Product Data Sheet
812 GP XX
Replace “XX” with 01 through 18 for number of poles
Terminal Block– Open Back
30 Amps, 600 Volts (AC/DC)
Insulator Strip Required for Voltage Rating
Copper Wire Only
Wire Range with Wire Binding Screw: #12 - #14 AWG
9/16” Centers
Application torque: 16 in. lbs
Electrical Ratings:
• 30A with Listed ring lug or unprepared wire, (Based on NEC Table 310-16, 75°C columns)
• 600 Volts AC/DC (UL 1059 Class B, User Group – Commercial Appliances)
• Short Circuit Current Rating: 10,000A (Default)
• Approved for Factory Wiring.
Mechanical Ratings:
• Storage and transportation temperature range: -35°C to 110°C (-31°F to 230°F)*
• Maximum insulator base temperature: 150°C (302°F)* UL RTI
• Flammability rating of insulator base: UL 94V-1
* Use outside these ratings needs to be judged in the end-use application.
Materials:
• Connector (Eyelet): Brass, tin plated.
• Insulator base: Phenolic
• Screw, #8-32 Binder head, Phil-Slot: Steel, nickel plated
Agency Approvals:
• UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.47811
• CSA Certified, CSA C22.2 No. 158, File No. LR19766
• CE compliant, IEC 60947-7-1
(6 Pole shown)
• RoHS Compliant
Wire Range:
Copper Wire Stranding Classes - Number of Strands
Wire Size Torque Solid Class B Class C
12 16 in. Lbs 1 7 19
14 16 in. Lbs 1 7 19
Suggested product mounting hardware: #10 fastener, torque to 25-30 in. lbs.
ACCESSORIES:
• JJ (GDI-30F) Material available. Glass-fiber filled, diallyl ortho-phthalate. UL-94 V0.
Certifiable to Military Specifications MIL-M-14 and MIL-P-19833.
• Printing (
• Marking strips - sub mounted or top mounted. Can be made
from XP (general purpose laminate), XXXPFR (flame retardant),
GME (glass cloth melamine), or GEE (glass cloth epoxy)
material.
• Insulator strips - sub mounted, black only (BB) (Printing Unavailable). Insulator Strip will be
the same width as the molding.
• Phil-Slot Brass Screw (PSB)
Accessory options may affect ratings – consult factory