![](/html/17/1704/1704b71bac3fde7e851468e3cf0b9a40e6f741f72124b7cb48159476cd82e79c/bg1.png)
Product Data Sheet
6SC30AXI
Replace “X” with 1, 2, 3 or 4 for number of poles
Class CC Enclosed Fuse Holder
30 Amps, 600 Volts AC/DC
with Blown Fuse Indicator
80V min for blown fuse indicator
Wire Range:
#6 - #14 AWG Cu
Recommended Torque: 17.7 lbf-in. (2.0 N·m)
Holds fuse size 13/32” diameter X 1 1/2”
Commonly used fuses in this holder: ATDR, ATMR, ATQR, CCMR, FRQ-R, KLDR,
KLKR, KTK-R, LP-CC
DIN Rail Mount
See table below for wire sizes.
Electrical Ratings:
• 0 - 30A max (amperage rating based on maximum fuse rating for that physical size)
• Copper wire only
• 600 Volts AC / DC
• Approved for 200,000 Amps RMS Withstand Rating
Mechanical Ratings:
• Maximum insulator base temperature: 125°C (257°F) UL RTI
• Flammability rating of insulator base: UL 94 V-0
• Touch protection: IP-20 (IEC 60529)
• Use outside these ratings needs to be judged in the end-use application.
Materials:
• Fuse Clip: Copper alloy, plated
• Box Connector: Plated Steel
• Insulator base: Glass-filled Polycarbonate (Thermoplastic)
![](/html/17/1704/1704b71bac3fde7e851468e3cf0b9a40e6f741f72124b7cb48159476cd82e79c/bg2.png)
Agency Approvals:
• UL Recognized, UL 512 Terminal Block Standard, File No. IZLT2.E35113
• CSA Certified
, CSA C22.2 No. 39 – M1987, File No. LR21455
• CE certified
RoHS Compliant
•
ccessories:
A
Pin k
• it (used for ganging multiple poles)
EFH-MCCK: includes 10 handle pins and 20 bod
Use one handle pin and two body clips per pole
y clips
Din Rail (35 x 7.5 mm, 2 m long, slotted): MN35-2
•
Dimensions mm Inches
A 17.80 0.70
B 35.60 1.40
C 53.30 2.10
D 71.10 2.80
E 43.20 1.70
F 61.00 2.40
G 9.90 0.39
H 78.20 3.08
PDS 0232 REV A 11/14/08