wire, 135A aluminum wire (Based on NEC Table 310-16, 75°C columns)
• CE Rated Voltage (Ui): 1,000 V AC/DC per IEC 60947-7-1
• 600 Volts AC/DC (Service Equipment according to National Electrical Code, NFPA 70)
• Minimum enclosure size: 16 X 12 X 6
• Factory and Field Wiring
NOTE: Use outside these ratings must be judged in end-use application
Short Circuit Current Ratings (Copper wire only):
Su i table C onduc tors O v e rcurrent Prot ect i on F use Required
Class/Max Amp Rating(kcmil/AWG)
Line Load J T RK1 RK5 G CC
2/0 - 6 2/0 - 6 200 2 00 200 100 60 30 100,0 00 600
Overcurrent Protection Circuit Breaker Required
Line Load SYM Amps Max
2/0 -2 2/0 -2 65,000 480Square D JLL36250 250
Mechanical Ratings:
• Insulator base temperature: -40°C/F 125°C (257°F) UL RTI
• Maximum insulator base plate temperature: 130°C (266°F) UL RTI
• Flammability rating of insulator base: UL 94 V-0
Mfr Type Max Amp
SCCR, RMS Volts
SY M Amps Max
SCCR, RMS Volts
![](/html/68/6866/6866817a864520900f94fc9754f017897a69168ea557a0ec41498aa0c6363407/bg2.png)
Materials:
• Connector: High conductivity aluminum, tin plated
• Insulator base: Glass filled polycarbonate (thermoplastic)
• Terminal set screws: Aluminum, tin plated
• Mounting screws: Steel, zinc plated
• Insulator base plate: Phenolic laminate
Agency Approvals:
• UL Listed, File No. QPQS.E309401
• Investigated to UL 1953
• UL 508A Feeder Circuit Terminal Spacing for up to 600 Volts
• CSA Certified, CSA C22.2 No. 158, File No LR 19766
• 600V Rating for Class 6228 01 – Use Groups A, B, C
• CE compliant to IEC 60947-7-1
• RoHS Compliant
Wire Ranges:
Line and Load Side Wire Range:
Copper Wire Stranding Classes - Number of Conductors
Wir e Size Tor que Solid Class B Cl ass C
N.m in. lbs
2/0 AWG 13.6 1 20 1 1
1/0 13.6 120 1 1
1 13.6 120 1 1
2 13.6 120 1 1
4 13.6 120 1 1
6 13.6 120 1 1
84.540 1 1
10 4.0 35 1 1 1
12 4.0 35 1 1 1
14 4.0 35 1 1 1
Aluminum stranded wire range: 2/0 – 14 AWG
• Wire strip length –11/16”
• Wire strip length, load side tap, top row - 3/8”, bottom row - 13/16”
• Hex key needed: 5/16”
Mounting:
• Panel mountable: #10 fastener, torque to 25-30 in. lbs.
Accessories:
• Marker Strips to mark circuits. Printing available. Consult factory.